You are on page 1of 16

Ultraclean®/Ultraconstant®

Air-Conditioning Units and Components for Clean


Room Applications and Experimental Chambers

Weiss Reinraumtechnik
Clean room applications for your requirements

Are you looking for a tailored solution If so, then Weiss Klimatechnik is the Weiss Klimatechnik has one of the most
for a clean room project? Do you want right address for you. For over 50 years extensive ranges for clean room appli-
to have suitable equipment and sys- Weiss Klimatechnik has been concerned cations and experimental chambers
tems to optimise your production? with manufacturing units and systems that you can turn to. We develop opti-
Or are your plans within a project for for generating optimum air-conditio- mum solutions for your requirements
high-grade and cost-efficient clean ning environments. based on these product lines.
room installations?

Tailored
solutions
Weiss air-conditioning systems have Your benefit: Food Industry
admirably proven themselves in many Beverage Industry
fields across the world and are ideally Weiss Klimatechnik is one of the few Medical technology
suited for clean-zone applications. companies worldwide that provide sys- Genetic and bio engineering
tems, air-conditioning units and pro- Laboratories
Depending on requirements, the sys- cess technology from a single source. Pharmaceutics
tems are fitted with partial or full air- Pharmacies
conditioning involving heating, cooling, In working together with Weiss Klima- Optoelectronics
humidifying and dehumidifying. Top technik, our customers particularly Microelectronics
quality filters ensure clean air for so- value the sound advice given in develo- Micromechanics
phisticated clean room air-conditioning. ping systems, support shown in design Automotive engineering
planning, close cooperation with instal- Nanotechnology
We provide our customers with integra- lation and startup as well as the service
ted systems and components for all and training.
clean room classes and applications.

2
Weiss
compact air-conditioning units
Single-module compact air-conditioning units
for universal use in clean rooms and experi-
mental chambers
Compact design with innovative technology
Air volume flows from 2,000 to 22,000 m3/h
Temperature constancy: ± 0.5 K
Humidity constancy: ± 2 % r.h.

Weiss
precision air-conditioning units

Guarantee ultra-clean and ultra-constant


air-conditioning
Application focus on all fields placing
stringent requirements on temperature and
humidity
Air volume flows from 1,000 to 6,000 m3/h
Temperature constancy: ± 0.2 K
Humidity constancy: ± 2 % r.h.

Weiss
air-conditioning chamber systems
For maximum demands on precision air-
conditioning and clean room technology,
customer-specific construction and design
Temperature constancy: ± 0.05 K
Humidity constancy: ± 1 % r.h.

3
Compact air-conditioning units

Universal, dependable, compact

The new generation of compact air-con-


ditioning units has been specially deve-
loped for universal use for differing air-
conditioning and clean room require-
ments. Compact design combined with
innovative technology ensure signifi-
cant operating cost benefits.

Nominal volume flow from


2,000 to 22,000 m3/h
Up- and downflow designs
Full air-conditioning function with
heating, cooling, humidifying and
dehumidifying
Complies with VDI 6022
Filter class: F7 standard, F9 possible
as second stage
Pumped cold water or active cooling
Integrated control cabinet
Temperature constancy: ± 0.5 K
Humidity constancy: ± 2 % r.h.

Compact
solution
Supply air

Clean room

Benefits at a glance

Exhaust air
Set-up possible near the clean room
Air-conditioning unit Minimum floor space needed
Short duct and supply stretches
Easy, rapid installation
Lateral inspection opening of the
External air heat exchanger
(purified) Service-friendly
Good cleanability as per VDI 6022
Design variant (upflow) as circulating air
appliance with external air proportion
4
Compact air-conditioning units

SIZE COMPACT AIR-CONDITIONING UNIT 35.3 55.3 75.3 90.3 120.3 160.3 220.3

NOMINAL VOLUME FLOW


Volume flow with max. ext. pressure loss m3/h 3,500 5,500 7,500 9,000 12,000 16,000 22,000
Max. external pressure loss Pa 600 900 620 580 900 700 750

HOUSING DIMENSIONS
Width mm 1,090 1,090 1,355 1,610 2,140 2,405 2,405
Depth mm 650 850 850 850 850 1,100 1,100
Height mm 1,950 1,950 1,950 1,950 1,950 1,950 1,950
Partial type code (width, depth) 10.6 10.8 13.8 16.8 21.8 24.11 24.11

COOLING – COOLING CIRCUIT, AIR-COOLED, EXTERNAL


Cooling capacity (tc=50 °C) as per EUROVENT
Suction temp. +27 °C/46 % r.h. - total/sens. kW 13.4/11.5 18.4/17.9 29.2/26.2 34.9/31.4 45.4/41.7 54.4/52.3 73.1/71.0
Partial type code (DX=direct evaporator) DX DX DX DX DX DX DX

COOLING – COLD WATER 7/12.5 °C *


Cooling capacity as per EUROVENT
Suction temp. +27 °C/46 % r.h. - total/sens.kW 11.6/9.8 26.1/20.4 36.6/28.5 42.9/33.5 60.6/46.8 75/58.9 106/82.7
Partial type code (CW=cold water) CW CW CW CW CW CW CW
*other temperatures on request

OPTIONS
HEATING – ELECTRIC HEATING
Product type plain tubular heaters, continuously controlled
Max. heating capacity kW 7.5 15 15 21 21 21 30
Current consumption A 10.8 21.7 21.7 30.3 30.3 30.3 43.4
Electrical connected load kVA 7.5 15 15 21 21 21 30

HEATING – HOT WATER 70/50


Heating capacity at suction temp. 15 °C kW 15.9 23.9 32.4 36.2 49.2 66.5 79.2
Hot water volume m3/h 0.7 1 1.4 1.6 2.2 2.9 3.5

HEATING – HOT WATER 70/50 (PREHEATER)*


Heating capacity at suction temp. -15 °C kW 22 34.7 47.2 57.6 79 114.6 138.5
Hot water volume m3/h 1 1.5 2.1 2.5 3.5 5 6.1
* Preheater in top-mounted box (only downflow)

HUMIDIFYING – STEAM GENERATOR


Product type electrode steam humidifier, internal; accuracy +/- 6 %
Current consumption A 4.7 7.4 10 11.9 15.9 21.1 29.1
Rated input kW 3.2 5 6.8 8.1 10.8 14.4 19.8
Electrical connected load kVA 3.2 5 6.8 8.1 10.8 14.4 19.8
Max. steam output kg/h 4.2 6.6 9 10.8 14.4 19.2 26.4
Water supply bar 1 - 10 1 - 10 1 - 10 1 - 10 1 - 10 1 - 10 1 - 10
Water conductivity µS/cm 125-900 125-900 125-900 125-900 125-900 125-900 125-900
On request external humidifier type MK5 P (resistance heating principle); accuracy +/- 2 %; also for preheated water

FAN MOTOR UNIT


Product type directly driven, free running
Nominal motor power kW 2.9 7.4 7.4 7.4 2 x 7.4 2 x 7.4 3 x 7.4
Current consumption, max. A 4.6 12.7 12.7 12.7 2 x 12.7 2 x 12.7 3 x 12.7
Electrical connected load kVA 3.2 8.8 8.8 8.8 17.6 17.6 26.4
Partial type code (D=Downflow/U=Upflow) D/U D/U D/U D/U D/U D/U D/U

FREQUENCY CONVERTER
Product type static frequency converter

5
Compact air-conditioning units

SIZE COMPACT AIR-CONDITIONING UNIT 35.3 55.3 75.3 90.3 120.3 160.3 220.3

FILTER F7 SUCTION SIDE


Product type cassette filter, pocket filter (only downflow), as per DIN EN 779

FILTER F9 SUCTION SIDE (OPTION)


Product type cassette filter, pocket filter (only downflow), as per DIN EN 779. Also available as second filter stage

STANDARD UNIT, COMPLETE


Complete weight DX/CW kg 325/286 384/312 534/471 628/523 890/778 1153/1038 1284/1086
Sound power level at nominal volume
flow and ext. pressure loss Pa 50 50 50 50 50 50 50
Exhaust air connection db (A) 74 70 76 83 76 84 86
Supply air connection db (A) 81 77 83 90 83 91 93
Housing radiation db (A) 68 58 64 71 64 70 72
Sound pressure level in free field
(1 m distance) db (A) 64 54 59 66 59 66 68
Supply voltage V/Ph/Hz 400/3/50
Electrical connected load* kVA 9.9 12.1 20.7 21.1 32.6 33.2 45.3
Full type code (ex.) 35.3DXD10.6N 55.3DXD10.8N 75.3DXD13.8N 90.3DXD16.8N 120.3DXD21.8N 160.3DXD24.11N 220.3DXD24.11N
*without condenser

CONDENSER, AIR-COOLED, EXTERNAL, TYPE KLDR

TYPE (TA= 35 °C/TC= 50 °C) KLDR 2 KLDR 3 KLDR 4 KLDR 5 KLDR 6


Product type axial fan condenserr
Cooling air volume flow, continuous m3/h 6,700 8,500 12,400 18,000 18,400
Max. sound pressure level at 5 m distance db (A) 57 56 60 59 59
Number of motors pcs. 1 1 2 2 2
Supply voltage V 230 230 230 230 230
Capacity kW 17 27 38 49 71
Current consumption A 3.0 3.3 2 x 3.0 2 x 3.3 2 x 3.3
Electrical connected load kVA 1.3 1.3 2 x 1.3 2 x 1.3 2 x 1.3
Overall length mm 1,190 1,415 1,420 2,130 2,680
Width, vertical air flow mm 790 1,120 1,120 1,120 1,120
Width, horizontal air flow mm 450 563 540 563 563
Height, vertical air flow mm 885 1,105 1,105 1,105 1,105
Height, horizontal air flow mm 1,155 1,615 1,615 1,615 1,615
Weight kg 73 109 132 160 217

CONDENSER, AIR-COOLED, EXTERNAL, TYPE KLI

TYPE (TA= 45 °C/TC= 52 °C) KLI KLI 3 KLI 4 KLI 5 KLI 6


Product Type axial fan condenser
Cooling air volume flow, continuous m3/h 8,280 18,360 27,720 27,000 44,064
Max. sound pressure level at 5 m distance db (A) 55 58 60 60 56
Number of motors pcs. 1 2 3 3 3
Supply voltage V 400 400 400 400 400
Capacity kW 17.6 26.4 39.8 49.7 72.9
Current consumption A 1.25 2 x 1.25 3 x 1.25 3 x 1.25 3 x 3.1
Electrical connected load kVA 1.0 1.73 2.6 2.6 6.4
Length mm 1,340 2,490 3,640 3,640 3,908
Width, vertical air flow mm 980.5 980.5 980.5 980.5 1,158
Width, horizontal air flow mm 800 800 800 800 1,225
Height, vertical air flow mm 870 870 870 870 1,225
Height, horizontal air flow mm 920.5 920.5 920.5 920.5 1,158
Weight kg 113 158 226 235 490

We reserve the right to make technical changes due to product improvements.


6
Compact air-conditioning units

Front view of unit Left view of unit View of unit from above
(symmetrical arrangement of connections)

Operating side

Maintenance space
min. unit depth

Options

All dampers also implementable as Max. air volume flow for each lateral Intake/blowoff honeycomb grid
connections connection: 9,000 m3/h possible at the side and front when
300 to 840 mm high top-mounted Media connections: left side no duct system is needed and the
and base boxes can be supplied (top, bottom or at the side) unit is directly in the room
150 to 650 mm high base frames Electrical connections: right side
can be supplied (top, bottom or at the side)

Supply connections
Side view from left Side view from right Partial plan view from above and
below

1. PHW heater supply flow


2. PHW heater return flow
3. Humidifier supply
4. Humidifier discharge
5. PCW supply flow/
Refrigerant/Liquid line
Unit L B L1 L2 L3 L4 B1 B2 H2
6. PCW return flow/
35.3 1,090 650 765 1,000 177 147 550 550 150-650
Refrigerant/Hot gas line
55.3 1,090 850 765 1,000 177 147 750 750 150-650
7. El. line inlets
75.3 1,355 850 1,030 1,255 172 152 750 750 150-650
90.3 1,610 850 1,260 1.505 192 157 750 750 150-650
8. Condensate discharge
120.3 2,140 850 1,790 2,035 192 157 710* 750 150-650
160.3 2,405 1,100 2,035 2,300 212 157 1000 (960*) 1,000 150-650 7
220.3 2,405 1,100 2,035 2,300 212 157 1000 (960*) 1,000 150-650
Precision air-conditioning units

For high demands – Fields of use


compact solution
The main fields of use are in manu-
Weiss precision air-conditioning units facturing processes where constant
guarantee ultra-clean and constant air- air-conditioning of a high consistency
conditioning and are suitable for all is needed within a process. An outstan-
clean rooms and experimental cham- ding feature of the units is their high
bers. The units are successfully in use precision temperature and humidity
throughout the world. Application is control.
focussed on process air-conditioning.
The units are fitted with a compact
Nominal volume flow from 1,000 to refrigeration system with water-cooled
6,000 m3/h condensers (air-cooled condenser
Upflow design optional). Humidification is provided
Full air-conditioning function with by process humidifying systems.
heating, cooling, humidifying and
dehumidifying (process humidification) Benefits at a glance
VDI 6022
Filter classes F7, second stage Plug and play
externally possible Very high availability rates (up to
Optional supply air filter 99.99 %)
Temperature constancy: ± 0.2 K Compact design
Humidity constancy: ± 2 % r.h. Minimum floor space needed
Insensitive to the power frequency
Optionally also with reheat system
Set-up possible in the clean room

ideal for
precision air-conditioning
Process supply air

Process

Outgoing air

Air-conditioning unit
Design variant as process air-conditio-
ning unit with unimpeded intake from
the environment and unimpeded out-
Ambient air
(environment) flow from the process area
Clean room

8
Precision air-conditioning units

SIZE PRECISION AIR-CONDITIONING UNIT 10.3 X1 20.3 X1 40.3 X1 60.3 X1 60.3 X2

NOMINAL VOLUME FLOW


Volume flow with max. ext. pressure loss m3/h 1,000 2,000 4,000 6,000 6,000
Max. external pressure loss* Pa 700 540 500 400 400
* enhanced motor unit on request

HOUSING DIMENSIONS
Width mm 1,090 1,355 1,355 1,605 1,605
Depth mm 850 850 1,100 1,100 1,100
Height mm 1,950 1,950 1,950 1,950 1,950

COOLING – COOLING CIRCUIT


Cooling capacity (tc=50 °C) as per EUROVENT
Suction temp. +24 °C/60 % r.h. - total/sens. kW 10.2 21.8 40.3 44.5 60

HUMIDIFYING – STEAM GENERATOR


Product type resistance steam humidifier, accuracy +/- 2 %
Current consumption A 8.7 11 26.2 32.3 32.3
Rated input kW 6 7.5 18.1 22.3 22.3
Electrical connected load kVA 6 7.6 18 22.3 22.3
Max. steam output kg/h 8 10 24 30 30

HEATING – ELECTRIC HEATING


Product type plain tubular heaters, continuously controlled
Max. heating capacity kW 10.5 14 28 28 28
Current consumption A 15.2 23 48 48 48
Electrical connected load kVA 10.5 15.9 28 28 28

FAN MOTOR UNIT


Product type directly driven, free running, IP 54, Iso class F
Nominal motor power kW 1.15 1.15 3.2 3.2 3.2
Current consumption, max. A 2.82 2.82 5 5 5
Electrical connected load kVA 1.95 1.95 3.46 3.46 3.46

FILTER SUCTION SIDE


Product type cassette filter, class F7 as per DIN EN 779

PLATE CONDENSER, WATER COOLED, INTERNAL*


Water volume flow at T=27/32 °C m3/h 3 5.8 6.4 6.4 6.4
Capacity kW 17.5 30.7 58 58 58
Pressure loss on water side kPa 10 13 35 35 35
* design with air-cooled condenser on request

REHEAT AS HEAT EXCHANGER


Max. heating capacity kW optional, on request 26
Control ein/aus

STANDARD UNIT, COMPLETE


Complete weight kg 500 620 710 900 1,000
Supply voltage V/Ph/Hz 400/3/50-60
Electrical connected load kVA 25.0 43.0 79.0 85.0 90.0

9
Precision air-conditioning units

Front view of unit View of unit from left View of unit from right

Supply air (SA)

Maintenance space
900 mm

Suction

View of unit from top

Gerät L L1 L2 B
Ultraconstant 10.3 X1 1,090 mm 990 mm 437 mm 850 mm
Ultraconstant 20.3 X1 1,355 mm 1,255 mm 437 mm 850 mm
Ultraconstant 40.3 X1 1,355 mm 1,255 mm 392 mm 1,100 mm
Maintenance
space Ultraconstant 60.3 X1 1,610 mm 1,505 mm 392 mm 1,100 mm
900 mm Ultraconstant 60.3 X2 1,610 mm 1,505 mm 392 mm 1,100 mm

Options

Duct connection (incoming air above) External air-cooled condenser


Increased pressing Reheat
Condensate lift pump Integration in building control system
HEPA filter as channel filter Alternative control systems

Supply connections

Gerät 1* 2* 3 4 5
Electrical Electrical Cooling water Cooling water Condensate
View from above Connection Connection Supply flow Supply flow Discharge/side

Ultraconstant 10.3 X1 64 mm 38 mm 1” 1” 40 mm
Ultraconstant 20.3 X1 64 mm 38 mm 1 3/4” 1 3/4” 40 mm
Ultraconstant 40.3 X1 64 mm 38 mm 1 3/4” 1 3/4” 40 mm
Ultraconstant 60.3 X1 64 mm 38 mm 1 3/4” 1 3/4” 40 mm
Ultraconstant 60.3 X2 64 mm 38 mm 1 3/4” 1 3/4” 40 mm

Position above above above above above


Operator side
1* supply connection 2* control systems

10
Control Systems

Control with pcs+ Operating terminal Inputs and outputs

Weiss air-conditioning units for clean LCD display, 8 lines, 22 characters 8/14/18 digital inputs
room applications are fitted as stan- 6 keys with LED feedback 8/13/18 digital outputs
dard with a pcs+ control. Warning horn 2/2/4 sensor inputs
Other controller makes on request. Front installation 3/6/6 universal inputs
IP 65 protection class 4/4/6 analogue outputs

Controller

Microprocessor 16 bit, 16 MHz,


256 kB RAM
Clock, battery-buffered
RS485 interface for pLAN
Display connection
Programme storage on non-volatile
flash memory

Control with PC 3

Weiss precision air-conditioning units Ethernet network connection 16 digital inputs, 12 digital outputs
are fitted as standard with a PC 3 10/100 MBit for connection to
control unit. Other controller makes Intranet/ Internet 4 analogue inputs, 0-10 V, 0 (4)-20 mA,
on request. 12 bit resolution
2 USB interfaces
The PC 3 control is implemented via an 4 analogue outputs, 0-10 V, 12 bit
industry controller on a PC basis with RS 232 interface resolution
200 MHz processor and 64 MB RAM.
Parallel interface
Equipment:
PS/2 interfaces
Battery-buffered system clock
Display connection
2 PC-104 extension socket for data
point extension of the base board or Compact flash extension for
connection to building control sys- operating data recording
tems using appropriate interface
types Data and programme storage on
non-volatile flash memory
CAN field bus for networking multi-
ple controllers and for connecting Data points (can be extended via
system components via remote field PC-104 cards)
bus modules

11
Air-conditioning chamber systems

Perfect for precise


and ultra-clean processes
Efficient solution

Weiss air-conditioning chamber systems DIN EN ISO 14644-1:


are the ideal solution where clean Clean room classes 5, 4, 3, 2, 1
room-compliant conditions for precise Temperature constancy: ± 0.05 K High performance air-conditioning
and ultra-clean processes are needed. Humidity constancy: ± 1 % r.h. units including process control
.
This is where the highest demands
placed on clean room technology and
adherence to environment conditions With quality assurance procedures, e.g.
encounter economical implementation. in the microelectronic and optoelectro-
nic industries, among others high-
The Weiss air-conditioning chamber accuracy measuring systems are used.
systems comprise, for example, a These measurements and instruments
high-capacity air-conditioning unit must be protected from any environ-
with process control, a filter area and mental effects on readings.
a self-contained process area.
To this end, we develop tailored air-
Air-conditioning chamber systems are conditioning solutions in close cooper-
for keeping the air temperature, air ation with our customers and optimised
humidity and air pressure constant to both process area and floor space.
as well as for keeping the process air
particle-free. Their most important
property is the very high precision of
temperature and humidity control.

Climate chamber
High-performance
air-conditioning unit

Air-conditioning chamber system


Clean room in clean room

12
Vorteile

Climate chamber with filter unit

Application example:
Microscope control

Benefits at a glance

Plug and play Materials selected to reflect the Certification in accordance


Integration possible in process use: stainless steel, aluminium, with SEMI
equipment powder-coated Customer-specific control system
Clean room and experimental cham- Compact design
ber technology at the highest level Minimal floor space

13
Further clean room solutions

Products and
Components

Laminar flow units,


standard and
customer-specific

Central air-conditioning units for interior and exterior location


Safety workbenches

Clean rooms and experimental chambers in modular Filter fan units with
construction. Economical and space-saving computer-assisted
14 control system
Complete clean room services

System consulting / Project planning / Designing


Austria
Feasibility studies
Concept planning Belgium
Profitability analyses
Financing management Brazil
Implementation planning
Cooperation in approval processes China
General contractor, cooperations, partnerships
Czech Republic

Denmark
Production Dubai
Equipment manufacturing
Plant construction
Egypt
Clean room components
France
Monitoring systems
Special designs
Great Britain
Special equipment
System solutions
Hungary

India

Installation / Commissioning Italy

Worldwide supervising and Japan


commissioning network
Extensive network of bases Mexico
Acceptance inspection measurements/
clean room measurements Netherlands
Documentation
Qualification/requalification Poland
(DQ, IQ, OQ, PQ)
Portugal

Romania
Training Russia
Clean room technology
Saudi Arabia
Air-conditioning technology
Systems / products
Slovenia
Clean room behaviour

Sweden

Switzerland
After-sales service
Taiwan
Spare parts management / consignment
warehouse
Tunisia
Maintenance / service worldwide
Dial-up data transfer
Turkey
Technical facility management for
small and medium-sized systems Ukraine
Qualification and requalification
ISO 9001: 2000 certified USA
Hygiene test as per VDI 6022 15
Competent, immediate information

We would be glad to advise you on:

Air-conditioning units and compo- Protective systems/high containment/ Miniature environments


nents for clean room applications barrier systems Hot air sterilizers and tunnels
and experimental chambers Mobile clean room containers, cells, Air showers
Complete clean room systems cabins and tents Personnel and material barrier
Complete experimental chambers Clean workbenches and microbio- systems
as per VDI/VDE 2627 logical safety workbenches Qualification/validation
Clean room wall, ceiling, floor and Barrier systems Training
illumination systems Filter fan modules

References

3D-MICROMAC DEMAG ERGOTECH ROCHE


ABB CALOR EMAG DEUTSCHE THOMSON RODENSTOCK
ACIBADEM DR. KADE SCHOTT
ANTIBIOTICE DR. THEISS SENSITEC
APOSAN DRK BLUTSPENDEDIENST SINGULUS
ASML E.ON RUHRGAS SIEMENS
ASTA MEDICA EPPENDORF POLYMERE SOLVAY PHARMACEUTICALS
ASTRA ZENECA EADS SPIMACO
SANOFI-AVENTIS GRUENENTHAL STEAG
BASF HASSIA MINERALQUELLEN TDK
BAYER HEMOTEQ TICONA
BOSCH I.G. BAUERHIN TRW
BRITA MANUFACTURING KRAUSS MAFFEI UMICORE
CARL ZEISS MARUBENI UNTERLAND
CELANESE CHEMICALS METZELER AUTOMOTIVE URSAPHARM
CONTI TEMIC MUE TEC VARTA
CONVAC OC OERLIKON BALZERS VISTEC
CURASAN OXOID BIOTECHNIK W.C. HERAEUS
DAIMLER CHRYSLER QIAGEN WESERGOLD
DEGUSSA RHEIN BIOTECH ZF LENKSYSTEME

D-Nr. RK 4.0.0.123e/5 0507 2

Weiss Klimatechnik GmbH


Geräte- und Anlagenbau
Greizer Straße 41– 49
D-35447 Reiskirchen-Lindenstruth

Telephone: +49 (6408) 84 71


Telefax: +49 (6408) 84 87 20

info@wkt.com
www.wkt.com

You might also like