Technical data Approximate dimensions

Di s sw con Te itch nec ch e t da nica s ta l

Selecting switches per NEC


Selecting switches per NEC Article 430 of the US National Electric Code includes two methods for properly sizing disconnect switches: 1. Single motor application A properly sized disconnect switch for a single motor will: a) have an ampere rating greater than or equal to 115 percent of the rated motor full load current; or, b) have a HP rating greater than or equal to the rated motor HP (at applied voltage) if the disconnect switch under consideration is HP rated. 2. Combination load application A properly sized disconnect switch for a combination load will be selected by adding all the simultaneous individual loads in the circuit under consideration. Using motor nameplate information, load information, and tables from section 430 of the NEC, determine one equivalent full load current and one equivalent locked rotor current. The equivalent locked rotor current can be used with table 430151 to determine an equivalent HP rating. Select a disconnect switch: a) greater than or equal to 115 percent of the equivalent full load current; and, b) greater than or equal to the equivalent HP rating.

Use of UL98 & UL508 Disconnects According to NEC Article 430


To supply

Motor feeder

UL98
Non-Fusible Switches OT30, OT60 OT100 OT200, OT400, OT600 OETL-NF800 thru OETL-NF2000

Feeder Circuit

UL98

Motor feeder short circuit and ground fault protection

UL98
Fusible Switches OS30, OS60, OS100, OS200, OS400, OS600 OES800

Motor disconnecting means


(NEC 430.101 - 430.113)

Motor branch-circuit short-circuit protection


(NEC 430.51 - 430.58)

18
Typical control panel

(NEC 430.81 - 4.30.91)

Motor controller

Branch Circuit

UL508

Motor overload protection


(NEC 430.31 - 4.30.44)

OL

UL508
Non-Fusible Switches OT16, OT25, OT40, OT63, OT80 (UL98 switches can also be applied)

OSHA Lockout/tagout disconnect


(NEC 430.81 - 430.91)

Motor

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

18.57
1SXU000023C0202

t ec nn es o h l sc Di witc nica s ch a Te dat

Technical data OT16F3 OT100F3 UL & CSA


UL & CSA
3 pole
2 pole 3 pole 4 pole

Catalog number
Approvals1

OT16F3
N/A UL508 & IEC UL508 & IEC

OT25F3
N/A UL508 & IEC UL508 & IEC

OT40F3
N/A UL508 & IEC UL508 & IEC

OT63F3
N/A UL508 & IEC UL508 & IEC

OT80F3
N/A UL508 & IEC UL508 & IEC

OT30F3
N/A UL98 & IEC UL98 & IEC

OT60F3
N/A UL98 & IEC UL98 & IEC

OT100F3
N/A UL98 & IEC UL98 & IEC

General purpose amp rating pf = 0.7 0.8 Max. operating voltage

-40 to 40C

A
V

20
600

30
600

40
600

60
600

80
600

30
600

60
600

100
600

Max. horsepower rating/motor FLA current, pf = 0.4 0.5 Three phase 240V 480V 600V Single phase 120V 240V Short circuit rating with fuse Fuse type Fuse type Fuse type Fuse type Fuse type Fuse type Fuse type Maximum fuse size Endurances Min. Electrical endurance, pf = 0.75 0.80 operation cycles Min. Electrical endurance, pf = 0.40 0.50 operation cycles Mechanical endurance operations Physical characteristics Weight, switches 3 pole 4 pole Dimension, switches 3 pole H W D Shaft set screw tightening torque Shaft size square Switch operating torque for rotary 3 pole switches Terminal lug kits Wire range Torque: Wire tightening Lug mounting Auxiliary contacts NEMA ratings, AC AC rated voltage AC thermal rated current AC maximum volt-ampere making AC maximum volt-ampere breaking NEMA ratings, DC DC rated voltage DC thermal rated current DC maximum make-break Torque: Wire tightening Wire range VDC A VA lb. in AWG VAC A VA VA AWG lb. in. lb. in. lb lb in in in in mm lb. in. 0.24 0.33 2.68 1.38 2.20 8.9 .24 x .24 6x6 8.8 Not required #18 8 7 Integral OA1G_ _ A600 600 10 7200 720 R300 300 1 28 7 #18 14 0.24 0.33 2.68 1.38 2.20 8.9 .24 x .24 6x6 8.8 Not required #18 8 7 Integral OA1G_ _ A600 600 10 7200 720 R300 300 1 28 7 #18 14 0.24 0.33 2.68 1.38 2.20 8.9 .24 x .24 6x6 8.8 Not required #18 8 7 Integral OA1G_ _ A600 600 10 7200 720 R300 300 1 28 7 #18 14 0.59 0.77 3.60 2.07 2.85 8.9 .24 x .24 6x6 10.5 Not required #14 4 18 Integral OA1G_ _ A600 600 10 7200 720 R300 300 1 28 7 #18 14 0.59 0.77 3.60 2.07 2.85 8.9 .24 x .24 6x6 10.5 Not required #14 4 18 Integral OA1G_ _ A600 600 10 7200 720 R300 300 1 28 7 #18 14 0.79 1.10 3.94 2.76 2.95 8.9 .24 x .24 6x6 17.5 Not required #14 4 55 Integral OA1G_ _ A600 600 10 7200 720 R300 300 1 28 7 #18 14 0.79 1.10 3.94 2.76 2.95 8.9 .24 x .24 6x6 17.5 Not required #14 4 55 Integral OA1G_ _ A600 600 10 7200 720 R300 300 1 28 7 #18 14 0.79 1.10 3.94 2.76 2.95 8.9 .24 x .24 6x6 17.5 Not required #8 1/0 55 Integral OA1G_ _ A600 600 10 7200 720 R300 300 1 28 7 #18 14 20,000 20,000 20,000 20,000 20,000 20,000 20,000 20,000 6000 1000 6000 1000 6000 1000 6000 1000 6000 1000 6000
2

HP/A HP/A HP/A HP/A HP/A kA kA kA kA kA kA kA A

5/15.2 10/14.0 10/11.0 1/16 2/13.2 10 10 10 10 5 30 10 10 5 60 4

7.5/22.0 15/21.0 20/22.0 1.5/20 3/18.7 10 10 10 10 5 30 10 10 5 60 4

10/28.0 20/27.0 25/27.0 3/24 5/30.8 10 10 10 10 5 30 10 10 5 60 4

15/42.0 30/40.0 30/32.0 2/24.0 7.5/40.0 100 100 10 100 5 5 150

20/54.0 40/52.0 40/41.0 2/24.0 10/57.5 100 100 10 100 5 5 150

10/28.0 20/27.0 30/32.0 2/24.0 5/28.0 50 50 60

20/54.0 40/52.0 40/41.0 3/34.0 7.5/40.0 50 50 150

30/80.0 50/65.0 50/52.0 5/56.0 15/68.0 50 50 150

CC J T RK1 RK5 L H

3 cycle short circuit current withstand rating 5 kA

6000
2

6000
2

lb. in.

18

1 2 3 4 5

UL Listed switches are also CSA Approved. UL98 overload test, 50 operations, pf 0.40 0.50 at 2x FLA. Multi-tap lug available, please see pg. 18.24 and 18.27. Fuse size 70A for RK5 When protected by any Listed fuse or Listed circuit breaker whose current rating does not exceed the maximum thermal current rating of the switch.

18.58
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Technical data OT200U03 OETL-NF3150 UL & CSA


UL & CSA
Catalog number
Approvals1

Di s sw con Te itch nec ch e t da nica s ta l

3 pole
2 pole 3 pole 4 pole

OT200U03 UL98 & IEC UL98 & IEC UL98 & IEC

OT400U03 UL98 & IEC UL98 & IEC UL98 & IEC

OT600U03 UL98 & IEC UL98 & IEC UL98 & IEC

OETL-NF800A UL98 & IEC UL98 & IEC IEC

OETL-NF1200 UL98 & IEC UL98 & IEC IEC

OETL-NF1600 UL98 & IEC UL98 & IEC IEC

OETL-NF2000 UL98 & IEC UL98 & IEC IEC

OETL-NF3150 5 IEC IEC IEC

General purpose amp rating pf = 0.7 0.8 Max. operating voltage pf = 0.4 0.5 Three phase 240V 480V 600V Single phase 120V 240V Short circuit rating with fuse Fuse type CC Fuse type J Fuse type T Fuse type RK1 Fuse type RK5 Fuse type L Fuse type H Maximum fuse size Endurances

-40 to 40C

200
600

400
600

600
600

800
600

1200
600

1600
600

2000
480

3150

Max. horsepower rating/Max. motor FLA current,

HP/A HP/A HP/A HP/A HP/A kA kA kA kA kA kA kA A

75/192.0 150/180.0 200/192.0 100 350 15

125/312.0 250/302.0 350/336.0 100 600 30

200/480.0 450/515 500/472.0 /100 100/ 100 /100 /100 600/800 50

250/602.0 500/590.0 600/576 100 1200 50

100 1200 50

100 2000 65

100 2000 65

3 cycle short circuit current withstand rating 6 kA Min. Electrical endurance, pf = 0.75 0.80 operation cycles Min. Electrical endurance, pf = 0.40 0.50 operation cycles Mechanical endurance Physical characteristics Weight, switches 3 pole 4 pole Dimension, switches 3 pole H W D Shaft set screw tightening torque Shaft size square Switch operating torque for rotary 3 pole switches Terminal lug kits Wire range Torque: Wire tightening Lug mounting Auxiliary contacts NEMA ratings, AC AC rated voltage AC thermal rated current AC maximum volt-ampere making AC maximum volt-ampere breaking NEMA ratings, DC DC rated voltage DC thermal rated current DC maximum make-break Torque: Wire tightening Wire range VDC A VA lb. in AWG VAC A VA VA lb. in. lb. in. AWG lb lb in in in in mm lb. in. operations

6000 2 20,000 2.9 3.5 6.69 6.67 3.27 14 - 17.7 .24 x .24 6x6 62 OZXA-200 #4-300kcmil3 200 72 OA_G_ A600 600 10 7200 720 P600 600 5 138 7 #22 #14

1000 2 20,000 5.7 6.8 8.66 8.70 4.15 .47 x .47 12 x 12 142 OZXA-400 #2-600kcmil3 375 240 OA_G_ A600 600 10 7200 720 P600 600 5 138 7 #22 #14

1000 2 10,000 11.4 14.3 9.84 10.48 5.47 .47 x .47 12 x 12 184 OZXA-800

500 2 10,000 35.9 45.15 14.65 14.25 4.92 .47 x .47 12 x 12 184 OZXA-30

500 2 10,000 38.55 49.56 14.65 14.25 4.92 .47 x .47 12 x 12 184 OZXA-28 (4)#2-600kcmil 375 230 OZXK-_ _ A600 600 10 7200 720 P600 600 5 138 7 #22 #14

500 2 6000 127.7 149.7 21.5 18.11 10.67 .47 x .47 12 x 12 438 OZXA-28 (4)#2-600kcmil 375 230 OZXK-_ _ A600 600 10 7200 720 P600 600 5 138 7 #22 #14

500 2 6000 127.7 149.7 21.5 18.11 10.67 .47 x .47 12 x 12 438 OZXA-28/2 (8)#2-600kcmil 375 230 OZXK-_ _ A600 600 10 7200 720 P600 600 5 138 7 #22 #14

400 2 6000 127.7 149.7 21.5 18.11 10.67 .47 x .47 12 x 12 438 OZXA-28/2 (8)#2-600kcmil 375 230 OZXK-_ _ A600 600 10 7200 720 P600 600 5 138 7 #22 #14

lb. in.

(2)#2-600kcmil3 (2)#2-600kcmil3 375 240 OA_G_ A600 600 10 7200 720 P600 600 5 138 7 #22 #14 375 230 OZXK-_ _ A600 600 10 7200 720 P600 600 5 138 7 #22 #14

18

1 2 3 4 5 6

UL Listed switches are also CSA Approved. UL98 overload test, 50 operations, pf 0.40 0.50 at 2x FLA. Multi-tap lug available, please see pg. 18.24 and 18.27. Fuse size 70A for RK5 IEC rated only. When protected by any Listed fuse or Listed circuit breaker whose current rating does not exceed the maximum thermal current rating of the switch.

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

18.59
1SXU000023C0202

t ec nn es o h l sc Di witc nica s ch a Te dat

Technical data OT16F3 OT100F3 IEC


IEC
3 pole
40C V kV A A A A A A A A A A A A A A A A A A A A A A A A A A A A kW kW kW kW kA A 750 8 25 25 25 750 8 32 32 32 750 8 40 40 40 750 8 63 63 63 750 8 80 80 80 750 8 40 40 40 750 8 63 63 63 750 8 115 115 115

Catalog number
Rated insulation and operation voltage, AC20 and DC20 Rated impulse withstand voltage Rated thermal current, Ith AC 20/DC 20 open 1

OT16F3

OT25F3

OT40F3

OT63F3

OT80F3

OT30F3

OT60F3

OT100F3

40C enclosed 60C enclosed 500V 690V 1000V 500V 690V 1000V 415V 500V 690V 1000V

Rated operational currents AC 21A

16
16 16 16 16 16 10 16/1 16/2 16/3 16/4 16/8 16/1 16/2 16/3 16/6 16/8 16/1 16/2 16/4 10/4 16/8 3 7.5 7.5 7.5 50 25

25
25 25 25 20 20 11 25/1 25/2 25/3 25/6 25/8 25/1 25/2 25/3 25/8 25/8 25/1 25/2 25/4 3 3 4 9 9 9 50 32

40
40 40 40 23 23 12 32/1 32/2 32/3 32/6 32/8 32/1 32/2 32/4 3 3 32/1 32/2 32/4 3 3 5.5 11 11 11 50 40

63
63 63 63 45 45 20 45/1 45/2 45/4 3 3 45/1 45/2 45/4 3 3 45/1 45/2 45/4 3 3 11 22 22 15 50 63

80
80 80 80 75 58 20 63/1 63/2 63/4 3 3 63/1 63/2 63/4 3 3 63/1 63/2 63/4 3 3 22 37 37 18.5 50 80

30
40 40 40 40 40 40 40/1 40/2 40/4 3 3 40/1 40/2 40/4 3 3 40/1 40/2 40/4 3 3 7.5 15 15 15 50 100

60
63 63 63 63 60 40 63/1 63/2 63/4 3 3 63/1 63/2 63/4 3 3 63/1 63/2 63/4 3 3 11 18.5 18.5 15 50 100

100
100 100 100 80 60 40 100/1 100/2 100/4 3 3 100/1 100/2 63/4 3 3 100/1 100/2 63/4 3 3 22 37 37 37 50 100

AC 22A

AC 23A

Rated operational currents/poles in series DC21A 48V 110V 220V 440V 750V 48V 110V 220V 440V 750V 48V 110V 220V 440V 750V 230V 400/415V 500V 690V

DC22A

DC23A

Rated operational power AC23A

Short-circuit current

with back-up fuses of size

18

Load

Load

Load

2 poles in series

3 poles in series

4 poles in series

1 The ambient air temperature does not exceed +40C and its average over a period of 24 hours does not exceed +35C according to IEC 947. 2 IEC 947-3, utilization category B, infrequent operation. 3 Not available at time of printing, please consult factory.

18.60
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Technical data OT200U03 OETL-NF3150 IEC


IEC
Catalog number
Rated insulation and operational voltage, AC20 and DC20 Rated impulse withstand voltage Rated thermal current, Ith AC 20/DC 20 open1 A 40C enclosed 60C enclosed Rated operational currents AC 21A 500V 690V 1000V AC 22A 500V 690V 1000V AC 23A 415V 500V 690V 1000V Rated operational currents/poles in series DC21A 48V 110V 220V 440V 750V DC22A 48V 110V 220V 440V 750V DC23A 48V 110V 220V 440V 750V Rated operational power AC23A 230V 400/415V 500V 690V Short-circuit current with back-up fuses of size kW kW kW kW kA A 75 132/140 170 240 100 400 110 220/230 280 355 100 800 450 560 800 100 800 250 400 450 50/504 250 400 450 50/504 250 400 450 50/634 250 400 450 50/634 A A A A A A A A A A A A A A A 250/1 250/2 250/2 250/3 250/4 250/1 250/2 250/2 250/3 250/4 250/1 250/2 250/2 250/3 250/4 630/2 630/2 630/2 630/3 630/2 630/2 630/2 630/3 630/2 630/2 630/2 800/2 800/2 800/2 800/3 800/2 800/2 800/2 800/3 1250/2 1250/2 1250/2 1250/3 1250/2 1250/2 1250/2 1600/2 1600/2 1600/2 1600/3 1600/2 1600/2 1600/2 2500/2 2500/2 2500/2 2500/3 2500/2 2500/2 2500/2 2500/2 2500/2 2500/2 2500/3 2500/2 2500/2 2500/2 A A A A A A A A A A A A 250 250 400 400 800 800 1250 1250 1000 1600 1600 1250 2500 2300 1950 3150 2300 1950

Di s sw con Te itch nec ch e t da nica s ta l

3 pole
40C V kV

OT200U03 1000 12

OT400U03 1000 12

OT600U03 1000 12

OETL-NF800A 1000 8

OETL-NF1200 1000 8

OETL-NF1600 1000 8

OETL-NF2000 1000 8

OETL-NF3150 1000 8

2600 2300

250
250 250 250 250 250 250

400
400 400 400 400 400 400

800
800 800 800 800 800 800 800 800 800

1250
1250 1250 800 800

1600
1600 1600 800 800

25002
25002 16002 8002 8002

25002
25002 16002 8002 8002

31502
31502 16002 8002 8002 3150/2 3150/2 3150/2 3150/2 3150/2 3150/2 3150/2 250 400 450 50/634

18

Load

Load

Load

2 poles in series

3 poles in series

4 poles in series

1 The ambient air temperature does not exceed +40C and its average over a period of 24 hours does not exceed +35C according to IEC 947. 2 IEC 947-3, utilization category B, infrequent operation. 3 Not available at time of printing, please consult factory. 4 690V / 500V

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

18.61
1SXU000023C0202

t ec nn es o h l sc Di witc nica s ch a Te dat

Technical data OT16F3 OT100F3 IEC


IEC

Catalog number
Rated short-circuit making capacity, prospective peak value, Icm Rated short time withstand current, RMS lcw 0.2s RMS lcw AC breaking capacity pf = 0.35 415V 500V 690V 1.0s

3 pole
kA kA kA A A A

OT16F3
0.7 0.5 128 128 80

OT25F3
0.7 0.5 160 160 88

OT40F3
0.7 0.5 184 184 96

OT63F3
1.4 1 240 240 160

OT80F3
1.4 1 304 256 160

OT30F3
3.6 2.5 320 320 320

OT60F3
3.6 2.5 504 480 320

OT100F3
3.6 2.5 640 480 320

DC breaking capacity/poles in series L/R = 15ms 48V 110V 220V 440V 750V A A A A A 64/1 64/2 64/3 1 1 100/1 100/2 100/4 1 1 128/1 128/2 128/4 1 1 180/1 180/2 180/4 1 1 252/1 252/2 180/4 1 1 160/1 160/2 160/4 1 1 252/1 252/2 252/4 1 1 400/1 400/2 252/4 1 1

Physical characteristics Electrical endurance at rated operational current, pf = 0.65 Mechanical endurance Weight 3 pole 4 pole 3 pole operation cycles operations kg kg H mm W mm D mm W mm Nm mm2 3000 20,000 0.11 0.15 68 35 56 0.3 6x6 1 0.75 10 OA1G_ _ VAC A A A A A A A A A A A A 690 16 6 2 4 2 2 2 3000 20,000 0.11 0.15 68 35 56 0.6 6x6 1 0.75 10 OA1G_ _ 690 16 62 4 2 22 3000 20,000 0.11 0.15 68 35 56 1 6x6 1 0.75 10 OA1G_ _ 690 16 62 4 2 22 3000 20,000 0.27 0.35 91.5 52.5 72.5 1.4 6x6 1.2 1.5 25 OA1G_ _ 690 16 62 4 2 22 3000 20,000 0.27 0.35 91.5 52.5 72.5 2.8 6x6 1.2 1.5 25 OA1G_ _ 690 16 62 4 2 22 3000 20,000 0.36 0.5 100 70 75 1 6x6 2 1.5 25 OA1G_ _ 690 16 62 4 2 22 3000 20,000 0.36 0.5 100 70 75 1.6 6x6 2 1.5 25 OA1G_ _ 690 16 62 4 2 22 3000 20,000 0.36 0.5 100 70 75 4 6x6 2 10 70 OA1G_ _ 690 16 62 4 2 22

Dimension

Power loss per pole Shaft size square

Switch operating torque for rotary 3 pole switches Bolt size Auxiliary contacts Ratings according to IEC 947-5-1 Rated voltage, Ui Thermal current, Ith AC12/DC12 Ie, A Ue =120V 125V 240V 250V 400V 415V 440V 480V 500V 600V 690V Suitable conductor cross section Cu

18

Load

Load

Load

2 poles in series

3 poles in series

4 poles in series

1 Not available at time of printing, please consult factory. 2 AC15, according to IEC947-5-1.

18.62
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Technical data OT200U03 OETL-NF3150 IEC


IEC
Catalog number
Rated short-circuit making capacity, prospective peak value, Icm500/690V Rated short time withstand current, RMS lcw RMS lcw AC breaking capacity pf = 0.35 415V 500V 690V DC breaking capacity/poles in series L/R = 15ms, 3 pole in series 48V 110V 220V 440V 750V Physical characteristics Electrical endurance at rated operational current, pf = 0.65 Mechanical endurance Weight Dimension 3 pole 4 pole 3 pole operation cycles operations kg kg H mm W mm D mm Power loss per one pole Shaft size square Switch operating torque for rotary 3 pole switches Suitable conductor cross section Cu Bolt size Auxiliary contacts Ratings according to IEC 947-5-1 Rated voltage, Ui Thermal rated current, Ith AC12/DC12 Ie, A Ue = 120V 125V 240V 250V 400V 415V 440V 480V 500V 600V 690V VAC A A A A A A A A A A A A 690 16 6/ 4/ 2/ 690 16 6/ 4/ 2/ 690 10 8/ /1.1 6/ /0.55 4/ 4/ /0.31 3/ 3/0.27 /0.2 2/ 690 10 8/ /1.1 6/ /0.55 4/ 4/ /0.31 3/ 3/0.27 /0.2 2/ 690 10 8/ /1.1 6/ /0.55 4/ 4/ /0.31 3/ 3/0.27 /0.2 2/ 690 10 8/ /1.1 6/ /0.55 4/ 4/ /0.31 3/ 3/0.27 /0.2 2/ 690 10 8/ /1.1 6/ /0.55 4/ 4/ /0.31 3/ 3/0.27 /0. 2/ Nm
mm2

Di s sw con Te itch nec ch e t da nica s ta l

3 pole
kA kA kA A A A

OT200U03 30 15 8 2000 2000 2000

OT400U03 65 28 15 3200 3200 3200

OT600U03 80 36 20 5760 5600 5600

OETL-NF800A 105 50 2 6400 6400 2500 3

OETL-NF1200 105 50 2 6400 6400 2500 3

OETL-NF1600 140/105 80 2 6400 6400 4800 4

OETL-NF2000 140/105 80 2 6400 6400 4800 4

OETL-NF3150 140/105 80 2 6400 6400 4800 4

0.2s 1.0s

A A A A A

1000/2 1000/2 1000/2 1000/3 1000/4

1 1 1600/2 1600 1

1 1 2000/2 2000/3 1

1 1 1900/2 1 1

1 1 2600/2 1 1

1 1 2600/2 1 1

1 1 2600/2 1 1

1 1 2600/2 1 1

1000 20,000 1.2 1.6 162 219 92.5 6.5 6x6 7 8 x 25 OA_G_

1000 16,000 2.2 2.6 216 260 130 10 12 x 12 16 10 x 30 OA_G_

1000 10,000 5.2 6.5 250 266 139 40 12 x 12 21 12 x 40 OA_G_

500 10,000 16.3 20.5 372 363 125 40 12 x 12 21 12 x 60 OZXK-_ _

500 10,000 17.5 22.5 372 363 125 67 12 x 12 21 12 x 60 OZXK-_ _

100 5 6000 37 47 546 468 271 90 12 x 12 50 12 x 60 OZXK-_ _

100 5 6000 37 47 546 468 271 90 12 x 12 50 12 x 60 OZXK-_ _

100 5 6000 37 47 546 468 271 140 12 x 12 50 12 x 60 OZXK-_ _ 690 10 8/ /1.1 6/ /0.55 4/ 4/ /0.31 3/ 3/0.27 2/0.2 2/

W mm

18

Load

Load

Load

2 poles in series

3 poles in series

4 poles in series

1 2 3 4 5

Not available at time of printing, please consult factory. Maximum distance between busbar support and switch terminal 70mm. pf 0.95. pf 0.65. IEC 947-3, utilization category B, infrequent operation.

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

18.63
1SXU000023C0202

t ec nn es o h l sc Di witc nica s ch a Te dat

Technical data OS30FA_12 OES800L3 UL & CSA


UL & CSA

Catalog number Approvals 1

3 pole 2 pole 3 pole 4 pole -40 to 40C

OS30FA_12 N/A UL98 & IEC UL98 & IEC

OS60J12 N/A UL98 & IEC UL98 & IEC

OS100J03 IEC UL98 & IEC UL98 & IEC

OS200J03 UL98 & IEC UL98 & IEC UL98 & IEC

OS400J03 UL98 & IEC UL98 & IEC UL98 & IEC

OS600J03 UL98 & IEC UL98 & IEC UL98 & IEC

OES800L3 UL98 & IEC UL98 & IEC UL98 & IEC

Technical ratings
General purpose amp rating pf = 0.7 0.8 Max operating voltage Max horsepower rating/ Max motor FLA current pf = 0.4 0.5 Three phase 240V 480V 600V Single phase 120V 240V Short circuit rating with fuse UL Fuse size UL Fuse type

A
V

30
600

60
600

100
600

200
600

400
600

600
600

800
600

HP/A HP/A HP/A HP/A HP/A kA A

7.5/22.0 15/21.0 20/22.0 2/24.0 3/17.0 200 30 J/CC

15/42.0 30/40.0 50/52.0 200 60 J

30/80.0 60/77.0 75/77.0 200 100 J/T

60/145.0 125/156.0 150/144.0 200 200 J/T

125/312.0 250/302.0 350/336.0 200 400 J

200/480.0 400/477.0 500/472.0 200 600 J

250/602.0 500/590.0 600/ 100 800 L

Endurances Min. Electrical endurance, pf = 0.75 0.80 operation cycles Mechanical endurance operation Physical characteristics Weight Dimension 3 pole lb 4 pole lb 3 pole H in W in D in in mm lb. in.

6000 20,000 1.54 1.98 3.66 4.15 4.10 .24 x .24 6x6 26.6 Integral

6000 20,000 2.86 3.52 3.94 5.63 5.04 .24 x .24 6x6 35.5 Integral #14 4 30 N/A OA_G_ A600 600 10 7200 720 R300 300 1 28 7 #18 14

6000 20,000 3.30 3.96 5.67 7.07 5.10 .24 x .24 6x6 70.9 OZXA-24 #14 2/0 120 50 OA_G_ A600 600 10 7200 720 R300 300 1 28 7 #18 14

6000 20,000 5.9 7.5 6.5 7.1 5.2 .24 x .24 6x6 195 OZXA-200 #4 300kcmil 200 72 OA_G_ A600 600 10 7200 720 R300 300 1 28 7 #18 14

1000 12,000 12.56 15.21 9.29 10.04 6.93 .47 x .47 12 x 12 195 OZXA-400 #2 600kcmil 500 480 OA_G_ A600 600 10 7200 720 P600 600 1 28 7 #18 14

1000 10,000 28.66 37.48 12.04 13.50 9.17 .47 x .47 12 x 12 248 OZXA-800 (2) #2 600 kcmil 500 480 OA_G_ A600 600 10 7200 720 P600 600 7 28 7 #18 14

500 7000 37.44 46.26 10.10 14.80 9.17 .47 x .47 12 x 12 248 OZXA-27 (2) #2 600 kcmil 500 480 OZXK-__ A600 600 10 7200 720 P600 600 5 138 7 #20 12

Shaft size square Switch operating torque for rotary 3 pole switches Terminal lug kits Wire range Torque: Wire tightening Lug mounting Auxiliary contacts NEMA ratings, AC AC rated voltage AC thermal rated current AC maximum volt ampere making AC maximum volt ampere breaking NEMA ratings, DC DC rated voltage DC thermal rated current DC maximum make break current Torque:

AWG lb. in. lb. in.

#18 8 17 N/A OA4G_ OA1/3G_ A600 600 10 7200 720 P300 300 1 28 7 #22 14/#18 14 250 6

VAC A VA VA VDC A A lb. in. AWG

18

Wire tightening Wire range

1 The following UL Listed switches are also CSA approved.

18.64
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Technical data OS30FA_12 OES800L3 IEC


IEC
Catalog number Technical ratings Rated insulation voltage Pollution degree 3 6 Dielectric strength Rated impulse withstand voltage Rated thermal current, Ith/ max. fuse power dissipation 1 AC 20/DC 20 open 2 40C enclosed Enclosed with solid links A/W A/W A/W 32/3.5 32/3.5 32 6 1000 32 32 32 32 32 32 32/2 3 32/2 32/2 32/4 32/2 3 32/2 32/2 32/4 32/2 3 32/2 32/2 32/4 8 14 15 18 25 63/7.5 63/7.5 85 16 1000 63 63 63 63 63 5 63 5 4 4 4 63/4 4 4 4 4 4 63/4 4 4 4 4 4 63/4 4 4 18.5 30 30 37 60 160/12 160/10, 135/12 175 70 1000 160 160 160 160 160 5 160 5 4 4 4 160/3 4 4 4 4 4 160/3 4 4 4 4 4 160/3 4 4 45 80 90 110 132 200/17 200/17 280 95 1000 200 200 200 200 200 200 200/1 200/1 200/1 200/2 180/4 200/1 200/1 200/1 200/2 180/4 200/1 200/1 200/1 200/2 180/4 60 110 110 140 190 400/45 400/34, 360/37 450 240 1000 400 400 400 400 400 400 400/2 400/2 400/2 400/2 400/3 400/4 400/2 400/2 400/2 400/2 400/3 400/4 400/2 400/2 400/2 400/2 400/3 132 220 230 280 400 630/60 600/45, 570/50 700 2 x 185 1000 630 630 630 630 630 630 200 355 355 450 630 3 pole -40 to 40C V kV 1000 10 12 1000 10 12 1000 10 12 1000 10 12 1000 10 12 1000 10 12 OS30FA_12 OS60J12 OS100J03 OS200J03 OS400J03 OS600J03

Di s sw con Te itch nec ch e t da nica s ta l

OES800L3

1000 10 12

50Hz/60Hz, 1 min kV

800/65 720/55 900 2 x 240 1000 800 800 800 800 720 720 800/2 800/2 800/2 800/2 800/3 800/4 800/2 800/2 800/2 800/2 800/3 800/4 800/2 800/2 800/2 800/2 800/3 800/4 200 350 380 470 600

with minimum cable cross section Cu mm2 Rated operational voltage AC 20 and DC 20V AC Rated operational currents AC 21A AC 22A AC 23A 500V 690V 500V 690V 500V 690V 48V 110V 220V 440V 750V 1000V 48V 110V 220V 440V 750V 1000V 48V 110V 220V 440V 750V 1000V A A A A A A A A A A A A A A A A A A A A A A A A AC23A kW kW kW kW kW

DC Rated operational currents/poles in series DC21A

DC22A

DC23A

Rated operational power 230V 400V 415V 500V 690V

18
Load Load Load

Load
2 + 2 parallel contacts in series

2 poles in series

3 poles in series

4 poles in series

1 2 3 4 5 6

Ambient temperature 60C: derating 20 percent. Mounting on ceiling: derating 10 percent. Mounting on wall, horizontal fuses: derating 8 percent. The ambient air temperature does not exceed +40C and its average over a period of 24h does not exceed +35C according to IEC 947. For 30A switches, use 2 + 2 parallel contacts in series. Available on request. IEC 947-3, utilization category B, infrequent operation. Pollution degree 3: Conductive pollution occurs, or dry, non-conductive pollution occurs, which becomes conductive due to condensation.

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

18.65
1SXU000023C0202

t ec nn es o h l sc Di witc nica s ch a Te dat

Technical data OS30FA_12 OES800L3 IEC


IEC

Catalog number Rated breaking capacity in category AC-23A 500V 690V

3 pole

OS30FA_12

OS60J12

OS100J03

OS200J03

OS400J03

OS600J03

OES800L3

A A

256 256 128/2 128/4 9 7.5 6 1

504 504 17 17 13 2.5

1280 1280 22 22 15 5

1600 1600 1000/2 1000/2 1000/3 35 37.5 35 8

3200 3200 1600/2 1600/2 1600/3 40 40 35 10

5760 5760 3200/2 3200/2 3200/3 3200/4 75 75 60 16

5760 5760 3200/2 3200/2 3200/3 3200/4 75 75 60 16

A A A A Rated conditional short-circuit current r.m.s. 3 80 kA, 415V kA 100 kA, 500 V kA 50 kA, 690 V kA Rated short time withstand current, 1s. kA Rated capacitor power The capacitor rating of the fusible disconnect switch is limited by the fuse link 400 V kVar 415V kVar 690V kVar Power loss/pole with rated current, without fuse W Mechanical endurance operations Fuse types, IEC 269-2 DIN 43620 NFC BS 88

Rated breaking capacity/poles in series in category DC-23 <220V 440V 500 750V 1000V

15 15 25 2 20,000 10 x 38, 14 x 51 A1, A2, F1 M4/44.5(A1) M5/73(A2)

30 32 50 4 20,000 000, 00 14 x 51, 22 x 58 A2 A3 M5/73

9 20,000 000, 00 22 x 58 A2 A4 M5/73 M8/94 1.5 1.8 144 179 129 6x6 M6 x 20 69 3.5 5 8 OA_G_ 2 690 16 6/ 4/ 2/

8 20,000 B1 B2 M6/111

180 200 325 30 16,000 02 02 B1 B4 M8/111

250 270 450 46 10,000 3 3 C1 C2 M10/133, 184

310 340 550 77 10,000 3 C1 C3 M10/133, 184

size/distance of link bolts Physical characteristics Weight Dimension 3 pole 4 pole 3 pole kg kg H mm W mm D mm square
2

0.7 0.9 93 106 104 6x6 0.5 10

1.3 1.6 100 143 120 6x6 2.5 25 3.5 3.5 4

2.6 7.9 198.5 181.5 132 6x6 M8 x 25 15 22 4 7 OA_G_ 2 690 16 6/ 4/ 2/

5.7 6.9 236 255 176 12 x 12 M10 x 40 30 44 15 22 OA_G_ 690 16 2/

13.0 17.0 306 343 233 12 x 12 M12 x 40 50 75 40 28 OA_G_ 690 16 2/

17.0 21.0 282 376 233 12 x 12 M12 x 40 50 75 40 28 OZXK-_ 690 10 8 / / 1.1 6/ / 0.55 4/ 4/ / 0.31 3/ 3 / 0.27 / 0.2 2/

Shaft size Terminals

mm

Built-in terminal size mm Terminal bolt size, metric thread diameter x length mm Terminal bolt tightening torque Fuse-links bolts tightening torque Operating torque Auxiliary contacts Ratings according to IEC 947-5-1 Rated voltage, Ui Thermal current, Ith Ue=24V AC12 / DC12, Ie 120V 125V 230V 250V 400V 415V 440V 480V 500V 600V 690V

Nm Nm Nm OA4G_ 1 VAC A A A A A A A A A A A A A 690 10 /6 /6 3 / 0.1 2/

2 2 3 OA1/3G 2 690 16 6/ 4/ 2/

OA_G_ 2 690 16 6/ 4/ 2/

18

1 AC15 / DC12, according to IEC 947-5-1 2 AC15, according to IEC 947-5-1 3 Values shown are corresponding max. allowed cut-off current, peak-values per single phase fuse tests.

18.66
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Auxiliary contact timing diagrams OT16 OT100

Di s sw con Te itch nec ch e t da nica s ta l

Legend
0
Main contacts
OFF
O OFF

30

60

90
ON
I ON

N.O. auxiliary contact N.C. auxiliary contact

OFF 0

= Contacts in closed position = Contacts in closed position

ON I

Contacts closing 1 Main contacts close 2 N.O. auxiliary contacts close 3 N.C. auxiliary contacts open

Contacts opening 4 Main contacts open 5 N.O. auxiliary contacts open 6 N.C. auxiliary contacts close 0 30 60 90

OT16, OT25, OT40


Catalog number Auxiliary contact Contact configuration

Main contacts OA1G10 N.O. auxiliary contact OA1G01 N.C. auxiliary contact OA2G11 N.O. auxiliary contact N.C. auxiliary contact

OT16, OT25, OT40

OA1G10 OA1G01 OA2G11

1 N.O. 1 N.C. 1 N.O. & 1 N.C.

OFF 0

= Contacts in closed position = Contacts in closed position

ON I

0
Main contacts

30

60

90

OT63, OT80
Catalog number Auxiliary contact Contact configuration

OA1G10 N.O. auxiliary contact OA1G01 N.C. auxiliary contact OA2G11 N.O. auxiliary contact N.C. auxiliary contact

OT63, OT80

OA1G10 OA1G01 OA2G11

1 N.O. 1 N.C. 1 N.O. & 1 N.C.

OFF 0

= Contacts in closed position = Contacts in closed position

ON I

18

30

60

90

OT30, OT60, OT100


Catalog number Auxiliary contact Contact configuration

Main contacts OA1G10 N.O. auxiliary contact OA1G01 N.C. auxiliary contact OA2G11 N.O. auxiliary contact N.C. auxiliary contact

OT30, OT60, OT100

OA1G10 OA1G01 OA2G11

1 N.O. 1 N.C. 1 N.O. & 1 N.C.

OFF 0

= Contacts in closed position = Contacts in closed position

ON I

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

18.67
1SXU000023C0202

t ec nn es o h l sc Di witc nica s ch a Te dat


OT200U03 OT600U03
Catalog number OT200U03 OT600U03

Auxiliary contact timing diagrams OT200U OETL-NF3150

Auxiliary contact OA1G10 OA3G01

Contact configuration 1 N.O. 1 N.C.

ON and OFF- functions of main and auxiliary contacts


Contact type Shaft movement
TEST -45

Handle movement
OFF 0 30 60 ON 90

Main contacts

0 0 0 0 0 0 0 0 0 0 0 0 0 0

I I I I I I I I I I I I I I

NO contacts inside the mechanism NC contacts inside the mechanism NO test indication-only contacts inside the mechanism NC test indication-only contacts inside the mechanism NO auxiliary contacts in the module on the side of the switch NC auxiliary contacts in the module on the side of the switch

OETL-NF800A OETL-NF3150
Catalog number Auxiliary contact Contact configuration

0
1 N.O. & 1 N.C. 2 N.O. & 2 N.C. 4 N.O. & 4 N.C.

30

60

90

OETL-NF800A OETL-NF3150

OZXK-1 OZXK-2 OZXK-3

Main contacts N.O. auxiliary contact N.C. auxiliary contact

OFF 0

= Contacts in closed position = Contacts in closed position OZXK-1 OZXK-2 OZXK-3

ON I

18

18.68
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Auxiliary contact timing diagrams OS30_ OS100

Di s sw con Te itch nec ch e t da nica s ta l

Legend
0
Main contacts N.O. auxiliary contact N.C. auxiliary contact

30

60 0 I 0 I 4
3 6 5 1 2

90 a
OFF
O OFF

I ON

ON

OFF 0

= Contacts in closed position = Contacts in closed position

ON I

Contacts closing 1 Main contacts close 2 N.O. auxiliary contacts close 3 N.C. auxiliary contacts open

Contacts opening 4 Main contacts open 5 N.O. auxiliary contacts open 6 N.C. auxiliary contacts close

OS30_
Catalog number Auxiliary contact Contact configuration

-45
OA4B1C OA1G10 OA3G01 1 N.O. & 1 N.C. 1 N.O. 1 N.C.
Main contacts OA4B1C N.O. auxiliary contact OA4B1C N.C. auxiliary contact OA1G10 N.O. auxiliary contact OA3G01 N.C. auxiliary contact Test

30

60

90 a

OS30_

OS60
Catalog number Auxiliary contact Contact configuration

-45
OA1G10 OA3G01 1 N.O. 1 N.C.
Installed in mechansim

30

60

90 a

Main contacts

OS60

OA1G10 N.O. auxiliary contact OA3G01 N.C. auxiliary contact OA1G10 N.O. auxiliary contact OA3G01 N.C. auxiliary contact Test
Installed on side of switch

OS100
Catalog number Auxiliary contact Contact configuration

-45
OA1G10 OA3G01 1 N.O. 1 N.C.
Ins talled in mechanis m

30

60

90

Main contacts N.O. auxiliary contact

18

OS100

OA3G01 N.C. auxiliary contact


Ins talled on s ide of s witch

OA1G10 N.O. auxiliary contact OA3G01 N.C. auxiliary contact


T es t location

OA1G10 N.O. auxiliary contact OA3G01 N.C. auxiliary contact Test

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

18.69
1SXU000023C0202

t ec nn es o h l sc Di witc nica s ch a Te dat


OS200 - OS600 ON and OFFContact type

Auxiliary contact timing diagrams OS200 OES800


functions of main and auxiliary contacts
Shaft movement
TEST -45

Handle movement
OFF 0 30 60 ON 90

Main contacts

0 0 0 0 0 0 0 0 0 0 0 0 0 0

I I I I I I I I I I I I I I

NO contacts inside the mechanism NC contacts inside the mechanism NO test indication-only contacts inside the mechanism NC test indication-only contacts inside the mechanism NO auxiliary contacts in the module on the side of the switch NC auxiliary contacts in the module on the side of the switch

OES800
Catalog number Auxiliary contact Contact configuration

0o
Main contacts N.O. auxiliary contact N.C. auxiliary contact

30

60

90

OES800

OZXK-1 OZXK-2 OZXK-3 OZXK-4 OZXK-5 OZXK-6

1 N.O. & 1 N.C. 2 N.O. & 2 N.C. 4 N.O. & 4 N.C. 2 N.O. 4 N.O. 8 N.O.

18

OZXK-1 OZXK-2 OZXK-3 OZXK-4 OZXK-5 OZXK-6

18.70
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Technical data Other configuration descriptions


Conversion mechanisms
6 or 8 pole
2

Di s sw con Te itch nec ch e t da nica s ta l

6 (8) pole mechanism allows two switches controlled by one handle to open or close simultaneously.

POS. O SW. A SW. B


X = Closed O = Open

POS.I X X

O O

Double throw1

Transfer mechanism manually transfers between two power sources using two switches and a center "OFF" position.

POS. I
SW. A SW. B SW. A SW. B SW. A SW. B

POS.O O O

POS.II O X

SW. A SW. B
X = Closed O = Open

X O

LOAD

LOAD

LOAD

II

Bypass1

Bypass mechanism operates three switches: Two switches in series and one changeover switch to allow power bypass.

POS. I SW. A SW. B SW. C


X = Closed O = Open

POS.O O O O

POS.II X X O

O O X

II

Mechanical interlock

SW. A SW. B POS. I POS. O SW. A SW. B


X = Closed O = Open

Mechanical interlock mechanism prevents both switches from being in the ON position at the same time.

X O

O X

18

1 Transfer and bypass enclosed switches include the load side bussed or cabled together and all switches come standard with ground lugs. 2 = Three poles

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

18.71
1SXU000023C0202

t ec nn es o h l sc Di witc nica s ch a Te dat

NEMA Environmental ratings

Introduction An enclosure is a surrounding case constructed to provide a degree of protection to personnel against accidental contact with the enclosed equipment and to provide a degree of protection to the enclosed equipment against specified environmental conditions. A brief description of the more common types of enclosures used by the electrical industry relating to their environmental

capabilities follows. Refer to NEMA Standards Publication for more information regarding applications, features and design tests. Individual NEMA product Standards Publications or third party certification standards may contain additional requirements for product testing and performance.

Definitions pertaining to nonhazardous locations

Definitions pertaining to hazardous locations

Type 1 Enclosures are intended for indoor use primarily to provide a degree of protection against limited amounts of falling dirt. (NEMA Standard 7-15-1991.)

Type 4X Enclosures are intended for indoor or outdoor use primarily to provide a degree of protection against corrosion, windblown dust and rain, splashing water, hose-directed water and damage from external ice formation. (NEMA Standard 1-10-1979)

Type 7 Enclosures are intended for indoor use in locations classified as Class I, Groups, A, B, C, or D, as defined in the National Electrical Code. (NEMA Standard 7-15-1991.)

Type 3R Enclosures are intended for outdoor use primarily to provide a degree of protection against rain, sleet and damage from external ice formation. (NEMA Standard 7-15-1991.)

Type 12 Enclosures are intended for indoor use primarily to provide a degree of protection against circulating dust, falling dirt, and dripping noncorrosive liquids. (NEMA Standard 7-15-1991.)

Type 9 Enclosures are intended for indoor use in locations classified as Class II, Groups E, F, or G, as defined in the National Electrical Code. (NEMA Standard 7-15-1991.)

Legend

18

Indoors
Type 4 Enclosures are intended for indoor or outdoor use primarily to provide a degree of protection against windblown dust and rain, splashing water, hose-directed water and damage from external ice formation. (NEMA Standard 1-10-1979.) Type 13 Enclosures are intended for indoor use primarily to provide a degree of protection against dust, spraying of water, oil and noncorrosive coolant. (NEMA Standard 1-10-1979.)

Outdoors Water Dirt/dust

Corrosion

18.72
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

IEC Environmental ratings

Di s sw con Te itch nec ch e t da nica s ta l

IP ratings

indicate the degree of protection against dust, liquids and impacts. The IP degrees of protection are defined by the French standard NFC 20-010. To rate a device's degrees of protection, the letters IP are followed by up to three numbers. These numbers are defined as follows:

protection against solid objects no protection

first number

protection against liquids no protection

second number

protection against mechanical impacts no protection

third number

IP 0 1

IP 0 1

IP 0 1

protected against solid objects over 50mm (e.g. accidental touch by hands.)

protected against vertically falling rain or condensation

impact 0,225 joule 150g falling from 15 cm

protected against solid objects over 12 mm (e.g. fingers)

protected against direct sprays of water up to 15 from vertical

impact 0,375 joule 250g falling from15 cm

protected against solid objects over 2.5 mm (tools & wires)

protected against sprays to 60 from vertical

impact 0,50 joule 250g falling from 20cm

protected against solid objects over 1mm (small tools & small wires)

protected against water sprayed from all directions

impact 2,00 joule 500g falling from 40 cm

protected against dust (no harmful deposit)

protected against low pressure jets of water from all directions

impact 6,00 joule 1.5kg falling from 40 cm

totally protected against dust

protected from strong jets of water (e.g. for use on ship decks)

impact 20,00 joule 5 kg falling from 40 cm

18

protected against the effects of immersion between 15cm and 1m

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

18.73
1SXU000023C0202

t ec nn es o h l sc Di witc nica s ch a Te dat

Definitions

AC Alternating current Current that reverses its direction of flow twice per cycle. Ambient temperature Temperature of the air surrounding the unit. Amp rating The basic unit of measurement for electric current (columbs / seconds). Conventional thermal current Ith Value of the current the disconnect switch can withstand with poles in closed position, in free air for an eight hour duty, without the temperature rise of its various parts exceeding the limits specified by the standards. Cycle duration Total time of the on-load + off-load period. DC Direct current Current that flows in only one direction. Electrical endurance Number of on-load operating cycles. IEC environmental protection type see page 18.48. Full load amp current FLA The current required by a motor to produce full-load torque at the motor's rated speed. Inductive load An electrical load characterized by having significant inrush (5 to 6 times FLA for typical design-B AC induction motors). kW Kilowatts (1000 watts) Lockout/Tagout Means of removing power from electrical equipment during inspection, service or repair. Make / Break ON / OFF Mechanical endurance Number of off-load operating cycles. Poles in series Means of connection poles using wires or bus bars to increase breaking capacity of load. Power factor The relationship between working power and total power consumed. Power factor measures how effectively electrical power is being used. Rated insulation Ui Voltage value which designates the unit and to which dielectric tests, clearance and creepage distances are referred.

Rated operating current Ie Current value stated by the manufacturer and taking into account the rated operating voltage Ue, the rated frequency, the rated duty, the utilization category, the electrical contact life and the type of protective enclosure. Rated operating voltage Ue Voltage value to which utilization characteristics of the disconnect switch are referred, i.e. phase-to-phase voltage in 3 phase circuits. Rated short circuit making capacity Icm The rated shortcircuit making capacity of a disconnect switch, a disconnector or a switch-disconnector is the value assigned to equipment at the rated operational voltage, frequency (if any) and specified power-factor for AC or time constant for DC. It is expressed as the maximum prospective peak current under prescribed conditions. Rated short time withstand current Icw The rated shorttime withstand current of a disconnect switch, a disconnector or a switch-disconnector is the value that the equipment can carry without damage, under the test conditions specified in the relevant product standard. The value of the rated shorttime withstand current shall be not less than twelve times the maximum rated operational current unless otherwise stated by manufacturer and the duration of the current shall be 1 s. Resistive load An electrical load characterized by not having any significant inrush current. Short circuit protection coordination Co-ordination types "1" and "2" are defined in IEC 947-4-1. Type 1 coordination There has to be no discharge of parts beyond the enclosure. Damage to the contactor and the overload is acceptable. Type 2 coordination No damage to the overload relay or other parts has occurred, except that welding of contactor or starter contacts is permitted, if they are easily separated. Time constant Ratio of inductance to the resistance: L/R = mH/Ohm = ms. Torque The force that produces rotation. It is commonly measured in pound-feet (lb-ft). Torque applies to such things as motor operations, handle rotations, wire tightening. NEMA environmental protection type see page 18.47. Volt The unit of electrical potential difference and electromotive force.

18

18.74
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage