Professional Documents
Culture Documents
For the
Prepared by
____________________________________
TABLE OF CONTENTS
1.0 PURPOSE AND OBJECTIVE(S) .................................................................................................................................... 4
2.0 BACKGROUND .............................................................................................................................................................. 4
3.0 SCOPE ........................................................................................................................................................................... 4
4.0 REFERENCES ............................................................................................................................................................... 4
5.0 RESPONSABILITIES ...................................................................................................................................................... 5
5.1 Validation Specialist ................................................................................................................................................... 5
5.2 Quality Dept. ............................................................................................................................................................... 5
5.3 Facility Dept. ............................................................................................................................................................... 5
6.0 METHODOLOGY............................................................................................................................................................ 6
6.1 Verification Data Sheet ............................................................................................................................................... 6
6.2 Deviation Report ......................................................................................................................................................... 6
6.3 Signature Log Sheet ................................................................................................................................................... 6
6.4 Test Instruments Calibration ....................................................................................................................................... 6
7.0 EQUIPMENT/PROCESS DESCRIPTION ....................................................................................................................... 7
7.1 Water Softener ........................................................................................................................................................... 7
7.2 Ozone Generator ........................................................................................................................................................ 7
7.3 Reverse Osmosis ....................................................................................................................................................... 7
7.4 Mixed Bed................................................................................................................................................................... 7
7.5 Ozone Destructor ....................................................................................................................................................... 7
7.6 De-gasifier .................................................................................................................................................................. 8
7.7 UV light ....................................................................................................................................................................... 8
7.8 Filter ........................................................................................................................................................................... 8
APPENDIX I: DEVIATION REPORT .......................................................................................................................................... 11
APPENDIX II: SIGNATURE IDENTIFICATION LOG SHEET .................................................................................................... 12
APPENDIX III: TESTING INSTRUMENTS LOG SHEET ........................................................................................................... 13
IQ-01 EQUIPMENT VERIFICATION .......................................................................................................................................... 15
IQ-02 DOCUMENT INVENTORY VERIFICATION .................................................................................................................... 37
IQ-03 DRAWING VERIFICATION .............................................................................................................................................. 56
IQ-04 SYSTEM DESIGN VERIFICATION.................................................................................................................................. 58
IQ-05 PLACEMENT VERIFICATION ......................................................................................................................................... 60
IQ-06 UTILITY VERIFICATION .................................................................................................................................................. 67
IQ-07 INSTRUMENTATION VERIFICATION ............................................................................................................................. 86
IQ-08 MAINTENANCE VERIFICATION ..................................................................................................................................... 88
IQ-09 SAFETY & ERGONOMICS VERIFICATION .................................................................................................................. 107
IQ-10 PROCEDURE VERIFICATION ...................................................................................................................................... 109
IQ CHECKLIST VERIFICATION .............................................................................................................................................. 127
REVISION HISTORY
2.0 BACKGROUND
In order to meet the new purified water utility demands at ___ I in ___ ___, ___ ___, a new purified
water system was purchased to replace the existing system. It is expected that this new purified
water system will increase the supply to up to 100 GPM. Additionally, it is intended to produce a
water quality that meets or exceeds current Purified Water USP and EP standards.
3.0 SCOPE
This protocol applies to the new equipment and auxiliary components that constitute the Purified
Water System, installed at ___ in ___ ___, ___ ___
4.0 REFERENCES
• FDA’s Office of Regulatory Affairs: “Guide To Inspections of High Purity Water Systems”
5.0 RESPONSABILITIES
5.1 Validation Specialist
• Prepare the documents that are applicable to the Validation exercise
• Coordinate efforts and resources, along with Facilities Dept., to perform the Validation
exercise
• Execute and collect the verification data for the Validation protocol
• Verify data against Acceptance Criteria and initiate deviation, as applicable
• Investigate, justify, and correct any deviation encountered during Validation execution
• Prepare validation Final Report
5.2 Quality Dept.
• Evaluate with the originator the extent of the validation required
• Review and approve documents for the validation exercise
• Review and approve validation activities for compliance and adherence to ___’s policies,
practices, and procedures
• Check that the collected data meets the acceptance criteria and that all the deviations (if
applicable) are properly resolved
• Once executed, review any deviations generated to confirm that investigation and
resolutions are complete
• Cooperate with Validation Specialist to investigate, justify, and correct any deviation
encountered during Validation execution
• Review and approve Final Report
• Maintain original validation documentation, except for drawings and equipment manuals
that will remain in the equipment information files
• Store the Validation Package in a designated filing area
5.3 Facility Dept.
• Review and approve documents for the validation exercise
• Coordinate efforts and resources to perform the validation activities
• Supply documentation and tools needed for the protocol execution
• Provide training in this protocol to all employees involved (internal and external) during the
execution of this protocol and ensure that all signatures are collected on Signature Log
Sheet
• Assist to document, investigate, justify, and correct any deviation encountered during the
IQ protocol execution
• Review and approve validation Final Report
• Provide technical support for trouble shooting during the execution
6.0 METHODOLOGY
6.1 Verification Data Sheet
All data resulting from test execution will be entered in Verification Data Sheets that will pre-
define the objective(s) to be attained with the verification, the procedure that will be followed
to reach such objective(s), the reference material to be used, and the criteria to evaluate as
to accept or not the testing results. All data entry will be properly signed and dated by the
executor in the “Performed By” and “Date” spaces. In cases where a Field Verification is
requested, a “Fail” condition will be applied to unverifiable information.
The comments/observations section included in each Data Collection Form will be used to
describe any additional information considered of importance for describing the validated
condition and/or discrepancies and resolution activities produced during the execution. The
comments/observations included must be signed or initialed and dated.
When the test execution is finished, a subject matter expert will sign and date on the
“Reviewed by” and “Date” spaces respectively, to state the completeness and correctness of
the data.
6.2 Deviation Report
The following deviations must be documented using the Deviation Report Form attached to
this protocol:
• Results invalidated and/or not in compliance with their pre-established Acceptance Criteria
• Testing procedure and/or sampling plan not followed or that could not be completed as
planned
These deviations will be handled as per ___ ___ PR
The investigation process due to deviated sampling results will be handled by contract
laboratory, following their own investigation procedures. These incidents will be informed to
who oversees the validation project in ___ ___, ___ PR, which in turn will open a deviation
report to follow the lifecycle of the investigation and to implement any possible changes due
to investigation resolution.
Typographic, text edit and syntax errors will be documented as such in the “Comments”
section under the corresponding test script, and considered as a minor issue that may not
invalidate a test or become cause for writing a deviation report. These will be explained in the
Final Report.
6.3 Signature Log Sheet
Each individual who signs or initials any page included in this protocol shall be identified
using the Signature Log Sheet by type/printed name, full signature, written initials and
department represented.
6.4 Test Instruments Calibration
All testing equipment used during for the execution shall be currently calibrated with
documented evidence of its “up to date” calibration status. Copies of the calibration
certificates shall be attached to the protocol and referred to the applicable test script.
7.0 EQUIPMENT/PROCESS DESCRIPTION
Purified Water▲ is water obtained by distillation, ion-exchange treatment, reverse osmosis, and
other suitable processes. It is prepared from water complying with the regulations of U.S.
Environmental Protection Agency (EPA) with respect to drinking water. It contains no added
substances.
The Purified Water system includes the following equipment, along with associated components:
ENGINEERING INVESTIGATION
Comments:
This sheet is intended to record each individual who takes part of the execution process and is not
included in the front page. The scope of this sheet applies to anyone who signs or initials any page
included in the attached qualification documents. Each person shall be identified by typed or printed
name, full signature, written initials, and department represented.
This sheet is intended to record all field test instrument that assists in the execution process.
COPY OF
CALIBRATION CERTIFICATE PERFORMED
INSTRUMENT ID DESCRIPTION TEST ID
DATE/DUE DATE ATTACHED? BY/DATE
(YES/NO)
VERIFICATION DATA SHEETS
INSTALLATION QUALIFICATION
MAIN COMPONENT VERIFICATION IQ-01
Objective:
• Assure that all main and auxiliary components of the Purified Water System are as per
manufacturer/vendor specifications (Manuals, Spec sheets, P & ID’s, etc.)
Procedure:
a. Per equipment, collect and document the required information thru physical inspection (tag,
engrave, plate, sticker, etc)
b. Evaluate findings against specifications
References Required:
• Note: Vendor/Manufacturer documentation (Manuals, Spec sheets, P & ID’s, etc.) does not
count as “Actual Result” reference
Acceptance Criteria:
EXPECTED PERFORMED
SPEC ACTUAL RESULT PASS/FAIL
RESULT BY/DATE
Tag ID
Cartridge
Manufacturer
Cartridge Part
No.
1A
Housing
Manufacturer
Housing
Part No.
Quantity
Tag ID
Cartridge
Manufacturer
Cartridge Part
No.
1B
Housing
Manufacturer
Housing
Part No.
Quantity
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
EXPECTED PERFORMED
SPEC ACTUAL RESULT PASS/FAIL
RESULT BY/DATE
Tag ID
Cartridge
Manufacturer
Cartridge Part
No.
2A
Housing
Manufacturer
Housing
Part No.
Quantity
Tag ID
Cartridge
Manufacturer
Cartridge Part
No.
2B
Housing
Manufacturer
Housing
Part No.
Quantity
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
EXPECTED PERFORMED
SPEC ACTUAL RESULT PASS/FAIL
RESULT BY/DATE
Tag ID
Cartridge
Manufacturer
Cartridge Part
No.
3A
Housing
Manufacturer
Housing
Part No.
Quantity
Tag ID
Cartridge
Manufacturer
Cartridge Part
No.
3B
Housing
Manufacturer
Housing
Part No.
Quantity
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
EXPECTED PERFORMED
SPEC ACTUAL RESULT PASS/FAIL
RESULT BY/DATE
Tag ID
Cartridge
Manufacturer
Cartridge Part
No.
4A
Housing
Manufacturer
Housing
Part No.
Quantity
Tag ID
Cartridge
Manufacturer
Cartridge Part
No.
4B
Housing
Manufacturer
Housing
Part No.
Quantity
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
EXPECTED PERFORMED
SPEC ACTUAL RESULT PASS/FAIL
RESULT BY/DATE
Tag ID
Cartridge
Manufacturer
Cartridge Part
No.
5A
Housing
Manufacturer
Housing
Part No.
Quantity
Tag ID
Cartridge
Manufacturer
Cartridge Part
No.
5B
Housing
Manufacturer
Housing
Part No.
Quantity
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
EXPECTED PERFORMED
SPEC ACTUAL RESULT PASS/FAIL
RESULT BY/DATE
Tag ID
Manufacturer
Model
Serial No.
Tag ID
Booster pump
Manufacturer
Model
Serial No.
Tag ID
Recirculation pump
Manufacturer
Model
Serial No.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
EXPECTED PERFORMED
SPEC ACTUAL RESULT PASS/FAIL
RESULT BY/DATE
Tag ID
Manufacturer
Model
Serial No.
Tag ID
Manufacturer
UV light
Model
Serial No.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
EXPECTED PERFORMED
SPEC ACTUAL RESULT PASS/FAIL
RESULT BY/DATE
Tag ID
Manufacturer
Unit A
Model
Serial No.
Tag ID
Manufacturer
Unit B
Model
Serial No.
Manufacturer
Control Panel
Model
Resin
Type
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
EXPECTED PERFORMED
SPEC ACTUAL RESULT PASS/FAIL
RESULT BY/DATE
Tag ID
Manufacturer
Model
Serial No.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
EXPECTED PERFORMED
SPEC ACTUAL RESULT PASS/FAIL
RESULT BY/DATE
Tag ID
Manufacturer
Description
Cartridge
Manufacturer
Cartridge
Vent Filter
Part No.
Housing
Manufacturer
Housing
Part No.
Manufacturer
Level
Part No.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
EXPECTED PERFORMED
SPEC ACTUAL RESULT PASS/FAIL
RESULT BY/DATE
Tag ID
Manufacturer
1A
Model
Serial No.
Tag ID
Manufacturer
2A
Model
Serial No.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
EXPECTED PERFORMED
SPEC ACTUAL RESULT PASS/FAIL
RESULT BY/DATE
Tag ID
Manufacturer
Description
Cartridge
Manufacturer
Cartridge
Vent Filter
Part No.
Housing
Manufacturer
Housing
Part No.
Manufacturer
Level
Part No.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
EXPECTED PERFORMED
SPEC ACTUAL RESULT PASS/FAIL
RESULT BY/DATE
Tag ID
Manufacturer
2A
Model
Serial No.
Tag ID
Manufacturer
2B
Model
Serial No.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
EXPECTED PERFORMED
SPEC ACTUAL RESULT PASS/FAIL
RESULT BY/DATE
Tag ID
Manufacturer
1A
Model
Serial No.
Tag ID
Manufacturer
1B
Model
Serial No.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
EXPECTED PERFORMED
SPEC ACTUAL RESULT PASS/FAIL
RESULT BY/DATE
Tag ID
Manufacturer
2A
Model
Serial No.
Tag ID
Manufacturer
2B
Model
Serial No.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
Tag ID
Manufacturer
Model
Serial No.
Tag ID
Feed Pump
Manufacturer
Model
Serial No.
Antiscalant Dosing System
Tag ID
Manufacturer
Model
Serial No.
Control Panel
Manufacturer
Model
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
Tag ID
Manufacturer
Model
Serial No.
Tag ID
Feed Pump
Manufacturer
Model
Serial No.
Antiscalant Dosing System
Tag ID
Manufacturer
Model
Serial No.
Control Panel
Manufacturer
Model
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
Tag ID
Manufacturer
Model
Serial No.
Tag ID
Cleaning Pump
Manufacturer
Model
Serial No.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
EXPECTED PERFORMED
SPEC ACTUAL RESULT PASS/FAIL
RESULT BY/DATE
Tag ID
Manufacturer
Model
Serial No.
Tag ID
Manufacturer
Pump
Model
Serial No.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
EXPECTED PERFORMED
SPEC ACTUAL RESULT PASS/FAIL
RESULT BY/DATE
Tag ID
Manufacturer
Unit A
Model
Serial No.
Tag ID
Manufacturer
Unit B
Model
Serial No.
Manufacturer
Control Panel
Model
Caustic
Acid &
Type
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
EXPECTED PERFORMED
SPEC ACTUAL RESULT PASS/FAIL
RESULT BY/DATE
Tag ID
Manufacturer
Part No.
Serial No.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
• Assure that all the basic literature required for the system operation/maintenance of the Purified
Water system is available and properly stored
Procedure:
a. Per equipment, collect all related documentation
b. Document all relevant information according to “Document Info” column
c. If any of the “document type” is not applicable, write an Not Apply to the “Document Info”
column and explain in the “Comments/Observations” section
References Required:
• At least the basic literature (see document type) was found for all equipment and was found to
be properly stored
Installation and
Operation
Manual
Purchase Order
Drawings
P & ID’s
Other
Documents
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________ If NO, refer to Deviation # __________
Installation and
Operation
Manual
Purchase Order
Drawings
P & ID’s
Other
Documents
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________ If NO, refer to Deviation # __________
Installation and
Operation
Manual
Purchase Order
Drawings
P & ID’s
Other
Documents
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________ If NO, refer to Deviation # __________
Installation and
Operation
Manual
Purchase Order
Drawings
P & ID’s
Other
Documents
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________ If NO, refer to Deviation # __________
Installation and
Operation
Manual
Purchase Order
Drawings
P & ID’s
Other
Documents
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________ If NO, refer to Deviation # __________
Installation and
Operation
Manual
Purchase Order
Drawings
P & ID’s
Other
Documents
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________ If NO, refer to Deviation # __________
Purchase Order
Electrical
Drawings
Mechanical
Drawings
P & ID’s
PLC Software
Backup &
Report
MSDS
Other
Documents
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________ If NO, refer to Deviation # __________
Installation and
Operation
Manual
Purchase Order
Drawings
P & ID’s
Other
Documents
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________ If NO, refer to Deviation # __________
Installation and
Operation
Manual
Purchase Order
Electrical
Drawings
Mechanical
Drawings
P & ID’s
Other
Documents
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________ If NO, refer to Deviation # __________
Installation and
Operation
Manual
Purchase Order
Drawings
P & ID’s
Other
Documents
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________ If NO, refer to Deviation # __________
Installation and
Operation
Manual
Purchase Order
Electrical
Drawings
Mechanical
Drawings
P & ID’s
Other
Documents
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________ If NO, refer to Deviation # __________
Installation and
Operation
Manual
Purchase Order
Electrical
Drawings
Mechanical
Drawings
P & ID’s
PLC Software
Backup &
Report
Other
Documents
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________ If NO, refer to Deviation # __________
Installation and
Operation
Manual
Purchase Order
Electrical
Drawings
P & ID’s
PLC Software
Backup &
Report
Other
Documents
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________ If NO, refer to Deviation # __________
Installation and
Operation
Manual
Purchase Order
Electrical
Drawings
P & ID’s
Other
Documents
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________ If NO, refer to Deviation # __________
Purchase Order
Electrical
Drawings
Mechanical
Drawing
P & ID’s
PLC Software
Backup &
Report
MSDS
Other
Documents
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________ If NO, refer to Deviation # __________
Installation and
Operation
Manual
Purchase Order
Electrical
Drawings
Mechanical
Drawings
P & ID’s
Other
Documents
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________ If NO, refer to Deviation # __________
Installation and
Operation
Manual
Purchase Order
Electrical
Drawings
P & ID’s
PLC Software
Backup &
Report
Other
Documents
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________ If NO, refer to Deviation # __________
Installation and
Operation
Manual
Purchase Order
Electrical
Drawings
P & ID’s
Other
Documents
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________ If NO, refer to Deviation # __________
• Assure concordance between drawings (P & I D’s and Electrical Schematics, etc.) and field
installation of the Purified Water System
Procedure:
a. Collect and document the drawings found thru IQ - 02: “Document Inventory Verification”
b. Verify against field installation by performing a physical inspection and redline drawings, if
discrepancy occurs
c. Sign, date & submit discrepancies to Facilities Dept. for review
d. Upon review, determine if drawings and/or field installation needs to be updated
e. Attach verified drawings to this protocol
References Required:
• Electrical Schematics
Acceptance Criteria:
• Discrepancies between drawings and field installation were satisfactorily resolved by submitting
changes and updating drawings and/or field installation
DRAWING VERIFICATION IQ-03
Sheet ______ of ______
Use additional pages as necessary
DRAWING REDLINED? UPDATE? PERFORMED
TITLE & REVISION
TYPE & ID (YES/NO) (DWG, FLD, NA) BY/DATE
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
• Assure that the installation design is in compliance with the specified requirements for systems
capable of producing Purified Water
Procedure:
• P & ID’s
• Material Safety Data Sheets
• Chemical Analysis Sheets
Acceptance Criteria:
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
• Assure that the equipments have the appropriate conditions to perform setup and maintenance
and to operate accordingly.
Procedure:
• Per equipment, verify field conditions by performing a physical inspection as per expected
results
• Skid Drawings
Acceptance Criteria:
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
• Utility Verification
a. Per equipment, perform utility verification as per expected results by using a calibrated test
instrument (when required), and document results
b. Attach copy of instrument calibration certificate and ensure it is up to date
c. Ensure that each utility connection is properly labeled
• Electrical Verification
ELECTRICAL PERFORMED
EXPECTED RESULT ACTUAL RESULT PASS/FAIL
SPECS BY/DATE
Voltage
Phase
Amperage
Frequency
Panel ID
PERFORMED
OTHER SPECS EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
Compressed Air
Chemical
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
Amperage
Frequency
Panel ID
Voltage
Phase
P-OZ1
Amperage
Frequency
Panel ID
Voltage
Phase
P-OZ2
Amperage
Frequency
Panel ID
Voltage
Transformer
Phase
Amperage
Frequency
Panel ID
To be filled by a licensed electrician or electrical engineer with PE license
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
ELECTRICAL PERFORMED
EXPECTED RESULT ACTUAL RESULT PASS/FAIL
SPECS BY/DATE
Voltage
Phase
Amperage
Frequency
Panel ID
Bulb installation
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
ELECTRICAL PERFORMED
EXPECTED RESULT ACTUAL RESULT PASS/FAIL
SPECS BY/DATE
Voltage
Phase
Amperage
Frequency
Panel ID
Bulb installation
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
ELECTRICAL PERFORMED
EXPECTED RESULT ACTUAL RESULT PASS/FAIL
SPECS BY/DATE
Voltage
Phase
Amperage
Frequency
Panel ID
Bulb installation
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
ELECTRICAL PERFORMED
EXPECTED RESULT ACTUAL RESULT PASS/FAIL
SPECS BY/DATE
Voltage
Phase
Amperage
Frequency
Panel ID
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
ELECTRICAL PERFORMED
EXPECTED RESULT ACTUAL RESULT PASS/FAIL
SPECS BY/DATE
Voltage
Phase
Amperage
Frequency
Panel ID
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
Phase
1
Amperage
2
Amperage
Frequency
Panel ID
1
Voltage
2
Voltage
1
Phase
Unit B
2
Phase
1
Amperage
2
Amperage
Frequency
Panel ID
To be filled by a licensed electrician or electrical engineer with PE license
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
ELECTRICAL PERFORME
EXPECTED RESULT ACTUAL RESULT PASS/FAIL
SPECS D BY/DATE
Voltage
Phase
Amperage
Frequency
Panel ID
To be filled by a licensed electrician or electrical engineer with PE license
Chemicals
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
ELECTRICAL PERFORMED
EXPECTED RESULT ACTUAL RESULT PASS/FAIL
SPECS BY/DATE
Voltage
R.O Feed Pump
Phase
Amperage
Frequency
Panel ID
Voltage
R.O. Cleaning
Phase
Pump
Amperage
Frequency
Panel ID
Voltage
ADS Pump
Phase
Amperage
Frequency
Panel ID
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
Voltage
Degas Panel
Phase
Amperage
Frequency
Panel ID
Voltage
Vacuum Pump
Phase
Amperage
Frequency
Panel ID
Compressed Air
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
ELECTRICAL PERFORMED
EXPECTED RESULT ACTUAL RESULT PASS/FAIL
SPECS BY/DATE
Voltage
Phase
Amperage
Frequency
Panel ID
To be filled by a licensed electrician or electrical engineer with PE license
Chemicals
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
• Assure that all the instrumentation installed in the Purified Water System that requires
calibration are added to a calibration program
Procedure:
a. Inspect all instruments evaluated with the “Calibration Program Addition Form” and verify that all
instruments installed at the Purified Water System were included
b. Record instruments (ID & type) that requires calibration according to the “Calibration Program
Addition Form”
c. Verify if the instrument that requires calibration is currently calibrated and record finding
d. Attach calibration certificate of all calibrated instruments
References Required:
Acceptance Criteria:
IT IS CURRENTLY
INSTRUMENT CALIBRATION PERFORMED
INSTRUMENT ID CALIBRATED?
TYPE DUE DATE BY/DATE
(YES/NO/NA)
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
• Assure that the Purified Water System is included in a Preventive Maintenance Program and a
spare parts list exists
Procedure:
a. Per equipment, verify and document the required information by collecting documented
evidence (i.e. PM checklist, PM schedule) of the inclusion of the Purified Water System
components into ___’s Preventive Maintenance Program
b. Collect the Spare Parts list; verify & document the required information
c. Collect the Lubricants list; verify & document the required information
d. If lubricant specifications is not applicable, write a Not Apply to the “Actual Result” column and
explain in the “Comments/Observations” section
References Required:
• Lubricants list
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
A PM checklist,
schedule or similar is
PMP available as evidence
of inclusion into the
PM program.
Lubricants inventory is
Lubricants available for the
equipment.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
A PM checklist,
schedule or similar is
PMP available as evidence
of inclusion into the
PM program.
Lubricants inventory is
Lubricants available for the
equipment.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
A PM checklist,
schedule or similar is
PMP available as evidence
of inclusion into the
PM program.
Lubricants inventory is
Lubricants available for the
equipment.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
A PM checklist,
schedule or similar is
PMP available as evidence
of inclusion into the
PM program.
Lubricants inventory is
Lubricants available for the
equipment.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
A PM checklist,
schedule or similar is
PMP available as evidence
of inclusion into the
PM program.
Lubricants inventory is
Lubricants available for the
equipment.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
A PM checklist,
schedule or similar is
PMP available as evidence
of inclusion into the
PM program.
Lubricants inventory is
Lubricants available for the
equipment.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
A PM checklist,
schedule or similar is
PMP available as evidence
of inclusion into the
PM program.
Lubricants inventory is
Lubricants available for the
equipment.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
A PM checklist,
schedule or similar is
PMP available as evidence
of inclusion into the
PM program.
Lubricants inventory is
Lubricants available for the
equipment.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
A PM checklist,
schedule or similar is
PMP available as evidence
of inclusion into the
PM program.
Lubricants inventory is
Lubricants available for the
equipment.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
A PM checklist,
schedule or similar is
PMP available as evidence
of inclusion into the
PM program.
Lubricants inventory is
Lubricants available for the
equipment.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
A PM checklist,
schedule or similar is
PMP available as evidence
of inclusion into the
PM program.
Lubricants inventory is
Lubricants available for the
equipment.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
A PM checklist,
schedule or similar is
PMP available as evidence
of inclusion into the
PM program.
Lubricants inventory is
Lubricants available for the
equipment.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
A PM checklist,
schedule or similar is
PMP available as evidence
of inclusion into the
PM program.
Lubricants inventory is
Lubricants available for the
equipment.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
A PM checklist,
schedule or similar is
PMP available as evidence
of inclusion into the
PM program.
Lubricants inventory is
Lubricants available for the
equipment.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
A PM checklist,
schedule or similar is
PMP available as evidence
of inclusion into the
PM program.
Lubricants inventory is
Lubricants available for the
equipment.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
A PM checklist,
schedule or similar is
PMP available as evidence
of inclusion into the
PM program.
Lubricants inventory is
Lubricants available for the
equipment.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
A PM checklist,
schedule or similar is
PMP available as evidence
of inclusion into the
PM program.
Lubricants inventory is
Lubricants available for the
equipment.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
PERFORMED
SPEC EXPECTED RESULT ACTUAL RESULT PASS/FAIL
BY/DATE
A PM checklist,
schedule or similar is
PMP available as evidence
of inclusion into the
PM program.
Lubricants inventory is
Lubricants available for the
equipment.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
• Assure that the Purified Water System complies with ___’s EHS Safety and Ergonomics
requirements
Procedure:
• Collect documented evidence (i.e. EHS checklist) of EHS evaluation of the Purified Water
System
EXPECTED PERFORMED
SPEC ACTUAL RESULT PASS/FAIL
RESULT BY/DATE
EHS Change
Management
AWO column
checklist was
completed and
approved.
PWS Safety &
Ergonomics
Compliance
EHS found
Purified Water
System to be in
compliance.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
• Assure written procedures for the operation and maintenance of the Purified Water System
Procedure:
a. Per equipment, collect and evaluate written procedures (i.e. operating, maintenance, cleaning)
and document findings
b. If any of the specifications is not applicable, write a Not Apply to the “Actual Result” column and
explain in the “Comments/Observations” section
• Draft procedures are available for each main component of the Purified Water System.
PROCEDURE VERIFICATION IQ-10
Filter set 1A & 1B
A procedure
Operating
exists at least in
Procedure
Draft form.
A procedure
Maintenance
exists at least in
Procedure
Draft form.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
A procedure
Operating
exists at least in
Procedure
Draft form.
A procedure
Maintenance
exists at least in
Procedure
Draft form.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
A procedure
Operating
exists at least in
Procedure
Draft form.
A procedure
Maintenance
exists at least in
Procedure
Draft form.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
A procedure
Operating
exists at least in
Procedure
Draft form.
A procedure
Maintenance
exists at least in
Procedure
Draft form.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
A procedure
Operating
exists at least in
Procedure
Draft form.
A procedure
Maintenance
exists at least in
Procedure
Draft form.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
A procedure
Operating
exists at least in
Procedure
Draft form.
A procedure
Maintenance
exists at least in
Procedure
Draft form.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
A procedure
Operating
exists at least in
Procedure
Draft form.
A procedure
Maintenance
exists at least in
Procedure
Draft form.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
A procedure
Operating
exists at least in
Procedure
Draft form.
A procedure
Maintenance
exists at least in
Procedure
Draft form.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
A procedure
Operating
exists at least in
Procedure
Draft form.
A procedure
Maintenance
exists at least in
Procedure
Draft form.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
A procedure
Operating
exists at least in
Procedure
Draft form.
A procedure
Maintenance
exists at least in
Procedure
Draft form.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
A procedure
Operating
exists at least in
Procedure
Draft form.
A procedure
Maintenance
exists at least in
Procedure
Draft form.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
A procedure
Operating
exists at least in
Procedure
Draft form.
A procedure
Maintenance
exists at least in
Procedure
Draft form.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
A procedure
Operating
exists at least in
Procedure
Draft form.
A procedure
Maintenance
exists at least in
Procedure
Draft form.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
A procedure
Operating
exists at least in
Procedure
Draft form.
A procedure
Maintenance
exists at least in
Procedure
Draft form.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
A procedure
Operating
exists at least in
Procedure
Draft form.
A procedure
Maintenance
exists at least in
Procedure
Draft form.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
A procedure
Operating
exists at least in
Procedure
Draft form.
A procedure
Maintenance
exists at least in
Procedure
Draft form.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
A procedure
Operating
exists at least in
Procedure
Draft form.
A procedure
Maintenance
exists at least in
Procedure
Draft form.
Comments/Observations:
Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________ If NO, refer to Deviation # __________
Verify each of the respective IQ tests and document completion and status.
ACCEPTANCE
TEST DEVIATION DEVIATION
TEST CRITERIA
TEST TITLE EXECUTED NUMBER SOLVED
NUMBER MET?
(YES/NO) (if applies) (YES/NO)
(YES/NO)
DOCUMENT INVENTORY
IQ-02
VERIFICATION