You are on page 1of 5

TECHNICAL SPECIFICATION OF MATERIALS

1 8 Mtr. / 200 Kg PSC Poles A) Over all length of the pole : Mtr 8.00 B) Working load : Kg 200 C) Top depth : MM 290 D) Breath : MM 145 E) Depth of planting : Mtr 1.5 F) Factor of safety : 2.5 G) No. of tensioned wire : No 12 H) No. of un-tensioned wire : No 2 I) Diameter of pestering wire : MM 4 J) Ultimate strength of pressing steel : Kg/mmsq. 175 K) Length of tensioned & un-tensioned wire MM 8 tension should not exceed More than 5% of UTS of the wire. L) Distance of concentrated load from the top : MM 0.6 M) Concrete grade : M-420 N) Size of agree gate : MM 12 MM O) Concrete quantity : CM 0.157 P) Steel quantity per pole : 11.05kg Q) Weight of Pole : 380kg (As per drawing Annexure-XI) 2 9Mtr. / 300 Kg PSC Poles A) Over all length of the pole : Mtr 9.00 B) Working load : Kg 300 C) Top depth : MM 185 D) Breath : MM 100 E) Depth of planting : Mtr 1.5 F) Flat of safety : 2 G) No. of tensioned wire : No 16 H) Bottom depth : MM 355 I) Diameter of pestering wire : MM 4 J) Ultimate strength of pressing steel : Kg/mmsq. 175 K) Length of tensioned & un-tensioned wire MM 9 tension should not exceed More than 5% of UTS of the wire. L) Distance of concentrated load from the top : MM 0.6 M) Concrete grade : M-400 N) Size of agree gate : MM 12 MM Down grade O) Concrete quantity : cum 0.243 P) Steel quantity : 14.2kg Q) Weight of Pole : 607 (As per drawing Annexure-XII) 3 12 Kv, 10 KA LIGHTENING ARRESTER 12 Kv, 10 KA rated Station class gapless type Class II Lightening Arrester suitable for 11 Kv, 3 Phase, 50 C/s system, Pole mounting Conforming to IEC 99-4 (1991) & relevant ISS & Amendments having the following technical parameters : a) Type : Station class b) No of Unit : One c) Rated Voltage : 12 Kv d) Normal Discharge Current in KA : 10 e) Reference Current in Ma : 2.25 f) Reference voltage in Kv r.m.s : 12 g) Protective Ratio : 1.83 h) Max. Continuous operative Voltage in Kv r.m.s : 12 Kv. i) High Current impulse withstand in KA : 100 j) Insulation withstand. i) Lightening Impulse (Kv Peak) : 75 ii) P.I dry / wet (Kv r.m.s) : 28 k) Total Creepage Distance (mm) : 300 l) Earthing Arrangement : To be provided m) Height of complete Unit ; 370

Page 1 of 5

AAA C 34 mm2 size All Aluminium Alloy Conductor as per IS : 398(Part-IV)/1994 of size : 34 mm2 (7/2.5 mm)

AAA C 55 mm2 size All Aluminium Alloy Conductor as per IS : 398(Part-IV)/1994 of size : 55 mm2 (7/3.15 mm)

11 KV., 200 Amp., 2 Pole Horizontal Type AB Switch

11 Kv, 200 Amperes, gang operated, single break, horizontally mounted, outdoor type, 2 Phase, 50 Hz A.B Switch having 2 numbers Post Insulators originally cemented per phase as per REC Construction standard Conforming to IS : 9920(Part-I to Part-IV) & IS :9921 (Part-1)/1981{Reaffirmed 1992}, IS : 9921 (Part-2)/1982{Reaffirmed 1992}, IS : 9921 (Part-3)/1982{Reaffirmed 1992}, IS : 9921 (Part-4)/1985{Reaffirmed 1992} & IS ; 2544/1973 (1st Revision, Amendment4, Reaffirmed1991) & IS : 2633/1986 (2nd Revision, Reaffirmed 1998).IS : 2629/1985(1st Revision, Amendment 2, Reaffirmed 1998), IS : 4736/1986 (1st Revision, Amendment 1, Reaffirmed 1998). Make of Insulators is to be mentioned 7 11 KV., 200 Amp., 3 Pole Horizontal Type AB Switch

11 Kv, 200 Amperes, gang operated, single break, horizontally mounted, outdoor type, 3 Phase, 50 Hz A.B Switch having 2 numbers Post Insulators of reputed make per phase & originally cemented Conforming to IS : 9920(Part-I to Part-IV) & IS : 9921 (Part-1)/1981{Reaffirmed 1992}, IS : 9921 (Part-2)/1982{Reaffirmed 1992}, IS : 9921 (Part3)/1982{Reaffirmed 1992}, IS : 9921 (Part-4)/1985{Reaffirmed 1992} & IS ; 2544/1973 (1st Revision, Amendment-4, Reaffirmed1991) & IS : 2633/1986 (2nd Revision, Reaffirmed 1998).IS : 2629/1985(1st Revision, Amendment 2, Reaffirmed 1998), IS : 4736/1986 (1st Revision, Amendment 1, Reaffirmed 1998). Make of Insulators is to be mentioned 8 11 KV., 200 Amp., 3 Pole HG Fuse

11 Kv, 200 Amperes, 3 Phase, 50 Hz H.G Fuse having 2 numbers 12 Kv Post Insulators of reputed make per phase & originally cemented as per REC Construction Standard Conforming to IS : 9385 (Part-1)/1979{Reaffirmed 1992}, IS : 9385 (Part-2)/1980{Reaffirmed 1992}, IS : 9385 (Part-3)/1980{Reaffirmed 1992}, IS : 9385 (Part-4)/1983{Reaffirmed 1992}, IS : 9385 (Part-5)/1983{Reaffirmed 1987} & IS ; 2544/1973 (1st Revision, Amendment-4, Reaffirmed1991) & IS : 2633/1986 (2nd Revision, Reaffirmed 1998). Make of Insulators is to be mentioned. 9 11 KV H.G Fuse 2 Pole (200 Amp.) 11 K.V 200 Amp. Capacity H.G Fuses suitable for 50 HZ 2 ph supply system having 2 nos. of 12 KV post insulator (Original Cemented) per phase as per enclosed drawing confirming to IS 5792/1970, IS 9358/1979 or latest amendment if any (As per drawing Annexure-II) 10 G.I. Pipe Earthing G.I pipe Earthing device with clamp circular type as per R.E.C standard J2. A) Standard to which pipe earthing confirm REC standard J2 B) Size of the pipe = 40 MM Nominal bore (Medium gauge) C) Length of the pipe = 2.5 Mtrs. D) Thickness of the pipe = 3.25 MM E) Standard for processing of galvanization and testing for uniformity and Mass of Zinc locating of the Earthing pipe. IS2629/85, IS-2633/86, IS-6745/72. (As per drawing Annexure-III)

Page 2 of 5

11

L.T Stay Set

A) M.S. Stay rod of 16mm dia 1800 MM in length, one side formed an eye and welded with internal dia 40 MM with one thimble and other side and the other side of the rods is threaded and fitted with 2 nos. of suitable hexagonal nuts and with one round washer of 3 MM thick ness complete with M.S. Anchor plate 150 X 150 X 6 MM, dimension with center hole of 40 MM dia. The entire rod, plate, thimble, nuts and washer should be not dipped galvanized. B) Single bow turn buckle made of 16 MM dia M.S. rod and the center rod of 20 MM dia of length 450 MM with one end formed an eye and welded. The bar channel have the bow of site 50 X 50 X 6 MM and 180 MM in length with thimble and 2 nos. suitable hexagonal nuts. All items should be not dipped galvanized (As per drawing Annexure-VII) 12 HT Stay Set

C) M.S. Stay rod of 20mm dia 1800 MM in length, one side formed an eye and welded with internal dia 40 MM with one thimble and other side and the other side of the rods is threaded and fitted with 2 nos. of suitable hexagonal nuts and with one round washer of 3 MM thick ness complete with M.S. Anchor plate 250 X 250 X 6 MM, dimension with center hole of 22 MM dia. The entire rod, plate, thimble, nuts and washer should be hot dipped galvanized as per IS 26371972. D) Single bow turnbuckle made of 16 MM dia M.S. rod and the center rod of 20 MM dia of length 450 MM with one end formed an eye and welded. The bar channel have the bow of site 75 X 40 X 6 MM and 180 MM in length with thimble and 2 nos. suitable hexagonal nuts. All items should be hot dipped galvanized. (As per drawing Annexure-VIII) 13 Diameter of the G.I. Wire SWG No. 8 No of the turn = 115 Length of turn = 450mm Outer diameter of the Coil = 50mm Length of the Extended terminal = 2500mm 14 Stay Wire (7/8, 7/10, 7/12) Earthing Coil

GI Stay wire as per IS 2141/1979. The relevant standard indicated their in grade 4 having minimum tensile strength of 700 N/MMSQ and galvanize with heavy coated wire type confirming to its 4826 with latest amendment if any. 15 No. 6 SWG (5.0 MM) G.I. Wire Hot dipped galvanized annealed iron wire confirming to provision of 15280 / 1978 and relevant standard indicated there in having tensile strength of 300-550 MPA and galvanized of heavily coated No. 6 SWG (5 MM dia)

16

LT Distribution box for 16 KVA A) LT Distribution box of size 375 X 475 X 100 MM suitable for 16 KVA, 11/0.23 S/S of LT less system. B) The box should be made of 18 SWG C.R. Sheet with single door fixed with suitable hinges on left side with looking arrangement should be made on right side. C) The box should be covered with PVC or rubber bedding to avoid water leakage. The box should be coated with one coats of red oxide paint and two loads of gray paint. The phase and neutral plate should be made out of 20 X 5 MM copper flat and should be fixed on insulator box. The kit Kat fuse incoming side should be connected to the phase plate and outgoing should be connected with outlet connector with 2 MMSQ PVC Copper single core wire. The nos. of clamp should be welded on the back side of the distribution box along with the nos. flat should be provided with poles (5/8 dia) suitable for fixing on the 8Mtr. PSC Pole. (As per drawing Annexure-IX)

Page 3 of 5

17

11 KV Pin Insulator

11 Kv Pin Insulator Conforming to IS: 731/1971 (2nd Revision), (Amendments - 6), Reaffirmed 1991 & Guaranteed Technical Particulars. Rates forJSI make as well as other reputed make shall be quoted. 18 11 KV G.I Pin 11 Kv G.I Pin Conforming to as per REC construction standard & IS: 2486 (Part - 1)/1993, 2nd Revision with its relevant latest amendments & as per drawing provided. 19 11 KV 45 KN Disc Insulator (T & C) Type

11 Kv Disc Insulator (T & C type) suitable for overhead power line as per REC construction standard Conforming to IS: 731/1971 (2nd Revision), (Amendments - 6), Reaffirmed 1991 & Guaranteed Technical Particulars. Rates forJSI make as well as other reputed make shall be quoted. 20 11 KV Stay Insulator HT Stay Insulator as per REC construction standard confirming to IS : 5300/1969 make insulators. Rates forJSI make as well as other reputed make shall be quoted. 21 11 KV Hardware Fittings (T & C) Type 11 Kv Hard ware fittings (T & C) type, suitable for AAAC to be used in 11 Kv overhead power line as per REC Construction standard Conforming to IS : 2486 (Part - I)/1993, (2nd Revision), 2486 (Part II)/1989(2nd Revision), 2486 (Part-III)/1974, ), 2486 (Part IV)/1981, Reaffirmed 1991. 22 11 KV V Cross Arms 11 KV V Cross arms made out of M.S. Channel 75 X 40 X 6 (7.14 Kg / Mtr.) with two coats of red oxide paint. (As per drawing ) 23 Pole top bracket Pole top bracket for 11 KV support made out of 50 x 8 MM M.S Flat with two coats of red oxide paints. (As per drawing Annexure-IV) 24 Back Clamp, Side Clamp Back Clamp, Side Clamp made out of 50 X 8 MM M.S. Flat with two coats of red oxide paints. Suitable for 11 KV V Cross arms to be and in 8 Mtr. Long 200 Kg PSC Pole. (As per drawing Annexure-V) 25 H.T Conductor Dead end Clamp / LT Dead end Clamp Dead end clamp shall be made of high strength aluminum alloy of designation 2280(IS: 617-1975) of tensile strength not less than 250 N/MMSQ (27 kgt / MMSQ). The U-bar shall be made of hot clip galvanized steel. The eye hooks shall be made of forget steel (IS: 2004) or Mild steel (IS: 1570) The clamp shall be suitable for holding both 25 MMSQ and 35 MMSQ messenger wire size of compacted, diameters of 5.8 MM and 6.8 MM respecting. The clamp shall have a come for holding the messenger wire and it shall automatically grip the messenger wire dues to tension of the wire. The clamp shall be free from all flows, irregulataries and sharp radius of curvature. All ferrocom fitting, eyehooks, bolts, nuts, washers, shall be galvanized with Zine conforming to grade Zn 98 of IS: 2091996. The spring washers and nuts etc. may be electro-galvanized. Nuts shall be made of materials conforming to property class 4.8 of IS: 1367 for its mechanical properties. (As per drawing Annexure-VI)

Page 4 of 5

26

Stay Clamp for H.T & L.T Stay clamp made out of 50 X 8 MM M.S. Flat with two coats of red oxide paints. Suitable for 9mtr. 300kg / 8mtr. 200kg PSC Pole

27

Concrete base plate suitable for PSC pole R.C.C / Anchor plate using M.S. Rod reinforcement as per REC construction A) Size of plate (450 X 450 X 75) MM. B) M.S. Road 8 Nos. (6 MM dia) (As per drawing Annexure-X) standard drawing K-1

Page 5 of 5