Differential Relays

Auxiliary current transformers 4AM50, 4AM51, 4AM52 and isolating transformers 7XR95

4AM5. Fig. 1

4AM5.... with varistor fitted

7XR9 500

Overview
Application Comment Climatic requirements according to former DIN 40 040 Features

Matching current transformer

Multitap aux. current transformer to match different current transformer ratios. 4AM51 707AA: Standard version, primarily for transformer overall differential protection. 4AM52 722AA: Version with double thermal withstand capability, e.g. when connecting to widerange current transformer (continuous rating 2 x IN). 4AM52 723AA: Version with higher saturation factor (mainly for the busbar differential protection). Greater overcurrent factor because of higher voltages Auxiliary current transformer for C.T. powered trip coils in stations where no battery supply can be made available. 4AM50 652CB: For 1 A C.T.s 4AM50 708AB: For 5 A C.T.s Suitable for tripping coils with IN x 0.5 A or 1 A, VN x 40 V or 20 V, P x 20 VA. Input and matching current transformer for phase selective busbar differential protection. 4AM51 201DA: For 1 A C.T.s 4AM51 202DA: For 5 A C.T.s1) Input 3phase summation current transformer for busbar differential protection. 4AM51 203DA: For 1 A C.T.s 4AM51 204DA: For 5 A C.T.s Isolating transformer for pilotwire differential protection. Provides galvanic isolation between pilot wires and relays. 7XR9 500: For differential protection relays 7SD10, 7SD74 and 7SD503 (for use with 3 wires of control cables or protection cables) 7XR9 513: For pilotwires differential relays 7SD24, 7SD76 and 7SD502 (for use with 1 pair of telephone wires).

HKG HKG HKG

Numerous ratios can be selected using terminal connections (see page 2/31) fN = 45 to 60 Hz

Aux. C.T. for C.T. powered tripping circuits

HKD HKD

Unlike transducers, no defined rated power or class accuracy required. fN = 45 to 60 Hz

Input and matching current transformer

fN = 45 to 60 Hz with varistor
HKG HKG

3phase summation input C.T.

HKG HKG

fN = 45 to 60 Hz with varistor

Isolating transformer

HKG HKG

7 kV insulation 20 kV insulation

Climatic requirements:

HKG = 25 _C to +125 _C relative humidity max. 75 % annual average <65 % on 60 days of the year up to 85 % (equally distributed over the year) condensation not permissible

HKD = 25 _C to +125 _C relative humidity max. 90 % annual average <80 % on 30 days of the year up to 100 % (equally distributed over the year) condensation permissible

1) If increased thermal withstand is required type 4AM51 204DA is recommended. Siemens LSA 2.2.6 . March 1995

1 e Siemens AG 1995

Differential Relays

Auxiliary current transformers 4AM50, 4AM51, 4AM52 and isolating transformers 7XR95

A B C D E F G H

KaLaKbLb

ka la

A B C

D E F

A B C

D E F

A B C D E F G H

J K L MN O P Q

KcLcKdLd

kb lb

G H J

Y Z

Y Z

J K L MN O Y Z

4AM51 707AA 4AM52 722AA 4AM52 723AA Fig. 2 Connection of windings Order No.

4AM50 708AB 4AM50 652CB

4AM51 201DA

4AM51 202DA

4AM51 203DA 4AM51 204DA

Windings of auxiliary current transformers Number of windings (in relation to each other)
A 1 B C 2 D E 7 F G 16 H I 1 K L 2 M N 7 O P 16 Q

Weight, approx.

4AM51 707AA 4AM52 722AA 4AM52 723AA 4AM50 652CB

Rated current IN1) Max. voltage Rated current IN1) Max. voltage Rated current IN1) Max. voltage Rated current IN1) Number of windings Number of windings Rated current IN1)

A V A V A V A

5 2 10 2 5 4 1

5 4 10 4 5 8 1

5 14 10 14 5 28 1

1 32 2 32 1 64 1

5 2 10 2 5 4

5 4 10 4 5 8

5 14 10 14 5 28

1 32 2 32 1 64

3.4 kg 5 5 kg kg

2.4 kg Primary windings Secondary windings

Ka La Kb Lb 110 110

Kc Lc Kd Ld 110 110

ka

88

la

kb

88

lb

1.25 5 5 5

1.25 5 Primary windings Secondary windings 2.4 kg

4AM50 708AB

Rated current IN1) Number of windings Number of windings Rated current IN1) Number of windings

Ka La Kb Lb 22 22

Kc Lc Kd Ld 22 22

ka

88

la

kb

88

lb

A
A

1.25
1 B 2 C D

1.25
E 4 8 F G 16 H 32 500 I Y Z

4AM51 201DA 4AM51 202DA

Max. current, continuously Max. voltage Max. current, continuously Max. voltage Number of windings Max. current, continuously Max. voltage

A V A V
A

6.8 0.4 0.8 26 0.4


B 3

6.8 1.6 3.2 26 1.6


D E 9 F

6.8 6.4 12.5 not fitted


H I 24 K L 36 M N

0.85 200 0.85 200


O 90 500 Y Z

3.5 kg 3.5 kg

0.8
C 6

3.2
G 18

4AM51 203DA

3.5 kg

A V

4 1.2
A 1 B

4 2.4
C 2 D

4 3.6
E 3 F

4 7.2
G 4 H

4 9.6
I 6 K

4 14.4
L 8 M

2 36
N 12 O Y

0.85 200
Z 500

4AM51 204DA

Number of windings Max. current, continuously Max. voltage A V

3.5 kg

17.5 0.4

17.5 0.8

17.5 1.2

17.5 1.6

17.5 2.4

17.5 3.2

8 4.8

0.85 200 approx. 15 kg

7XR9 500

Isolating transformer for differential protection with three pilotwires Isolating transformer for differential protection with two pilotwires

a9 a10 a8

b9 b10 b8 K1 M1 L1

Isolating transformer 1 : 1 for voltages up to 4,2 kV test voltage 7 kV Isolating transformer 1 : 1, max. 550 V 0,4 A continously, 3 A 10 s, 10 A 1 s test voltage 20 kV, 50 Hz, 1 min

7XR9 513

approx. 5 kg

K2 M2 L2

1) Thermal withstand with simultaneous loading of all the windings: 1.2 x IN/continuously; 10 x IN/10 s; 25 x IN/1 s.

Siemens LSA 2.2.6 . March 1995

Differential Relays

Dimension drawings in mm

c g

Type 4AM50
f

a 84 84 90

b 96 96 120

c 102 116 110

d 70 84 83

e 88 103 102

f 106 106 123

4AM51
5.8 a b d e

4AM52

Fig. 3 Auxiliary current transformers 4AM50, 4AM51, 4AM52 without varistor

58

72

5.8 84 96 39 84 102.5

11

Fig. 4 Auxiliary current transformer 4AM51 with varistor

Isolation transformer 7XR95

ca.55

6.5

106

108

90

181.5

292

204 220

162 143

108 172 8.5

77 8 220

40

100 122

86

Fig. 5 Isolation transformer 7XR9513

Fig. 6 Isolation transformer 7XR9500

Siemens LSA 2.2.6 . March 1995

Differential Relays

Conditions of Sale and Delivery S Export Regulations S Trademarks S Dimensions


Conditions of Sale and Delivery Subject to the General Conditions of Supply and Delivery for Products and Services of the Electrical and Electronic Industry and to any other conditions agreed upon with the recipients of catalogs.

The technical data, dimensions and weights are subject to change unless otherwise stated on the individual pages of this catalog. The illustrations are for reference only.

We reserve the right to adjust the prices and shall charge the price applying on the date of delivery.

A 9.91 a

Export Regulations In accordance with present German and US export regulations export licences (dated 02.95) are not required for the products listed in this catalog. Export and reexport are therefore

permissible without the approval of the relevant authorities except where current German export regulations contain countryspecific restrictions.

Subject to change. Relevant are the criteria stated in the delivery note and in the invoice. An export licence may be required due to countryspecific application of the product.

Trademarks All product designations used are trademarks or product names of Siemens AG or of suppliers.

Dimensions All dimensions in this catalog are given in mm

Responsible for Technical contents: Norbert Schuster, Siemens AG, EV S T11, Nrnberg General editing: Claudia KhnSutiono, Siemens AG, EV MK 2, Erlangen

Bereich Energiebertragung und -verteilung Geschftsgebiet Zhler, Sekundr- und Netzleittechnik P. O. Box 48 06 D-90026 Nrnberg 4 Siemens Aktiengesellschaft

Power Transmission and Distribution


Order No.: E50001-K5722A161A17600 Siemens LSA 2.2.6 . March 1995 Printed in the Federal Republic of Germany