ExProtectionConcepts Electrical
Symbol TypicalIEC TypicalZones EPL Increasedsafety e Gb 1,2 Typen(nonsparking) T ( ki ) nA A Gc G 2 Flameproof d Gb 1,2 Typen(enclosedbreak) nC Gc 2 Quartz/sandfilled q Gb 1,2 Intrinsicsafety ia Ga 0,1,2 Intrinsicsafety I ti i f t ib Gb 1,2 12 Intrinsicsafety ic Gc 2 Typen(energylimitation) nL Gc 2 Pressurised(upto2007) p Gb 1,2 Pressurised px Gb 1,2 Pressurised i d py Gb b 1,2 Pressurised pz Gc 2 Typen(sealing&hermetic nC Gc 2 sealing) nR Gc 2 Typen(restricted breathing) Typen(simplepressurised) nZ Gc 2 Encapsulation ma Ga 0,1,2 Encapsulation mb Gb 1,2 Oilimmersion o Gb 1,2 Electrical IECStandard Basicconceptofprotection (statusatJuly2008) IEC600797 Noarcs,sparksorhotsurfaces. EnclosureIP54orbetter Enclosure IP54 or better IEC6007915 IEC 60079 15 IEC600791 Containtheexplosion,quenchthe flame IEC6007915 IEC600795 Quenchtheflame IEC6007911 IEC6007911 IEC 60079 11 Limittheenergyofsparksandsurface i i h f k d f temperatures IEC6007911 IEC6007915 IEC600792 IEC600792 IEC600792 IEC600792 IEC6007915 IEC6007915 IEC6007915 IEC6007918 IEC6007918 IEC600796 Keeptheflammablegasout
t i
Standard protection for dusts, rugged tight enclosure Similar to t, but with some relaxations if circuit inside is intrinsically safe Protection by encapsulation of incendive parts Protection by pressurisation of enclosure
Encapsulation Pressurised
m p Db,Dc
22 21,22
Exd FlameproofConcept
Lamps,circuitsandsparkingdevicesare containedwithinflameproofenclosure. Wiringentersenclosureviaflameproofcable glandorflameproofbarrier. Jointsoncoversoropeningsareprotectedby i i db theflamepath. Doesnotpreventexplosionoccurringbut containstheexplosionandpreventsignitionof surroundingatmosphere.
Exd FlameproofBarrier
Cable
Enclosurewall
Flameproofvs.ExplosionProof
DifferencebetweenFlameproof&Explosion proofboxes Enclosuremusthave recessedscrewsorboltsfor access 1.5safetyfactorvs.4times Typicallymustbemachined andfabricatedatthefactory vs.thefield MostEXdenclosuresindividuallytested
FlangedJoint
ThreadedJoint
SpigotJoint
FieldModificationofExdEquipment
Flameproofenclosuresarenormallysuppliedcompletewithallinternal Flameproof enclosures are normally supplied complete with all internal componentsfittedandcertifiedasasingleentitybyarecognizedtest authority.Thetestingprocedurewilltakeintoconsiderationthefreeinternal volumeafterallthecomponentshavebeenfitted,thetemperaturerise, creepageandclearancedistancesandtheriseinpressureasaresultofan internalexplosionusingagas/airmixtureinitsmostexplosiveproportions. Thecertification,thereforesealsthedesignoftheapparatussothatany unauthorizedmodificationswilleffectivelyinvalidatethe approval/certification.Modificationswillmodifytheoriginaltestresultsand approval/certification Modifications will modify the original test results and consequently,thefollowingpointsshouldbeobserved: Replacementcomponentsshouldbethesameastheoriginalcomponents. Forexample,acomponentlargerorsmallerthantheoriginalwillaffectthe internalgeometryoftheenclosure.Pressurepilingisapossibilityifalarger l f h l l bl f l componentisfittedandincreasedvolumewillresultifasmallercomponent isfitted. Drillingandtappingoftheentriesshouldonlybecarriedoutbythe g pp g y y manufactureroftheenclosureorhisapprovedagent.Thethreadsofthe entriesarerequiredtobecompatiblewiththoseofthecableglandsor conduitintermsoftypeofthread,threadpitchandclearancetolerancesince flamepathsexistatthesepoints. Gasketscanonlybereplaced,theymustnotbeaddedretrospectivelyifnot includedaspartoftheoriginaldesign.
ExdIIBvs.ExdIICConstruction
Canyouspotthedifferenceinconstruction?...
ExdFlamproofConduitSystems
Although,conduitisnotwidelyusedinNorthernEurope,thistechniqueisincludedintheCENELECstandardand theIECstandardsasoneoftheentrymethodsintoflameproofenclosures.Thedesignandtestingrequirements arecontainedintheCENELECstandard50018andIECStandardIEC600791.Eithertapered(NPT)orparallel (straightormetric)threadsareacceptable.Theconditionsare: TheExdenclosuremustbecertified. OnlythemanufacturercanmakethedrilledandtappedentriesintotheEx denclosure. Only the manufacturer can make the drilled and tapped entries into the Exd enclosure. Allconduitsorcableglandsenteringtheenclosuremustbesealedbyanapprovedmethod. Fromtheareabeyondtheenclosureseal,allofthewiringmethodsandfittingsareconsideredinstallation materialsandnotsubjecttoanycertificateorapproval.Thus,gettingfittingscertifiedtotheATEXdirectivewould notbeacommonpractice.ThecorrectuseofconduitinstallationisspelledoutintheinstallationstandardEN tb ti Th t f d it i t ll ti i ll d t i th i t ll ti t d d EN 6007914andIEC6007914.
WeatherproofingExdEquipment
Ingeneral,theuseofEx d flameproof equipment without the use of gaskets or seals will In general the use of Ex dflameproofequipmentwithouttheuseofgasketsorsealswill onlyprovideprotectionuptoIP54.ForapplicationsrequiringhigherlevelsofIPprotection, theuseofgasketsintegratedwithintheflamepathisacommonoptiontoconsider.Other weatherproofingmaterialsconsideredandcommonlyusedarenonhardeninggreasebearing textiletapeintheUKandnonsettinggreaseorcompounds. Theuseofnonsettinggreaseonmachinedsurfacesofflamepathshastwoadvantagessince inadditiontoprovidinganadditionallevelofingressprotection,italsoinhibitstheformation ofrustonthesesurfaces.Siliconebasedgreasesrequirecarefulconsiderationinorderto avoidpossibledamagetotheelementsofgasdetectors. avoid possible damage to the elements of gas detectors Ingeneral,consultwiththemanufacturerofExdequipmentforrecommendationsinvolving lubricantsandtapestobesure.
FlameproofExdQuiz
Componentswhicharcorsparkinnormaloperationarepermitted withExdenclosures Gapsatflamepaths arenotnecessary True True
A AnenclosuremarkedExdIIAissuitableforallsubgroups l k d d IIA i i bl f ll b
False F l
It i Itisacceptableforonefixingscrewtobeleftourofaflameproof t bl f fi i t b l ft f fl f enclosurecover
False
Itisnotacceptabletoremoveanunusedcomponentfromwithina flameproofenclosure
True
Generalrequirementsforterminalsare: Th Theymustbedesignedtoallowtheconductortobeeasilyinserted tb d i d t ll th d t t b il i t d andclamped,sothatcontactpressureismaintainedwithoutreducing thecrosssectionalareaoftheconductorandshallincorporatea positivelockingdevicetopreventconductorsworkinglooseby vibration. SpecifiedcreepagedistancesasdetailedEN/IEC600797forthe gradeofinsulationmaterial(CTI)andsubsequentmaximumvoltage rating. Temperaturelimitation Currentderatingoftheterminals(andconductors)of50% Current de rating of the terminals (and conductors) of 50%
IncreasedSafetyExeQuiz
ExedesignedapparatusissuitableforuseinZone0 False
Increasedsafetyenclosuresmustalwayswithstandthepressure causedbyaninternalexplosion
False
ExeterminalboxescanbeusedinconjunctionwithExd equipment
True
TypicalIgnitionCurvesforI.S.
ZenerBarriers Concept
Enclosure Hazardous Location Zener Z Protecting Fuse Currentlimitingresistor Current limiting resistor Fault VoltageSource Voltage Source +
I.S. Circuit
FaultCurrent
NonHazardousLocation Good Isolation fromGround required (500Vmin.) GoodGround Good Ground Connection 1Max.
GalvanicIsolatedBarriers Concept
FaultVoltage Source Transformer ProtectingFuse + Fault Current = Isolation not needed NonHazardousLocation
Hazardous Location
Currentlimitingresistor
I.S. Circuit
SafetyTransformer
I.S. Circuit
FaultCurrent
FaultCurrent togroundin Hazardous Location! 250V 250A FaultCurrent togroundin Non Hazardous Location! GoodGround Connection i 1Max.
ProtectionUnderFaultCondition IsolatedBarriers
Enclosure Hazardous Location Currentlimitingresistor FaultVoltage Source Transformer ProtectingFuse Protecting Fuse + Voltage Voltage limiting Zeners = Fault Fault Current remains in Non Hazardou sLocation
I.S. Circuit
NonHazardousLocation
SafetyTransformer
Noneedof SafetyGround
ZenerBarriers
Advantages Lowerpartscost Elementarythreecomponentsdevice Disadvantages DedicatedSafetyGroundCost D di dS f G dC SafetyDependson GoodSafetyGround GoodLinesIsolation VoltageDropacrossResistor Zeners leakageInfl.accuracy IsolationoflinesInfl.Accuracy RequiresroutineChecks. Requires routine Checks Groundednonlinearsemiconductor (Zener)reducesimmunityto interferences(commonmode rejection) Applicableonlywithsensorsthatare wellisolatedfromground(500V)
GalvanicallyIsolatedBarriers
Advantages No Safety Ground requirement (No cost / No NoSafetyGroundrequirement(Nocost/No maintenance) Safetynotimpairedbyafaulttoground. Fullvoltageavailability. Betteroverallaccuracy Better overall accuracy ZenerLeakagedoesnotaffectaccuracy Isolationoflinesdoesnotaffectaccuracy Highercommonmoderejectionandimmunity tointerferences to interferences Allowstheuseofgroundedorpoorlyisolated sensors Disadvantages Higherpartcost Higher part cost
CombiningwiringforISand nonIScircuitscanalsobe nonIS circuits can also be combinedinsingleenclosures aslongaspropersegregation andidentificationmethodsare employed. employed
IntrinsicSafetyExiQuiz
Theminimumrequiredprotectionforintrinsicallysafeequipment isIP55 Terminalsforintrinsicallysafecircuitsmustbeatleast50mm fromterminalsoruninsulatedconductorsofanynonintrinsically safecircuits ExncannotbedesignedforapparatusgasgroupingIIC False
True
False
Intrinsicallysafeequipmentmarked(Exia)IICisdesignedtobe installedinahazardousarea
False
IntrinsicSafetyExiQuiz
Intrinsically safe and non intrinsically safe cables may be run in the True Intrinsicallysafeandnonintrinsicallysafecablesmayberuninthe samecabletrayifthecablesarearmoured You cannot use any terminal color but blue for terminals containing False Youcannotuseanyterminalcolorbutblueforterminalscontaining onlyintrinsicallysafecircuits
Electricmotors(Squirrelcage motors),terminalboxes,fuses, LEDs,transformers,apparatus requiringlowenergy, plugconnectors,cells,batteries, plug connectors cells batteries etc.
Temperaturebasedupon externalhotspot
EXnRvs.Division2Lighting Example(NEC)
HighPressureSodium(SON) Wattage 400Watt 250Watt 250 Watt 150Watt 100Watt 70Watt Div.2UnitTCode T2A T2A T 2A T2B T3 T3 ExnRUnitT Code T3C T3C T 3C T3C T4A T4A Change 120oC 120oC 100oC 80oC 80oC
Implicationforlightingdesignistheuseofhigherwattagefixturesandusingfewerofthemfor particularareasmostnotablyforfloodlightsandwellglassapplications
Basic"Encapsulation" encloseddevice nonignitablecomponentContactmechanismorhousingdesignedsuchthat ignitionisavoided. h hermeticallysealeddeviceSealingbymeansofafusingprocesssuchassoftsoldering i ll l d d i S li b f f i h f ld i orbrazing,weldingorfusingofglassinmetal sealeddevicesoconstructed,thatitcannotbeopenedduring normaloperation. encapsulateddevicecompletelyenclosedinan p p y encapsulatingcompound.
NonIncendiveExnQuiz
AcertifiedglandmustalwaysbeusedforanExnapplication ForExnstandards,hermeticsealingofenclosurecanbe satifactory achievedbytheuseofOringsand/orgaskets ExncannotbedesignedforapparatusgasgroupingIIC b d i df i IIC True
True
False
LiveworkingisnotpermittedonExntypeequipment
True
Exp Pressurized(EN/IEC600792:2008)
Entireroomsorbuildingscanbepressurizedas wellasenclosures. TherequirementsofIEC6007913mustmeetthe following: Positivepressuremusthavesufficientcapacityto maintainpressureofatleast25Pa(2.5mmwater maintain pressure of at least 25 Pa (2 5mm water gauge)intheroomandtheroommusthaveeither airlocksforthedoorsortheoutwardvelocitymust beatleast0.305m/swithalldoorsandany openingssimultaneouslyopened. Pressurizinggasmustbeair(containingatleast 19.5%Oxygenbyvolume Whenthepressurizingsystemfails,any equipmentsuchaslightsthatcannotbeswitched offmustbeprotectedbyothermeanssuitablefor off must be protected by other means suitable for thelocation. Onenote:theNFPArequires25Painternal pressureforenclosures,whiletheIECrequires50 PaforenclosuresinZone1and25Pafor f l i 1 d2 f pressurizedrooms. Zone1&2Suitable
HybridExProtectionTechniques
Itisverycommontouseavarietyofprotectionconceptsinasingle productShownbelowaretwoexamples. ThelightfittingisratedEExedmusingIncreasedsafetyforthehousing& terminal,EExdforthedisconnectswitchandlampholdersandEExmfor terminal EEx d for the disconnect switch and lamp holders and EEx m for encapsulationoftheballast..FinalproductratedEExedm ThecontrolpanelbelowisusingEExeincreasedsafetyforthehousing andterminalsandEExdforflameproofoperatorsFinalproductrated EExed EE d
HybridProtectionTechniques
Theseproductsalsousehybridtechnologiestoreachthesameeffectbutindifferentways These products also use hybrid technologies to reach the same effect but in different ways TheenclosuresbelowareratedeitherEExdflameprooforEExeincreasedsafetywiththearcing componentshousedinthedchamber,whiletheeterminalsareintheattachedeenclosure separatedwiththeuseoflinebushingsthatprovideanflameproofbarrierbetweenthetwo enclosures. Ingeneral,thefirstletterintheprimarymeansofprotectionwhilethecorrespondinglettersarethe secondarymeansofprotection,i.e.EExdeisflameproofenclosure,increasedsafetycomponents, whileEExedisincreasedsafetyenclosurewithflameproofcomponents. while EEx ed is increased safety enclosure with flameproof components
Arcing/Sparking
NonArcing/Sparking o c g/Spa g
HybridExProtectionTechniques
Howmanyprotectiontechniquescanyoufindinthispicture? Hint:Totaloffivemethods
Exm
Exe
Exia
Exd WhatZoneisthisenclosuresuitablefor???
ExnR Zone2
HybridEExd&eProtection
EExeenclosure e&delectricalcomponents: thecontactsmakeandbreak inaflameproofdchamber p EExdecomponent
Ingeneral,manyofthelatestdevelopmentsofproductsforhazardous locationsinvolvethecombiningofvariousprotectiontechniques.As longascombinationofprotectiontechniquesareallsuitableforthe sameZoneorCategoryofhazard,theproductissuitableforthat same Zone or Category of hazard, the product is suitable for that hazard.Example,bothe&dprotectiontechniquesaresuitablefor Category2(22)orZone1hazardousareas.
WhichEXprotectionmethodisthemostcost effectivesolution?
Generalities IfZone1locations EExeIncreasedSafetyistypicallythewaytogoifatallpossibleduetoweight, costandeaseofmaintenance EExdusedwheneprotectionisnotpractical,i.e.MotorStarters,Circuit Breakers,etc. Hybride&dusuallythebestconceptwhereyoutakethebestofbothand combinethetwo. combine the two. Lighting Zone1HIDlightingisgoingtoalwaysbeEExdconstruction,where fluorescentsaremorelikelytobeEExeplastics.Forlowmountingapplications, fluorescentsareusuallyamostcosteffectivesolution.Tominimizefixturecount, higherwattageHIDsinZone2ornonhazardouslocationswithintermixed Fluorescentshasbeenthetrend. Fl t h b th t d InstrumentationcircuitsforZone1aretypicallyI.S. Generalities IfZone2locations. MoreprotectionconceptsareavailablesuchasExnRlighting,ExnAlighting,ExnC nonsparking,etc.ThemajorareaofpotentialsavingsisZone2lightingHID, restrictedbreathingvs.FlameproofExdconstruction.Thecomponentissueswith glandsandenclosuresforthemostpartwillnotchangefromZone1construction, i.e.brassglands,fiberglassenclosures,etc. i e brass glands fiberglass enclosures etc Ingeneral,lookatEExeconstructionwhereverpossible,minimizetheEExd whereverpossibleandlookfor