Professional Documents
Culture Documents
SYMMETRICAL COMPONENTS
Chapter 6
Page 1
Symmetrical Components
SYMMETRICAL COMPONENTS
INTRODUCTION SEQUENCE COMPONENTS FAULT CONDITION PHASOR DIAGRAMS SEQUENCE IMPEDANCE FOR TRANSFORMERS SEQUENCE IMPEDANCE FOR CABLES SEQUENCE IMPEDANCE FOR MOTORS SEQUENCE IMPEDANCE FOR GENERATORS EQUIVALENT CIRCUIT FOR LINE TO GROUND FAULTS PROBLEM 4
Chapter 6
Page 2
Symmetrical Components
INTRODUCTION
The symmetrical components method (mathematical operations) is the foundation for obtaining and understanding ground fault data on three-phase power systems. In short, the method of symmetrical components is one of the relay/coordination engineers most powerful technical tools. While the method and mathematics are quite simple, the practical value lies in the ability to think and visualize in symmetrical components. This skill requires practice and experience. The symmetrical components method consists of reducing an unbalanced three-phase system of phasors into three balanced or symmetrical systems: the positive, negative, and zero phase sequence components. This balanced reduction can be performed in terms of current, voltage, and impedance. BALANCED SYSTEM A balanced system (i.e., a three-phase fault) consists of three phasors, all equal in magnitude and 120o apart (Figure 6-1). For example: IA = 10o = 1.0 + j0 IB = 1240o = -0.5 - j0.866 IC = 1120o = -0.5 + j0.866 I A + IB + IC = 0 |IA| = |IB| = |IC|
Chapter 6
Page 3
Symmetrical Components
Unbalanced System
An unbalanced system (e.g., a line-to-ground fault) consists of three-phasors, not all equal in magnitude or degrees apart (Figure 6-2). For example: IA = 10o = 1.0 + j0 IB = 2 225o = -1.0 - j1.0
Chapter 6
Page 4
Symmetrical Components
SEQUENCE COMPONENTS
The sequence components consist of three sequence sets: positive (+) sequence, negative (-) sequence, and zero (0) sequence. Positive sequence (+) components consist of three phasors equal in magnitude, displaced from each other by 120o in phase, and having the same phase sequence (abc) as the original unbalanced phasors (abc). The term positive derives from the fact that Ib1 is a positive (+) 120o behind Ia1 (Figure 6-3). Note: Subscript 1 identifies the positive sequence component, subscript 2 identifies the negative sequence component, and the subscript 0 identifies the zero sequence component.
Negative sequence (-) components consist of three phasors equal in magnitude, displaced from each other by 120o in phase, and having the phase sequence opposite (acb) to that of the original phasors (abc). The term negative derives from the fact that Ib2 is a negative (-) 120o behind Ia2 (Figure 6-4).
Chapter 6
Page 5
Symmetrical Components
Zero sequence (0) components consist of three phasors equal in magnitude and with zero phase displacement (0o) from each other (Figure 6-5).
Chapter 6
Page 6
Symmetrical Components
Operators (J, A)
The j operator is a unit phasor with an angle displacement of 90o (Figure 6-6). j = 1 90o = 0 + j1.0 = j j2 = 1 180o = -1.0 + j0 = -1.0 j3 = 1 270o = 0 - j1.0 = -j j4 = 1 360o = 1.0 + j0 = 1.0 -j = 1 270o = 0 - j1.0 = -j = j3
The a operator is a unit phasor with an angle displacement of 120o (Figure 6-7). a = 1 120o = - 0.5 + j0.866 -a = 1 300o = + 0.5 - j0.866 a2 = 1 240o = - 0.5 - j0.866 -a2 = 1 60o = + 0.5 + j0.866
Chapter 6
Page 8
Symmetrical Components
o No negative or zero sequence currents flow for three-phase faults; only positive sequence currents flow. o Only positive and negative sequence currents flow for line-to-line faults. o Positive, negative, and zero sequence currents flow for faults involving ground.
Sequence Voltages Figure 6-9 shows and the following characteristics apply to the voltage sequence component sets for three-phase faults and line-to-line faults.
o No negative or zero sequence voltages exist for a three-phase fault and the positive sequence voltage collapses to zero at the point of the fault. o No zero sequence voltages exist for line-to-line faults. o Positive, negative, and zero sequence voltages exist for faults involving ground.
Chapter 6
Page 9
Symmetrical Components
Sequence Currents
Chapter 6
Page 10
Symmetrical Components
Sequence Voltages
Chapter 6
Page 11
Symmetrical Components
o If either one of the neutrals of a wye-wye (Y-Y) transformer bank is ungrounded, zero sequence current (I0) cannot flow in either winding. o Where both neutrals of a wye-wye (Y-Y) transformer bank are grounded, zero sequence current (I0) flows in both windings. o In delta-wye (-Y) or wye-delta (Y-) transformer grounded banks, zero sequence currents (I0) have a path only through the wye (Y) winding. o No zero sequence currents (I0) flow in a delta-delta (-) transformer bank. o If the connection from neutral to ground contains an impedance (ZN), the zero sequence equivalent circuit model must be modeled as an impedance of 3ZN.
Chapter 6
Page 12
Symmetrical Components
Chapter 6
Page 13
Symmetrical Components
Chapter 6
Page 14
Symmetrical Components
Chapter 6
Page 15
Symmetrical Components
PROBLEM 4
10 MVA 6% 13.8 kV
Ground Fault
200 HP
Calculate the line to ground fault current in the 4.16kV system using the following methods: A. B. C. Approximate method (only grounding resistor) Ignoring motor contribution. Including motor contribution.
Note: For the utility, transformers, cable, and motor: Assume that the total impedance is reactive.
Chapter 6
Page 16
Symmetrical Components
PROBLEM 6 SOLUTION
Utility Contribution SCC Z(p.u. on 100 MVA base) = = 1200 MVA 100 SCC (MVA) Z(p.u. on 100 MVA base) = = 10 MVA Transformer (Branch 100) Z% Z(p.u. new) = = 6.0 % Z(p.u. old) * MVA (base-new) 100 1200 .0833 P.U.
MVA (base-old) Z(p.u. new) = 6.0 100 Z(p.u. new) = 0.060 * MVA (base-new) MVA (base-old) 100 10 Z(p.u. new) = 0.6000 P.U.
Chapter 6
Page 17
Symmetrical Components
Z(p.u. new)
5.50 100
Z(p.u. new)
0.0550
Z(p.u. new)
2.200 P.U.
X (p.u.) =
X (ohms) Z (base)
= 0.10 1.90440
0.0525
P.U.
R (p.u.)
= R (ohms) R (base)
= 6.0 17.3056
34.671
P.U.
Chapter 6
Page 18
Symmetrical Components
MVA (base-old) X(p.u.) = 0.17 * MVA (base-new) MVA (base-old) X(p.u.) = 0.17 100
1) Ilg
Chapter 6
Page 19
Symmetrical Components
j 0.0833
j 0.6 3 * (34.671)
j 0.0525
Grounding 2.5 MVA TXMR
j 2.2
j 2.2
3 j(8.0716) + 104.13
= Ifault =
.028756 P.U.
Chapter 6
Page 20
Symmetrical Components
= =
Chapter 6
Page 21
Symmetrical Components
Utility 10 MVA
j 0.0833
j
j 0.6
j 8.5
Cable j 0.0525 200 HP
3 * (34.671)
2.5 MVA
Groundin j 2.2
2.5 MVA
j 2.2
Zero Sequence
XP.U.
2.18212 P.U.
Ilg
3E Z1 + Z2 + Z0 + 3Zn
3 j(6.56424) + 104.13
3 104.2199
.02875 P.U.
Ifault
IP.U. * Ibase
Chapter 6
Page 22
Symmetrical Components
= =
Chapter 6
Page 23
Symmetrical Components