Professional Documents
Culture Documents
Station-Bus Protection
Revised by: SOLVEIG WARD
Figure 11-4 Connection of one CA-16 relay per phase to Figure 11-6 Connection of one CA-16 relay per phase to
protect a bus with three equivalent circuits. (Connections for protect a bus with six equivalent circuits. (Connections for
one phase only are shown.) one phase only are shown.)
completely saturated, and there is no saturation in the KAB relay application, the knee voltage is
source current transformers. The maximum voltage is defined as the intersection of the extension of
equal to the resistance drop produced by the secondary the two straight-line portions of the saturation
current through the leads and secondary winding of curve. The ordinate and abscissa must use the
the saturated current transformer. In practice, the same scales.
faulted current transformer will never completely
saturate, and the source current transformers will The margin factor curve, shown in Figure 11-8, is
tend to saturate. As a result, the actual maximum based on tests of the KAB relay in the high-power
voltage is less than the theoretical value. The margin laboratory. A safety factor of 2 has been included in
factor K, which modifies this voltage, varies directly constructing this curve.
with the current transformer saturation factor SF: The maximum number of circuits that can be
connected to the relay, or the minimum internal fault
1 ðRS þ RL ÞIF current required to operate the relay, can be estimated
¼ ð11-5Þ
SF NVk from the following equation:
where
Imin ¼ ðXIe þ IR þ IV ÞN ð11-6Þ
Vk ¼ knee voltage value of the poorest current
transformer connected to the relay. For type where
tially different main circuit current transformers to be associated with the circuit on which the external fault
accommodated and also reduce current to a suitable occurred, restraint is developed across the resistor Rs.
level for the relay. The RED-521, being a micropro- Any condition that produces I DIFF current will,
cessor relay, is able to accept widely varying inputs through the transformer and the full-wave bridge,
from the main current transformers and to provide, generate a voltage Vd3. For the through fault case, the
internally, the appropriate scaling factors. The RED- restraint voltage Vs will exceed the operating voltage
521 is therefore very suitable for double-bus-single- Vd3, and the relay will refrain from operating. For the
breaker arrangements as no external ct switching takes internal fault case, I DIFF will be large, Vd3 will exceed
place. The ct is connected to the appropriate protection Vs, current will be passed through the diode and the
zone numerically inside the relay. reed relay DR, and tripping will occur. SR is a ‘‘start’’
Taking advantage of Kirchoff’s law, the scheme relay whose contact supervises tripping to add to the
compares the sum of all of the currents entering the overall security of the relay. It is obvious that this relay
bus with the sum of all of the currents leaving the bus. is extremely fast because the decision to trip is based
These are instantaneous currents (as opposed to rms or on instantaneous currents.
average currents.) The RED-521 numerical relay uses this principle,
In the circuit of Figure 11-11, the currents are but is not encumbered by need for the auxiliary
delivered to the relay through the diodes. The sum of matching current transformers, the diodes, or any
the currents through the lower group of diodes is other of the components inherently required in the
representative of the instantaneous sum of the incom- comparison process. The individual samples of cur-
ing currents to the bus, and the current flowing to the rents are collected and summed appropriately to
upper group of diodes is representative of the develop numerically the I IN and I OUT values and
instantaneous sum of the currents leaving the bus. the corresponding restraint quantity. This is compared
These two sum currents are always in perfect balance with the difference of these individual sums, I DIFF,
provided the current transformers perform their job and a determination of the need to trip is established.
faithfully and there is no fault on the bus (or to state it
more correctly, provided there are no current paths off
of the bus that are unaccounted for). 6 PROTECTING A BUS THAT INCLUDES A
If an internal fault (phase or ground) were to occur, TRANSFORMER BANK
the currents in and out would no longer match. They
would differ by the amount of the fault current. This Ideally, when the bus includes a power transformer
difference current appears as I DIFF in the relay. bank, separate protection should be provided for the
To accommodate the inherent errors in the current bus and transformer, even though both protection
transformers for an external fault, particularly in the ct schemes must trip all breakers around the two units.
Two bus differential zones are provided, one for each in one or more of the circuits are not included in the
bus, with each one overlapping the bus breaker. Each phasor summation of the current to the relay.
primary circuit is normally switched to a specific bus, In this scheme, only the source circuits are
and relay input circuits and breaker control circuits are differentially connected, as shown in Figure 11-17b,
wired accordingly. The additional check-zone device using a high-set overcurrent relay with time delay. The
supervises the trip circuits. If it becomes necessary to ct’s protecting the feeders or circuits are not in the
clear one of the buses, all the primary circuits may be differential connection.
switched to the opposite bus and it is needless to Essentially, this arrangement combines time-delay
disable the bus protection before any switching bus protection with feeder backup protection. The
operation. However, this scheme still has two draw- sensitivity and speed of this scheme are not as good as
backs when any one or all of the primary circuits is with complete differential protection. This method
switched to the opposite bus: (1) It will lose its may be used as a backup to a complete differential
selectivity, and (2) it will reduce its sensitivity since scheme, as primary protection for a station with loads
the two relays are paralleled. protected by fuses, or to provide local breaker failure
A numerical scheme, such as RED-521, overcomes protection for load breakers.
these drawbacks as there is no external ct switching In modern microprocessor systems, provision has
involved. The ct’s are connected to the appropriate been included to allow communications between the
zone by numerical switching in the relay. feeder breaker relaying and the source breaker relaying.
The feeder breakers are each equipped with a nontrip-