You are on page 1of 15

11

Station-Bus Protection
Revised by: SOLVEIG WARD

1 INTRODUCTION 1.1 Current Transformer Saturation Problem


and Its Solutions on Bus Protection
A bus is a critical element of a power system, as it is the
point of convergence of many circuits, transmission, Bus differential relaying is complicated by the fact that
generation, or loads. The effect of a single bus fault is for an external fault on one circuit, all of the other
equivalent to many simultaneous faults and usually, circuits connected to the bus contribute to that fault.
due to the concentration of supply circuits, involves The current through the circuit breaker for the faulted
high-current magnitudes. High-speed bus protection is circuit will be substantially higher than that for any of
often required to limit the damaging effects on the other circuits. With this very high current flowing
equipment and system stability or to maintain service through the current transformer and its circuit breaker,
to as much load as possible. The bus protection there is a very high likelihood that some degree of
described refers to protection at the bus location, saturation will occur. A saturated current transformer
independent of equipment at remote locations. will not deliver its appropriate current to the bus relay.
Differential protection is the most sensitive and With the lower currents in the other circuits for this
reliable method for protecting a station bus. The external fault, the degree of saturation is expected to be
phasor summation of all the measured current entering considerably lower. This may lead to a large differ-
and leaving the bus must be 0 unless there is a fault ential current that will tend to cause the relay to sense
within the protective zone. For a fault not in the an internal fault rather than the actual external fault
protective zone, the instantaneous direction of at least that exists. The relay must accommodate this error
one current is opposite to the others, and the sum of current without misoperation.
the currents in is identical to the sum out. A fault on A widely used equivalent diagram for a current
the bus provides a path for current flow that is not transformer appears in Figure 11-3b. It consists of a
included in these summations. This is called the perfect transformation from the high current side to
differential current. Detection of a difference exceeding the low current side (e.g., 600:5). All of the significant
the predictable errors in the comparison is one imperfections are lumped into Rp, Rs, and Xm. The Rs
important basis for bus relaying. represents the internal secondary resistance of the ct
In dealing with high-voltage power systems, the (current transformer), and the X represents a current
relay is dependent on the current transformers in the path that accommodates the exciting requirements.
individual circuits to provide information to it regard- The ct is assumed to have a uniformly distributed
ing the high-voltage currents. Figure 11-1 shows winding and, therefore, to manifest no significant
typical examples of the location of current transfor- leakage reactance.
mers that are used for this purpose. The arrowheads When the ct is subjected to excessive flux, the ct is
indicate the reference direction of the currents. said to ‘‘saturate,’’ meaning that the core of the ct has

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


Figure 11-1 Common bus arrangements with relay input sources.

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


been forced to carry more flux than it can handle. The (zone-2 trip) and may interrupt unnecessarily a tapped
flux then spills into the area surrounding the core, load. When local bus protection is applied, the
causing the magnetizing reactance to have a much following information is required for the scheme
lower value than normal. It can be seen that any selection, relay selection, and setting calculations:
current that flows in X subtracts from the perfectly
1. Information about the bus configuration is
transformed current, producing a deficiency in the
required. The common bus arrangements are
current that is delivered to the devices connected to the
as shown in Figure 11-1, such as single bus,
ct. The black blocks are the polarity markers. A single
double bus, main-and-transfer bus, ring bus,
polarity marker has no significance. With two, it is
breaker and a half, bus tie-breaker, double-bus-
acknowledged that, at the instant of time at which
single-breaker, etc.
current is flowing into the polarity marker on the high
2. Maximum and minimum bus fault currents
current side of the ct, current is flowing out of the
(single-phase-to-ground fault and three-phase
polarity marker on the low current side. Of course, the
fault)
current reverses every half cycle, but both the high and
3. Current transformer information, including
low reverse together.
Direct current saturation is much more serious than Current transformer location
ac saturation because a relatively small amount of dc Current transformer ratios
from an asymmetrical fault wave will saturate the Current transformer accuracy class
current transformer core and appreciably reduce the Current transformer saturation curves
secondary output. The L/R ratio of the power-system
4. Operating speed requirement
impedance, which determines the decay of the dc
component of fault current, should strongly influence
the selection of the bus protective relaying. Typically,
1.3 Normal Practices on Bus Protection
the dc time constants for the different circuit elements
can vary from 0.01 sec for lines to 0.3 sec or more for
The normal practices on bus protection are
generating plants. The nearer a bus location is to a
strong source of generation, the greater the L/R ratio 1. There is one set of bus relays per bus section.
and the slower the decay of the resulting dc component 2. Use a dedicated ct for bus differential protec-
of fault current. tion. If possible, the connection of meters,
Of the several available methods for solving the auxiliary ct’s, and other relays in differential-
unequal performance of current transformers, four are type bus schemes should be avoided since these
in common use: devices introduce an additional burden into the
main circuit.
1. Eliminating the problem by eliminating iron in
3. Lead resistance, as well as ct winding resistance,
the current transformer [a linear coupler (LC)
contributes to ct saturation. Therefore, the
system]
length of secondary lead runs should be held
2. Using a multirestraint, variable-percentage dif-
to a minimum.
ferential relay which is specifically designed to
4. Usually, the full-ct secondary winding tap
be insensitive to dc saturation (CA-16 relay
should be used. This has two advantages. It
system)
minimizes the burden effect of the cable and,
3. Using a high impedance differential relay with a
second, leads by minimizing the secondary
series resonant circuit to limit sensitivity to ct
current and makes use of the full-voltage
saturation (KAB relay system)
capability of the ct.
4. Using a Differential Comparator relay with
5. Normally, there is no bus relay required for the
moderately high impedance to limit sensitivity
transfer bus on a main-and-transfer bus
to ct saturation (RED-521)
arrangement. The transfer bus is normally
deenergized and will be included in the main
1.2 Information Required for the Preparation of bus section when it is energized.
a Bus Protective Scheme 6. No bus relay is required for a ring bus because
the bus section between each pair of circuit
Some bus protection schemes rely on the operation of breakers is protected as a part of the connected
a remote breaker. It is simple and economic, but slow circuit.

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


7. Special arrangements should be considered if than three primary time constants, and its setting must
there is any other apparatus, such as station be greater than the exciting current of the current
service transformers, capacitor banks, ground- transformer under worst-case conditions. This may
ing transformers, or surge arresters, inside the require a setting of 10 or more amperes and a time
bus differential zone. setting of, say, 18 cycles. These values may be
8. There is no simple scheme available for a acceptable for smaller substation buses, but more
double-bus-single-breaker arrangement (Fig. sophistication and faster relaying speed are generally
11-1e), because its current transformers are mandatory for more extensive and higher-voltage
normally located on the line side. These buses.
applications greatly benefit from numerical In these applications a ‘‘short time’’ or ‘‘extremely
schemes, such as the RED-521. (Refer to Sec. inverse’’ characteristic overcurrent relay is used in the
9 of this chapter for more information.) interests of getting faster tripping speeds at high
current. Operating times of 8 to 18 cycles are expected.
Although the relay cost is low, the engineering cost
may be high because of the usual need for considerable
2 BUS DIFFERENTIAL RELAYING WITH study for the application to assure correct operation.
OVERCURRENT RELAYS
2.1 Overcurrent Differential Protection
2.2 Improved Overcurrent Differential
This differential scheme requires that a time-over- Protection
current relay be paralleled with all of the current
transformers for a particular phase, as shown in The sensitivity of the overcurrent differential scheme
Figure 11-2. It is permissible to use auxiliary ct’s to (Fig. 11-2) can be improved by externally connecting a
match ratios, but it is preferred that all of the ct’s have series resistor with each overcurrent relay, as shown in
the same ratio on the tap chosen and that the use of Figure 11-3. These resistors are called stabilizing
auxiliary ct’s be avoided. resistors. If we assume that an external fault causes
In this scheme, the overcurrent relay must be set to the ct on the faulted feeder to be saturated completely,
override the maximum error current that results from the ct excitation reactance will approach 0. As shown
an external fault (phase or ground). It may also be in Figure 11-3, the error current Id that flows through
necessary to have sufficient time delay to refrain from
tripping during the time that one or more of the
current transformers is severely saturated by the dc
component of the primary current. To assure this,
using a simple overcurrent relay, the current transfor-
mers must be chosen to have no more than 20 times
rated current flowing in their primary for the worst-
case external fault, and each have a burden no more
than the rated value (relaying-accuracy-class voltage/
100). The operating time of the relay must not be less

Figure 11-3 The improved overcurrent differential bus


Figure 11-2 The overcurrent differential bus protection. protection.

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


the overcurrent unit would be percentage is small for maximum sensitivity. For heavy
  external faults, current transformer performance is
2RL þ RS
Id ¼ IF ð11-1Þ likely to be poor, and the percentage is large. The
2RL þ RS þ Rd variable-percentage characteristic is obtained by ener-
where Rd is the resistance in the differential path. gizing the operating unit through a built-in saturating
In order to reduce the error current Id in the autotransformer.
differential path for improving the sensitivity of the The saturating autotransformer also presents a high
scheme, the most effective way is to increase the value impedance to the false differential current, which tends
of Rd. The limitations of this additional resistance are to limit the current through the operating coil and to
determined by (1) the overvoltage to the ct circuit and force more equal saturation of the current transfor-
(2) the minimum available internal fault current. It mers. On internal faults, in which a desirable high
should be limited to differential current exists, saturation reduces the
impedance. A further advantage of the saturating
VCL autotransformer is that it provides a very effective
Rd ¼ O ð11-2Þ
46Imin pickup shunt for the dc component, appreciably reducing the
dc sensitivity of the operating units. At the minimum
Note: The multiplier 4 includes a safety factor of 2.
pickup current of 0.15 + 5% A, the restraining coils
are ineffective.
When using the CA-16 relay, the current transfor-
3 MULTIRESTRAINT DIFFERENTIAL SYSTEM mers should not saturate when carrying the maximum
external symmetrical fault current; that is, the exciting
Multirestraint differential schemes use conventional current should not exceed one secondary ampere rms.
current transformers, which may saturate on heavy This requirement is met if the burden impedance does
external faults. For this reason, the secondary current not exceed
output may not represent the primary. In a differential
scheme, the current transformers and relay function as ½NP VCL  ðIEXT  100ÞRS
ð11-3Þ
a team. When the current transformers do not perform 1:33 IEXT
adequately, the relay can within limits make up for the
where
deficiency.
The multirestraint differential scheme uses the CA- NP ¼ proportion of total current transformer
16 variable-percentage differential relay, which con- turns in use
sists of three induction restraint units and one VCL ¼ current transformer accuracy-class voltage
induction operating unit per phase. Two of the units IEXT ¼ maximum external symmetrical fault current
are placed opposite each other and operate on a in secondary (amperes rms) (use IEXT ¼ 100
common disc. In turn, the two discs are connected to a if IEXT < 100)
common shaft with the moving contacts. All four of RS ¼ current transformer secondary winding resis-
the units are unidirectional; that is, current flow in tance of the turns in use (in ohms); for
either direction through the windings generates con- example, if the 400:5 tap of a 600:5 wye-
tact-opening torque for the restraint units or contact- connected class C200 current transformer is
closing torque for the operating unit. Each restraint used, then NP ¼ 400/600 ¼ 0.67 and
unit (called R, S, and T) also has two windings to VCL ¼ 200
provide restraint proportional to the sum or difference,
depending on the direction of the current flow. If the If IEXT ¼ 120 A and RS ¼ 0.5 O, then the burden of
currents in the two paired windings are equal and the ct’s secondary circuit, excluding current transfor-
opposite, the restraint is cancelled. Thus, the paired mer secondary winding resistance, should not exceed
restraint windings have a polarity with respect to each 0:676200  ð120  100Þ0:5
other. With this method six restraint windings are ¼ 0:78 O
1:336120
available per phase.
In addition to providing multiple restraint, the Settings for the CA-16 relay need not be calculated.
variable-percentage characteristic helps in overcoming Field experience indicates that one CA-16 relay per
current transformer errors. At light fault currents, phase is satisfactory for the vast majority of applica-
current transformer performance is good, and the tions.

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


External connections are as shown in Figures 11-4
through 11-6. Figure 11-4 may be used if only three
circuits are involved. The term circuit refers to a source
or feeder group.
When several circuits exist and the bus can be
reduced to four circuits, then the scheme of Figure 11-5
may be used. For example, assume a bus consists of
two sources and six feeders, and that the feeders are
lumped into two groups. The bus now reduces to four
circuits.
In paralleling current transformers, each feeder
group must have less than 14 A load current (restraint
coil continuous rating).
If the bus reduces to more than four circuits, then
the scheme of Figure 11-6 should be used. In applying
the scheme of Figure 11-6, each primary circuit must
be identified as either a source or feeder. As defined
here, a feeder contributes only a small portion of the
total fault current for a bus fault. All other circuits are
sources. Next, a number of feeders are lumped into a
Figure 11-5 Connection of one CA-16 relay per phase to
feeder group by paralleling feeder current transfor- protect a bus with four equivalent circuits. (Connections for
mers. Each feeder group must have less than 14 A load one phase only are shown.)
current and not contribute more than 10% of the total
phase- or ground-fault current for a bus fault. Then
connect the ‘‘source’’ and ‘‘feeder groups’’ alternately
as shown in Figure 11-6.
Note that in Figures 11-4 through 11-6, electro-
magnets R, S, and T are referred to. Each of these
elements has two windings. The polarity markings are
extremely significant as related to one another on the
same electromagnet, but have no significance with
respect to one another on different electromagnets. If
the current into a polarity marker is equal to the

Figure 11-4 Connection of one CA-16 relay per phase to Figure 11-6 Connection of one CA-16 relay per phase to
protect a bus with three equivalent circuits. (Connections for protect a bus with six equivalent circuits. (Connections for
one phase only are shown.) one phase only are shown.)

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


current out of the polarity marker on the same overcurrent differential’’ approach. It uses a high
electromagnet, there will be no restraining torque impedance voltage element instead of ‘‘a low impe-
produced by that electromagnet. The sum of all of the dance overcurrent element plus an external resistor.’’
restraint torques is compared to that produced by the The high impedance differential KAB relay consists
operating coil. Current into the operating coil circuit of an instantaneous overvoltage cylinder unit (V), a
produces a much stronger effect than the same current voltage-limiting suppressor (varistor), an adjustable
through a single restraint winding. For an external tuned circuit, and an instantaneous current unit (IT).
fault, there is no current through the operating coil if On external faults, the voltage across the relay
the current transformers perform perfectly. There will terminals will be low, essentially 0, unless the current
be substantial restraint for this same condition, even transformers are unequally saturated. On internal
though in some restraint electromagnets some (or even faults, the voltage across the relay terminals will be
total) cancellation may take place. high and will operate the overvoltage unit. Since the
Consider a fault on the bus of Figure 11-5 in which impedance of the overvoltage unit is 2600 O, this high
all of the high-voltage circuits contribute the same voltage may approach the open-circuit voltage of the
value of current. All of the restraint cancels because in current transformer secondaries. The varistor limits
each of the electromagnets the current into the polarity this voltage to a safe level.
marker equals the current out of its paired coil. All of Since offset fault current or residual magnetism
the internal fault current (in secondary terms, of exists in the current transformer core, there is an
course) flows into the operating coil circuit and fast appreciable dc component in the secondary current.
tripping occurs. Practical cases with widely differing The dc voltage that appears across the relay will be
fault contributions produce similar effects even though filtered out by the tuned circuit, preventing relay
considerable restraint torque may be present. pickup.
Consider, now, an external fault on the upper circuit The IT current unit provides faster operation on
off of the bus with the equal fault current contributions severe internal faults and also backup to the voltage
that were assumed in the previous case. Torque unit. The range of adjustment is 3 to 48 A.
cancellation occurs in electromagnet T, as before. The KAB relay has successfully performed opera-
Substantial restraint torque is produced by R and S. tions up to external fault currents of 200 A secondary
The operating coil current cannot exceed the error and down to an internal fault current of 0.27 A
current in the faulted circuit (which may well be secondary. Its typical operating speed is 25 msec.
extreme due to the effect of saturation). The overvoltage unit is set by calculating the
This is a very sensitive bus relaying scheme, and it is maximum possible voltage for an external fault as
very secure against operation for external faults even follows:
though severe ct saturation may occur for one or more
ct’s. It is reasonably fast. Another advantage is that it IF
VR ¼ KðRS þ RL Þ ð11-4Þ
can accept auxiliary ct’s in the circuit, which allows N
different ratios of the main ct’s. Two shortcomings are
Where
its comparative inflexibility as other circuits are added
to the bus and the need to bring all circuits back from VR ¼ pickup setting of the V unit in volts rms
the switchyard to the relay location. RS ¼ dc resistance of current transformer secondary
winding, including internal leads to bushing
terminals
4 HIGH IMPEDANCE DIFFERENTIAL SYSTEM RL ¼ resistance of lead from junction points to the
most distant current transformer (one-way
Although the high impedance differential scheme also lead for phase faults, two-way lead for
uses conventional current transformers, it avoids the phase-to-ground faults)
problem of unequal current transformer performance IF ¼ maximum external primary fault current, in
by loading them with a high impedance relay (Fig. amperes rms, contributed by the bus
11-7). N ¼ current transformer turns ratio
This arrangement tends to force the false differential K ¼ margin factor
currents through the current transformers rather than
the relay operating coil. Actually, the high impedance The maximum voltage occurs for the external fault
differential concept comes from the above ‘‘improved when the faulted circuit current transformer is

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


Figure 11-7 External connection of type KAB bus differential relay.

completely saturated, and there is no saturation in the KAB relay application, the knee voltage is
source current transformers. The maximum voltage is defined as the intersection of the extension of
equal to the resistance drop produced by the secondary the two straight-line portions of the saturation
current through the leads and secondary winding of curve. The ordinate and abscissa must use the
the saturated current transformer. In practice, the same scales.
faulted current transformer will never completely
saturate, and the source current transformers will The margin factor curve, shown in Figure 11-8, is
tend to saturate. As a result, the actual maximum based on tests of the KAB relay in the high-power
voltage is less than the theoretical value. The margin laboratory. A safety factor of 2 has been included in
factor K, which modifies this voltage, varies directly constructing this curve.
with the current transformer saturation factor SF: The maximum number of circuits that can be
connected to the relay, or the minimum internal fault
1 ðRS þ RL ÞIF current required to operate the relay, can be estimated
¼ ð11-5Þ
SF NVk from the following equation:
where
Imin ¼ ðXIe þ IR þ IV ÞN ð11-6Þ
Vk ¼ knee voltage value of the poorest current
transformer connected to the relay. For type where

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


The use of auxiliary ct’s is discouraged, though,
with proper consideration of their resistance in
series with the lead resistance (raising the
effective RL), they may be used at the sacrifice
of some sensitivity of fault recognition. The same
comment applies to the introduction of other
devices in the current transformer circuits.
The junction point for all of the ct’s in the bus
differential system should be in such a location as
to equalize as much as possible the distance from
each ct to this point. This will minimize RL, the
value used in the setting calculation and thus
allow better sensitivity to be achieved. Departure
from this requirement is permissible in metal-clad
Figure 11-8 Empirical margin factor for setting the V-unit switchgear because of the comparatively short
of the KAB relay. distances usually involved.
The lead resistance from the junction point to the
Imin ¼ minimum primary fault current in amperes relay terminals is not critical.
rms
Note that with this system total saturation of the
Ie ¼ secondary excitation current of the current
current transformer on a circuit feeding an external
transformer at a voltage equal to the setting
fault is allowed and the relay remains secure.
value of the V unit in amperes
IR ¼ current in the V unit at setting voltage VR in
amperes, that is, IR ¼ VR/2600 4.2 Factors that Relate to the High-Voltage
IV ¼ current in varistor circuit at a voltage equal to Problem
the setting value of the V unit in amperes
(generally negligible) All ct’s in the bus differential circuit should be
N ¼ current transformer turns ratio operated on their full-tap position. Refer to
X ¼ number of circuits connected to the bus Figure 11-9; a high voltage will be induced on the
In general, the following factors should be considered unused portion of the ct circuit due to auto-
when applying a high impedance bus differential relay. transformer action.
All current transformers should have the same ratio.
If taps must be used, the windings between the
4.1 Factors that Relate to the Relay Setting

The V-unit setting of the KAB relay is based on the


calculated result of Eq. (11–4), which is determined by
the values of K, RS, RL, and IF. In order to keep this
setting value within the available relay range of 75 to
400 V, it is necessary to keep the values of (RS þ RL)
and any additional burden in the ct secondary as low
as possible. This includes the consideration of the
following:
Use fully distributed winding current transformers,
such as bushing ct’s or current transformers with
toroidally wound cores, such as those used in
metal-clad switchgear. These ct’s provide a
negligible leakage reactance and therefore do
not contribute to the internal impedance in the
equivalent circuit of the ct. Only the RS resistance Figure 11-9 High voltage induced by autotransformer
is needed in series with RL in Eq. (11–4). action.

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


taps must be completely distributed, and any
high voltage at the full-tap terminal caused by
autotransformer action should be checked to
avoid insulation breakdown. In general, auxiliary
ct’s should not be used to match ratios.

4.3 Setting Example for the KAB Bus Protection

Assume a six-circuit bus for which the maximum


external three-phase fault current is 60,000 A rms,
symmetrical; the maximum external phase-to-ground
fault current is 45,000 A, and the minimum internal
fault current is 10,000 A. The current transformer
ratios are 2000:5, ANSI class C400, Vk is 375 V. The
secondary winding resistance RS is 0.93, and one-way
lead resistance to junction point RL is 1.07 O. Figure 11-10 Setting of KAB instantaneous unit.

the example, the ordinate value is


4.3.1 Settings for the V Voltage Unit ð0:93 þ 1:07Þ60,000
Three-phase fault ¼ ¼ 300
For the three-phase fault condition [using Eq. (11-5)], 400
Phase-to-ground fault
1 ð0:93 þ 1:07Þ60,000
¼ ¼ 0:8 ð0:93 þ 261:07Þ45,000
SF 4006375 ¼ ¼ 345
400
From Figure 11-8, 1.2 > K  0.82 (use the lower value
of 0.82 for sensitivity); therefore, using Eq. (11-4), we From these numbers, it is obvious from Figure 11-10
get that the IT unit is incapable of operating for an
external fault. The lowest available setting of 3 A will
60,000 usually be adequate because of the high conduction
VR  0:82ð0:93 þ 1:07Þ ¼ 246 V
400 level of present-day varistors. The principal tripping
For the phase-to-ground fault condition, function is accomplished at high speed by the voltage
unit, and only in extreme circumstances will the IT unit
1 ð0:93 þ 261:07Þ645,000 operate for an internal fault.
¼ ¼ 0:92
SF 4006375
And from Figure 11-8, 1.1 > K  0.77; therefore, using
Eq. (11-4) yields 5 DIFFERENTIAL COMPARATOR RELAYS
45,000
VR  0:77ð0:93 þ 261:07Þ ¼ 266 V These relays use the fundamental principle described in
400 Figure 11-11. The RADSS is a solid-state version, the
The minimum setting of the V unit in the KAB relay, REB-103 is similar to this, but the logic is accomplished
therefore, should be 266 V, the larger value for either with a microprocessor, while the RED-521 is entirely a
the three-phase or phase-to-ground conditions, as numerical relay. All are very high-speed relays (9- to 16-
calculated. msec tripping) and are very secure against misoperation
for external faults; all reliably and sensitively detect
internal faults and are quite flexible in accommodating
additional circuits. They may also be used for generator
4.3.2 Setting for the IT Current Unit
stator protection and for shunt reactor protection
The IT setting is determined from Figure 11-10. The though their prime application area is for bus protection.
higher value is used as the ordinate as determined from The RADSS and the REB-103 relays use external
the three-phase and phase-to-ground fault. Thus, for auxiliary current transformers which allow substan-

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


Figure 11-11 Differential comparator relay.

tially different main circuit current transformers to be associated with the circuit on which the external fault
accommodated and also reduce current to a suitable occurred, restraint is developed across the resistor Rs.
level for the relay. The RED-521, being a micropro- Any condition that produces I DIFF current will,
cessor relay, is able to accept widely varying inputs through the transformer and the full-wave bridge,
from the main current transformers and to provide, generate a voltage Vd3. For the through fault case, the
internally, the appropriate scaling factors. The RED- restraint voltage Vs will exceed the operating voltage
521 is therefore very suitable for double-bus-single- Vd3, and the relay will refrain from operating. For the
breaker arrangements as no external ct switching takes internal fault case, I DIFF will be large, Vd3 will exceed
place. The ct is connected to the appropriate protection Vs, current will be passed through the diode and the
zone numerically inside the relay. reed relay DR, and tripping will occur. SR is a ‘‘start’’
Taking advantage of Kirchoff’s law, the scheme relay whose contact supervises tripping to add to the
compares the sum of all of the currents entering the overall security of the relay. It is obvious that this relay
bus with the sum of all of the currents leaving the bus. is extremely fast because the decision to trip is based
These are instantaneous currents (as opposed to rms or on instantaneous currents.
average currents.) The RED-521 numerical relay uses this principle,
In the circuit of Figure 11-11, the currents are but is not encumbered by need for the auxiliary
delivered to the relay through the diodes. The sum of matching current transformers, the diodes, or any
the currents through the lower group of diodes is other of the components inherently required in the
representative of the instantaneous sum of the incom- comparison process. The individual samples of cur-
ing currents to the bus, and the current flowing to the rents are collected and summed appropriately to
upper group of diodes is representative of the develop numerically the I IN and I OUT values and
instantaneous sum of the currents leaving the bus. the corresponding restraint quantity. This is compared
These two sum currents are always in perfect balance with the difference of these individual sums, I DIFF,
provided the current transformers perform their job and a determination of the need to trip is established.
faithfully and there is no fault on the bus (or to state it
more correctly, provided there are no current paths off
of the bus that are unaccounted for). 6 PROTECTING A BUS THAT INCLUDES A
If an internal fault (phase or ground) were to occur, TRANSFORMER BANK
the currents in and out would no longer match. They
would differ by the amount of the fault current. This Ideally, when the bus includes a power transformer
difference current appears as I DIFF in the relay. bank, separate protection should be provided for the
To accommodate the inherent errors in the current bus and transformer, even though both protection
transformers for an external fault, particularly in the ct schemes must trip all breakers around the two units.

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


Such a system offers maximum continuity of service,
since faults are easier to locate and isolate. Also, using
a bus differential relay for bus protection and
transformer differential relay for transformer protec-
tion provides maximum sensitivity and security with
minimum application engineering.
However, economics and location of current trans-
formers often dictate that both units be protected in
one differential zone. For these applications, either the
multirestraint HU-4 or CA-26 relays should be used.
The HU-4 relay is similar to the HU and HU-1 relays,
except that it has four restraint windings. Also, the Figure 11-13 Protection of a typical transformer section
rectified outputs of the restraint transformers are where the transformer tertiary is brought out for load or
connected in series, providing a higher restraint force connected to an external source.
when a through fault occurs on the bus. Since the dc
saturation of current transformers will allow current to
pass into the HRU transformers and possibly pick up the The CA-26 relay is applicable to relatively small
IIT, the IIT unit of the HU-4 relay is set at 15 times the transformers remote from generating stations, HV,
rms tap value to prevent false tripping for external faults. and EHV buses. Here, inrush will usually be light and
Similar to the CA-16, the CA-26 relay has a not cause the CA-26 to operate. If, however, complete
stronger contact spring and higher pickup of security against inrush is required, the HU-4 must be
1.25 + 5% A to help override inrush. Its variable applied.
restraint curve is steeper than the CA-16, and its With CA-26 relays, the four-circuit bus connections
operating time is approximately three cycles. of Figure 11-5 are not recommended for bus protec-
Of the two types, the HU-4 relay is preferred, as it is tion, since the relay may have too much restraint for a
immune from operation on transformer magnetizing bus fault.
inrush. The HU-4 should always be applied for large The bus CA-16 relay should not be used for the
transformer banks or those associated with HV and transformer differential, since it is too sensitive to
EHV buses. A typical application, shown in Figure 11- override magnetizing inrush.
12, protects a three-winding transformer bus with four
circuits. Figure 11-13 illustrates another typical appli-
cation used in EHV systems. 7 PROTECTING A DOUBLE-BUS SINGLE-
BREAKER WITH BUS TIE ARRANGEMENT

The double-bus single-breaker with bus tie (Figure 11-


1e) provides economic and operating flexibility com-
parable to the double-bus double-breaker arrangement
(Fig. 11-1c). However, the ct’s are normally on the
line-side location, which results in increased differen-
tial relaying problems. Two different approaches have
been used in the bus protection of such arrangements:
the fully switched scheme (Fig. 11-14) and the
paralleling switch scheme (Fig. 11-15). They are both
complicated (inserting switch contacts in the ct
circuits) and/or imperfect in protection. These schemes
either require switching ct’s and/or disabling the bus
protection before any switching operation. This is a
period when the probability of a bus fault occurring is
Figure 11-12 Typical application of HU-4 relay for high and it is most desirable that the bus protection be
protecting a large transformer bank associated with HV in service. A third scheme as shown in Figure 11-16 can
and EHV buses. (Auxiliary current transformers for ratio be considered. It is similar to the paralleling switched
matching are not shown.) scheme except a check-zone relay is added as shown.

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


Figure 11-14 Fully switched scheme.

Figure 11-15 Paralleled switched scheme.

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


Figure 11-16 Paralleled switch with check zone scheme.

Two bus differential zones are provided, one for each in one or more of the circuits are not included in the
bus, with each one overlapping the bus breaker. Each phasor summation of the current to the relay.
primary circuit is normally switched to a specific bus, In this scheme, only the source circuits are
and relay input circuits and breaker control circuits are differentially connected, as shown in Figure 11-17b,
wired accordingly. The additional check-zone device using a high-set overcurrent relay with time delay. The
supervises the trip circuits. If it becomes necessary to ct’s protecting the feeders or circuits are not in the
clear one of the buses, all the primary circuits may be differential connection.
switched to the opposite bus and it is needless to Essentially, this arrangement combines time-delay
disable the bus protection before any switching bus protection with feeder backup protection. The
operation. However, this scheme still has two draw- sensitivity and speed of this scheme are not as good as
backs when any one or all of the primary circuits is with complete differential protection. This method
switched to the opposite bus: (1) It will lose its may be used as a backup to a complete differential
selectivity, and (2) it will reduce its sensitivity since scheme, as primary protection for a station with loads
the two relays are paralleled. protected by fuses, or to provide local breaker failure
A numerical scheme, such as RED-521, overcomes protection for load breakers.
these drawbacks as there is no external ct switching In modern microprocessor systems, provision has
involved. The ct’s are connected to the appropriate been included to allow communications between the
zone by numerical switching in the relay. feeder breaker relaying and the source breaker relaying.
The feeder breakers are each equipped with a nontrip-

8 OTHER BUS PROTECTIVE SCHEMES

Other methods for protecting buses are in limited use:


(1) partial differential schemes, (2) directional compar-
ison relaying, and (3) the fault-bus method. Except for
the latter, these schemes are most often applied as
economic compromises for the protection of buses.

8.1 Partial Differential Relaying

This type of protection is also referred to as ‘‘bus


overload’’ or ‘‘selective backup’’ protection. It is a
variation of the differential principle in which currents Figure 11-17 Partial differential protection.

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


ping low-set instantaneous overcurrent function that is
set somewhat above their maximum load. The source
breakers have an instantaneous overcurrent unit with
slight time delay that is set above the maximum total
load current for the bus, and they are equipped to
receive a status input from the feeder breakers. For a
fault on one of the feeder circuits, the low-set
instantaneous overcurrent unit operates and applies a
block signal to the source relay. The instantaneous unit
of the source breaker operates, but is unable to trip
because of the block signal. The time-delayed and
coordinated tripping of the source breaker is not
affected so its backup function stays intact.
For a bus fault, the block signal is absent, and
tripping of the source breaker occurs at high speed.
Some partial differential circuits use distance-type
relays in the scheme. The use of a distance relay for this
scheme produces both faster and more sensitive
operation than the overcurrent scheme.

8.2 Directional Comparison Relaying


Figure 11-18 Directional comparison bus protection.

Occasionally, it is desirable to add bus protection to an


older substation where additional ct’s and control cable and have only one connection to ground. An over-
are too costly to install. In this instance, the existing ct current relay is connected in this ground path as shown
circuits used for line relaying can also be used for the in Figure 11-19. Any ground fault to the supporting
directional comparison bus relaying protection. structure will cause fault current to flow through the
As shown in Figure 11-18, the directional comparison relay circuit, tripping the bus through the multiple-
relaying uses individual directional overcurrent relays contact auxiliary tripping relay. A fault detector,
on all sources and instantaneous overcurrent relays on energized from the neutral of the grounded transfor-
all feeders. The directional relays close contacts when mer or generator, prevents accidental tripping. This
fault power flows into the bus section. Back contacts on scheme requires special construction measures and is
the overcurrent relays open when the fault is external on expensive.
the feeder. All contacts are connected in series, and when
the fault occurs on the bus, the trip circuit is energized
through a timer. A time delay of at least four cycles will
allow all the relays to decide correctly the direction of the
fault and to permit contact coordination.
In this scheme, the ct’s in each circuit do not require
the same ratio and can be used for other forms of
relaying and metering.
The disadvantage of this scheme is the large number
of contacts and complex connections required. There is
also the remote possibility of the directional elements
not operating on a solid three-phase bus fault as a
result of 0 voltage.

8.3 Fault Bus (Ground-Fault Protection Only)

This method requires that all the bus supporting


structure and associated equipment be interconnected Figure 11-19 Fault bus.

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.

You might also like