SAUDI ARAMCO TEST REPORT


Emergency Eyewash/Shower Functional Test Report
PROJECT TITLE

SATR NUMBER

DATE APPROVED

QR NUMBER

SATR-B-4001
WBS / BI / JO NUMBER

18-May-05

PLUMB

CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) LAYOUT DRAWING NUMBER SCHEDULED TEST DATE & TIME SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO INSPECTION LEVEL

EQUIPMENT DESCRIPTION REV. NO. PURCHASE ORDER NUMBER

EQPT CODE

SYSTEM ID.

PLANT NO.

EC / PMCC / MCC NO. QUANTITY INSP. MH's SPENT TRAVEL TIME

ACTUAL TEST DATE & TIME SAUDI ARAMCO ACTIVITY NUMBER CONTRACTOR INSPECTION LEVEL

SAUDI ARAMCO USE ONLY


WORK PERMIT REQUIRED?

ITEM No.

TEST PROCEDURE ACCEPTANCE CRITERIA

REFERENCE

PASS

FAIL

N/A

RE-TEST DATE

A. TEST PROCEDURE AND CHECKLIST With the unit Correctly connected to the water sources and valve(s) closed, visually check the piping connections for leaks (ANSI Para 4.6.5.1) Open the valve to the full open position. The valves shall remain open without requiring further use of the operator's hand (ANSI 4.6.5.2) Measure The face of the shower head from the surface on which the user stands. (ANSI 4.6.5.3) (Applicable to Emergency showers only) With the valve in the " full on" position, measure the diameter of the sprays pattern. (ANSI 4.6.5.4) (Applicable to emergency showers only) Measure the water temperature at the discharge point. (SAES-B-069 Para 5.3) SAES-B-069 Section 7 SAES-B-069 Section 7 SAES-B-069 Section 7

A1

A2

A3

A4

SAES-B-069 Section 7 SAES-B-069 Section 7

A5

B. TEST EQUIPMENT AND MATERIALS CRITERIA See SATR-A-2003 (Calibration Test Report-Temperature Gauge) C. TEST RESULTS

Measured value from the face of the shower head to the surface on which the user stands Measured diameter of the spray pattern

CM

CM

Measured water temperature

Page 1 of 2

SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)

SAUDI ARAMCO TEST REPORT


Emergency Eyewash/Shower Functional Test Report
PROJECT TITLE

SATR NUMBER

DATE APPROVED

QR NUMBER

SATR-B-4001
WBS / BI / JO NUMBER

18-May-05

PLUMB

CONTRACTOR / SUBCONTRACTOR

D. CONCLUSIONS ITEM No. D1 TEST RESULTS ACCEPTANCE CRITERIA The face of the shower head from the surface on which the user stands is between 208.3 cm (82 inches) and 243.8 cm (96 inches) (ANSI 4.6.5.3) Note: Applicable to Emergency showers only With the valve in the " full on" position, measured diameter of the sprays pattern is a minimum of 50.8 cm (20 inch) at 152.4 cm (60 inch) above the standing surface. The center of the spray shall be at least 40.6 cm (16 inches) from any obstruction. (ANSI 4.6.5.4) (Applicable to emergency showers only) Measured water temperature is between 15C (min) and 38C (max) Test results are acceptable and in accordance with Saudi Aramco Engineering Standards and contractural requirements. REFERENCE SAES-B-069 Section 7 PASS FAIL N/A RE-TEST DATE

D2

SAES-B-069 Section 7

D3 D4

SAES-B-069 Para 5.3 N/A

REMARKS:

REFERENCE DOCUMENTS: 1-SAES-B-069 -- Emergency Eyewash and Showers, 31 January 2001 2-ANSI Z358.1 -- American National Standard for Emergency and Shower Equipment, 1990

Contractor / Third-Party
Technician Performing Test*
Name, Title, Department, Company, Initials and Date: Test Performed Successfully and Results are Acceptable: Name, Initials and Date:

Saudi Aramco
PMT Representative
T&I Witnessed QC Record Reviewed Work Verified

QC Inspector
Witnessed Test Name, Initials and Date: Work / Rework May Proceed

PID Representative
T&I Witnessed Name, Initials and Date: QC Record Reviewed Work Verified

QC Supervisor
Quality Record Approved: Name, Sign and Date: *Person Responsible for Implementation of Test and Analysis of Results

Proponent and Others


Name, Organization, Initials and Date: T&I Witnessed QC Record Reviewed Work Verified

Y = YES

N = NO F = FAILED

Page 2 of 2