Electrical Requirements for Health Care Facilities
Forward
The Office of Statewide Health Planning and Development (OSHPD) is responsible for enforcing all building standards, codes, and regulations pertaining to health care facilities in the State. The following document was compiled by the OSHPD electrical engineering staff as a guide for plan review to verify compliance and is intended for OSHPD use. It highlights and summarizes the most common requirements encountered in the review of health care facilities. All others who use this information for any other purpose do so with the full knowledge that it may not contain every requirement or change in policy and that the requirements are as interpreted by OSHPD. All projects submitted on or after January 1, 2008 are subject to the 2007 California Electrical Code (CEC) which is the 2005 National Electrical Code (NEC) with the 2007 California Amendments.
Page i
OSHPD
Electrical Requirements for Health Care Facilities
Table of Contents
Plan Review Check List................................................................................................................................. 1 Acute Care Hospital ...................................................................................................................................... 2 Acute Psychiatric Hospital........................................................................................................................... 29 Nursing Facility............................................................................................................................................ 30 Clinics.......................................................................................................................................................... 42 Appendix A .................................................................................................................................................. 43 Appendix B .................................................................................................... Error! Bookmark not defined. Index............................................................................................................................................................ 49
Page ii
OSHPD
Electrical Requirements for Health Care Facilities
Item 1 2 3 4 5
Description All electrical plans and specifications signed by the electrical engineer of record. List of symbols and abbreviations used on plans and their meaning. Correct electrical code version cited. Room names and numbers on all plan sheets. Single line diagram of the electrical system showing normal source and segregation of the essential electrical system. Clearly identify components as normal, critical, life safety, or equipment. Site plan showing service entrance, distribution system, service transformer, and generator location. Drawings showing details of all switchboards, panels, and equipment. Load calculations or other approved methods showing verification of load capacity for all equipment and conductors. Show effect on both normal and emergency system. Panel schedules with totalized, tabulated loads. Panel schedules shall indicate rating of panel, feeder conductor, feeder overcurrent protective device, branch/system (critical, life safety, equipment) and loads served. Schedules of ratings of equipment requiring electrical connection. Schedule showing all feeders phase and ground conductors, conduit sizes, estimated lengths, and overcurrent protective devices. Location and power source for all wiring devices, including receptacles, lights, switches, junction boxes, power outlets, and telephone outlets. Fire alarm system. Provide specifications for equipment, show location of all devices, and show connection to life safety power source. Indicate if power limited. Nurse call system. Provide specifications for equipment, show location of all devices, and show connection to power source. Indicate if power limited. All equipment must be listed, labeled, or certified by a Nationally Recognized Testing Laboratory including X-ray and diagnostic equipment.
7 8
10 11
12
13
14
15
Page 1
OSHPD
Electrical Requirements for Health Care Facilities
ELECTRICAL SYSTEM
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
Essential electrical system shall be comprised of two (2) systems with basically three (3) branches. The emergency system contains the critical and life safety branches, while the equipment system contains the equipment branches. Minimum of three (3) transfer switches are required, at least one (1) for each branch. [One (1) transfer switch allowed for maximum demand on essential electrical system of #150kVA] Branch wiring shall be independent of all other wiring and equipment except in transfer switches, exit signs, two source emergency lighting. Essential services may originate or pass through existing facilities provided they are seismically conforming facilities. Load capacity verification required for all modifications to existing systems. [See Policy Intent Notice, Appendix B]
CEC 517.30(B)
CEC 517.30(B)(4)
CEC 220.87
Critical
At least one receptacle and minimal lighting in electrical rooms. Ground fault protection required on service main 1000 ampere or greater for LG voltage > 150V. Ground fault protection required on feeders if supplied on main. This includes upgrades of existing facilities. No other function other than those listed in this Code section are allowed to be connected to the life safety branch of the emergency system.
CEC 517.33(A)(8)(n)
Normal
Life Safety
CEC 517.32
Page 2
OSHPD
Electrical Requirements for Health Care Facilities
EMERGENCY POWER
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
Alternate source of power shall be a generator Task illumination battery charger at generator set Selected receptacles at generator set Automatic restoration of power within 10 seconds
CEC 517.35(B) CEC 517.32(E) CEC 517.32(E) CEC 517.31 & 700.12
5 6
Battery and charger for automatic starting On site fuel supply for at least 24 hours of operation at full demand Equipment Means for automatically transferring from one fuel supply to another when using dual supply. Fuel transfer pump shall be on emergency. Audible and visual alarms to indicate generator running, water temperature, oil pressure, 3-hour fuel, charger status. Automatic transfer switches require bypass and isolation capability. Separately derived grounding systems require four (4) pole transfer switches. Overcurrent protection Separate generator room
CEC 700.12(B)(2)&(3)
CEC 517.30(B)(7)
10
11 12
13
Page 3
OSHPD
Electrical Requirements for Health Care Facilities
Materials Installation
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
Non-metallic rigid and non-metallic tubing are not permitted for use in patient care areas of health care facilities. Flexible metal conduit (FMC) is permitted for use in patient care areas with all of the following conditions: installed with a green insulated copper ground conductor required by CEC 517.13 the total length in any ground return path is less than six feet the conduit is terminated in fittings approved for grounding the circuit overcurrent protective device is 20A or less the conduit is not installed for flexibility
CEC 517.13(A)
Non-metallic sheathed cable (i.e. NM, NMC, Romex) is not permitted for use in patient areas, emergency system wiring or structures of Types I and II construction. Flat conductor cable (FCC) is not permitted for use in health care facilities. continued on next page
CEC 324.12(4)
Page 4
OSHPD
Electrical Requirements for Health Care Facilities
Materials Installation
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
Low voltage cables for fire alarm, nurse call, communications systems, etc. installed without the use of conduit is permitted if power supplies are "power limited" type and conductor is listed for such use. All emergency system wiring shall be installed in non-flexible metallic raceway. [Schedule 40 PVC conduit is allowed for underground
emergency system wiring inside or outside the building envelope, provided it is concrete encased. Schedule 80 PVC conduit is allowed without concrete encasement. Neither are allowed for branch circuits serving patient care areas.]
CEC 517.30(C)(3)
Separation of 24 inches (horizontal distance) for outlet boxes in fire rated wall and partitions.
CBC 712.3.2
Page 5
OSHPD
Electrical Requirements for Health Care Facilities
MISCELLANEOUS
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
All receptacles connected to the emergency system and all light switches controlling emergency lighting shall be identified in a conspicuous and permanent manner such as with red colored plates and/or red colored devices. All receptacles in critical care patient areas shall be marked with panel and circuit number supplying them. Identify all boxes and enclosures for emergency All rooms and passage ways shall have artificial lighting with levels per the Illuminating Engineers Society (IES) Handbook. [See PIN 13 in Appendix A] Lamps shall be considered protected against accidental breakage if provided as follows: with an enclosing lens or diffuser with louvers having a maximum cell size of 64 square inches open bottom luminaires limited to 64 square inch opening wire guards or plastic tube guards in service areas such as electrical, equipment, & janitor
517.30(E)
Critical
CEC 517.19(A)
3 4
CEC 517.22(C)
Page 6
OSHPD
Electrical Requirements for Health Care Facilities
NO.
BRANCH
Separate System
Fire pumps shall comply with all of the requirements of NFPA 20 and CEC 695. [Key points are separate service to the pump or power supply
tapped ahead of the main building over current device; integrated controller, motor, and pump; separate transfer switch; short circuit calculations required; overload protection sized for locked rotor amps.]
CEC 517.24
Page 7
OSHPD
Electrical Requirements for Health Care Facilities
GROUNDING BONDING
NO.
BRANCH
Receptacles in patient areas shall be provided with a green insulated copper grounding conductor Fixed equipment in patient area Branch circuits, provide redundant ground path Panelboard bonding and grounding General care patient area receptacles Critical care patient area receptacles Anesthetizing area grounding Generator grounding GFCI for receptacles and fixed equipment in wet locations GFCI for receptacles in bathrooms, kitchens and on roofs, and outdoors in public spaces, and where required for servicing HVAC equipment. Therapeutic pools and tubs Light switches in vicinity of shower stalls and bathtubs
CEC 517.13(B)
2 3 4 5
CEC 517.13(B) CEC 517.13(B) CEC 517.14 & 19(D) CEC 517.18(B) & (C) CEC 517.19(B) CEC 517.62 CEC 250.20(D) & 30 CEC 517.20(A)
6 7 8
CEC 210.8(B)
10 11
CEC 680 Part VI CEC 404.8(A)(2) Switches CEC 406.8(C)(1) Receptacles CEC 517.19(F) & CEC 517.20(B) CEC 517.19(G) CEC 517.78 Page 8
12
13
14 15
OSHPD
Electrical Requirements for Health Care Facilities
MECHANICAL EQUIPMENT
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
Equipment
HVAC - heating and cooling required by the California Mechanical Code (CMC) HVAC - supply and exhaust fans required for positive or negative pressure Delayed automatic connection for medical and surgical central suction including controls Delayed automatic connection for sump pumps and other equipment required to operate for the safety of major apparatus including associated controls and alarms Delayed automatic connection for medical and surgical compressed air systems including controls At least one receptacle and minimal lighting in mechanical rooms Single switch for chiller rooms to shutdown system located immediately outside room. [If equipment is on emergency power the shutdown controls should be on the same system] Lighting fixture and switch at or near equipment requiring servicing installed under floor or attic spaces. Service receptacle located within 25 feet of all HVAC equipment
CEC 517.34(B)(1.1) CMC Section 316.0 CMC 316.4 CEC 517.34(A)(6) CEC 517.34(A)(1)
Equipment
CEC 517.34(A)(2)
Equipment
CEC 517.34(A)(3)
Critical
CEC 517.33(A)(8)(n)
CEC 210.70(C)
10
Life Safety
Page 9
OSHPD
Electrical Requirements for Health Care Facilities
ELEVATORS
Elevators
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
Life Safety
Cab lighting, control, communications, and signal systems Separate branch circuit for car (cab) lights, receptacles, auxiliary power, lighting source, and ventilation for each elevator car. Overcurrent device located in elevator machinery room. Dedicated branch circuit for HVAC equipment. Overcurrent device located elevator machinery room.
CEC 517.32(F)
Life Safety
CEC 620.22(A)
CEC 620.22(B)
Pit lighting
CEC 620.24
5 6
Machinery Room Lighting Automatic or manual connection for at least one elevator Overcurrent protection of control wiring: #18 not over 7 amps, #16 not over 10amps Motor duty classified as intermittent Receptacle required in pits
CEC 620 Part VII CEC 725.23 CEC 430.33 CEC 620.24(C) CEC 620.23(C) CEC 517.33(A)(8)(n) CEC 620 Part VI
8 9 Critical
10
Page 10
OSHPD
Electrical Requirements for Health Care Facilities
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
On branch as required
Low voltage cables for fire alarm, nurse call, communications systems, etc. installed without the use of conduit is permitted if power supplies are "power limited" type and conductor is listed for such use. Nurse call power on emergency Fire alarm power on emergency [This includes control panel, automatic fire and smoke detection devices, electric water flow devices.] Medical Gas alarm power Communication systems used for issuing instruction during emergency conditions
2 3
4 5
Page 11
OSHPD
Electrical Requirements for Health Care Facilities
NON-PATIENT AREA
NO.
BRANCH
Life Safety
Emergency power for egress illumination Minimum of 1 foot candle Switch control for emergency egress illumination Exit signs [Batteries are not an acceptable source of alternate power] Automatically operated doors Automatically operated doors used for building egress
CEC 517.32(A) CBC 1006.2 CEC 700.20 CEC 517.32(B) CBC 1011.2&1011.4 CEC 517.34(B)(5) CEC 517.32(G)
2 3
4 5
Page 12
OSHPD
Electrical Requirements for Health Care Facilities
NON-PATIENT AREA
NO.
BRANCH
1 2 3
Critical Critical
Task illumination on emergency At least one receptacle on emergency Appliances shall comply with Article 422
Page 13
OSHPD
Electrical Requirements for Health Care Facilities
NON-PATIENT AREA
NO.
BRANCH
1 2 3
Task illumination on emergency At least one receptacle on emergency Laboratory fume hoods on emergency
Page 14
OSHPD
Electrical Requirements for Health Care Facilities
NON-PATIENT AREA
NO.
BRANCH
1 2 3
Task illumination on emergency At least one receptacle on emergency Nurse call system (required at nurses station only)
Page 15
OSHPD
Electrical Requirements for Health Care Facilities
NO.
BRANCH
Two (2) separate branch circuits per bed. Two (2) duplex hospital grade receptacles per bed.
2 3 Critical
Tamper resistant receptacles in pediatric locations Patient nurse call station at each bed location
CEC 517.18(C) CEC 517.123(A)(1) CEC 517.33(A)(5) CEC 517.123(A)(2) CEC 517.33(A)(5)
Critical
Patient nurse call station at each toilet, bath, and shower room. Cords shall be within 12 of the floor. HVAC Artificial lighting levels per IES handbook
5 6
Equipment
CEC 517.34(B)(1.1) CEC 517.22(A) and (B) CEC 517.33(A)(8)a.1 CEC 517.33(A)(8)
Critical
Page 16
OSHPD
Electrical Requirements for Health Care Facilities
Lithotripsy
APPLICABLE CODES
1 2 3 4 5 6
Task illumination on emergency Selected receptacles on emergency Staff emergency call required HVAC Patient lift on emergency (lithotripsy) Provide GFI on the feeder serving wet procedure equipment. GFI on feeder not required if supplied with mobile unit. (lithotripsy) GFCI type receptacles (lithotripsy) Equipment to be listed, labeled, or certified by a Nationally Recognized Testing Laboratory
CEC 517.33(A)(8)j CEC 517.33(A) (8)j CEC 517.123(B)(1) CEC 517.34(B)(1.1) CEC 517.33(A)(8)(j) CEC 680.62(A)
7 8
Page 17
OSHPD
Electrical Requirements for Health Care Facilities
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
1 2
Disconnecting means Disconnecting means not required for portable equipment served by 120 volt receptacle rated 30A or less Rating of supply conductor and overcurrent protective device Grounding and bonding Equipment to be listed, labeled, or certified by a Nationally Recognized Testing Laboratory
CEC 517.73
4 5
Page 18
OSHPD
Electrical Requirements for Health Care Facilities
NO.
BRANCH
There are not any specialized electrical requirements for MRI rooms or systems. However, due to the strong magnetic fields associated with this equipment it is recommended that manufacturers' recommendations be followed. Below are some of the commonly encountered and OSHPD acceptable recommendations. They may differ between manufacturers. non-ferrous conduit and lighting fixture housings no fluorescent fixtures in MRI room dimmers should not be used
Page 19
OSHPD
Electrical Requirements for Health Care Facilities
Hemodialysis
NO. BRANCH REQUIREMENTS APPLICABLE CODES
1 2
Critical Critical
Page 20
OSHPD
Electrical Requirements for Health Care Facilities
Labor Room Birthing Room Alternate Birthing Center (ABC) Labor/Delivery/Recovery (LDR) Labor/Delivery/Recovery/Postpartum (LDRP)
REQUIREMENTS APPLICABLE CODES
NO.
BRANCH
Two (2) separate branch circuits per bed Two (2) duplex hospital grade receptacles per bed
2 3
LDR and LDRP are viewed electrically by OSHPD as patient bedrooms. The requirements for critical care recovery rooms and delivery rooms are not applicable.
Page 21
OSHPD
Electrical Requirements for Health Care Facilities
Nursery
NO.
BRANCH
APPLICABLE CODES
1 2 3
Critical Critical
Task illumination At least one duplex receptacle on emergency One duplex receptacle shall be provided for every two bassinets
4 5 6
Critical
Equipment
HVAC
Page 22
OSHPD
Electrical Requirements for Health Care Facilities
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
1 2 3 4 Critical
Illumination level at 100 foot candles Dimmer or multi-level switching of lighting Task illumination At least five (5) duplex hospital grade receptacles per bed Normal & Critical or two Critical Critical Critical At least two (2) branch circuits per bed, one must be a dedicated emergency circuit serving only that bed location
CEC 517.19(A)
6 7
Staff emergency call required Emergency Alarm System (Code Blue) at control desk in NICU HVAC
Equipment
CEC 517.34(B)(1.1)
Page 23
OSHPD
Electrical Requirements for Health Care Facilities
Delivery Room [Delivery rooms must meet all of the requirements of operating rooms.]
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
1 2 3 Critical Critical
CEC 517.63(A) CEC 517.33(A)(1) CEC 517.33(A)(1) CBC 1224.32.3.4 CEC 517.33(A)(1) CEC 517.61(C)(2) CEC 517.33(A)(1) CEC 517.123 (B)(1) CEC 517.33 (A)(8)(l) CBC 1224.32.3.3
4 5 6 7 8
Selected receptacles on emergency Hospital grade receptacles Fixed electrical equipment on emergency Staff emergency call required Standard clock with sweep second hand and elapsed timer which is direct wired or battery operated Grounding and bonding Wiring and equipment in non-hazardous area
9 10 11 12 Equipment Critical
CEC 517.19 & 62 CEC 517.61(C) & 63 CEC 517.34(B)(1.1) CEC 517.160
Page 24
OSHPD
Electrical Requirements for Health Care Facilities
Emergency Room
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
1 2 3
Page 25
OSHPD
Electrical Requirements for Health Care Facilities
Recovery Room
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
1 2
Critical
Task illumination on emergency At least three (3) duplex or six (6) single hospital grade receptacles per bed
At least two (2) branch circuits per bed, one must be a dedicated emergency circuit serving only that bed location
CEC 517.19(A)
4 5
Emergency Alarm System (Code Blue) Patient nurse call station at each toilet, bath, and shower room Staff emergency call required HVAC
6 7
Critical Equipment
Page 26
OSHPD
Electrical Requirements for Health Care Facilities
NO.
BRANCH
Critical
Dimmer or multi-level switching of individual bed area lighting At least five (5) duplex hospital grade receptacles per bed Normal & Critical or two Critical Critical Critical At least two (2) branch circuits per bed, one must be a dedicated emergency circuit serving only that bed location
CEC 517.19(A)
5 6
Patient nurse call at each bed location Patient nurse call station at each toilet, bath, and shower room Emergency Alarm System (Code Blue) Staff emergency call required from control desk HVAC
7 8 9
Page 27
OSHPD
Electrical Requirements for Health Care Facilities
NO.
BRANCH
Battery-powered emergency lighting units Task illumination Surgical light Selected receptacles on emergency Hospital grade receptacles Fixed electrical equipment on emergency Staff emergency call required Standard clock required at scrub-up sinks
CEC 517.63(A) CEC 517.33(A)(1) CEC 517.33(A)(1) CEC 517.33(A)(1) CEC 517.61(C)(2) CEC 517.33(A)(1) CEC 517.123(B)(1) CEC 517.33(A)(8)(l) CBC 420A.15.4 CEC 517.62 CEC 517.61(C) & 63 CEC 517.34(B)(1.1) CEC 517.160
9 10 11 12 Equipment Critical
Grounding and bonding Wiring and equipment in non-hazardous area HVAC Isolated power systems
Page 28
OSHPD
Electrical Requirements for Health Care Facilities
Receptacles in Patient Care Areas Emergency Generator Fuel Supply Nurse Call System
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
Receptacles are not required in psychiatric security rooms On site fuel supply shall be sufficient for six (6) hours of operation at full demand Critical Task illumination on emergency [The task is to provide night lighting, so that psychiatric patients are not in complete darkness upon loss of normal power.] Nurse Call: a. Where cords are supplied they shall be detachable cords b. Patient/nurse call system not required for facilities where patients are not confined to bed.
CEC 517.33(A)(3)e
Page 29
OSHPD
Electrical Requirements for Health Care Facilities
Nursing Facility
ELECTRICAL SYSTEM
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
Essential electrical system shall be comprised of two (2) separate branches, critical and life safety. Minimum of two (2) transfer switches are required, at least one (1) for each branch. [One (1) transfer switch allowed for maximum demand on essential electrical system #150kVA] Independent of all other wiring and equipment except in transfer switches, exit signs, two source emergency lighting. Essential services may originate or pass through existing facilities provided they comply with minimum SPC and NPC requirements. Load capacity verification required for all modifications to existing systems. [See Policy Intent Notice 3-220 REV, Appendix A]
CEC 517.41(A)
CEC 517.41(B)
Life Safety
CEC 220.87
Normal
Ground fault protection required on service main 1000 ampere or greater for LG voltage > 150V. Ground fault protection required on feeders if supplied on main. No other function other than those listed in this Code section are allowed to be connected to the life safety branch of the emergency system. Task lighting and at least one receptacle in electrical and mechanical rooms
Life Safety
CEC 517.42
Critical
CEC 517.43(A)(7)
Page 30
OSHPD
Electrical Requirements for Health Care Facilities
Nursing Facility
EMERGENCY POWER
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
Alternate source of power shall be a generator Task illumination at generator set Selected receptacles at generator set Automatic restoration of power within 10 seconds Battery and charger for automatic starting Onsite fuel supply for at least six (6) hours of operation at full demand Critical Means for automatically transferring from one fuel supply to another when using dual supply. Fuel transfer pump shall be on emergency. Audible and visual alarms to indicate generator running, water temperature, oil pressure, 3-hour fuel, charger status. Separately derived grounding systems require four (4) pole transfer switches. NOTE: Automatic transfer switches do not require by pass and isolation Overcurrent protection Separate generator room
CEC 517.44(B.1) CEC 517.42(F) CEC 517.42(F) CEC 517.42 & 700.12 CEC 700.12(B)(4) CEC 700.12(B)(2) Ex. 2
10
11 12
Page 31
OSHPD
Electrical Requirements for Health Care Facilities
Nursing Facility
Material Installation
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
Non-metallic rigid and non-metallic tubing are not permitted for use in patient care areas of health care facilities. Flexible metal conduit (FMC) is permitted for use in patient care areas with all of the following conditions: installed with a green insulated copper ground conductor required by CEC 517.13 the total length in any ground return path is less than six feet the conduit is terminated in fittings approved for grounding the circuit overcurrent protective device is 20A or less
Non-metallic sheathed cable (i.e. NM, NMC, Romex) is not permitted for use in patient care areas or in structures of Types I & II construction. Flat conductor cable (FCC) is not permitted for use in health care facilities. Low voltage cables for fire alarm, nurse call, communications systems, etc. installed without the use of conduit is permitted if power supplies are "power limited" type and conductor is listed for such use. Separation of 24 inches (horizontal distance) for outlet boxes in fire rated wall and partitions.
CEC 324.12(4)
CBC 712.3.2
Page 32
OSHPD
Electrical Requirements for Health Care Facilities
Nursing Facility
MISCELLANEOUS
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
All receptacles connected to the emergency system and all light switches controlling emergency lighting shall be identified in a conspicuous and permanent manner such as with red colored plates and/or red colored devices. Identify all boxes and enclosures for emergency All rooms and passage ways shall have artificial lighting with levels per the Illuminating Engineers Society (IES Handbook [See PIN 13 in Appendix A] Lamps shall be considered protected against accidental breakage if provided as follows: with an enclosing lens or diffuser with louvers having a maximum cell size of 64 square inches open bottom luminaires limited to 64 square inch opening wire guards or plastic tube guards in service areas such as electrical, equipment, & janitor
CEC 517.41(E)
2 3
CEC 517.22(C)
Page 33
OSHPD
Electrical Requirements for Health Care Facilities
Nursing Facility
GROUNDING BONDING
NO.
BRANCH
Receptacles in patient areas shall be provided with an insulated copper grounding conductor Fixed equipment in patient area Branch circuits, provide redundant ground path Panelboard bonding and grounding Generator grounding GFCI required in wet locations GFCI for receptacles in bathrooms, kitchens, on roofs, and outdoor in public spaces and where required for servicing HVAC equipment Therapeutic pools and tubs Light switches in vicinity of shower stalls & bathtubs Receptacles in vicinity of shower stalls & bathtubs
CEC 517.13(B)
2 3 4 5 6 7
CEC 517.13(B) CEC 517.13 (B) CEC 517.14 & 19 (D) CEC 250.20(D) & 30 CEC 517.20(A) CEC 210.8(B)
8 9
10
CEC 406.8(C)(1)
Page 34
OSHPD
Electrical Requirements for Health Care Facilities
Nursing Facility
MECHANICAL EQUIPMENT
HVAC Sump Pumps Central Suction (medical) Chiller Rooms Mechanical Rooms
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
Critical
Delayed automatic or manual connection for HVAC - heating and cooling required by the California Mechanical Code (CMC) HVAC - supply and exhaust fans required for positive or negative pressure Delayed automatic connection for sump pumps and other equipment required to operate for the safety of major apparatus including associated controls and alarms Single switch for chiller rooms to shutdown system located immediately outside room Service receptacles located within 25 feet of all HVAC equipment Lighting fixtures and switch at or near equipment requiring servicing installed under floor or attic spaces.
Critical
Critical
CMC 1109.4
Critical
CEC 517.43(A)(7)
Page 35
OSHPD
Electrical Requirements for Health Care Facilities
Nursing Facility
ELEVATORS
Elevators
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
Life Safety
Cab lighting, control, communications and signal systems Separate branch circuit for car (cab) lights for each elevator. Overcurrent device in elevator machinery room Delayed automatic or manual connection to emergency power for all elevators to allow the release of passengers Dedicated branch circuit for HVAC equipment. Overcurrent device located in elevator machinery room. Overcurrent protection of control wiring: #18 not over 7 amps, #16 not over 10 amps Motor duty classified as intermittent Receptacle required in pits
CEC 517.42(G)
Life Safety
CEC 620.22(A)
Critical
CEC 517.43(B)(2)
CEC 620.22(B)
CEC 620 Part VII CEC 725.23 CEC 430.33 CEC 620.24(C) CEC 620.23(C) CEC 517.43(A)(7) CEC 620 Part VI
6 7 Critical
Task lighting and receptacles required in machinery rooms Disconnecting devices for all power sources
Page 36
OSHPD
Electrical Requirements for Health Care Facilities
Nursing Facility
Nurse Call Fire Alarm Medical Gas Cable TV Emergency Communications
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
On Branch as required
Low voltage cables for fire alarm, nurse call, communications systems, etc. installed without the use of conduit is permitted if power supplies are "power limited" type and conductor is listed for such use. Nurse call power on emergency Fire alarm power on emergency [This includes control panel, automatic fire and smoke
detection devices, automatic actuators under fire alarm control, electric water flow devices]
2 3
Life Safety
CEC 517.42(C)(3)
Life Safety
CEC 517.42(C)(1)
4 5
Medical gas alarm power Communication systems used for issuing instruction during emergency conditions
Page 37
OSHPD
Electrical Requirements for Health Care Facilities
Nursing Facility
PATIENT AREA
NO.
BRANCH
Life Safety
Emergency power for egress illumination Minimum at 1 foot candle Emergency power for egress illumination in dining and recreation areas Switch control for emergency egress illumination Exit signs
Life Safety
3 4
Critical
Selected receptacles in patient room corridors so that any patient bed can be reached with a fifty foot extension cord [Not required if each bed location served by receptacles complying with CEC 517.18 (A) & (B)]
CEC 517.43(A)(6)
Page 38
OSHPD
Electrical Requirements for Health Care Facilities
Nursing Facility
NON-PATIENT AREA
NO.
BRANCH
CEC 422
Page 39
OSHPD
Electrical Requirements for Health Care Facilities
Nursing Facility
NON-PATIENT AREA
NO.
BRANCH
1 2 3
Task illumination At least one receptacle on emergency Nurse call system (required at nurses station only)
Page 40
OSHPD
Electrical Requirements for Health Care Facilities
Nursing Facility
GENERAL CARE PATIENT AREA
Patient Bedroom
NO.
BRANCH
REQUIREMENTS
APPLICABLE CODES
Life Safety
Life Safety
Patient nurse call station at each toilet, bath, and shower room. Cords shall be within 12 of the floor. HVAC Artificial lighting levels per IES handbook
3 4
Critical
Page 41
OSHPD
Electrical Requirements for Health Care Facilities
Clinics
Grounding in patient care areas: Provide a green insulated copper ground conductor to all receptacles. All branch circuits shall be installed in metal conduit suitable for redundant ground return path.
CEC 517.13
Hemodialysis clinic shall have egress lighting and exit signs with at least 1 hour battery backup. Surgical clinics shall have emergency power supplied by a generator with at least 4 hours of on site fuel. Where electrical life support equipment is required or where critical care areas are present, surgical clinics shall comply with CEC 517.30 through 517.35. All receptacles connected to the emergency system and all light switches controlling emergency lighting shall be identified in a conspicuous and permanent manner such as with red colored plates and/or red colored devices.
CEC 517.45(G)
CEC 517.45(E)
Page 42
OSHPD
Electrical Requirements for Health Care Facilities
Appendix A
Policy Intent Notices (PIN) Available: www.oshpd.ca.gov
Page 43
OSHPD
Electrical Requirements for Health Care Facilities
Appendix B
Standard Details
Subject Electrical System (Small Nursing Home) Electrical System (Large Nursing Home) Electrical System (Small Hospital) Electrical System (Large Hospital)
Page 44
OSHPD
Electrical Requirements for Health Care Facilities
GENERATOR
G
AUTOMATIC TRANSFER SWITCH
Panel L
Panel C
Panel C
Panel C
CRITICAL BRANCH
Description
Scale
Detail
MINIMUM ELECTRICAL SYSTEM TYPICAL SMALL NURSING HOME 150 kVA MAXIMUM DEMAND ON ESSENTIAL ELECTRICAL SYSTEM
NONE
Drawn
E0002-01
Date
JJG
3/17/98
Page 45
OSHPD
Electrical Requirements for Health Care Facilities
Panel L
Panel C
CRITICAL BRANCH
ESSENTIAL ELECTRICAL SYSTEM (CEC 517.40 & 41) L LIFE SAFETY BRANCH CIRCUITS C CRITICAL BRANCH CIRCUITS OSHPD STANDARD DETAILS
Description
MINIMUM ELECTRICAL SYSTEM TYPICAL LARGE NURSING HOME GREATER THAN 150 kVA MAXIMUM DEMAND ON ESSENTIAL ELECTRICAL SYSTEM
NONE
Drawn
E0002-02
Date
JJG
8/22/96
Page 46
OSHPD
Electrical Requirements for Health Care Facilities
G
AUTOMATIC TRANSFER SWITCH
Panel L
Panel C
Panel E
EQUIPMENT SYSTEM
ESSENTIAL ELECTRICAL SYSTEM (CEC 517.30) L LIFE SAFETY BRANCH CIRCUITS C CRITICAL BRANCH CIRCUITS E EQUIPMENT BRANCH CIRCUITS OSHPD STANDARD DETAILS
Description
MINIMUM ELECTRICAL SYSTEM TYPICAL SMALL HOSPITAL 150 kVA MAXIMUM DEMAND ON ESSENTIAL ELECTRICAL SYSTEM
NONE
Drawn
E0003-01
Date
JJG
8/21/96
Page 47
OSHPD
Electrical Requirements for Health Care Facilities
EQUIPMENT SYSTEM
MINIMUM ELECTRICAL SYSTEM TYPICAL LARGE HOSPITAL GREATER THAN 150 kVA MAXIMUM DEMAND ON ESSENTIAL ELECTRICAL SYSTEM
NONE
Drawn
E0003-02
Date
JJG
8/21/96
Page 48
OSHPD
Electrical Requirements for Health Care Facilities
Index
Electrical Rooms........................................ 2, 30 Elevators ................................................ 10, 36 Emergency Power .... 3, 9, 10, 12, 31, 36, 38, 42 Emergency Room........................................... 25 Entrances ............................................... 12, 38 Exits ...................................................... 12, 38
A
Acute Care Hospital ................................... 228 Acute Psychiatric Hospital ............................... 29 Alarms ............................................... 3, 31, 37 Ambulatory Surgical Clinic .............................. 42 Anesthetizing Areas ......................................... 8 Angiography ................................................. 28 Angioplasty .................................................. 28 Appendix A .................................................. 43 Appendix B .................................................. 44 Appendix C .................................................. 45
F
Fire Alarm .............................................. 11, 37 Fire Pumps ..................................................... 7 Flat Conductor Cable .................................. 4, 32 Flexible Metal Conduit ............................... 4, 32 Food Preparation Area .............................. 13, 39 Fuel Supply .............................................. 3, 31
B
Blood, Bone, and Tissue Banks......................... 14
G
Generator ........................................... 3, 29, 31 GFCI ................................................. 8, 17, 34 GFI ............................................................. 17 Ground Conductor.................................. 1, 4, 32 Grounding .... 3, 4, 8, 18, 24, 28, 31, 32, 34, 42
C
C.T. Scanner ................................................. 18 Cable TV ............................................... 11, 37 Cardiac Cath Lab ........................................... 28 Central Suction .......................................... 9, 35 Central Supply .............................................. 14 Chiller ..................................................... 9, 35 Clean Utility ................................................. 14 Clinics ......................................................... 42 Code Application Notices ................................ 44 Communications ................................ 11, 36, 37 Coronary Care Unit ........................................ 27 Corridors ................................................ 12, 38 Cytoscopy .................................................... 28
H
Hemodialysis ................................................ 20 Hemodialysis Clinic ....................................... 42 Human Physiology Laboratory ......................... 14 HVAC .... 9, 16, 17, 21, 22, 23, 24, 25, 26, 27,
28, 35, 41
I D
Delivery Room .............................................. 24 Dining ......................................................... 38 Identification ............................................. 6, 33 IES.............................................. 6, 16, 33, 41 Intensive Care Unit ........................................ 27 Isolation Room .............................................. 16
E
Egress Illumination .................................. 12, REVISION: January 01, 2008
38
Page 49
OSHPD
Electrical Requirements for Health Care Facilities
K
Kitchen .................................................. 13,
39
L
Laser Operating ............................................. 28 Lighting ............................................. 6, 10, 33 Lithotripsy .................................................... 17
Labor Room .............................................. 21 Labor/Delivery/Recovery (LDR) ................... 21 Neonatal Intensive Care Unit ........................ 23 Pharmacy ..................................................... 15 Pharmacy Dispensing Area .............................. 40 Plan Review Check List .................................... 1 Policy Intent Notices ...................................... 43 Postpartum ................................................... 21 Power Limited ........................... 1, 5, 11, 32, 37
M
Magnetic Resonance Imaging ........................... 19 Mammography .............................................. 18 Materials Installation .................................. 4, 32 Mechanical Rooms ............................... 9, 30, 35 Medical Gas............................................ 11, 37 Medication Preparation Area ...................... 15, 40 Mobile Medical Facilities .................................. 7
R
Radiology ..................................................... 18 Receptacles 1, 3, 6, 8, 9, 10, 13, 14, 15, 16, 17,
21, 22, 23, 24, 25, 26, 27, 28, 29, 31, 33, 34, 35, 36, 38, 40, 41, 42 Recovery ...................................................... 26 Recreation .................................................... 38 S
N
Non-metallic Sheathed Cable ....................... 4, 32 Nourishment ........................................... 13, 39 Nurse Call . 1, 5, 11, 15, 16, 21, 26, 27, 29, 32,
Service Equipment ..................................... 2, 30 Soiled Utility................................................. 14 Standard Details ............................................ 45 Sump Pumps ............................................. 9, 35 System Segregation .................................... 2, 30
T
Task Illumination .. 3,
O
Operating ............................................... 24, 28 Outpatient Surgical Clinic ................................ 42 Overcurrent Protection .................... 3, 10, 31, 36
13, 14, 15, 17, 20, 22, 23, 24, 25, 26, 27, 28, 29, 31, 40, 42 Telephone .................................................... 14 Transfer Switches ............................ 2, 3, 30, 31 W
Wet Locations ........................................... 8, Wiring ....... 1, 2, 4, 5, 6, 10, 24, 28, 30, 33, Wiring Devices.......................................... 6,
P
Panelboard................................................ 8, 34 Patient Areas ............................................. 8, 34 Patient Bedroom ...................................... 16, 41 Perinatal Alternate Birthing Center............................. 21 Birthing Room........................................... 21
34 36 33
X
X-Ray ...................................................... 8,
18
Page 50