The Micro-Bay series is a functional and multi-purpose narrow profile fluorescent High-Bay that incorporates premium performance with durabile construction. Designed for T5 fluorescent technology, the MBF series offers both high performance and application versatility with three optical configurations for general and aisle applications. Illumination solution in commerical, industrial and retail applications, MBF series can be used in warehouses and retail store distribution centers.
SPECIFICATION FEATURES AConstruction CFinish

Catalog # Project Comments Prepared by

Type

Date

Mounting

Die formed channel from 20 gauge prime cold rolled steel. Numerous KOs for ease of installation. End plate quickly converts to snap-in channel connector for continuous row alignment. Push-in style lampholders snap in to installed tracks. Channel/wireway cover positively secured with mechanical fastener.
BElectrical*

Multistage iron phosphate pretreatment ensures maximum bonding and rust inhibitor.

Ballasts are Class P and are positively secured. Rotor-lock lampholders ensure positive lamp retention. Optional pre-wired factory installed multiple circuit plug-in connectors. UL/CUL listed. Suitable for damp locations.

Suspension is convenient and flexible with the SS Aircraft Cable Y Toggle Mounting Kits. Adjustment DChannel/Wireway for luminaire mounting Cover height is provided at lumiHeavy gauge prime cold rolled steel. naire rather than structure. Tight fit for ease of maintenance. Order a rigid exterior connector/coupling with preERef lector Specular Miro reflectors for precise light punched holes facilitates easy installation of coupled control minimum 95% total reflectivity. sections up to 32' long. Three optical distribution patterns are available: Option Focus - SC < .5 Integral occupancy sensor Task - .5 SC < .9 available and provides from Normal - .9 SC 1.2 600 sq. ft. up to 1250 sq. ft. of coverage in a maximum mounting height of 40'.

MBF 154 254


4' OR 8' MICROBAY* 1 OR 2 LAMP

A
FOCUS BEAM

C D

T 5 L a m p Te ch n o l o g y Ta s k B e a m Focus Beam Normal Beam

3-1/8" [80mm]

4-7/16" [113mm]

ENERGY DATA
Input Watts @ 120V: Electronic Ballast & STD Lamps 154 (62) 254 (117) 454 (229) 8T154 (117) 8T254 (229)
1-1/8" [29mm] 2-9/16" [66mm] 10-3/16" [258mm]

LAMP CONFIGURATIONS
FOCUS BEAM, 1 T5 LAMP
X 3-1/8" [80mm] X=4-1/4" [108mm] 4-7/16" [113mm] X=4-1/4" [108mm] 8-15/16" [226mm] X=4-1/4" [108mm] 8" [202mm]

TASK BEAM, 1 T5 LAMP


X

NORMAL BEAM, 1 T5 LAMP


X

FOCUS BEAM, 2 T5 LAMPS


X 4-1/16" [104mm]

1-1/8" [29mm]

5-3/8" [137mm]

1-1/8" [29mm]

5-5/8" [144mm]

1-1/8" [29mm]

X=4-1/4" [108mm]

Luminaire Efficacy Rating LER = 69 Catalog Number: MB-154T5 Yearly Cost of 1000 lumens, 3000 hrs at .08 KWH = $3.47

NORMAL BEAM, 2 T5 LAMPS


X 4-9/16" [116mm] 2-9/16" [66mm] 9-1/4" [234mm]

MOUNTING DATA
1-1/8" [29mm]

4' Y=5" [127mm] 4-1/4" [108mm] X=3-1/2" [89mm] 2" [51mm] KO 11/16" x 1" KO (2 Places) X 3-1/4" [83mm] 48" [1220mm] Hole for Toggle 7/8" [22mm] K.O. (3) Y 7/8" [22mm] K.O. (3) Ceiling Stand-Off Embossments Ground Screw Hole for Toggle Reference the lamp/ballast data in the Technical Section for specific lamp/ballast requirements.

X=4-1/4" [108mm]

8' Y=5" [127mm] 4-1/4" [108mm] X=3-1/4" [83mm] 11/16" x 1" KO (2 Places) 2" [51mm] K.O. X 24-1/2" [622mm] 96" [2438mm] Y Ceiling Stand-Off Embossments Ground Screw

LAMPS CONTAIN MERCURY. DISPOSE ACCORDING TO LOCAL, STATE OR FEDERAL LAWS

11/16" [17mm] K.O. (2)

3-1/4" [83mm] 4-5/8" [118mm]

Safe and convenient means of disconnecting power *Patent Pending

COOPER LIGHTING

ADF060486

MBF T5

PHOTOMETRICS

MBF-254-NB (1) Electronic Ballast (2) 54W T5 lamp 4400 lumens Spacing criterion: (II) 1.3 x mounting height, () 1.1 x mounting height Efficiency 96.3% Test Report: MBF-254NB.IES LER =FL71 Yearly Cost of 1000 lumens, 3000 hrs at .08 KWH = $3.38

Candela
Angle 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 Along II 3736 3743 3716 3643 3528 3374 3182 2960 2708 2434 2147 1849 1548 1241 936 640 362 122 0 45 3736 3791 3751 3846 3730 3636 3488 2905 2103 1612 1424 1133 913 665 395 354 30 16 0 Across 3736 3756 3860 3822 3839 3514 2564 1939 1783 1497 1244 1018 700 522 476 40 0 0 0

MBF-154FB (1) Electronic Ballast (1) 54W T5 lamp 4400 lumens Spacing criterion: (II) 1.2 x mounting height, () 0.5 x mounting height Efficiency 105% Test Report: MBF-154FB.IES LER =FL74 Yearly Cost of 1000 lumens, 3000 hrs at .08 KWH = $3.24

Candela
Angle 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 Along II 3538 3528 3477 3393 3275 3126 2944 2734 2498 2239 1961 1663 1357 1043 729 438 197 39 0 45 3538 3409 2970 2349 1777 1376 1020 752 596 504 449 416 396 378 364 353 289 131 0 Across 3538 3281 2542 1786 1322 915 714 613 564 543 537 534 534 534 535 473 312 135 0

Coefficients of Utilization
rc rw RCR 0 1 2 3 4 5 6 7 8 9 10 Effective floor cavity reflectance 80% 70% 70 50 30 10 70 50 30 10 115 106 98 90 83 77 71 67 62 58 55 115 102 91 81 73 66 60 54 50 46 43 115 99 85 74 65 58 52 47 42 39 35 115 96 80 68 59 52 46 41 37 34 31 112 104 95 88 81 75 70 65 61 57 54 112 100 89 80 71 65 59 54 49 46 42 112 97 84 73 64 57 51 46 42 38 35 112 94 79 68 59 52 46 41 37 33 31 20% 50% 50 30 10 107 96 86 77 69 63 57 52 48 44 41 107 94 81 71 63 56 50 46 41 38 35 107 91 78 67 58 51 45 41 37 33 30 30% 50 30 10 103 93 83 74 67 61 55 51 47 43 40 103 90 79 69 62 55 50 45 41 37 35 103 88 76 66 57 50 45 40 36 33 30 50 98 89 80 72 65 59 54 50 46 42 40 10% 30 10 98 87 77 68 60 54 49 44 40 37 34 98 86 74 64 57 50 45 40 36 33 30 0% 0 96 84 72 62 55 48 43 38 35 31 29

Coefficients of Utilization
rc rw RCR 0 1 2 3 4 5 6 7 8 9 10 Effective floor cavity reflectance 80% 70% 70 50 30 10 70 50 30 10 125 115 105 97 89 83 77 73 68 64 61 125 110 97 86 77 70 64 59 55 51 48 125 125 105 101 90 84 78 71 69 62 61 55 56 49 51 45 46 41 43 37 40 35 122 112 102 94 87 81 76 71 67 63 59 122 107 95 84 76 69 63 58 54 50 47 122 103 88 77 68 61 55 50 46 43 40 122 100 83 71 62 55 49 44 41 37 35 20% 50% 50 30 10 117 103 91 81 73 67 62 57 53 49 46 117 99 86 75 66 60 54 49 46 42 39 117 96 81 70 61 54 49 44 40 37 35 30% 50 30 10 112 99 88 78 71 65 60 55 52 48 45 112 96 83 73 65 59 53 49 45 42 39 112 93 79 68 60 53 48 44 40 37 34 50 107 95 84 76 69 63 58 54 50 47 44 10% 30 10 107 93 81 71 64 57 52 48 44 41 38 107 91 77 67 59 53 48 43 40 37 34 0% 0 105 88 75 65 57 51 46 42 38 35 33

Zonal Lumen Summary


Zone 0-30 0-40 0-60 0-90 0-180 Lumens 3050 4711 7390 8479 8479 %Lamp 34.7 53.5 84.0 96.3 96.3 %Fixture 36.0 55.6 87.2 100.0 100.0

Luminance Data
Angle in Deg 45 55 65 75 85 Average 0-Deg cd/sm 13251 12410 11304 9519 5389 Average 45-Deg cd/sm 8776 7406 6057 5265 707 Average 90-Deg cd/sm 8150 6832 4755 595 0

Zonal Lumen Summary


Zone 0-30 0-40 0-60 0-90 0-180 Lumens 1775 2479 3657 4632 4632 %Lamp 40.4 56.3 83.1 105.3 105.3 %Fixture 38.3 53.5 79.0 100.0 100.0

Luminance Data
Angle in Deg 45 55 65 75 85 Average 0-Deg cd/sm 22714 20798 17703 12139 3210 Average 45-Deg cd/sm 5113 5203 6416 9784 10782 Average 90-Deg cd/sm 5509 6678 9064 13110 11111

Visit our web site at www.cooperlighting.com


Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770.486.4801 9/10 ADF060486

MBF T5

ORDERING INFORMATION
SAMPLE NUMBER: MBF-154T5-FB-UNV-EBT1-U

Tandem Blank= 4' Length 8T= 8' Length Series MBF=Micro-Bay Number of Lamps
(Not included)

1=1 Lamp 2=2 Lamps Lamp Types 49T5=49W T5HO (48") 51T5=51W T5HO (48") 54T5=54W T5HO (48") Reflector FB=Focus Beam TB=Task Beam (Medium -1 lamp only) NB=Normal Beam Voltage (1) 120V=120 Volt 277V=277 Volt 347V=347 VoltUNV=Universal 120-277 Voltage UNC=Universal 347/480 Voltage Options GL=Single Element Fuse GM=Double Element Fuse EL=Emergency Installed (2)

Ballast Type T5 Systems EBT =T5 Linear Electronic Program Rapid Start. Total Harmonic Distortion < 10% No. of Ballast 1 or 2 EHT =T5 Linear Electronic Program Rapid Start High Ambient. Total Harmonic Distortion < 10% (4) No. of Ballast 1 or 2 DIM=Dimming (ballast must be specified)

Options Packaging PI/CPI=Plug-In (1, 2 or 3) See pg. 52 U=Unit Pack C3=3' Power Cord C6=6' Power Cord PC3-=3' Power Cord & Plug (Specify Voltage) (3) PC6-=6' Power Cord & Plug (Specify Voltage) (3) Accessories (order separately) AYC-CHAIN/SET/U=(2) Hooks, 36" Chain Sets w/S-Hooks Y- TOGGLE=Y Mounting Toggle, #2 Cable (Specify 10' or 30') (6) TOGGLE- =Single Toggle, #2 Cable (Specify 10' or 30') SSF-EXT-LONG-CONN-KIT-U=Rigid Connector Support for Continuous Channel Installation MBF-SENSOR-KIT-CTR/MT-U=Aisle Coverage Motion Sensor, Center Mount Hardware, 120/277V (3), (5) MBF-SENSOR-KIT-END/MT-U=Aisle Coverage Motion Sensor, End Mount Hardware, 120/277V (3), (5) ATG-SSF-4-U=Tong Hanger

NOTES: (1) Products also available in non-US voltages and frequencies for international markets. (2) Voltage to be specified with emergency ballast option.(3)Voltage must be specified when ordered with plugs, motion sensor or emergency ballasts. (4)2 lamp ballast configurations only in UNC versions. (5) Must ship separately. (6) Use with continuous row mount at fixture joint only.

PI OPTION ORDERING INFORMATION

Catalog Number Suffix PI 1 BLK PI 2 BLU PI 2 BLK PI 3 RED PI 3 BLU PI 3 BLK

Number of Circuits 1 2 2 3 3 3

Circuit Wired To Ballast Black Blue Black Red Blue Black

Catalog Numbering System


The PI System is available in sections up to 8' in length for continuous row wiring by simply plugging the sections together. Each PI section is factory wired to the ballast leads. Color coding of wires is as follows: PI-1 = One Circuit - 2 Wires: one black, one white PI-2 = Two Circuits - 3 Wires: one black, one blue, one white PI-3 = Three Circuits - 4 wires: one black, one blue, one red, one white When ordering the PI2/PI3 System it is necessary to specify the number of fixtures required for each circuit. Each circuit in fixture must be ordered as a separate line item, with a different hot wire color specified. All wiring to external feeds, using cord or cord & plug, are responsibility of installing licensed contractor. Cord and cord & plug sets must be ordered separately if PI option is chosen.

PI1 - Single Circuit Plug-In


SAMPLE NUMBER: PI1BLK-WG

PI2 - Two Circuit Plug-In


SAMPLE NUMBER: PI2BLK-WG

PI1= Single Circuit BLK=Black Hot

NG= No Ground (ground provided by fixture body) WG= With Ground (separate ground wire in harness)

PI2= Two Circuit BLK=Black Hot BLU=Blue Hot Leave Blank=Single Neutral /WHT=White Neutral /GRY=Gray Neutral

Leave Blank=Single Neutral 2NEU=Two Neutrals

NG= No Ground (ground provided by fixture body) WG= With Ground (separate ground wire in harness)

PI3 - Three Circuit Plug-In


SAMPLE NUMBER: PI3BLK-WG

PI3= Three Circuit BLK=Black Hot BLU=Blue Hot RED=Red Hot Leave Blank=Single Neutral /WHT=White Neutral /GRY=Gray Neutral

Leave Blank=Single Neutral 2NEU=Two Neutrals

NG= No Ground (ground provided by fixture body) WG= With Ground (separate ground wire in harness)

For complete product data, reference the Fluorescent Specification binder. Specifications & dimensions subject to change without notice. Consult your Cooper Lighting Representative for availability and ordering information.

SHIPPING INFORMATION
Catalog No. MBF-154T5 Wt. 6 lbs.