You are on page 1of 12

Appendix 1-454-465 21/06/02 10:51 Page 454

Appendix 1
Ter minolog y
Appendix 1-454-465 21/06/02 10:51 Page 455

Appendix 1
Terminolog y

The introduction of computer technology means that the


Protection Engineer must now be familiar with a range
of technical terms in this field, in addition to the terms
long associated with Protection and Control. Below is a
list of terms and their meanings that are now commonly
encountered in the Protection and Control field.
AC
Alternating Current
ACB
Air Circuit Breaker
Accuracy
The accuracy of a transducer is defined by the limits of
intrinsic error and by the limits of variations.
Accuracy class
A number used to indicate the accuracy range of a
measurement transducer, according to a defined
standard.
Active power (watt) transducer
A transducer used for the measurement of active
electrical power
ADC
Analogue to Digital Converter
A/D Conversion
The process of converting an analogue signal into an
equivalent digital one, involving the use of an analogue
to digital converter
Adjustment
The operation intended to bring a transducer into a state
of performance suitable for its use
AGC
Automatic Gain Control
AI
Analogue Input
AIS
Air Insulated Switchgear

Network Protection & Automation Guide • 455 •


Appendix 1-454-465 21/06/02 10:51 Page 456

Alarm Bay
An alarm is any event (see below) tagged as an alarm Set of LV, MV, or HV plant and devices, usually controlled
during the configuration phase by a bay computer
All-or-nothing relay BC
An electrical relay which is intended to be energised by Bay Computer. Computer dedicated to the control of one
a quantity, whose value is either higher than that at or several bays within a substation
which it picks up or lower than that at which it drops out
BCD
Anti-pumping device Binary Coded Decimal
A feature incorporated in a Circuit Breaker or reclosing
BCP
scheme to prevent repeated operation where the closing
Bay Control Point. A local keypad at bay level to control
impulse lasts longer than the sum of the relay and CB
the elements of a single bay
operating times
Biased relay
AO
A relay in which the characteristics are modified by the
Analogue Output
introduction of some quantity other than the actuating
AR quantity, and which is usually in opposition to the
Auto Reclose: A function associated with CB, actuating quantity
implemented to carry out reclosure automatically to try
Bias current
to clear a transient fault
The current used as a bias quantity in a biased relay
ARBITER
BIOS
Proprietary protocol for time synchronisation from
Basic Input/Output System (of a computer or
ARBITER Systems, Inc. Paso Robles, California USA
microprocessor)
Arcing time
BT
A p p e n d i x 1 - Te r m i n o l o g y

The time between instant of separation of the CB


Booster Transformer
contacts and the instant of arc extinction
B o o s t e r Tr a n s f o r m e r
Auto-transformer
A current transformer whose primary winding is in series
A power transformer that does not provide galvanic
with the catenary and secondary winding in the return
isolation between primary and secondary windings
conductor of a classically-fed a.c. overhead electrified
AUX railway. Used at intervals to ensure that stray traction
Auxiliary return currents, with their potential to cause
interference in nearby communication circuits, are
Auxiliary circuit
minimised
A circuit which is usually energised by the auxiliary
supply but is sometimes energised by the measured Burden
quantity The loading imposed by the circuits of the relay on the
energising power source or sources, expressed as the
Auxiliary relay
product of voltage and current (volt-amperes, or watts if
An all-or-nothing relay energised via another relay, for
• A1 • example a measuring relay, for the purpose of providing
d.c.) for a given condition, which may be either at
‘setting’ or at rated current or voltage. The rated output
higher rated contacts, or introducing a time delay, or
of measuring transformers, expressed in VA, is always at
providing multiple outputs from a single input.
rated current or voltage and it is important, in assessing
Auxiliary supply the burden imposed by a relay, to ensure that the value
An a.c. or d.c. electrical supply other than the measured of burden at rated current is used
quantity which is necessary for the correct operation of
C
the transducer
Capacitance
AV R
CAD
Automatic Voltage Regulator
Computer Aided Design
Back-up protection
Calibration
A protection system intended to supplement the main
The set of operations which establish, under specified
protection in case the latter should be ineffective, or to
conditions, the relationship between values indicated by
deal with faults in those parts of the power system that
a transducer and the corresponding values of a quantity
are not readily included in the operating zones of the
realized by a reference standard. (This should not be
main protection
confused with ‘adjustment’, q.v.)

• 456 • Network Protection & Automation Guide


Appendix 1-454-465 21/06/02 10:51 Page 457

CB Closing Time
Circuit Breaker The time for a CB to close, from the time of energisation
of the closing circuit to making of the CB contacts
CBC
Compact Bay Controller. Small capacity bay computer Compliance voltage (accuracy limiting
for Medium Voltage applications output voltage)
For current output signals only, the output voltage up to
CBCT
which the transducer meets its accuracy specification
Core Balance Current Transformer
Conjunctive test
CCR
A test of a protection system including all relevant
Central Control Room
components and ancillary equipment appropriately
CDM interconnected. The test may be parametric or specific
Conceptual Data Modelling is an activity whose aims are:
Conversion coefficient
• to define objects and links and naming conventions for The relationship of the value of the measurand to the
their identifications corresponding value of the output
• to guarantee interoperability between subsystems C o r e B a l a n c e C u r r e n t Tr a n s f o r m e r
• to define standard exchange formats between system A ring-type Current Transformer in which all primary
configurator and subsystem configurators conductors are passed through the aperture of the CBCT.
Hence the secondary current is proportional only to any
Characteristic angle imbalance in current. Used for sensitive earth-fault
The angle between the vectors representing two of the protection
energising quantities applied to a relay and used for the
declaration of the performance of the relay Counting Relay
A relay that counts the number of times it is energised
Characteristic curve

A p p e n d i x 1 - Te r m i n o l o g y
and actuates an output after a desired count has been
The curve showing the operating value of the reached.
characteristic quantity corresponding to various values
or combinations of the energising quantities CSV
Character (or Comma) Separated Values format. A
Characteristic Impedance Ratio (C.I.R.) widely used format for the exchange of data between
The maximum value of the System Impedance Ratio up different software, in which the individual data items a
to which the relay performance remains within the separated by a known character – usually a comma
prescribed limits of accuracy
CT
Characteristic quantity Current Transformer
A quantity, the value of which characterises the
operation of the relay, for example, current for an Current transducer
overcurrent relay, voltage for a voltage relay, phase angle A transducer used for the measurement of a.c. current
for a directional relay, time for an independent time CVT
delay relay, impedance for an impedance relay Capacitor Voltage Transformer. A voltage transformer
Check protection system that uses capacitors to obtain a voltage divider effect. • A1 •
An auxiliary protection system intended to prevent Used at EHV voltages instead of an electromagnetic VT
tripping due to inadvertent operation of the main for size/cost reasons
protection system DAC
CHP Digital to Analogue Converter
Combined Heat and Power DAR
Circuit insulation voltage Delayed auto-reclose
The highest circuit voltage to earth on which a circuit of D AT
a transducer may be used and which determines its Digital Audio Tape
voltage test
DBMS
Class index Data Base Management system
The number which designates the accuracy class
DCF77
Closing Impulse time LF transmitter located at Mainflingen, Germany,
The time during which a closing impulse is given to the broadcasting a time signal on a 77.5kHz frequency
CB

Network Protection & Automation Guide • 457 •


Appendix 1-454-465 21/06/02 10:51 Page 458

DCP Direct-on-Line
Device Control Point: local keypad on device level to A method of motor starting, in which full line voltage is
control the switchgear, often combined with applied to a stationary motor
local/remote switch
Drop-out (or drop-off)
DCS A relay drops out when it moves from the energised
Distributed Control System position to the un-energised position
Dead Time (auto-reclose) Drop-out/pick-up ratio
The time between the fault arc being extinguished and The ratio of the limiting values of the characteristic
the CB contacts re-making quantity at which the relay resets and operates. This
value is sometimes called the differential of the relay
De-ionisation time (auto-reclose)
The time required for dispersion of ionised air after a DSP
fault is cleared so that the arc will not re-strike on re- Digital Signal Processing
energisation
DT
Delayed Auto-Reclose Definite time
An auto-reclosing scheme which has a time delay in
Earth fault protection system
excess of the minimum required for successful operation
A protection system which is designed to respond only to
Dependent time measuring relay faults to earth
A measuring relay for which times depend, in a specified
Earthing transformer
manner, on the value of the characteristic quantity
A three-phase transformer intended essentially to
DFT provide a neutral point to a power system for the
Discrete Fourier Transform purpose of earthing
Digital Signal Processor Effective range
A p p e n d i x 1 - Te r m i n o l o g y

A microprocessor optimised in both hardware The range of values of the characteristic quantity or
architecture and software instruction set for the quantities, or of the energising quantities to which the
processing of analogue signals digitally, through use of relay will respond and satisfy the requirements
the DFT and similar techniques concerning it, in particular those concerning precision
Digital Signal Processing Effective setting
A technique for the processing of digital signals by The ‘setting’ of a protection system including the effects
various filter algorithms to obtain some desired of current transformers. The effective setting can be
characteristics in the output. The input signal to the expressed in terms of primary current or secondary
processing algorithm is usually the digital representation current from the current transformers and is so
of an analogue signal, obtained by A/D conversion designated as appropriate
Directional relay Electrical relay
A protection relay in which the tripping decision is A device designed to produce sudden predetermined
dependent in part upon the direction in which the changes in one or more electrical circuits after the
• A1 • measured quantity is flowing appearance of certain conditions in the electrical circuit
or circuits controlling it
Discrimination
The ability of a protection system to distinguish between NOTE: The term ‘relay’ includes all the ancillary
power system conditions for which it is intended to equipment calibrated with the device
operate and those for which it is not intended to operate
Electromechanical relay
Distortion factor An electrical relay in which the designed response is
The ratio of the r.m.s. value of the harmonic content to developed by the relative movement of mechanical
the r.m.s. value of the non-sinusoidal quantity elements under the action of a current in the input
circuit
DNP
Distributed Network Protocol. A proprietary EMC
communication protocol used on secondary networks Electro-Magnetic Compatibility
between HMI, substation computers or Bay Computers
Embedded generation
and protective devices
Generation that is connected to a distribution system
DOL (possibly at LV instead of HV) and hence poses particular
Direct-on-Line problems in respect of electrical protection

• 458 • Network Protection & Automation Guide


Appendix 1-454-465 21/06/02 10:51 Page 459

e.m.f. G l o b a l Po s i t i o n i n g S y s t e m
Electro-motive Force ( or voltage) A system used for locating objects on Earth precisely,
using a system of satellites in geostationary orbit in
Energising quantity
Space. Used by some numerical relays to obtain accurate
The electrical quantity, either current or voltage, which
time information
along or in combination with other energising quantities,
must be applied to the relay to cause it to function GMT
Greenwich Mean Time
EPROM
Electrically Programmable Read Only Memory GPS
Global Positioning System
Error (of a transducer)
The actual value of the output minus the intended value G TO
of the output, expressed algebraically Gate Turn-off Thyristor
Event Half- duplex communications
An event is any information acquired or produced by the A communications system in which data can travel in
digital control system both directions, but only in one direction at a time
F AT High-speed reclosing
Factory Acceptance Test. Validation procedures A reclosing scheme where re-closure is carried out
witnessed by the customer at the factory without any time delay other than that required for de-
ionisation, etc.
F a u l t Pa s s a g e I n d i c a t o r
A sensor that detects the passage of current in excess of HMI
a set value (i.e. current due to a fault) at the location of Human Machine Interface. The means by which a human
the sensor. Hence, it indicates that the fault lies inputs data to and receives data from a computer-based
downstream of the sensor system. Usually takes the form of a Personal Computer

A p p e n d i x 1 - Te r m i n o l o g y
(PC) (desktop or portable) with keyboard, screen and
FBD
pointing device
Functional Block Diagram: One of the IEC 61131-3
programming languages HRC
High Rupturing Capacity (applicable to fuses)
Fiducial value
A clearly specified value to which reference is made in HSR
order to specify the accuracy of a transducer. (For High Speed Reclosing
transducers, the fiducial value is the span, except for
HV
transducers having a reversible and symmetrical output
High Voltage
when the fiducial value may be either the span or half
the span as specified by the manufacturer. It is still HVDC
common practice, however, for statements of accuracy High Voltage Direct Current
for frequency transducers to refer to ‘percent of centre- I
scale frequency’ and, for phase angle transducers, to an Current
error in electrical degrees.)
ICCP • A1 •
FPI Term used for IEC 60870-6-603 protocol
Fault Passage Indicator
ICT
Frequency transducer Interposing Current Transformer (software implemented)
A transducer used for the measurement of the frequency
of an a.c. electrical quantity I . D . M . T.
Inverse Definite Minimum Time
Full duplex communications
A communications system in which data can travel I G BT
simultaneously in both directions Insulated Gate Bipolar Transistor

Gateway I/O
The Gateway is a computer which provides interfaces Input/Output
between the local computer system and one or several IED
SCADA (or RCC) systems Intelligent Electronic Device. Equipment containing a
GIS microprocessor and software used to implement one or
Gas Insulated Switchgear (usually SF6) more functions in relation to an item of electrical

Network Protection & Automation Guide • 459 •


Appendix 1-454-465 21/06/02 10:53 Page 460

equipment (e.g. a bay controller, remote SCADA Knee-point e.m.f.


interface/protocol converter). A microprocessor-based That sinusoidal e.m.f. applied to the secondary terminals
numerical relay is also an IED. IED is a generic term used of a current transformer, which, when increased by 10%,
to describe any microprocessor-based equipment, apart causes the exciting current to increase by 50%
from a computer
L
I G BT Inductance
Insulated Gate Bipolar Transistor
LAN
Independent time measuring relay Local Area Network
A measuring relay, the specified time for which can be
LCD
considered as being independent, within specified limits,
Liquid Crystal Display
of the value of the characteristic quantity
LED
Influence quantity
Light Emitting Diode
A quantity which is not the subject of the measurement
but which influences the value of the output signal for a LD
constant value of the measurand Ladder Diagram. One of the IEC 61131-3 programming
languages
Input quantity
The quantity, or one of the quantities, which constitute LDC
the signals received by the transducer from the measured Line drop compensator
system Limiting value of the output current
Instantaneous relay The upper limit of output current which cannot, by
A relay that operates and resets with no intentional time design, be exceeded under any conditions
delay. Local Control Mode
A p p e n d i x 1 - Te r m i n o l o g y

NOTE: All relays require some time to operate; it is When set for a given control point it means that the
possible, within the above definition, to discuss the commands can be issued from this point
operating time characteristics of an instantaneous relay Lock-out (auto-reclose)
I n s u l a t e d G a t e B i p o l a r Tr a n s i s t o r Prevention of a CB reclosing after tripping
A special design of transistor that is suitable for handling Long-term stability
high voltages and currents (relative to an ordinary The stability over a period of one year
transistor). Frequently used in static power control
equipment (inverters, controlled rectifiers, etc) due to the Low-speed auto-reclose
flexibility of control of the output See Delayed Auto-Reclose

Intrinsic error LV
An error determined when the transducer is under Low Voltage
reference conditions Main protection
Inverse time delay relay The protection system which is normally expected to
operate in response to a fault in the protected zone
• A1 • A dependent time delay relay having an operating time
which is an inverse function of the electrical Maximum permissible values of the input
characteristic quantity current and voltage
Inverse time relay with definite minimum Values of current and voltage assigned by the
t i m e ( I . D . M . T. ) manufacturer which the transducer will withstand
An inverse time relay having an operating time that indefinitely without damage
tends towards a minimum value with increasing values MCB
of the electrical characteristic quantity Miniature Circuit Breaker
IRIG-B MCCB
An international standard for time synchronisation Moulded Case Circuit Breaker
ISO Mean-sensing transducer
International Standards Organisation A transducer which actually measures the mean
K-bus (K-bus Courier) (average) value of the input waveform but which is
Term used for the Courier protocol on K-Bus interface for adjusted to give an output corresponding to the r.m.s.
K-Relay range manufactured by Alstom value of the input when that input is sinusoidal

• 460 • Network Protection & Automation Guide


Appendix 1-454-465 21/06/02 10:53 Page 461

Measurand Nominal range of use


A quantity subjected to measurement A specified range of values which it is intended that an
influence quantity can assume without the output signal
Measuring element
of the transducer changing by amounts in excess of
A unit or module of a transducer which converts the
those specified
measurand, or part of the measurand, into a
corresponding signal Notching relay
A relay which switches in response to a specific number
Measuring range of applied impulses
That part of the span where the performance complies
with the accuracy requirements NPS
Negative Phase Sequence
Measuring relay
An electrical relay intended to switch when its NS
characteristic quantity, under specified conditions and Neutral Section (electrified railways)
with a specified accuracy attains its operating value Numerical relay
Metering (non-tariff) A protection relay which utilises a Digital Signal
Values computed depending on the values of digital or Processor to execute the protection algorithms in
analogue inputs during variable periods software
OCB
Metering (tariff)
Oil Circuit Breaker
Energy values computed from digital and/or analogue
inputs during variable periods and dedicated to energy O f f - L o a d Ta p C h a n g e r
measurement for billing (tariff) purposes A tap changer that is not designed for operation while
the transformer is supplying load
M i d Po i n t S e c t i o n i n g S u b s t a t i o n
OHL

A p p e n d i x 1 - Te r m i n o l o g y
A substation located at the electrical interface of two
sections of electrified railway. It contains provision for Overhead line
the coupling of the sections electrically in the event of O LTC
loss of supply to one section On Load Tap Changer.
ModBus O n L o a d Ta p C h a n g e r
Proprietary communication protocol used on secondary A tap changer that can be operated while the
networks between HMI, substation computers or Bay transformer is supplying load.
Computers and protective devices
Opening time
MPSS The time between energisation of a CB trip coil and the
Mid Point Sectioning Substation (electrified railways) instant of contact parting
Multi-element transducer Operating current (of a relay)
A transducer having two or more measuring elements. The current at which a relay will pick up
The signals from the individual elements are combined to Operating time (CB)
produce an output signal corresponding to the The time between energisation of a CB trip coil and arc • A1 •
measurand extinction
Multi-section transducer Operating time (relay)
A transducer having two or more independent measuring With a relay de-energised and in its initial condition, the
circuits for one or more functions time which elapses between the application of a
Multi-shot reclosing characteristic quantity and the instant when the relay
A reclosing scheme that permits more than one reclosing operates
operation of a CB after a fault occurs before lock-out Operating time characteristic
occurs The curve depicting the relationship between different
MV values of the characteristic quantity applied to a relay
Medium Voltage and the corresponding values of operating time

N/C Operating value


Normally Closed The limiting value of the characteristic quantity at which
the relay actually operates
N/O
Normally Open

Network Protection & Automation Guide • 461 •


Appendix 1-454-465 21/06/02 10:53 Page 462

OPGW Phase angle transducer


Optical Ground Wire – a ground wire that includes A transducer used for the measurement of the phase
optical fibres to provide a communications link angle between two a.c. electrical quantities having the
same frequency
OSI 7-layer model
The Open Systems Interconnection 7-layer model is a Pick-up
model developed by ISO for modelling of a A relay is said to ‘pick-up’ when it changes from the de-
communications network. energised position to the energised position
Output common mode interference voltage Pilot channel
An unwanted alternating voltage which exists between A means of interconnection between relaying points for
each of the output terminals and a reference point the purpose of protection
Output current (of a transducer) PLC
The current produced by the transducer which is an Programmable Logic Controller. A specialised computer
analogue function of the measurand for implementing control sequences using software
Output load PLCC
The total effective resistance of the circuits and Power Line Carrier Communication
apparatus connected externally across the output
Po i n t o f C o m m o n C o u p l i n g
terminals
The interface between an in-plant network containing
Output power (of a transducer) embedded generation and the utility distribution
The power available at the transducer output terminals network to which the in-plant network is connected
Output series mode interference voltage POW
An unwanted alternating voltage appearing in series Point-on- Wave. Point-on-wave switching is the process
between the output terminals and the load to control moment of switching to minimise the effects
A p p e n d i x 1 - Te r m i n o l o g y

(inrush currents, overvoltages)


Output signal
An analogue or digital representation of the measurand Po w e r E l e c t r o n i c D e v i c e
An electronic device (e.g. thyristor or IGBT) or assembly
Output span (span)
of such devices (e.g. inverter). Typically used in a power
The algebraic difference between the lower and upper
transmission system to provide smooth control of output
nominal values of the output signal
of an item of plant
Overcurrent relay
Po w e r f a c t o r
A protection relay whose tripping decision is related to
The factor by which it is necessary to multiply the
the degree by which the measured current exceeds a set
product of the voltage and current to obtain the active
value.
power
Overshoot time
Po w e r L i n e C a r r i e r C o m m u n i c a t i o n
The overshoot time is the difference between the
A mean of transmitting information over a power
operating time of the relay at a specified value of the
transmission line by using a cariier fraquency
input energising quantity and the maximum duration of
• A1 • the value of input energising quantity which, when
superimpozed on the normal power frequency.
suddenly reduced to a specific value below the operating PPS
level, is insufficient to cause operation Positive Phase Sequence
Pa r a m e t r i c c o n j u n c t i v e t e s t Protected zone
A conjunctive test that ascertains the range of values of The portion of a power system protected by a given
each parameter for which the test meets specific protection system or a part of that protection system
performance requirements
Protection equipment
PCB The apparatus, including protection relays, transformers
Printed Circuit Board and ancillary equipment, for use in a protection system
PCC Protection relay
Point of Common Coupling A relay designed to initiate disconnection of a part of an
electrical installation or to operate a warning signal, in
PED
the case of a fault or other abnormal condition in the
Power Electronic Device
installation. A protection relay may include more than
one electrical element and accessories

• 462 • Network Protection & Automation Guide


Appendix 1-454-465 21/06/02 10:53 Page 463

Protection scheme Reclaim time (auto-reclose)


The time between a successful closing operation,
The co-ordinated arrangements for the protection of one
measured from the time the auto-reclose relay closing
or more elements of a power system. A protection
contact makes until a further reclosing sequence is
scheme may comprise several protection systems
permitted in the event of a further fault occurring
Protection system
REF
A combination of protection equipment designed to
Restricted Earth Fault
secure, under predetermined conditions, usually
abnormal, the disconnection of an element of a power Reference conditions
system, or to give an alarm signal, or both Conditions of use for a transducer prescribed for
performance testing, or to ensure valid comparison of
Protocol
results of measurement
A set of rules that define the method in which a function
is carried out – commonly used in respect of Reference range
communications links, where it defines the hardware and A specified range of values of an influence quantity
software features necessary for successful within which the transducer complies with the
communication between devices. requirements concerning intrinsic errors
PSM Reference value
Plug Setting Multiple – a term used in conjunction with A specified single value of an influence quantity at which
electromechanical relays, denoting the ratio of the fault the transducer complies with the requirements
current to the current setting of the relay concerning intrinsic errors
PSTN Relay
Public Switched Telephone Network See Protection relay
P T 10 0 Resetting value

A p p e n d i x 1 - Te r m i n o l o g y
Platinum resistance temperature probe The limiting value of the characteristic quantity at which
the relay returns to its initial position
R
Resistance Residual current
The algebraic sum, in a multi-phase system, of all the
R.M.S.-sensing transducer
line currents
A transducer specifically designed to respond to the true
r.m.s. value of the input and which is characterised by Residual voltage
the manufacturer for use on a specified range of The algebraic sum, in a multi-phase system, of all the
waveforms line-to-earth voltages
Ratio correction Response time
A feature of digital/numerical relays that enables The time from the instant of application of a specified
compensation to be carried out for a CT or VT ratio that change of the measurand until the output signal reaches
is not ideal and remains at its final steady value or within a specified
band centred on this value
Rating
The nominal value of an energising quantity that appears Reversible output current • A1 •
in the designation of a relay. The nominal value usually An output current which reverses polarity in response to
corresponds to the CT and VT secondary ratings a change of sign or direction of the measurand
RCD Ripple content of the output
Residual Current Device. A protection device which is With steady-state input conditions, the peak-to-peak
actuated by the residual current value of the fluctuating component of the output
RCP r. m . s .
Remote Control Point. The Remote Control Point is a Root Mean Square
SCADA interface. Several RCP’s may be managed with
RMU
different communication protocols. Physical
Ring Main Unit
connections are done at a Gateway or at substation
computers or at a substation HMI ROCOF
Rate Of Change Of Frequency (protection relay)
Reactive power (var) transducer
A transducer used for the measurement of reactive RSVC
electrical power Relocatable Static Var Compensator

Network Protection & Automation Guide • 463 •


Appendix 1-454-465 21/06/02 10:53 Page 464

RTD Specific conjunctive test


Resistance Temperature Detector A conjunctive test using specific values of each of the
parameters
R TO S
Real Time Operating System Spring winding time
For spring-closed CB’s, the time for the spring to be fully
RTU
charged after a closing operation
Remote Terminal Unit. An IED used specifically for
interfacing between a computer and other devices. ST
Sometimes may include control/monitoring/storage Structured Text: One of the IEC 61131-3 programming
functions languages
S AT Stability (of a transducer)
Site Acceptance Test. Validation procedures for The ability of a transducer to keep its performance
equipment executed with the customer on site characteristics unchanged during a specified time, all
conditions remaining constant
SCADA
Supervisory Control and Data Acquisition Stability (of a protection system)
The quantity whereby a protection system remains
SCL
inoperative under all conditions other than those for
Substation Configuration Language. Normalised
which it is specifically designed to operate
configuration language for substation modelling (as
expected by IEC 61850-6) Stability limits (of a protection system)
The r.m.s. value of the symmetrical component of the
SCP
through fault current up to which the protection system
Substation Control Point. HMI computers at substation
remains stable
level allowing the operators to control the substation
Starting relay
SCS
A p p e n d i x 1 - Te r m i n o l o g y

A unit relay which responds to abnormal conditions and


Substation Control System
initiates the operation of other elements of the
Setting protection system
The limiting value of a ‘characteristic’ or ‘energising’
S TATC O M
quantity at which the relay is designed to operate under
A particular type of Static Var Compensator, in which
specified conditions. Such values are usually marked on
Power Electronic Devices such as GTO’s are used to
the relay and may be expressed as direct values,
generate the reactive power required, rather than
percentages of rated values, or multiples
capacitors and inductors
SFC
Static relay
Sequential Function Chart: One of the IEC 61131-3
An electrical relay in which the designed response is
programming languages
developed by electronic, magnetic, optical or other
Short-term stability components without mechanical motion. Excludes
The stability over a period of 24 hours relays using digital/numeric technology
• A1 • Simplex communications system S t a t i c Va r C o m p e n s a t o r
A communications system in which data can only travel A device that supplies or consumes reactive power,
in one direction comprised solely of static equipment. It is shunt-
Single-shot reclosing connected on transmission lines to provide reactive
An auto-reclose sequence that provides only one power compensation
reclosing operation, lock-out of the CB occurring if it S TC
subsequently trips Short Time Current (rating of a CT)
S.I.R. Storage conditions
System Impedance Ratio The conditions, defined by means of ranges of the
Single element transducer influence quantities, such as temperature, or any special
A transducer having one measuring element conditions, within which the transducer may be stored
(non-operating) without damage
SOE
Sequence Of Events SVC
Static Var Compensator
S OT F
Switch on to Fault (protection)

• 464 • Network Protection & Automation Guide


Appendix 1-454-465 21/06/02 10:53 Page 465

System disturbance time (auto-reclose) Unit protection


The time between fault inception and CB contacts A protection system that is designed to operate only for
making on successful re-closure abnormal conditions within a clearly defined zone of the
power system
System impedance ratio
The ratio of the power system source impedance to the Unrestricted protection
impedance of the protected zone A protection system which has no clearly defined zone of
operation and which achieves selective operation only by
T 101
time grading
Term used for IEC 60870-5-101 protocol
UCA
Ta p c h a n g e r
Utility Communications Architecture
A mechanism, usually fitted to the primary winding of a
transformer, to alter the turns ratio of the transformer by UPS
small discrete amounts over a defined range Uninterruptible Power Supply
TC P / I P U TC
Transmission Control Protocol/Internet Protocol. A Universal Time Coordinates
common protocol for the transmission of messages over
V
the Internet
Voltage
TC S
VCB
Trip Circuit Supervision
Vacuum Circuit Breaker
TC 5 7
VDEW
Technical Committee 57 working for the IEC and
Term used for IEC 60870-5-103 protocol. The VDEW
responsible for producing standards in the field of
protocol is a subset of the IEC 60870-5-103 protocol
Protection (e.g. IEC 61850)

A p p e n d i x 1 - Te r m i n o l o g y
Ve c t o r g r o u p c o m p e n s a t i o n
TF
A feature of digital and numerical relays that
a) Transfer Function of a device (usually an element of a
compensates for the phase angle shift that occurs in
control system
transformers (including VT’s) due to use of dissimilar
b) Transient Factor (of a CT) winding connections – e.g. transformers connected
delta/star
Through fault current
The current flowing through a protected zone to a fault Vo l t a g e t r a n s d u c e r
beyond that zone A transducer used for the measurement of a.c. voltage
Time delay VT
A delay intentionally introduced into the operation of a Voltage Transformer
relay system
X
Time delay relay Reactance
A relay having an intentional delaying device
Z
TPI Impedance • A1 •
Tap Position Indicator (for transformers)
Transducer (electrical measuring
transducer)
A device that provides a d.c. output quantity having a
definite relationship to the a.c. measurand
Tr a n s d u c e r w i t h o f f s e t z e r o ( l i v e z e r o )
A transducer which gives a predetermined output other
than zero when the measurand is zero
Tr a n s d u c e r w i t h s u p p r e s s e d z e r o
A transducer whose output is zero when the measurand
is less than a certain value
Unit electrical relay
A single relay that can be used alone or in combinations
with others

Network Protection & Automation Guide • 465 •

You might also like