You are on page 1of 96

Head Office/Factory :

Jl. Gatot Subroto Km 7,8 Kel Pasir Jaya, Kec. Jati Uwung, Tangerang 15135-Indonesia
Phone : (62-21) 5922404, 5928066 (Hunting) Fax. : (62-21) 59301979, 5922576, 5901469
c
Copyright Sumi Indo Kabel 2007
All rights reserved. This catalogue is the copyright work of PT. Sumi Indo Kabel Tbk. No part of this publication may be reproduced, stored in a retrieval system, or transmitted,
in any form or by means, electronic, mechanical, photocopying, recording or otherwise, without prior permission of PT. Sumi Indo Kabel.
All information contained in this catalogue is believed to be accurate at the time issue. PT. Sumi Indo Kabel reserve the right to change information or specification at any time
in the light of technical developments or revisions.

Issue : Second Date: September '07


Section 1 - Contents & Information

Low Voltage Catalogue Index


Page Number
SECTION 1 - Contents & Information
Index Page 1
Company Profile of PT. SUMI INDO KABEL Tbk 2
Cable Specification 3

SECTION 2 - PVC Insulated Cables


Unarmoured Cables
450/750 Volts PVC Insulated Cables (Cu/PVC, NYA) 5
450/750 Volts PVC Insulated Cables (Flexible Cu/PVC, NYAF) 6
300/500 Volts PVC Insulated and PVC Sheathed Cables (PVC/PVC, NYM) 8
300/500 Volts PVC Insulated and PVC Sheathed Cables (Flexible PVC/PVC, NYMHY) 10
450/750 Volts PVC Insulated and PVC Sheathed Cables (Flexible PVC/PVC, NYYHY) 11

600/1000 Volts PVC Insulated and PVC Sheathed Cables (PVC/PVC, NYY) 18
600/1000 Volts PVC Insulated, Copper Tape Shielded and PVC Sheathed Cables (PVC/PVC-S, NYSY) 30

Armoured Cables
600/1000 Volts PVC Insulated, Steel Wire Armoured and PVC Sheathed Cables (PVC/SWA/PVC, NYRY) 35
600/1000 Volts PVC Insulated, Flat Steel Wire Armoured and PVC Sheathed Cables (PVC/FSWA/PVC, NYFGbY) 41
600/1000 Volts PVC Insulated, Double Steel Tape Armoured and PVC Sheathed Cables (PVC/DSTA/PVC, NYBY) 46

SECTION 3 - XLPE Insulated Cables


Unarmoured Cables
600/1000 Volts XLPE Insulated and PVC Sheathed Cables (XLPE/PVC, N2XY) 52
600/1000 Volts XLPE Insulated, Copper Tape Shielded and PVC Sheathed Cables (XLPE/PVC-S, N2XSY) 62

Armoured Cables
600/1000 Volts XLPE Insulated, Steel Wire Armoured and PVC Sheathed Cables (XLPE/SWA/PVC, N2XRY) 67
600/1000 Volts XLPE Insulated, Flat Steel Wire Armoured and PVC Sheathed Cables (XLPE/FSWA/PVC, N2XFGbY) 73
600/1000 Volts XLPE Insulated, Double Steel Tape Armoured and PVC Sheathed Cables (XLPE/DSTA/PVC, N2XBY) 78

SECTION 4 - General Information


Current Carrying Capacity for XLPE Insulated cable (single core) 83
Current Carrying Capacity for XLPE Insulated cable (multicore) 84
Current Carrying Capacity for PVC Insulated cable (single core) 85
Current Carrying Capacity for PVC Insulated cable (multicore) 86
Correction factor of Curent carrying capacity 87
Cable arrangement for Installation purpose 88
Explanation of Flame Retardant / Fire Resistant Characteristic 91

Page - 1
Section 1 - Contents & Information

Company Profile of PT. Sumi Indo Kabel Tbk

The Company was established on July 23, 1981 with its Head Office
and Factory located in Tangerang, Banten. The Company is engaged 1
in the manufacturing of Power Cable, Telecommunication Cable &
Fiber Optic, and Copper Wire.

The Company was listed in the Jakarta and Surabaya Stock Exchanges
in 1990. The Company became Foreign Capital Investment (PMA)
in 1994, with the participation of Sumitomo Electric Industries, Ltd.,
Japan, one of the biggest in cable and wire industries in the world. The
name of Company became PT Sumi Indo Kabel Tbk. since 1999.

The Company received official recognition of its quality management


system standard from SGS, certification ISO 9001 : 2000 for its Power
Cable & Control Cable, Telephone Cable & Fiber Optic Cable, and
Copper Wire Rod in 2002. This was the first recognition in Indonesia
for Electric Cable and Wire industries.

Page - 2
Section 1 - Contents & Information

Cable Specification

1 Scope
These specification apply to material and constructions of cross-linked thermosetting polyethylene
(XLPE) or Polivinyl chloride (PVC) insulated wire and cables for rated voltages 0.3/0.5 kV up to
0.6/1(1.2) kV accordance to IEC 60502-1, Indonesia Electric Power Company (SPLN)

2 Conductor
The conductor shall be formed from plain annealed copper or aluminium complying with IEC
60228, ASTM B3 and B8.
The conductor shall be solid, circular stranded or compacted stranded.

3 Insulation
The insulation shall be cross-linked polyethylene (XLPE) or Polivinyl chloride (PVC) in accordance
to IEC 60502-1.

4 Identification of cores
The cores of all cables shall be identified by color or numbered printed on the surface of insulation
in accordance with the following sequence or other sequence.
Number of core Identification of cores
Single core Black (Natural for XLPE insulated)
Two cores Red, Black
Three cores Red, Yellow, Blue
Four cores Red, Yellow, Blue, Black
Five core or more Black insulation with white numbered code.

5 Cabling and filling


The multi cores shall be laid up together with suitable filler to give the completed cable a
substantially circular cross section and bound with suitable binder tape.

6 Metallic Shielding (if required)


The metallic shielding shall consist of either one or more Copper tapes or a concentric layer of
copper wires.

7 Inner sheath (armour cable only).


The inner sheath shall consist of extruded thermoplastic compound such as :polyvinyl chloride
(PVC), polyethylene (PE),halogen free (LSOH), etc in accordance to IEC 60502-1.

8 Metallic armour
The metallic armour shall consist of single layer of round galvanized steel wire or flat galvanized
steel wire and steel tape or double layer of galvanized steel tapes in accordance to IEC 60502-1.
The armour of single core cables shall consist of single layer of aluminium wire or double layers of
aluminium tape as non magnetic material.

9 Outer sheath
The outer sheath shall consist of a thermoplastic compound such as polyvinyl chloride (PVC),
polyethylene (PE), halogen free (LSOH), etc in accordance with IEC 60502-1.

Page - 3
Section 2 - PVC Insulated Cables
Unarmoured Cables

450/750 V PVC INSULATED WIRE (Cu/PVC)


acc. to IEC 60227

Copper Conductor (Solid) PVC Insulation

Copper Conductor (Stranded) PVC Insulation

Colour of Insulation : Red, White, Black, Green, Brown, Blue, Yellow, Green-yellow

450/750 V PVC INSULATED WIRE (Cu/PVC Flexible)


acc. to IEC 60227

Copper Conductor (Flexible) PVC Insulation

Colour of Insulation : Red, White, Black, Green, Brown, Blue, Yellow, Green-yellow

Note : Special application upon request


* Available product in accordance to : SPLN or other requirement.
* Tin coated Copper conductor.

Page - 4
Section 2 - PVC Insulated Cables
Unarmoured Cables

450/750 V PVC INSULATED WIRE


CU/PVC (IEC 60227)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 450/750 V
Insulation : PVC Compound type C Operating Temperature
Colour Ident. : Red, White, Black, Green, Maximum 70°C
Blue, Yellow, Green-yellow

Conductor Nominal Nominal Maximum Minimum AC


Nominal No./ Diameter Thickness Overall Weight Conductor Insulation Test
Cross- Diameter of of Diameter of Resistance Resistance Voltage
section of wire Conductor Insulation wire at 20°C at 70°C
area (approx.) (approx.) (Approx.) (Approx.)
mm² No./mm mm mm mm kg/km Ω/km MΩ.km V/5 min

1.5 1 / 1.38 1.38 0.7 3.0 22 12.1 0.011 2500


1.5 7 / 0.52 1.56 0.7 3.5 23 12.1 0.010 2500
2.5 1 / 1.78 1.78 0.8 4.0 33 7.41 0.010 2500
2.5 7 / 0.67 2.01 0.8 4.0 35 7.41 0.009 2500
4 1 / 2.26 2.26 0.8 4.5 49 4.61 0.0085 2500
4 7 / 0.85 2.55 0.8 4.5 52 4.61 0.0077 2500
6 1 / 2.77 2.77 0.8 5.0 69 3.08 0.0070 2500
6 7 / 1.04 3.12 0.8 5.0 72 3.08 0.0065 2500
10 1 / 3.57 3.57 1.0 6.0 113 1.83 0.0070 2500
10 7 / 1.35 4.05 1.0 6.5 119 1.83 0.0065 2500
16 7 / 1.70 5.10 1.0 7.5 179 1.15 0.0050 2500
25 7 / 2.13 6.39 1.2 9.0 277 0.727 0.0050 2500
35 7 / 2.52 7.56 1.2 10.5 377 0.524 0.0040 2500
50 19 / 1.83 9.15 1.4 12.5 530 0.387 0.0045 2500
70 19 / 2.17 10.85 1.4 14.0 727 0.268 0.0035 2500
95 19 / 2.52 12.60 1.6 16.5 985 0.193 0.0035 2500
120 37 / 2.03 14.21 1.6 18.0 1218 0.153 0.0032 2500
150 37 / 2.27 15.89 1.8 20.0 1522 0.124 0.0032 2500
185 37 / 2.52 17.64 2.0 22.0 1873 0.0991 0.0032 2500
240 61 / 2.26 20.34 2.2 25.5 2465 0.0754 0.0032 2500
300 61 / 2.52 22.68 2.4 28.0 3055 0.0601 0.0030 2500
400 61 / 2.86 25.74 2.6 31.5 3927 0.0470 0.0028 2500

Page - 5
Section 2 - PVC Insulated Cables
Unarmoured Cables

450/750 V PVC INSULATED WIRE


CU/PVC-Flexible (IEC 60227)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type C Operating Temperature
Colour Ident. : Red, White, Black, Green, Maximum 70°C
Blue, Yellow, Green-yellow

Conductor Nominal Nominal Maximum Minimum AC


Nominal Maximum Diameter Thickness Overall Weight Conductor Insulation Test
Cross- Diameter of of Diameter of Resistance Resistance Voltage
section of wire Conductor Insulation wire at 20°C at 70°C
area (approx.) (approx.) (Approx.) (Approx.)
mm² mm mm mm mm kg/km Ω/km MΩ.km V/5 min

1.5 0.26 1.58 0.7 3.5 22 13.30 0.010 2500


2.5 0.26 2.04 0.8 4.0 34 7.98 0.009 2500
4 0.31 2.59 0.8 4.5 50 4.95 0.007 2500
6 0.31 3.46 0.8 5.5 75 3.30 0.006 2500
10 0.41 4.62 1.0 7.0 130 1.91 0.0056 2500
16 0.41 5.66 1.0 8.0 186 1.21 0.0046 2500
25 0.41 7.06 1.2 10.0 286 0.78 0.0044 2500
35 0.41 8.43 1.2 11.0 395 0.554 0.0038 2500
50 0.41 10.07 1.4 13.5 550 0.386 0.0037 2500
70 0.51 11.97 1.4 15.0 760 0.272 0.0032 2500
95 0.51 13.73 1.6 17.5 1008 0.206 0.0032 2500
120 0.51 15.53 1.6 19.5 1270 0.161 0.0029 2500
150 0.51 17.56 1.8 22.0 1605 0.129 0.0029 2500
185 0.51 19.16 2.0 24.0 1914 0.106 0.0029 2500
240 0.51 22.0 2.2 27.0 2491 0.0801 0.0028 2500

Page - 6
Section 2 - PVC Insulated Cables
Unarmoured Cables

300/500 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (NYM) - IEC 60227 , SPLN 42-2

Conductor PVC Inner covering


PVC Insulation PVC Sheath

300/500 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC Flexible (NYMHY) - IEC 60227 , SPLN 42-2

Conductor
PVC Insulation PVC Sheath

450/750 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC Flexible (IEC 60227, SPLN 42-6-3)

Tape (manufacturer's option)


Conductor PVC Sheath
PVC Insulation
Filler (Polyprophylene yarn,or extruded filler up to request)

Page - 7
Section 2 - PVC Insulated Cables
Unarmoured Cables

300/500 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (NYM) - IEC 60227 , SPLN 42-2

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 and 2) Uo/U - 300/500 V
Insulation : PVC Compound Operating Temperature
Inner covering : PVC Compound Maximum 70°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation : Two cores - Red,Black
Three cores - Red,Yellow, Blue
Sheath - White

TWO AND THREE CORES


Conductor Nominal Nominal Overall Maximum

No. Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor

of Cross- Diameter of of of Inner of of of Resistance

Core section of wire Conductor Insulation covering Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
- mm² No./mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.7 0.4 1.2 9.5 129 12.1
7 / 0.52 1.56 0.7 0.4 1.2 10.0 138 12.1
2.5 1 / 1.78 1.78 0.8 0.4 1.2 11.0 173 7.41
7 / 0.67 2.01 0.8 0.4 1.2 11.0 184 7.41
4 1 / 2.26 2.26 0.8 0.4 1.2 12.0 222 4.61

2 7 / 0.85 2.55 0.8 0.4 1.2 12.5 239 4.61


6 1 / 2.77 2.77 0.8 0.4 1.2 13.0 294 3.08
7 / 1.04 3.12 0.8 0.4 1.2 14.0 313 3.08
10 1 / 3.57 3.57 1.0 0.6 1.4 16.0 453 1.83
7 / 1.35 4.05 1.0 0.6 1.4 17.0 492 1.83
16 7 / 1.70 5.10 1.0 0.6 1.4 19.0 668 1.15
25 7 / 2.13 6.39 1.2 0.8 1.4 23.0 998 0.727
35 7 / 2.52 7.56 1.2 1.0 1.6 26.0 1336 0.524
1.5 1 / 1.38 1.38 0.7 0.4 1.2 10.0 150 12.1
7 / 0.52 1.56 0.7 0.4 1.2 10.5 159 12.1
2.5 1 / 1.78 1.78 0.8 0.4 1.2 11.5 205 7.41
7 / 0.67 2.01 0.8 0.4 1.2 12.0 216 7.41
4 1 / 2.26 2.26 0.8 0.4 1.2 12.5 266 4.61

3 7 / 0.85 2.55 0.8 0.4 1.2 13.0 286 4.61


6 1 / 2.77 2.77 0.8 0.4 1.4 14.0 357 3.08
7 / 1.04 3.12 0.8 0.4 1.4 14.5 381 3.08
10 1 / 3.57 3.57 1.0 0.6 1.4 17.0 557 1.83
7 / 1.35 4.05 1.0 0.6 1.4 18.0 600 1.83
16 7 / 1.70 5.10 1.0 0.8 1.4 20.5 849 1.15
25 7 / 2.13 6.39 1.2 0.8 1.6 24.5 1270 0.727
35 7 / 2.52 7.56 1.2 1.0 1.6 27.5 1679 0.524

Page - 8
Section 2 - PVC Insulated Cables
Unarmoured Cables

300/500 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (NYM) - IEC 60227 , SPLN 42-2

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 and 2) Uo/U - 300/500 V
Insulation : PVC Compound Operating Temperature
Inner covering : PVC Compound Maximum 70°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation : Four core - Red,Yellow, Blue, Black
Five core - Black with numbering code
Sheath - White

FOUR AND FIVE CORES


Conductor Nominal Nominal Overall Maximum

No. Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor

of Cross- Diameter of of of Inner of of of Resistance

Core section of wire Conductor Insulation covering Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
- mm² No./mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.7 0.4 1.2 11.0 177 12.1
7 / 0.52 1.56 0.7 0.4 1.2 11.5 189 12.1
2.5 1 / 1.78 1.78 0.8 0.4 1.2 12.5 247 7.41
7 / 0.67 2.01 0.8 0.4 1.2 13.0 262 7.41
4 1 / 2.26 2.26 0.8 0.4 1.4 14.0 340 4.61

4 7 / 0.85 2.55 0.8 0.4 1.4 14.5 361 4.61


6 1 / 2.77 2.77 0.8 0.4 1.4 15.5 456 3.08
7 / 1.04 3.12 0.8 0.4 1.4 16.0 482 3.08
10 1 / 3.57 3.57 1.0 0.6 1.4 18.5 690 1.83
7 / 1.35 4.05 1.0 0.6 1.4 19.5 742 1.83
16 7 / 1.70 5.10 1.0 0.8 1.4 22.5 1059 1.15
25 7 / 2.13 6.39 1.2 1.0 1.6 27.5 1616 0.727
35 7 / 2.52 7.56 1.2 1.0 1.6 30.0 2107 0.524
1.5 1 / 1.38 1.38 0.7 0.4 1.2 11.5 210 12.1
7 / 0.52 1.56 0.7 0.4 1.2 12.0 223 12.1
2.5 1 / 1.78 1.78 0.8 0.4 1.2 13.5 293 7.41
7 / 0.67 2.01 0.8 0.4 1.2 14.0 313 7.41
4 1 / 2.26 2.26 0.8 0.6 1.4 15.5 424 4.61

5 7 / 0.85 2.55 0.8 0.6 1.4 16.5 452 4.61


6 1 / 2.77 2.77 0.8 0.6 1.4 17.0 548 3.08
7 / 1.04 3.12 0.8 0.6 1.4 17.5 579 3.08
10 1 / 3.57 3.57 1.0 0.6 1.4 20.0 839 1.83
7 / 1.35 4.05 1.0 0.6 1.4 21.5 898 1.83
16 7 / 1.70 5.10 1.0 0.8 1.6 25.0 1310 1.15
25 7 / 2.13 6.39 1.2 1.0 1.6 30.0 1969 0.727
35 7 / 2.52 7.56 1.2 1.2 1.6 33.5 2617 0.524

Page - 9
Section 2 - PVC Insulated Cables
Unarmoured Cables

300/500 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC Flexible (IEC 60227, SPLN 42-6-2)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 300/500 V
Insulation : PVC Compound type D Operating Temperature
Sheath : PVC Compound type ST5 Maximum 70°C
Colour Ident. : Insulation: Two core - Red,Black
Three core - Red,Yellow, Blue
Four core - Red,Yellow, Blue, Black
Five core - Black with numbering code
Sheath - White

Conductor Nominal Nominal Overall Maximum

Number Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor

of Cross- Diameter of of of of of Resistance

Core section of wire Conductor Insulation Sheath cable cable at 20°C


area (approx.) (approx.) (approx.) (approx.)

- mm² mm mm mm mm mm kg/km Ω/km

0.75 0.21 1.13 0.6 0.8 7.0 64 26.0

2 1 0.21 1.31 0.6 0.8 7.5 74 19.5


1.5 0.26 1.58 0.7 0.8 8.5 98 13.3
2.5 0.26 2.04 0.8 1.0 10.0 145 7.98
0.75 0.21 1.13 0.6 0.8 7.5 75 26.0

3 1 0.21 1.31 0.6 0.8 7.5 87 19.5


1.5 0.26 1.58 0.7 0.9 9.0 121 13.3
2.5 0.26 2.04 0.8 1.1 10.5 180 7.98
0.75 0.21 1.13 0.6 0.8 8.0 90 26.0

4 1 0.21 1.31 0.6 0.9 8.5 108 19.5


1.5 0.26 1.58 0.7 1.0 10.0 150 13.3
2.5 0.26 2.04 0.8 1.1 11.5 219 7.98
0.75 0.21 1.13 0.6 0.9 9.0 111 26.0

5 1 0.21 1.31 0.6 0.9 9.5 129 19.5


1.5 0.26 1.58 0.7 1.1 11.0 182 13.3
2.5 0.26 2.04 0.8 1.2 13.0 266 7.98

Page - 10
Section 2 - PVC Insulated Cables
Unarmoured Cables

450/750 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC Flexible (IEC 60227, SPLN 42-6-3)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Red,Black
Sheath - Black

TWO CORES
Conductor Nominal Nominal Overall Maximum
Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² mm mm mm mm mm kg/km Ω/km

1.5 0.26 1.58 0.7 1.8 10.5 126 13.3


2.5 0.26 2.04 0.8 1.8 12.0 166 7.98
4 0.31 2.59 1.0 1.8 14.0 230 4.95
6 0.31 3.46 1.0 1.8 15.5 297 3.30
10 0.41 4.62 1.0 1.8 18.0 422 1.91
16 0.41 5.66 1.0 1.8 20.0 562 1.21
25 0.41 7.06 1.2 1.8 23.5 809 0.780
35 0.41 8.43 1.2 1.8 26.0 1061 0.554
50 0.41 10.07 1.4 1.8 30.5 1451 0.386
70 0.51 11.97 1.4 1.9 34.5 1949 0.272
95 0.51 13.73 1.6 2.0 39.0 2546 0.206
120 0.51 15.53 1.6 2.1 43.0 3160 0.161

Page - 11
Section 2 - PVC Insulated Cables
Unarmoured Cables

450/750 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC Flexible (IEC 60227, SPLN 42-6-3)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Red,Yellow , Blue
Sheath - Black

THREE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² mm mm mm mm mm kg/km Ω/km

1.5 0.26 1.58 0.7 1.8 11.0 153 13.3


2.5 0.26 2.04 0.8 1.8 12.5 204 7.98
4 0.31 2.59 1.0 1.8 14.5 287 4.95
6 0.31 3.46 1.0 1.8 16.5 380 3.30
10 0.41 4.62 1.0 1.8 19.0 552 1.91
16 0.41 5.66 1.0 1.8 21.0 744 1.21
25 0.41 7.06 1.2 1.8 25.0 1085 0.780
35 0.41 8.43 1.2 1.8 28.0 1443 0.554
50 0.41 10.07 1.4 1.8 32.5 1986 0.386
70 0.51 11.97 1.4 2.0 37.0 2702 0.272
95 0.51 13.73 1.6 2.1 42.0 3542 0.206
120 0.51 15.53 1.6 2.2 46.0 4408 0.161

Page - 12
Section 2 - PVC Insulated Cables
Unarmoured Cables

450/750 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC Flexible (IEC 60227, SPLN 42-6-3)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Red,Yellow , Blue , Black
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Overall Maximum
Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² mm mm mm mm mm kg/km Ω/km

1.5 0.26 1.58 0.7 1.8 12.0 181 13.3


2.5 0.26 2.04 0.8 1.8 13.5 247 7.98
4 0.31 2.59 1.0 1.8 16.0 353 4.95
6 0.31 3.46 1.0 1.8 18.0 471 3.30
10 0.41 4.62 1.0 1.8 20.5 696 1.91
16 0.41 5.66 1.0 1.8 23.5 942 1.21
25 0.41 7.06 1.2 1.8 27.5 1390 0.780
35 0.41 8.43 1.2 1.8 31.0 1856 0.554
50 0.41 10.07 1.4 1.9 36.0 2579 0.386
70 0.51 11.97 1.4 2.1 41.0 3517 0.272
95 0.51 13.73 1.6 2.2 47.0 4610 0.206
120 0.51 15.53 1.6 2.4 51.5 5769 0.161

Page - 13
Section 2 - PVC Insulated Cables
Unarmoured Cables

450/750 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC Flexible (IEC 60227, SPLN 42-6-3)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² mm mm mm mm mm kg/km Ω/km

1.5 0.26 1.58 0.7 1.8 13.0 215 13.3


2.5 0.26 2.04 0.8 1.8 14.5 290 7.98
4 0.31 2.59 1.0 1.8 17.0 425 4.95
6 0.31 3.46 1.0 1.8 19.5 567 3.30
10 0.41 4.62 1.0 1.8 22.5 847 1.91
16 0.41 5.66 1.0 1.8 25.5 1154 1.21
25 0.41 7.06 1.2 1.8 30.5 1703 0.780
35 0.41 8.43 1.2 1.9 34.0 2297 0.554
50 0.41 10.07 1.4 2.0 40.0 3200 0.386

Page - 14
Section 2 - PVC Insulated Cables
Unarmoured Cables

450/750 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC Flexible (IEC 60227, SPLN 42-6-3)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 1.5 mm²


Conductor Nominal Nominal Overall Maximum
Maximum Diameter Thickness Thickness diameter Weight Conductor
No Diameter of of of of of Resistance
of of wire Conductor Insulation Sheath cable cable at 20°C
core (approx.) (approx.) (approx.) (approx.)
mm mm mm mm mm kg/km Ω/km

6 0.26 1.58 0.7 1.8 14.0 240 13.3


7 0.26 1.58 0.7 1.8 14.0 258 13.3
8 0.26 1.58 0.7 1.8 15.0 295 13.3
9 0.26 1.58 0.7 1.8 16.0 326 13.3
10 0.26 1.58 0.7 1.8 17.0 360 13.3
12 0.26 1.58 0.7 1.8 17.5 408 13.3
14 0.26 1.58 0.7 1.8 18.5 458 13.3
15 0.26 1.58 0.7 1.8 19.0 489 13.3
16 0.26 1.58 0.7 1.8 19.0 514 13.3
18 0.26 1.58 0.7 1.8 20.0 562 13.3
19 0.26 1.58 0.7 1.8 20.0 580 13.3
20 0.26 1.58 0.7 1.8 21.0 614 13.3
24 0.26 1.58 0.7 1.8 23.5 725 13.3
30 0.26 1.58 0.7 1.8 24.5 868 13.3
32 0.26 1.58 0.7 1.8 25.0 921 13.3
37 0.26 1.58 0.7 1.8 26.5 1034 13.3
40 0.26 1.58 0.7 1.8 27.5 1110 13.3
50 0.26 1.58 0.7 1.9 30.5 1374 13.3
52 0.26 1.58 0.7 1.9 31.5 1424 13.3
60 0.26 1.58 0.7 1.9 33.0 1617 13.3
61 0.26 1.58 0.7 1.9 33.0 1635 13.3

Page - 15
Section 2 - PVC Insulated Cables
Unarmoured Cables

450/750 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC Flexible (IEC 60227, SPLN 42-6-3)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 2.5 mm²


Conductor Nominal Nominal Overall Maximum
Maximum Diameter Thickness Thickness diameter Weight Conductor
No Diameter of of of of of Resistance
of of wire Conductor Insulation Sheath cable cable at 20°C
core (approx.) (approx.) (approx.) (approx.)
mm mm mm mm mm kg/km Ω/km

6 0.26 2.04 0.8 1.8 15.5 331 7.98


7 0.26 2.04 0.8 1.8 15.5 358 7.98
8 0.26 2.04 0.8 1.8 17.0 406 7.98
9 0.26 2.04 0.8 1.8 18.0 455 7.98
10 0.26 2.04 0.8 1.8 19.5 505 7.98
12 0.26 2.04 0.8 1.8 20.0 577 7.98
14 0.26 2.04 0.8 1.8 21.0 654 7.98
15 0.26 2.04 0.8 1.8 21.5 697 7.98
16 0.26 2.04 0.8 1.8 22.0 732 7.98
18 0.26 2.04 0.8 1.8 23.0 806 7.98
19 0.26 2.04 0.8 1.8 23.0 834 7.98
20 0.26 2.04 0.8 1.8 24.0 887 7.98
24 0.26 2.04 0.8 1.8 27.0 1049 7.98
30 0.26 2.04 0.8 1.8 28.5 1266 7.98
32 0.26 2.04 0.8 1.8 29.0 1342 7.98
37 0.26 2.04 0.8 1.9 31.0 1527 7.98
40 0.26 2.04 0.8 1.9 32.0 1644 7.98
50 0.26 2.04 0.8 2.0 35.5 2037 7.98
52 0.26 2.04 0.8 2.0 36.5 2115 7.98
60 0.26 2.04 0.8 2.1 39.0 2423 7.98
61 0.26 2.04 0.8 2.1 39.0 2450 7.98

Page - 16
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (acc. to IEC 60502-1)

1 1

2 2

3
4

5 5

Constructions : Note : Special application upon request


1 Conductor (Annealed Copper) * Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
2 Insulation (PVC Compound)
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
3 Filler (Polyprophylene yarn,or extruded filler * Anti termite performance.
up to request) * Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed
4 Binding tape (Manufacturer's option)
5 Outer sheath (PVC Compound)

Page - 17
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Sheath : PVC Compound type ST1 Maximum 70°C
Colour Ident. : Insulation - Black
Sheath - Black

SINGLE CORE
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.4 6.5 55 12.1
1.5 7 / 0.52 1.56 0.8 1.4 6.5 58 12.1
2.5 1 / 1.78 1.78 0.8 1.4 7.0 68 7.41
2.5 7 / 0.67 2.01 0.8 1.4 7.0 71 7.41
4 1 / 2.26 2.26 1.0 1.4 7.5 94 4.61
4 7 / 0.85 2.55 1.0 1.4 8.0 98 4.61
6 7 / 1.04 3.12 1.0 1.4 8.5 123 3.08
10 7 / 1.35 4.05 1.0 1.4 9.5 172 1.83
16 7 / 1.70 5.10 1.0 1.4 10.5 239 1.15
25 7 / 2.13 6.39 1.2 1.4 12.0 349 0.727
35 7 / 2.52 7.56 1.2 1.4 13.5 457 0.524
50 19 / 1.83 9.15 1.4 1.4 15.5 623 0.387
70 19 / 2.17 10.85 1.4 1.4 17.0 832 0.268
95 19 / 2.52 12.60 1.6 1.5 19.5 1114 0.193
120 37 / 2.03 14.21 1.6 1.5 21.0 1359 0.153
150 37 / 2.27 15.89 1.8 1.6 23.5 1689 0.124
185 37 / 2.52 17.64 2.0 1.7 25.5 2068 0.0991
240 61 / 2.26 20.34 2.2 1.8 29.0 2698 0.0754
300 61 / 2.52 22.68 2.4 1.9 32.0 3327 0.0601
400 61 / 2.86 25.74 2.6 2.0 36.0 4249 0.0470
500 61 / 3.20 28.80 2.8 2.1 39.5 5266 0.0366
630 91 / 2.96 32.56 2.8 2.2 43.5 6580 0.0283
800 127 / 2.85 37.05 2.8 2.3 48.0 8345 0.0221
1000 127 / 3.20 41.60 3.0 2.5 53.5 10455 0.0176

Page - 18
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Black
Sheath - Black

TWO CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section area of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.8 10.5 128 12.1
1.5 7 / 0.52 1.56 0.8 1.8 11.0 136 12.1
2.5 1 / 1.78 1.78 0.8 1.8 11.5 159 7.41
2.5 7 / 0.67 2.01 0.8 1.8 12.0 168 7.41
4 1 / 2.26 2.26 1.0 1.8 13.0 220 4.61
4 7 / 0.85 2.55 1.0 1.8 14.0 231 4.61
6 7 / 1.04 3.12 1.0 1.8 15.0 287 3.08
10 7 / 1.35 4.05 1.0 1.8 17.0 398 1.83
16 7 / 1.70 5.10 1.0 1.8 19.0 545 1.15
25 7 / 2.13 6.39 1.2 1.8 22.0 794 0.727
35 7 / 2.52 7.56 1.2 1.8 24.5 1032 0.524
50 19 / 1.83 9.15 1.4 1.8 28.5 1411 0.387
70 19 / 2.17 10.85 1.4 1.9 32.0 1880 0.268
95 19 / 2.52 12.60 1.6 2.0 37.0 2507 0.193
120 37 / 2.03 14.21 1.6 2.1 40.5 3065 0.153
150 37 / 2.27 15.89 1.8 2.2 45.0 3796 0.124
185 37 / 2.52 17.64 2.0 2.4 49.5 4654 0.0991
240 61 / 2.26 20.34 2.2 2.6 56.0 6067 0.0754
300 61 / 2.52 22.68 2.4 2.7 62.0 7463 0.0601

Page - 19
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Yellow , Blue
Sheath - Black

THREE CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section area of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.8 11.0 155 12.1
1.5 7 / 0.52 1.56 0.8 1.8 11.5 163 12.1
2.5 1 / 1.78 1.78 0.8 1.8 12.0 195 7.41
2.5 7 / 0.67 2.01 0.8 1.8 12.5 207 7.41
4 1 / 2.26 2.26 1.0 1.8 14.0 277 4.61
4 7 / 0.85 2.55 1.0 1.8 14.5 290 4.61
6 7 / 1.04 3.12 1.0 1.8 15.5 367 3.08
10 7 / 1.35 4.05 1.0 1.8 18.0 521 1.83
16 7 / 1.70 5.10 1.0 1.8 20.0 728 1.15
25 7 / 2.13 6.39 1.2 1.8 23.5 1078 0.727
35 7 / 2.52 7.56 1.2 1.8 26.0 1410 0.524
50 6.8 1.4 1.8 25.0 1741 0.387
70 8.2 1.4 2.0 28.0 2415 0.268
95 Three- 9.7 1.6 2.1 33.0 3319 0.193
120 Segmental 10.9 1.6 2.2 35.5 3963 0.153
150 Stranded 11.9 1.8 2.3 38.5 4851 0.124
185 13.6 2.0 2.5 43.5 6056 0.0991
240 15.8 2.2 2.7 49.0 8072 0.0754
300 17.5 2.4 2.9 54.0 10034 0.0601

Page - 20
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Yellow , Blue , Black
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section area of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.8 12.0 184 12.1
1.5 7 / 0.52 1.56 0.8 1.8 12.5 193 12.1
2.5 1 / 1.78 1.78 0.8 1.8 13.0 239 7.41
2.5 7 / 0.67 2.01 0.8 1.8 13.5 251 7.41
4 1 / 2.26 2.26 1.0 1.8 15.0 342 4.61
4 7 / 0.85 2.55 1.0 1.8 16.0 360 4.61
6 7 / 1.04 3.12 1.0 1.8 17.0 461 3.08
10 7 / 1.35 4.05 1.0 1.8 19.5 658 1.83
16 7 / 1.70 5.10 1.0 1.8 22.0 930 1.15
25 7 / 2.13 6.39 1.2 1.8 26.0 1378 0.727
35 7 / 2.52 7.56 1.2 1.8 29.0 1818 0.524
50 8.1 1.4 1.9 28.5 2264 0.387
70 9.7 1.4 2.1 32.0 3148 0.268
95 Four- 11.4 1.6 2.2 37.5 4326 0.193
120 Segmental 12.9 1.6 2.4 41.0 5198 0.153
150 Stranded 14.2 1.8 2.5 45.0 6373 0.124
185 16.0 2.0 2.7 50.0 7938 0.0991
240 18.2 2.2 2.9 56.0 10564 0.0754
300 20.6 2.4 3.1 62.5 13201 0.0601

Page - 21
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section area of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.8 13.0 218 12.1
1.5 7 / 0.52 1.56 0.8 1.8 13.5 230 12.1
2.5 1 / 1.78 1.78 0.8 1.8 14.0 280 7.41
2.5 7 / 0.67 2.01 0.8 1.8 14.5 296 7.41
4 1 / 2.26 2.26 1.0 1.8 16.5 408 4.61
4 7 / 0.85 2.55 1.0 1.8 17.5 430 4.61
6 7 / 1.04 3.12 1.0 1.8 18.5 556 3.08
10 7 / 1.35 4.05 1.0 1.8 21.5 800 1.83
16 7 / 1.70 5.10 1.0 1.8 24.0 1135 1.15
25 7 / 2.13 6.39 1.2 1.8 28.5 1692 0.727
35 7 / 2.52 7.56 1.2 1.9 32.0 2257 0.524
50 19 / 1.83 9.15 1.4 2.1 38.0 3152 0.387

Page - 22
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 1.5 mm² (Solid conductor)


Conductor Nominal Nominal Overall Maximum
No Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
of Cross-section Diameter of of of of of Resistance
core area of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
6 1.5 1 / 1.38 1.38 0.8 1.8 14.0 245 12.1
7 1.5 1 / 1.38 1.38 0.8 1.8 14.0 263 12.1
8 1.5 1 / 1.38 1.38 0.8 1.8 15.0 297 12.1
9 1.5 1 / 1.38 1.38 0.8 1.8 16.0 332 12.1
10 1.5 1 / 1.38 1.38 0.8 1.8 17.0 367 12.1
12 1.5 1 / 1.38 1.38 0.8 1.8 17.5 416 12.1
14 1.5 1 / 1.38 1.38 0.8 1.8 18.5 468 12.1
15 1.5 1 / 1.38 1.38 0.8 1.8 19.0 500 12.1
16 1.5 1 / 1.38 1.38 0.8 1.8 19.5 525 12.1
18 1.5 1 / 1.38 1.38 0.8 1.8 20.0 575 12.1
19 1.5 1 / 1.38 1.38 0.8 1.8 20.0 593 12.1
20 1.5 1 / 1.38 1.38 0.8 1.8 21.0 628 12.1
21 1.5 1 / 1.38 1.38 0.8 1.8 21.0 650 12.1
24 1.5 1 / 1.38 1.38 0.8 1.8 23.5 742 12.1
30 1.5 1 / 1.38 1.38 0.8 1.8 24.5 889 12.1
32 1.5 1 / 1.38 1.38 0.8 1.8 25.0 943 12.1
37 1.5 1 / 1.38 1.38 0.8 1.8 26.5 1059 12.1
40 1.5 1 / 1.38 1.38 0.8 1.8 27.5 1139 12.1
50 1.5 1 / 1.38 1.38 0.8 1.9 30.5 1408 12.1
52 1.5 1 / 1.38 1.38 0.8 1.9 31.5 1460 12.1
60 1.5 1 / 1.38 1.38 0.8 2.0 33.5 1674 12.1
61 1.5 1 / 1.38 1.38 0.8 2.0 33.5 1692 12.1

Page - 23
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 1.5 mm² (Stranded conductor)


Conductor Nominal Nominal Overall Maximum
No Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
of Cross-section Diameter of of of of of Resistance
core area of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
6 1.5 7 / 0.52 1.56 0.8 1.8 14.5 259 12.1
7 1.5 7 / 0.52 1.56 0.8 1.8 14.5 278 12.1
8 1.5 7 / 0.52 1.56 0.8 1.8 15.5 314 12.1
9 1.5 7 / 0.52 1.56 0.8 1.8 16.5 351 12.1
10 1.5 7 / 0.52 1.56 0.8 1.8 18.0 389 12.1
12 1.5 7 / 0.52 1.56 0.8 1.8 18.5 439 12.1
14 1.5 7 / 0.52 1.56 0.8 1.8 19.0 494 12.1
15 1.5 7 / 0.52 1.56 0.8 1.8 19.5 527 12.1
16 1.5 7 / 0.52 1.56 0.8 1.8 20.0 554 12.1
18 1.5 7 / 0.52 1.56 0.8 1.8 21.0 608 12.1
19 1.5 7 / 0.52 1.56 0.8 1.8 21.0 626 12.1
20 1.5 7 / 0.52 1.56 0.8 1.8 22.0 663 12.1
21 1.5 7 / 0.52 1.56 0.8 1.8 22.0 687 12.1
24 1.5 7 / 0.52 1.56 0.8 1.8 24.5 786 12.1
30 1.5 7 / 0.52 1.56 0.8 1.8 26.0 939 12.1
32 1.5 7 / 0.52 1.56 0.8 1.8 26.5 996 12.1
37 1.5 7 / 0.52 1.56 0.8 1.8 28.0 1119 12.1
40 1.5 7 / 0.52 1.56 0.8 1.8 29.0 1204 12.1
50 1.5 7 / 0.52 1.56 0.8 1.9 32.0 1488 12.1
52 1.5 7 / 0.52 1.56 0.8 1.9 33.0 1543 12.1
60 1.5 7 / 0.52 1.56 0.8 2.0 35.0 1770 12.1
61 1.5 7 / 0.52 1.56 0.8 2.0 35.0 1788 12.1

Page - 24
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 2.5 mm² (Solid conductor)


Conductor Nominal Nominal Overall Maximum
No Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
of Cross-section Diameter of of of of of Resistance
core area of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
6 2.5 1 / 1.78 1.78 0.8 1.8 15.0 320 7.41
7 2.5 1 / 1.78 1.78 0.8 1.8 15.0 348 7.41
8 2.5 1 / 1.78 1.78 0.8 1.8 16.0 394 7.41
9 2.5 1 / 1.78 1.78 0.8 1.8 17.0 442 7.41
10 2.5 1 / 1.78 1.78 0.8 1.8 18.5 488 7.41
12 2.5 1 / 1.78 1.78 0.8 1.8 19.0 558 7.41
14 2.5 1 / 1.78 1.78 0.8 1.8 20.0 636 7.41
15 2.5 1 / 1.78 1.78 0.8 1.8 20.5 673 7.41
16 2.5 1 / 1.78 1.78 0.8 1.8 21.0 710 7.41
18 2.5 1 / 1.78 1.78 0.8 1.8 22.0 783 7.41
19 2.5 1 / 1.78 1.78 0.8 1.8 22.0 811 7.41
20 2.5 1 / 1.78 1.78 0.8 1.8 23.0 863 7.41
21 2.5 1 / 1.78 1.78 0.8 1.8 23.5 890 7.41
24 2.5 1 / 1.78 1.78 0.8 1.8 26.0 1018 7.41
30 2.5 1 / 1.78 1.78 0.8 1.8 27.5 1232 7.41
32 2.5 1 / 1.78 1.78 0.8 1.8 28.0 1303 7.41
37 2.5 1 / 1.78 1.78 0.8 1.9 29.5 1487 7.41
40 2.5 1 / 1.78 1.78 0.8 1.9 30.5 1600 7.41
50 2.5 1 / 1.78 1.78 0.8 2.0 34.0 1981 7.41
52 2.5 1 / 1.78 1.78 0.8 2.0 35.0 2060 7.41
60 2.5 1 / 1.78 1.78 0.8 2.1 37.0 2359 7.41
61 2.5 1 / 1.78 1.78 0.8 2.1 37.0 2387 7.41

Page - 25
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 2.5 mm² (Stranded conductor)


Conductor Nominal Nominal Overall Maximum
No Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
of Cross-section Diameter of of of of of Resistance
core area of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
6 2.5 7 / 0.67 2.01 0.8 1.8 15.5 338 7.41
7 2.5 7 / 0.67 2.01 0.8 1.8 15.5 365 7.41
8 2.5 7 / 0.67 2.01 0.8 1.8 17.0 415 7.41
9 2.5 7 / 0.67 2.01 0.8 1.8 18.0 465 7.41
10 2.5 7 / 0.67 2.01 0.8 1.8 19.5 515 7.41
12 2.5 7 / 0.67 2.01 0.8 1.8 20.0 590 7.41
14 2.5 7 / 0.67 2.01 0.8 1.8 21.0 669 7.41
15 2.5 7 / 0.67 2.01 0.8 1.8 21.5 713 7.41
16 2.5 7 / 0.67 2.01 0.8 1.8 22.0 749 7.41
18 2.5 7 / 0.67 2.01 0.8 1.8 23.0 826 7.41
19 2.5 7 / 0.67 2.01 0.8 1.8 23.0 854 7.41
20 2.5 7 / 0.67 2.01 0.8 1.8 24.0 908 7.41
21 2.5 7 / 0.67 2.01 0.8 1.8 24.5 938 7.41
24 2.5 7 / 0.67 2.01 0.8 1.8 27.0 1074 7.41
30 2.5 7 / 0.67 2.01 0.8 1.8 28.5 1298 7.41
32 2.5 7 / 0.67 2.01 0.8 1.8 29.0 1377 7.41
37 2.5 7 / 0.67 2.01 0.8 1.9 31.0 1567 7.41
40 2.5 7 / 0.67 2.01 0.8 1.9 32.5 1687 7.41
50 2.5 7 / 0.67 2.01 0.8 2.0 35.5 2088 7.41
52 2.5 7 / 0.67 2.01 0.8 2.0 36.5 2168 7.41
60 2.5 7 / 0.67 2.01 0.8 2.1 39.0 2488 7.41
61 2.5 7 / 0.67 2.01 0.8 2.1 39.0 2515 7.41

Page - 26
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 clas 1) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 4 mm² (Solid conductor)


Conductor Nominal Nominal Overall Maximum
No Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
of Cross-section Diameter of of of of of Resistance
core area of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
6 4 1 / 2.26 2.26 1.0 1.8 17.5 465 4.61
7 4 1 / 2.26 2.26 1.0 1.8 17.5 508 4.61
8 4 1 / 2.26 2.26 1.0 1.8 19.0 579 4.61
9 4 1 / 2.26 2.26 1.0 1.8 20.5 650 4.61
10 4 1 / 2.26 2.26 1.0 1.8 22.0 722 4.61
12 4 1 / 2.26 2.26 1.0 1.8 23.5 831 4.61
14 4 1 / 2.26 2.26 1.0 1.8 24.0 950 4.61
15 4 1 / 2.26 2.26 1.0 1.8 24.5 1012 4.61
16 4 1 / 2.26 2.26 1.0 1.8 25.5 1068 4.61
18 4 1 / 2.26 2.26 1.0 1.8 26.5 1178 4.61
19 4 1 / 2.26 2.26 1.0 1.8 26.5 1221 4.61
20 4 1 / 2.26 2.26 1.0 1.8 27.5 1294 4.61
21 4 1 / 2.26 2.26 1.0 1.8 28.0 1344 4.61
24 4 1 / 2.26 2.26 1.0 1.9 31.5 1555 4.61
30 4 1 / 2.26 2.26 1.0 2.0 33.5 1904 4.61
32 4 1 / 2.26 2.26 1.0 2.0 34.0 2020 4.61
37 4 1 / 2.26 2.26 1.0 2.1 26.5 2300 4.61
40 4 1 / 2.26 2.26 1.0 2.1 37.5 2478 4.61
50 4 1 / 2.26 2.26 1.0 2.3 42.0 3090 4.61
52 4 1 / 2.26 2.26 1.0 2.3 43.0 3212 4.61
60 4 1 / 2.26 2.26 1.0 2.4 46.0 3678 4.61
61 4 1 / 2.26 2.26 1.0 2.4 46.0 3721 4.61

Page - 27
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 clas 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 4 mm² (Stranded conductor)


Conductor Nominal Nominal Overall Maximum
No Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
of Cross-section Diameter of of of of of Resistance
core area of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
6 4 7 / 0.85 2.55 1.0 1.8 18.5 491 4.61
7 4 7 / 0.85 2.55 1.0 1.8 18.5 535 4.61
8 4 7 / 0.85 2.55 1.0 1.8 20.0 610 4.61
9 4 7 / 0.85 2.55 1.0 1.8 21.5 686 4.61
10 4 7 / 0.85 2.55 1.0 1.8 23.5 760 4.61
12 4 7 / 0.85 2.55 1.0 1.8 24.0 875 4.61
14 4 7 / 0.85 2.55 1.0 1.8 25.5 1000 4.61
15 4 7 / 0.85 2.55 1.0 1.8 26.0 1066 4.61
16 4 7 / 0.85 2.55 1.0 1.8 27.0 1126 4.61
18 4 7 / 0.85 2.55 1.0 1.8 28.0 1243 4.61
19 4 7 / 0.85 2.55 1.0 1.8 28.0 1287 4.61
20 4 7 / 0.85 2.55 1.0 1.8 29.0 1364 4.61
21 4 7 / 0.85 2.55 1.0 1.8 29.5 1417 4.61
24 4 7 / 0.85 2.55 1.0 1.9 33.0 1638 4.61
30 4 7 / 0.85 2.55 1.0 2.0 35.5 2006 4.61
32 4 7 / 0.85 2.55 1.0 2.0 36.0 2128 4.61
37 4 7 / 0.85 2.55 1.0 2.1 38.5 2424 4.61
40 4 7 / 0.85 2.55 1.0 2.1 40.0 2612 4.61
50 4 7 / 0.85 2.55 1.0 2.3 44.5 3254 4.61
52 4 7 / 0.85 2.55 1.0 2.3 45.5 3380 4.61
60 4 7 / 0.85 2.55 1.0 2.4 48.5 3877 4.61
61 4 7 / 0.85 2.55 1.0 2.4 48.5 3922 4.61

Page - 28
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES


PVC/PVC-S (IEC 60502-1)

Constructions : Note : Special application upon request


1 Conductor (Annealed Copper) * Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
2 Insulation (PVC Compound)
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
3 Filler (Polyprophylene yarn,or extruded filler * Anti termite performance.
up to request) * Tin coated Copper conductor.
* Copper wire screen.
4 Binding tape (Manufacturer's option) * Polyethylene / Low smoke Halogen Free sheathed
5 Copper Tape screen
6 Binding tape (Manufacturer's option)
7 Outer sheath (PVC Compound)

Page - 29
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES


PVC/PVC-S (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Black
Sheath - Black

TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of of Resistance
section area of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.8 0.1 1.8 10.5 145 12.1


1.5 7 / 0.52 1.56 0.8 0.1 1.8 11.0 147 12.1
2.5 1 / 1.78 1.78 0.8 0.1 1.8 11.5 176 7.41
2.5 7 / 0.67 2.01 0.8 0.1 1.8 11.5 179 7.41
4 1 / 2.26 2.26 1.0 0.1 1.8 13.0 240 4.61
4 7 / 0.85 2.55 1.0 0.1 1.8 13.5 246 4.61
6 7 / 1.04 3.12 1.0 0.1 1.8 14.5 304 3.08
10 7 / 1.35 4.05 1.0 0.1 1.8 16.5 418 1.83
16 7 / 1.70 5.10 1.0 0.1 1.8 18.5 568 1.15
25 7 / 2.13 6.39 1.2 0.1 1.8 22.0 822 0.727
35 7 / 2.52 7.56 1.2 0.1 1.8 24.5 1064 0.524
50 19 / 1.83 9.15 1.4 0.1 1.8 28.5 1450 0.387
70 19 / 2.17 10.85 1.4 0.1 1.9 32.0 1910 0.268
95 19 / 2.52 12.60 1.6 0.1 2.0 36.5 2542 0.193
120 37 / 2.03 14.21 1.6 0.1 2.1 40.0 3103 0.153
150 37 / 2.27 15.89 1.8 0.1 2.2 44.5 3840 0.124
185 37 / 2.52 17.64 2.0 0.1 2.4 49.0 4679 0.0991
240 61 / 2.26 20.34 2.2 0.1 2.6 55.5 6096 0.0754
300 61 / 2.52 22.68 2.4 0.1 2.7 61.5 7523 0.0601

Page - 30
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES


PVC/PVC-S (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Yellow , Blue
Sheath - Black

THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of of Resistance
section area of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.8 0.1 1.8 11.0 173 12.1


1.5 7 / 0.52 1.56 0.8 0.1 1.8 11.5 174 12.1
2.5 1 / 1.78 1.78 0.8 0.1 1.8 12.0 214 7.41
2.5 7 / 0.67 2.01 0.8 0.1 1.8 12.5 220 7.41
4 1 / 2.26 2.26 1.0 0.1 1.8 14.0 298 4.61
4 7 / 0.85 2.55 1.0 0.1 1.8 14.5 306 4.61
6 7 / 1.04 3.12 1.0 0.1 1.8 15.0 385 3.08
10 7 / 1.35 4.05 1.0 0.1 1.8 17.5 542 1.83
16 7 / 1.70 5.10 1.0 0.1 1.8 20.0 753 1.15
25 7 / 2.13 6.39 1.2 0.1 1.8 23.5 1108 0.727
35 7 / 2.52 7.56 1.2 0.1 1.8 26.0 1445 0.524
50 6.8 1.4 0.1 1.9 25.0 1774 0.387
70 8.2 1.4 0.1 2.0 28.0 2439 0.268
95 Three- 9.7 1.6 0.1 2.1 32.5 3348 0.193
120 Segmental 10.9 1.6 0.1 2.2 35.0 3994 0.153
150 Stranded 11.9 1.8 0.1 2.4 38.5 4885 0.124
185 13.6 2.0 0.1 2.5 43.0 6076 0.0991
240 15.8 2.2 0.1 2.7 48.5 8095 0.0754
300 17.5 2.4 0.1 2.9 53.5 10060 0.0601

Page - 31
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES


PVC/PVC-S (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Yellow , Blue , Black
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of of Resistance
section area of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.8 0.1 1.8 12.0 202 12.1


1.5 7 / 0.52 1.56 0.8 0.1 1.8 12.5 206 12.1
2.5 1 / 1.78 1.78 0.8 0.1 1.8 13.0 260 7.41
2.5 7 / 0.67 2.01 0.8 0.1 1.8 13.5 265 7.41
4 1 / 2.26 2.26 1.0 0.1 1.8 15.0 366 4.61
4 7 / 0.85 2.55 1.0 0.1 1.8 15.5 378 4.61
6 7 / 1.04 3.12 1.0 0.1 1.8 17.0 482 3.08
10 7 / 1.35 4.05 1.0 0.1 1.8 19.5 682 1.83
16 7 / 1.70 5.10 1.0 0.1 1.8 21.5 957 1.15
25 7 / 2.13 6.39 1.2 0.1 1.8 26.0 1412 0.727
35 7 / 2.52 7.56 1.2 0.1 1.8 28.5 1856 0.524
50 8.1 1.4 0.1 2.0 28.5 2302 0.387
70 9.7 1.4 0.1 2.1 32.0 3177 0.268
95 Four- 11.4 1.6 0.1 2.2 37.0 4360 0.193
120 Segmental 12.9 1.6 0.1 2.4 40.5 5217 0.153
150 Stranded 14.2 1.8 0.1 2.5 44.5 6394 0.124
185 16.0 2.0 0.1 2.7 49.5 7962 0.0991
240 18.2 2.2 0.1 2.9 55.5 10591 0.0754
300 20.6 2.4 0.1 3.1 61.5 13179 0.0601

Page - 32
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES


PVC/PVC-S (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of of Resistance
section area of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.8 0.1 1.8 12.5 238 12.1


1.5 7 / 0.52 1.56 0.8 0.1 1.8 13.5 244 12.1
2.5 1 / 1.78 1.78 0.8 0.1 1.8 14.0 302 7.41
2.5 7 / 0.67 2.01 0.8 0.1 1.8 14.5 312 7.41
4 1 / 2.26 2.26 1.0 0.1 1.8 16.5 434 4.61
4 7 / 0.85 2.55 1.0 0.1 1.8 17.0 450 4.61
6 7 / 1.04 3.12 1.0 0.1 1.8 18.5 578 3.08
10 7 / 1.35 4.05 1.0 0.1 1.8 21.0 827 1.83
16 7 / 1.70 5.10 1.0 0.1 1.8 24.0 1166 1.15
25 7 / 2.13 6.39 1.2 0.1 1.8 28.5 1730 0.727
35 7 / 2.52 7.56 1.2 0.1 1.9 31.5 2286 0.524
50 19 / 1.83 9.15 1.4 0.1 2.1 37.5 3057 0.387

Page - 33
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, ALUMINIUM WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/AWA/PVC (acc. to IEC 60502-1)

1 Constructions :
2 1 Conductor (Annealed Copper)
3 2 Insulation (PVC Compound)
4 3 Inner Covering (PVC Compound)
5 4 Round Aluminium Wire armour
5 Binding tape (Manufacturer's option)
6 6 Outer sheath (PVC Compound)

600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/SWA/PVC (acc. to IEC 60502-1)

Constructions :
1
1 Conductor (Annealed Copper)
2 2 Insulation (PVC Compound)
3 3 Filler (Polyprophylene yarn,or extruded filler
4 up to request)
5 4 Binding tape (Manufacturer's option)
6 5 Inner Covering (PVC Compound)
6 Galvanized Round Steel Wire armour
7
7 Binding tape (Manufacturer's option)
8 Outer sheath (PVC Compound)
8

Note : Special application upon request


* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed

Page - 34
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED,ALUMINIUM WIRE ARMOURED AND PVC SHEATHED CABLES


PVC/AWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Inner covering : PVC Compound ST1 Maximum 70°C
Armour : Aluminium Wire
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black
Sheath - Black

SINGLE CORE
Conductor Nominal Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter of Thickness diameter Weight Conductor
Cross- Diameter of of of inner Aluminium of of of Resistance
section of wire Conductor Insulation covering wire Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km

16 7 / 1.70 5.10 1.0 1.0 0.8 1.8 14.5 370 1.15

25 7 / 2.13 6.39 1.2 1.0 0.8 1.8 16.5 495 0.727

35 7 / 2.52 7.56 1.2 1.0 0.8 1.8 17.5 620 0.524

50 19 / 1.83 9.15 1.4 1.0 1.25 1.8 20.5 845 0.387

70 19 / 2.17 10.85 1.4 1.0 1.25 1.8 22.0 1075 0.268

95 19 / 2.52 12.60 1.6 1.0 1.25 1.8 24.5 1380 0.193

120 37 / 2.03 14.21 1.6 1.0 1.6 1.8 27.0 1705 0.153

150 37 / 2.27 15.89 1.8 1.0 1.6 1.8 29.0 2054 0.124

185 37 / 2.52 17.64 2.0 1.0 1.6 1.8 31.0 2450 0.0991

240 61 / 2.26 20.34 2.2 1.0 1.6 1.9 34.0 3110 0.0754

300 61 / 2.52 22.68 2.4 1.0 2.0 2.0 38.0 3865 0.0601

400 61 / 2.86 25.74 2.6 1.2 2.0 2.1 42.0 4885 0.0470

500 61 / 3.20 28.80 2.8 1.2 2.0 2.2 46.0 5965 0.0366

630 91 / 2.96 32.56 2.8 1.2 2.0 2.4 50.0 7335 0.0283

800 127 / 2.85 37.05 2.8 1.4 2.5 2.5 56.0 9410 0.0221

1000 127 / 3.20 41.60 3.0 1.4 2.5 2.7 61.0 11635 0.0176

Page - 35
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/SWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Black
Sheath - Black

TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Diameter Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. of of of Resistance
section of wire Conductor Insulation covering Steel wire Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.8 1.0 0.8 1.8 14.0 332 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 1.8 14.5 347 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 1.8 15.0 380 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 1.8 15.5 395 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 1.8 16.5 473 4.61
4 7 / 0.85 2.55 1.0 1.0 0.8 1.8 17.5 494 4.61
6 7 / 1.04 3.12 1.0 1.0 1.25 1.8 19.0 667 3.08
10 7 / 1.35 4.05 1.0 1.0 1.25 1.8 21.0 837 1.83
16 7 / 1.70 5.10 1.0 1.0 1.25 1.8 23.0 1019 1.15
25 7 / 2.13 6.39 1.2 1.0 1.6 1.8 27.5 1507 0.727
35 7 / 2.52 7.56 1.2 1.0 1.6 1.8 30.0 1810 0.524
50 19 / 1.83 9.15 1.4 1.0 1.6 1.9 34.0 2318 0.387
70 19 / 2.17 10.85 1.4 1.0 2.0 2.0 38.0 3122 0.268
95 19 / 2.52 12.60 1.6 1.2 2.0 2.2 43.5 3987 0.193
120 37 / 2.03 14.21 1.6 1.2 2.0 2.3 47.0 4695 0.153
150 37 / 2.27 15.89 1.8 1.2 2.5 2.4 52.0 5994 0.124
185 37 / 2.52 17.64 2.0 1.4 2.5 2.6 57.0 7109 0.0991
240 61 / 2.26 20.34 2.2 1.4 2.5 2.8 63.5 8827 0.0754
300 61 / 2.52 22.68 2.4 1.6 2.5 2.9 70.0 10574 0.0601

Page - 36
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/SWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Yellow, Blue
Sheath - Black

THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Diameter Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. of of of Resistance
section of wire Conductor Insulation covering Steel wire Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.8 1.0 0.8 1.8 14.5 371 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 1.8 15.0 385 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 1.8 15.5 429 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 1.8 16.0 446 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 1.8 18.0 637 4.61
4 7 / 0.85 2.55 1.0 1.0 1.25 1.8 18.5 660 4.61
6 7 / 1.04 3.12 1.0 1.0 1.25 1.8 20.0 768 3.08
10 7 / 1.35 4.05 1.0 1.0 1.25 1.8 22.0 973 1.83
16 7 / 1.70 5.10 1.0 1.0 1.25 1.8 24.0 1229 1.15
25 7 / 2.13 6.39 1.2 1.0 1.6 1.8 29.0 1819 0.727
35 7 / 2.52 7.56 1.2 1.0 1.6 1.8 31.5 2230 0.524
50 6.8 1.4 1.0 1.6 2.0 30.5 2558 0.387
70 Sector Shape 8.2 1.4 1.2 2.0 2.1 34.5 3577 0.268
95 stranded 9.7 1.6 1.2 2.0 2.2 39.0 4653 0.193
120 10.9 1.6 1.2 2.0 2.3 42.0 5410 0.153
150 11.9 1.8 1.4 2.5 2.5 46.0 6830 0.124
185 13.6 2.0 1.4 2.5 2.7 51.0 8260 0.0991
240 15.8 2.2 1.6 2.5 2.9 57.0 10632 0.0754
300 17.5 2.4 1.6 2.5 3.1 62.0 12795 0.0601

Page - 37
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/SWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Yellow, Blue, Black
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Diameter Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. of of of Resistance
section of wire Conductor Insulation covering Steel wire Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.8 1.0 0.8 1.8 15.5 412 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 1.8 16.0 434 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 1.8 16.5 486 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 1.8 17.0 508 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 1.8 19.5 736 4.61
4 7 / 0.85 2.55 1.0 1.0 1.25 1.8 20.0 762 4.61
6 7 / 1.04 3.12 1.0 1.0 1.25 1.8 21.0 894 3.08
10 7 / 1.35 4.05 1.0 1.0 1.25 1.8 23.5 1142 1.83
16 7 / 1.70 5.10 1.0 1.0 1.6 1.8 27.0 1621 1.15
25 7 / 2.13 6.39 1.2 1.0 1.6 1.8 31.0 2183 0.727
35 7 / 2.52 7.56 1.2 1.0 1.6 1.9 34.0 2698 0.524
50 8.1 1.4 1.2 2.0 2.1 35.0 3467 0.387
70 Sector Shape 9.7 1.4 1.2 2.0 2.2 38.5 4455 0.268
95 stranded 11.4 1.6 1.2 2.5 2.4 44.5 6222 0.193
120 12.9 1.6 1.4 2.5 2.5 48.5 7248 0.153
150 14.2 1.8 1.4 2.5 2.7 52.5 8663 0.124
185 16.0 2.0 1.6 2.5 2.9 58.0 10503 0.0991
240 18.2 2.2 1.6 2.5 3.1 63.5 13414 0.0754
300 20.6 2.4 1.6 2.5 3.3 70.0 16298 0.0601

Page - 38
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/SWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Diameter Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. of of of Resistance
section of wire Conductor Insulation covering Steel wire Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.8 1.0 0.8 1.8 16.5 465 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 1.8 17.0 488 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 1.8 17.5 551 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 1.8 18.0 572 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 1.8 20.5 835 4.61
4 7 / 0.85 2.55 1.0 1.0 1.25 1.8 21.5 865 4.61
6 7 / 1.04 3.12 1.0 1.0 1.25 1.8 22.5 1021 3.08
10 7 / 1.35 4.05 1.0 1.0 1.6 1.8 26.5 1479 1.83
16 7 / 1.70 5.10 1.0 1.0 1.60 1.8 29.0 1893 1.15
25 7 / 2.13 6.39 1.2 1.0 1.6 1.9 33.5 2577 0.727
35 7 / 2.52 7.56 1.2 1.0 2.0 2.0 38.0 3468 0.524
50 19 / 1.83 9.15 1.4 1.2 2.0 2.2 44.0 4503 0.387

Page - 39
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (acc. to IEC 60502-1)

3
4

C Constructions :
1 Conductor (Annealed Copper) Note : Special application upon request
2 Insulation (PVC Compound) * Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
3 Filler (Polyprophylene yarn,or extruded filler * Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
up to request) * Anti termite performance.
* Tin coated Copper conductor.
4 Inner Covering (PVC Compound)
* Polyethylene / Low smoke Halogen Free sheathed
5 Galvanized Flat Steel Wire armour
6 Galvanized Steel Tape binding
7 Outer sheath (PVC Compound)

Page - 40
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Black
Sheath - Black

TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. thickness of of of Resistance
section of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.0 0.8 0.3 1.8 14.0 406 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 0.3 1.8 14.5 417 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 0.3 1.8 15.0 442 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 0.3 1.8 15.5 480 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 0.3 1.8 17.0 569 4.61
4 7 / 0.85 2.55 1.0 1.0 0.8 0.3 1.8 17.5 584 4.61
6 7 / 1.04 3.12 1.0 1.0 0.8 0.3 1.8 18.5 674 3.08
10 7 / 1.35 4.05 1.0 1.0 0.8 0.3 1.8 20.5 826 1.83
16 7 / 1.70 5.10 1.0 1.0 0.8 0.3 1.8 22.5 1040 1.15
25 7 / 2.13 6.39 1.2 1.0 0.8 0.3 1.8 26.0 1365 0.727
35 7 / 2.52 7.56 1.2 1.0 0.8 0.3 1.8 28.0 1672 0.524
50 19 / 1.83 9.15 1.4 1.0 0.8 0.3 1.8 32.0 2134 0.387
70 19 / 2.17 10.85 1.4 1.0 0.8 0.3 1.9 35.5 2691 0.268
95 19 / 2.52 12.60 1.6 1.2 0.8 0.3 2.1 41.0 3484 0.193
120 37 / 2.03 14.21 1.6 1.2 0.8 0.3 2.2 44.5 4149 0.153
150 37 / 2.27 15.89 1.8 1.2 0.8 0.3 2.3 49.0 4995 0.124
185 37 / 2.52 17.64 2.0 1.4 0.8 0.3 2.4 53.5 5968 0.0991
240 61 / 2.26 20.34 2.2 1.4 0.8 0.3 2.6 60.0 7540 0.0754
300 61 / 2.52 22.68 2.4 1.6 0.8 0.3 2.8 66.5 9178 0.0601

Page - 41
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Yellow, Blue
Sheath - Black

THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. thickness of of of Resistance
section of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.0 0.8 0.3 1.8 14.5 437 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 0.3 1.8 15.0 447 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 0.3 1.8 15.5 509 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 0.3 1.8 16.0 524 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 0.3 1.8 17.5 631 4.61
4 7 / 0.85 2.55 1.0 1.0 0.8 0.3 1.8 18.0 649 4.61
6 7 / 1.04 3.12 1.0 1.0 0.8 0.3 1.8 19.0 760 3.08
10 7 / 1.35 4.05 1.0 1.0 0.8 0.3 1.8 21.5 982 1.83
16 7 / 1.70 5.10 1.0 1.0 0.8 0.3 1.8 23.5 1230 1.15
25 7 / 2.13 6.39 1.2 1.0 0.8 0.3 1.8 27.0 1685 0.727
35 7 / 2.52 7.56 1.2 1.0 0.8 0.3 1.8 30.0 2089 0.524
50 6.8 1.4 1.0 0.8 0.3 1.9 28.5 2385 0.387
70 Sector Shape 8.2 1.4 1.2 0.8 0.3 2.0 32.0 3149 0.268
95 stranded 9.7 1.6 1.2 0.8 0.3 2.2 37.0 4184 0.193
120 10.9 1.6 1.2 0.8 0.3 2.3 39.5 4902 0.153
150 11.9 1.8 1.4 0.8 0.3 2.4 43.0 5887 0.124
185 13.6 2.0 1.4 0.8 0.3 2.6 47.5 7212 0.0991
240 15.8 2.2 1.6 0.8 0.3 2.8 54.0 9457 0.0754
300 17.5 2.4 1.6 0.8 0.3 2.9 58.5 11517 0.0601

Page - 42
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Yellow, Blue, Black
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. thickness of of of Resistance
section of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.0 0.8 0.3 1.8 15.5 497 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 0.3 1.8 16.0 510 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 0.3 1.8 16.5 560 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 0.3 1.8 17.0 602 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 0.3 1.8 18.5 731 4.61
4 7 / 0.85 2.55 1.0 1.0 0.8 0.3 1.8 19.5 754 4.61
6 7 / 1.04 3.12 1.0 1.0 0.8 0.3 1.8 20.5 890 3.08
10 7 / 1.35 4.05 1.0 1.0 0.8 0.3 1.8 23.0 1157 1.83
16 7 / 1.70 5.10 1.0 1.0 0.8 0.3 1.8 25.5 1498 1.15
25 7 / 2.13 6.39 1.2 1.0 0.8 0.3 1.8 29.5 2055 0.727
35 7 / 2.52 7.56 1.2 1.0 0.8 0.3 1.9 32.5 2567 0.524
50 8.1 1.4 1.2 0.8 0.3 2.0 32.5 3041 0.387
70 Sector Shape 9.7 1.4 1.2 0.8 0.3 2.1 36.0 3991 0.268
95 stranded 11.4 1.6 1.2 0.8 0.3 2.3 41.5 5307 0.193
120 12.9 1.6 1.4 0.8 0.3 2.4 45.0 6286 0.153
150 14.2 1.8 1.4 0.8 0.3 2.6 49.0 7567 0.124
185 16.0 2.0 1.6 0.8 0.3 2.7 54.5 9306 0.0991
240 18.2 2.2 1.6 0.8 0.3 3.0 60.5 12117 0.0754
300 20.6 2.4 1.6 0.8 0.3 3.2 66.5 14861 0.0601

Page - 43
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. thickness of of of Resistance
section of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.0 0.8 0.3 1.8 16.5 538 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 0.3 1.8 17.0 580 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 0.3 1.8 17.5 635 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 0.3 1.8 18.0 654 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 0.3 1.8 20.0 832 4.61
4 7 / 0.85 2.55 1.0 1.0 0.8 0.3 1.8 21.0 860 4.61
6 7 / 1.04 3.12 1.0 1.0 0.8 0.3 1.8 22.0 1022 3.08
10 7 / 1.35 4.05 1.0 1.0 0.8 0.3 1.8 25.0 1338 1.83
16 7 / 1.70 5.10 1.0 1.0 0.8 0.3 1.8 27.5 1745 1.15
25 7 / 2.13 6.39 1.2 1.0 0.8 0.3 1.8 32.0 2413 0.727
35 7 / 2.52 7.56 1.2 1.0 0.8 0.3 1.9 35.5 3066 0.524
50 19 / 1.83 9.15 1.4 1.2 0.8 0.3 2.1 41.5 4013 0.387

Page - 44
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, ALUMINIUM TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DATA/PVC (acc. to IEC 60502-1)

1
Constructions :
2 1 Conductor (Annealed Copper)
2 Insulation (PVC Compound)
3
3 Inner Covering (PVC Compound)
4
4 Double Aluminium Tape armour
5 Outer sheath (PVC Compound)
5

600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (acc. to IEC 60502-1)

Constructions :
1 1 Conductor (Annealed Copper)
2 Insulation (PVC Compound)
2
3 Filler (Polyprophylene yarn,or extruded filler
3
up to request)
4
4 Binding tape (Manufacturer's option)
5
5 Inner Covering (PVC Compound)
6
6 Double Galvanized Steel Tape armour
7 Outer sheath (PVC Compound)

Note : Special application upon request


* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed

Page - 45
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, ALUMINIUM TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DATA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Inner covering : PVC Compound Maximum 70°C
Armour : Double Aluminium tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black
Sheath - Black

SINGLE CORE
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- Diameter of of of Inner thickness of of of of Resistance
section of wire Conductor Insulation covering Aluminium Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
50 19 / 1.83 9.15 1.4 1.0 0.5 1.8 19.5 817 0.387
70 19 / 2.17 10.85 1.4 1.0 0.5 1.8 21.0 1045 0.268
95 19 / 2.52 12.60 1.6 1.0 0.5 1.8 23.5 1344 0.193
120 37 / 2.03 14.21 1.6 1.0 0.5 1.8 25.0 1607 0.153
150 37 / 2.27 15.89 1.8 1.0 0.5 1.8 27.0 1949 0.124
185 37 / 2.52 17.64 2.0 1.0 0.5 1.8 29.5 2339 0.0991
240 61 / 2.26 20.34 2.2 1.0 0.5 1.9 32.5 2987 0.0754
300 61 / 2.52 22.68 2.4 1.0 0.5 1.9 35.0 3628 0.0601
400 61 / 2.86 25.74 2.6 1.2 0.5 2.1 39.5 4638 0.0470
500 61 / 3.20 28.80 2.8 1.2 0.5 2.2 43.5 5694 0.0366

Page - 46
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Black
Sheath - Black

TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. of of of Resistance
section of wire Conductor Insulation covering Steel tape Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.0 0.2 1.8 13.0 237 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.2 1.8 13.0 250 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.2 1.8 13.5 276 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.2 1.8 14.0 290 7.41
4 1 / 2.26 2.26 1.0 1.0 0.2 1.8 15.5 357 4.61
4 7 / 0.85 2.55 1.0 1.0 0.2 1.8 16.0 374 4.61
6 7 / 1.04 3.12 1.0 1.0 0.2 1.8 17.0 440 3.08
10 7 / 1.35 4.05 1.0 1.0 0.2 1.8 19.0 574 1.83
16 7 / 1.70 5.10 1.0 1.0 0.2 1.8 21.0 742 1.15
25 7 / 2.13 6.39 1.2 1.0 0.2 1.8 24.5 1026 0.727
35 7 / 2.52 7.56 1.2 1.0 0.2 1.8 27.0 1290 0.524
50 19 / 1.83 9.15 1.4 1.0 0.2 1.8 31.0 1712 0.387
70 19 / 2.17 10.85 1.4 1.0 0.2 1.9 34.0 2262 0.268
95 19 / 2.52 12.60 1.6 1.2 0.2 2.1 39.0 2896 0.193
120 37 / 2.03 14.21 1.6 1.2 0.5 2.2 43.5 3921 0.153
150 37 / 2.27 15.89 1.8 1.2 0.5 2.3 48.0 4722 0.124
185 37 / 2.52 17.64 2.0 1.4 0.5 2.4 52.5 5675 0.0991
240 61 / 2.26 20.34 2.2 1.4 0.5 2.6 58.5 7166 0.0754
300 61 / 2.52 22.68 2.4 1.6 0.5 2.8 64.5 8710 0.0601

Page - 47
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Yellow, Blue
Sheath - Black

THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. of of of Resistance
section of wire Conductor Insulation covering Steel tape Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.0 0.2 1.8 13.5 270 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.2 1.8 13.5 281 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.2 1.8 14.0 318 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.2 1.8 14.5 335 7.41
4 1 / 2.26 2.26 1.0 1.0 0.2 1.8 16.0 420 4.61
4 7 / 0.85 2.55 1.0 1.0 0.2 1.8 16.5 441 4.61
6 7 / 1.04 3.12 1.0 1.0 0.2 1.8 18.0 530 3.08
10 7 / 1.35 4.05 1.0 1.0 0.2 1.8 20.0 707 1.83
16 7 / 1.70 5.10 1.0 1.0 0.2 1.8 22.0 935 1.15
25 7 / 2.13 6.39 1.2 1.0 0.2 1.8 26.0 1328 0.727
35 7 / 2.52 7.56 1.2 1.0 0.2 1.8 28.5 1685 0.524
50 6.8 1.4 1.0 0.2 1.9 27.0 2002 0.387
70 8.2 1.4 1.2 0.2 2.0 30.5 2724 0.268
95 Three- 9.7 1.6 1.2 0.5 2.2 36.5 4062 0.193
120 Segmental 10.9 1.6 1.2 0.5 2.3 39.5 4765 0.153
150 Stranded 11.9 1.8 1.4 0.5 2.4 42.5 5745 0.124
185 13.6 2.0 1.4 0.5 2.6 47.5 7055 0.0991
240 15.8 2.2 1.6 0.5 2.8 53.5 9254 0.0754
300 17.5 2.4 1.6 0.5 2.9 58.0 11299 0.0601

Page - 48
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Yellow, Blue, Black
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. of of of Resistance
section of wire Conductor Insulation covering Steel tape Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.0 0.2 1.8 14.0 307 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.2 1.8 14.5 322 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.2 1.8 15.0 372 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.2 1.8 15.5 390 7.41
4 1 / 2.26 2.26 1.0 1.0 0.2 1.8 17.5 499 4.61
4 7 / 0.85 2.55 1.0 1.0 0.2 1.8 18.0 524 4.61
6 7 / 1.04 3.12 1.0 1.0 0.2 1.8 19.0 638 3.08
10 7 / 1.35 4.05 1.0 1.0 0.2 1.8 21.5 860 1.83
16 7 / 1.70 5.10 1.0 1.0 0.2 1.8 24.0 1158 1.15
25 7 / 2.13 6.39 1.2 1.0 0.2 1.8 28.0 1650 0.727
35 7 / 2.52 7.56 1.2 1.0 0.2 1.8 31.0 2120 0.524
50 8.1 1.4 1.2 0.2 2.0 31.0 2592 0.387
70 9.7 1.4 1.2 0.5 2.1 36.0 3862 0.268
95 Four- 11.4 1.6 1.2 0.5 2.3 41.0 5171 0.193
120 Segmental 12.9 1.6 1.4 0.5 2.4 44.5 6122 0.153
150 Stranded 14.2 1.8 1.4 0.5 2.6 49.0 7405 0.124
185 16.0 2.0 1.6 0.5 2.7 54.0 9113 0.0991
240 18.2 2.2 1.6 0.5 3.0 60.0 11899 0.0754
300 20.6 2.4 1.6 0.5 3.2 66.5 14624 0.0601

Page - 49
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. of of of Resistance
section of wire Conductor Insulation covering Steel tape Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.0 0.2 1.8 15.0 350 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.2 1.8 15.5 368 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.2 1.8 16.0 424 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.2 1.8 16.5 446 7.41
4 1 / 2.26 2.26 1.0 1.0 0.2 1.8 18.5 578 4.61
4 7 / 0.85 2.55 1.0 1.0 0.2 1.8 19.5 609 4.61
6 7 / 1.04 3.12 1.0 1.0 0.2 1.8 20.5 748 3.08
10 7 / 1.35 4.05 1.0 1.0 0.2 1.8 23.5 1022 1.83
16 7 / 1.70 5.10 1.0 1.0 0.2 1.8 26.0 1386 1.15
25 7 / 2.13 6.39 1.2 1.0 0.2 1.8 30.5 1991 0.727
35 7 / 2.52 7.56 1.2 1.0 0.2 1.9 34.0 2577 0.524
50 19 / 1.83 9.15 1.4 1.2 0.2 2.1 40.0 3400 0.387

Page - 50
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES


XLPE/PVC (IEC 60502-1)

Constructions : Note : Special application upon request


1 Conductor (Annealed Copper) * Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
2 Insulation (XLPE Compound)
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
3 Filler (Polyprophylene yarn,or extruded filler * Anti termite performance.
up to request) * Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed
4 Binding tape (Manufacturer's option)
5 Outer sheath (PVC Compound)

Page - 51
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES


XLPE/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Sheath : PVC Compound type ST2 Maximum 90°C
Colour Ident. : Insulation - Black
Sheath - Black

SINGLE CORE
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.7 1.4 6.0 49 12.1


1.5 7 / 0.52 1.56 0.7 1.4 6.5 51 12.1
2.5 1 / 1.78 1.78 0.7 1.4 6.5 62 7.41
2.5 7 / 0.67 2.01 0.7 1.4 7.0 64 7.41
4 1 / 2.26 2.26 0.7 1.4 7.0 80 4.61
4 7 / 0.85 2.55 0.7 1.4 7.5 83 4.61
6 7 / 1.04 3.12 0.7 1.4 8.0 106 3.08
10 7 / 1.35 4.05 0.7 1.4 9.0 152 1.83
16 4.7 0.7 1.4 9.5 206 1.15
25 5.9 0.9 1.4 11.0 302 0.727
35 7.1 0.9 1.4 12.0 399 0.524
50 8.1 1.0 1.4 13.5 518 0.387
70 Compact 9.7 1.1 1.4 15.0 721 0.268
95 round 11.6 1.1 1.5 17.5 979 0.193
120 stranded 12.9 1.2 1.5 19.0 1212 0.153
150 14.3 1.4 1.6 21.0 1502 0.124
185 16.0 1.6 1.6 23.0 1854 0.0991
240 18.3 1.7 1.7 26.0 2406 0.0754
300 20.7 1.8 1.8 28.5 2996 0.0601
400 23.4 2.0 1.9 32.0 3799 0.0470
500 26.5 2.2 2.0 35.5 4842 0.0366
630 30.3 2.4 2.2 40.0 6233 0.0283
800 34.3 2.6 2.3 45.0 7933 0.0221
1000 127 / 3.2 41.6 2.8 2.4 53.0 10109 0.0176

Page - 52
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES


XLPE/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Black
Sheath - Black

TWO CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.7 1.8 10.0 116 12.1


1.5 7 / 0.52 1.56 0.7 1.8 10.5 121 12.1
2.5 1 / 1.78 1.78 0.7 1.8 11.0 145 7.41
2.5 7 / 0.67 2.01 0.7 1.8 11.5 150 7.41
4 1 / 2.26 2.26 0.7 1.8 12.0 188 4.61
4 7 / 0.85 2.55 0.7 1.8 12.5 196 4.61
6 7 / 1.04 3.12 0.7 1.8 13.5 246 3.08
10 7 / 1.35 4.05 0.7 1.8 15.5 352 1.83
16 4.7 0.7 1.8 17.0 468 1.15
25 5.9 0.9 1.8 20.0 684 0.727
35 Compact 7.1 0.9 1.8 22.5 899 0.524
50 round 8.1 1.0 1.8 25.0 1162 0.387
70 stranded 9.7 1.1 1.8 28.5 1607 0.268
95 11.6 1.1 2.0 32.5 2185 0.193
120 12.9 1.2 2.1 36.0 2709 0.153
150 14.3 1.4 2.2 39.5 3350 0.124
185 16.0 1.6 2.3 44.5 4152 0.0991
240 18.3 1.7 2.5 50.0 5382 0.0754
300 20.7 1.8 2.7 55.5 6711 0.0601
400 23.4 2.0 2.9 62.0 8494 0.0470

Page - 53
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES


XLPE/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow, Blue
Sheath - Black

THREE CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.7 1.8 10.5 139 12.1


1.5 7 / 0.52 1.56 0.7 1.8 11.0 145 12.1
2.5 1 / 1.78 1.78 0.7 1.8 11.5 175 7.41
2.5 7 / 0.67 2.01 0.7 1.8 12.0 183 7.41
4 1 / 2.26 2.26 0.7 1.8 12.5 234 4.61
4 7 / 0.85 2.55 0.7 1.8 13.5 243 4.61
6 7 / 1.04 3.12 0.7 1.8 14.5 314 3.08
10 7 / 1.35 4.05 0.7 1.8 16.5 458 1.83
16 4.7 0.7 1.8 18.0 626 1.15
25 5.9 0.9 1.8 21.0 928 0.727
35 Compact 7.1 0.9 1.8 24.0 1232 0.524
50 round 8.1 1.0 1.8 26.5 1605 0.387
70 stranded 9.7 1.1 1.9 30.5 2251 0.268
95 11.6 1.1 2.0 35.0 3051 0.193
120 12.9 1.2 2.1 38.0 3799 0.153
150 14.3 1.4 2.3 42.5 4720 0.124
185 16.0 1.6 2.4 47.5 5862 0.0991
240 18.3 1.7 2.6 53.5 7618 0.0754
300 20.7 1.8 2.8 59.5 9494 0.0601
400 23.4 2.0 3.1 67.0 12111 0.0470

Page - 54
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES


XLPE/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow, Blue, Black
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.7 1.8 11.5 162 12.1


1.5 7 / 0.52 1.56 0.7 1.8 12.0 170 12.1
2.5 1 / 1.78 1.78 0.7 1.8 12.5 215 7.41
2.5 7 / 0.67 2.01 0.7 1.8 13.0 224 7.41
4 1 / 2.26 2.26 0.7 1.8 13.5 286 4.61
4 7 / 0.85 2.55 0.7 1.8 14.5 298 4.61
6 7 / 1.04 3.12 0.7 1.8 15.5 391 3.08
10 7 / 1.35 4.05 0.7 1.8 18.0 576 1.83
16 4.7 0.7 1.8 19.5 796 1.15
25 5.9 0.9 1.8 23.5 1190 0.727
35 Compact 7.1 0.9 1.8 26.0 1584 0.524
50 round 8.1 1.0 1.9 29.5 2091 0.387
70 stranded 9.7 1.1 2.0 34.0 2940 0.268
95 11.6 1.1 2.1 38.5 3997 0.193
120 12.9 1.2 2.3 42.5 4995 0.153
150 14.3 1.4 2.4 47.0 6184 0.124
185 16.0 1.6 2.6 53.0 7700 0.0991
240 18.3 1.7 2.8 59.5 9999 0.0754
300 20.7 1.8 3.0 66.5 12495 0.0601

Page - 55
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES


XLPE/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.7 1.8 12.5 192 12.1


1.5 7 / 0.52 1.56 0.7 1.8 13.0 200 12.1
2.5 1 / 1.78 1.78 0.7 1.8 13.5 251 7.41
2.5 7 / 0.67 2.01 0.7 1.8 14.0 261 7.41
4 1 / 2.26 2.26 0.7 1.8 15.0 344 4.61
4 7 / 0.85 2.55 0.7 1.8 15.5 358 4.61
6 7 / 1.04 3.12 0.7 1.8 17.0 469 3.08
10 7 / 1.35 4.05 0.7 1.8 19.5 696 1.83
16 Compact 4.7 0.7 1.8 21.0 974 1.15
25 round 5.9 0.9 1.8 25.5 1234 0.727
35 stranded 7.1 0.9 1.8 29.0 1950 0.524
50 8.1 1.0 2.0 32.5 2590 0.387

Page - 56
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES


XLPE/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 clas 1) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler (if necessary) : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 1.5 mm² (Solid conductor)


Conductor Nominal Nominal Overall Maximum
No Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
of Cross-section Diameter of of of of of Resistance
core area of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
6 1.5 1 / 1.38 1.38 0.7 1.8 13.0 214 12.1
7 1.5 1 / 1.38 1.38 0.7 1.8 13.0 229 12.1
8 1.5 1 / 1.38 1.38 0.7 1.8 14.0 256 12.1
9 1.5 1 / 1.38 1.38 0.7 1.8 15.0 286 12.1
10 1.5 1 / 1.38 1.38 0.7 1.8 16.0 316 12.1
12 1.5 1 / 1.38 1.38 0.7 1.8 16.5 358 12.1
14 1.5 1 / 1.38 1.38 0.7 1.8 17.5 400 12.1
15 1.5 1 / 1.38 1.38 0.7 1.8 18.0 426 12.1
16 1.5 1 / 1.38 1.38 0.7 1.8 18.5 448 12.1
18 1.5 1 / 1.38 1.38 0.7 1.8 19.0 488 12.1
19 1.5 1 / 1.38 1.38 0.7 1.8 19.0 502 12.1
20 1.5 1 / 1.38 1.38 0.7 1.8 19.5 532 12.1
24 1.5 1 / 1.38 1.38 0.7 1.8 22.0 628 12.1
30 1.5 1 / 1.38 1.38 0.7 1.8 23.5 748 12.1
32 1.5 1 / 1.38 1.38 0.7 1.8 24.0 793 12.1
37 1.5 1 / 1.38 1.38 0.7 1.8 25.0 888 12.1
40 1.5 1 / 1.38 1.38 0.7 1.8 26.0 953 12.1
50 1.5 1 / 1.38 1.38 0.7 1.9 29.0 1178 12.1
52 1.5 1 / 1.38 1.38 0.7 1.9 29.5 1221 12.1
60 1.5 1 / 1.38 1.38 0.7 1.9 31.5 1384 12.1
61 1.5 1 / 1.38 1.38 0.7 1.9 31.5 1398 12.1

Page - 57
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES


XLPE/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 clas 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler (if necessary) : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 1.5 mm² (Stranded conductor)


Conductor Nominal Nominal Overall Maximum
No Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
of Cross-section Diameter of of of of of Resistance
core area of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
6 1.5 7 / 0.52 1.56 0.7 1.8 14.0 224 12.1
7 1.5 7 / 0.52 1.56 0.7 1.8 14.0 239 12.1
8 1.5 7 / 0.52 1.56 0.7 1.8 15.0 269 12.1
9 1.5 7 / 0.52 1.56 0.7 1.8 16.0 300 12.1
10 1.5 7 / 0.52 1.56 0.7 1.8 17.0 331 12.1
12 1.5 7 / 0.52 1.56 0.7 1.8 17.5 374 12.1
14 1.5 7 / 0.52 1.56 0.7 1.8 18.5 418 12.1
15 1.5 7 / 0.52 1.56 0.7 1.8 19.0 447 12.1
16 1.5 7 / 0.52 1.56 0.7 1.8 19.0 468 12.1
18 1.5 7 / 0.52 1.56 0.7 1.8 20.0 511 12.1
19 1.5 7 / 0.52 1.56 0.7 1.8 20.0 526 12.1
20 1.5 7 / 0.52 1.56 0.7 1.8 21.0 557 12.1
24 1.5 7 / 0.52 1.56 0.7 1.8 23.5 657 12.1
30 1.5 7 / 0.52 1.56 0.7 1.8 24.5 786 12.1
32 1.5 7 / 0.52 1.56 0.7 1.8 25.0 830 12.1
37 1.5 7 / 0.52 1.56 0.7 1.8 26.5 928 12.1
40 1.5 7 / 0.52 1.56 0.7 1.8 27.5 997 12.1
50 1.5 7 / 0.52 1.56 0.7 1.9 30.5 1232 12.1
52 1.5 7 / 0.52 1.56 0.7 1.9 31.5 1276 12.1
60 1.5 7 / 0.52 1.56 0.7 1.9 33.0 1447 12.1
61 1.5 7 / 0.52 1.56 0.7 1.9 33.0 1462 12.1

Page - 58
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES


XLPE/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler (if necessary) : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 2.5 mm² (Solid conductor)


Conductor Nominal Nominal Overall Maximum
No Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
of Cross-section Diameter of of of of of Resistance
core area of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
6 2.5 1 / 1.78 1.78 0.7 1.8 14.5 284 7.41
7 2.5 1 / 1.78 1.78 0.7 1.8 14.5 307 7.41
8 2.5 1 / 1.78 1.78 0.7 1.8 15.5 348 7.41
9 2.5 1 / 1.78 1.78 0.7 1.8 16.5 389 7.41
10 2.5 1 / 1.78 1.78 0.7 1.8 18.0 431 7.41
12 2.5 1 / 1.78 1.78 0.7 1.8 18.5 490 7.41
14 2.5 1 / 1.78 1.78 0.7 1.8 19.0 558 7.41
15 2.5 1 / 1.78 1.78 0.7 1.8 19.5 590 7.41
16 2.5 1 / 1.78 1.78 0.7 1.8 20.0 622 7.41
18 2.5 1 / 1.78 1.78 0.7 1.8 21.0 684 7.41
19 2.5 1 / 1.78 1.78 0.7 1.8 21.0 707 7.41
20 2.5 1 / 1.78 1.78 0.7 1.8 22.0 754 7.41
24 2.5 1 / 1.78 1.78 0.7 1.8 24.5 887 7.41
30 2.5 1 / 1.78 1.78 0.7 1.8 26.0 1070 7.41
32 2.5 1 / 1.78 1.78 0.7 1.8 26.5 1131 7.41
37 2.5 1 / 1.78 1.78 0.7 1.8 28.0 1276 7.41
40 2.5 1 / 1.78 1.78 0.7 1.9 29.0 1386 7.41
50 2.5 1 / 1.78 1.78 0.7 2.0 32.5 1714 7.41
52 2.5 1 / 1.78 1.78 0.7 2.0 33.0 1782 7.41
60 2.5 1 / 1.78 1.78 0.7 2.0 35.0 2024 7.41
61 2.5 1 / 1.78 1.78 0.7 2.0 35.0 2046 7.41

Page - 59
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES


XLPE/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler (if necessary) : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 2.5 mm² (Stranded conductor)


Conductor Nominal Nominal Overall Maximum
No Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
of Cross-section Diameter of of of of of Resistance
core area of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
6 2.5 7 / 0.67 2.01 0.7 1.8 15.0 296 7.41
7 2.5 7 / 0.67 2.01 0.7 1.8 15.0 320 7.41
8 2.5 7 / 0.67 2.01 0.7 1.8 16.0 362 7.41
9 2.5 7 / 0.67 2.01 0.7 1.8 17.0 405 7.41
10 2.5 7 / 0.67 2.01 0.7 1.8 18.5 449 7.41
12 2.5 7 / 0.67 2.01 0.7 1.8 19.0 510 7.41
14 2.5 7 / 0.67 2.01 0.7 1.8 20.0 580 7.41
15 2.5 7 / 0.67 2.01 0.7 1.8 20.5 614 7.41
16 2.5 7 / 0.67 2.01 0.7 1.8 21.0 647 7.41
18 2.5 7 / 0.67 2.01 0.7 1.8 22.0 712 7.41
19 2.5 7 / 0.67 2.01 0.7 1.8 22.0 736 7.41
20 2.5 7 / 0.67 2.01 0.7 1.8 23.0 784 7.41
24 2.5 7 / 0.67 2.01 0.7 1.8 26.0 923 7.41
30 2.5 7 / 0.67 2.01 0.7 1.8 27.5 1114 7.41
32 2.5 7 / 0.67 2.01 0.7 1.8 28.0 1177 7.41
37 2.5 7 / 0.67 2.01 0.7 1.8 29.5 1328 7.41
40 2.5 7 / 0.67 2.01 0.7 1.9 30.5 1443 7.41
50 2.5 7 / 0.67 2.01 0.7 2.0 34.0 1784 7.41
52 2.5 7 / 0.67 2.01 0.7 2.0 35.0 1854 7.41
60 2.5 7 / 0.67 2.01 0.7 2.0 37.0 2105 7.41
61 2.5 7 / 0.67 2.01 0.7 2.0 37.0 2129 7.41

Page - 60
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES


XLPE/PVC-S (IEC 60502-1)

1 Constructions :
1 Conductor (Annealed Copper)
2 2 Insulation (XLPE Compound)
3 Filler (Polyprophylene yarn,or extruded filler
up to request)
3
4 Binding tape (Manufacturer's option)
4
5 Copper Tape screen
5 6 Binding tape (Manufacturer's option)
7 Outer sheath (PVC Compound)
6

7 Note : Special application upon request


* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Copper wire screen.
* Polyethylene / Low smoke Halogen Free sheathed

Page - 61
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES


XLPE/PVC-S (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Black
Sheath - Black

TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of of Resistance
section area of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.7 0.1 1.8 10.0 125 12.1


1.5 7 / 0.52 1.56 0.7 0.1 1.8 10.5 131 12.1
2.5 1 / 1.78 1.78 0.7 0.1 1.8 11.0 155 7.41
2.5 7 / 0.67 2.01 0.7 0.1 1.8 11.5 162 7.41
4 1 / 2.26 2.26 0.7 0.1 1.8 12.0 200 4.61
4 7 / 0.85 2.55 0.7 0.1 1.8 12.5 209 4.61
6 1 / 2.77 2.77 0.7 0.1 1.8 13.0 250 3.08
6 7 / 1.04 3.12 0.7 0.1 1.8 13.5 261 3.08
10 7 / 1.35 4.05 0.7 0.1 1.8 15.5 369 1.83
16 4.7 0.7 0.1 1.8 16.5 489 1.15
25 5.9 0.9 0.1 1.8 20.0 712 0.727
35 Compact 7.1 0.9 0.1 1.8 22.5 934 0.524
50 round 8.1 1.0 0.1 1.8 24.5 1196 0.387
70 stranded 9.7 1.1 0.1 1.9 28.5 1648 0.268
95 11.6 1.1 0.1 2.0 32.5 2226 0.193
120 12.9 1.2 0.1 2.1 35.5 2753 0.153
150 14.3 1.4 0.1 2.2 39.5 3394 0.124
185 16.0 1.6 0.1 2.3 44.0 4205 0.0991
240 18.3 1.7 0.1 2.5 49.5 5425 0.0754
300 20.7 1.8 0.1 2.7 55.0 6752 0.0601
400 23.4 2.0 0.1 2.9 61.5 8543 0.0470

Page - 62
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES


XLPE/PVC-S (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow , Blue
Sheath - Black

THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of of Resistance
section area of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.7 0.1 1.8 10.5 149 12.1


1.5 7 / 0.52 1.56 0.7 0.1 1.8 11.0 155 12.1
2.5 1 / 1.78 1.78 0.7 0.1 1.8 11.5 186 7.41
2.5 7 / 0.67 2.01 0.7 0.1 1.8 12.0 195 7.41
4 1 / 2.26 2.26 0.7 0.1 1.8 12.5 246 4.61
4 7 / 0.85 2.55 0.7 0.1 1.8 13.0 257 4.61
6 1 / 2.77 2.77 0.7 0.1 1.8 13.5 318 3.08
6 7 / 1.04 3.12 0.7 0.1 1.8 14.0 330 3.08
10 7 / 1.35 4.05 0.7 0.1 1.8 16.5 478 1.83
16 4.7 0.7 0.1 1.8 17.5 650 1.15
25 5.9 0.9 0.1 1.8 21.0 959 0.727
35 Compact 7.1 0.9 0.1 1.8 23.5 1273 0.524
50 round 8.1 1.0 0.1 1.8 26.5 1642 0.387
70 stranded 9.7 1.1 0.1 1.9 30.0 2282 0.268
95 11.6 1.1 0.1 2.0 34.5 3106 0.193
120 12.9 1.2 0.1 2.2 38.0 3868 0.153
150 14.3 1.4 0.1 2.3 42.0 4775 0.124
185 16.0 1.6 0.1 2.4 47.0 5907 0.0991
240 18.3 1.7 0.1 2.6 53.0 7673 0.0754
300 20.7 1.8 0.1 2.8 59.0 9561 0.0601
400 23.4 2.0 0.1 3.1 66.0 12110 0.0470

Page - 63
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES


XLPE/PVC-S (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow , Blue , Black
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of of Resistance
section area of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.7 0.1 1.8 11.5 173 12.1


1.5 7 / 0.52 1.56 0.7 0.1 1.8 12.0 182 12.1
2.5 1 / 1.78 1.78 0.7 0.1 1.8 12.5 228 7.41
2.5 7 / 0.67 2.01 0.7 0.1 1.8 13.0 237 7.41
4 1 / 2.26 2.26 0.7 0.1 1.8 13.5 300 4.61
4 7 / 0.85 2.55 0.7 0.1 1.8 14.0 318 4.61
6 1 / 2.77 2.77 0.7 0.1 1.8 14.5 394 3.08
6 7 / 1.04 3.12 0.7 0.1 1.8 15.5 409 3.08
10 7 / 1.35 4.05 0.7 0.1 1.8 18.0 598 1.83
16 4.7 0.7 0.1 1.8 19.5 823 1.15
25 5.9 0.9 0.1 1.8 23.0 1227 0.727
35 Compact 7.1 0.9 0.1 1.8 26.0 1632 0.524
50 round 8.1 1.0 0.1 1.9 29.0 2120 0.387
70 stranded 9.7 1.1 0.1 2.0 33.5 2976 0.268
95 11.6 1.1 0.1 2.2 38.5 4073 0.193
120 12.9 1.2 0.1 2.3 42.5 5052 0.153
150 14.3 1.4 0.1 2.5 47.0 6243 0.124
185 16.0 1.6 0.1 2.6 52.5 7751 0.0991
240 18.3 1.7 0.1 2.8 59.0 10066 0.0754
300 20.7 1.8 0.1 3.0 65.5 12547 0.0601
400 23.4 2.0 0.1 3.3 73.5 15898 0.0470

Page - 64
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES


XLPE/PVC-S (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of of Resistance
section area of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.7 0.1 1.8 12.0 204 12.1


1.5 7 / 0.52 1.56 0.7 0.1 1.8 12.5 214 12.1
2.5 1 / 1.78 1.78 0.7 0.1 1.8 13.5 265 7.41
2.5 7 / 0.67 2.01 0.7 0.1 1.8 14.0 276 7.41
4 1 / 2.26 2.26 0.7 0.1 1.8 14.5 360 4.61
4 7 / 0.85 2.55 0.7 0.1 1.8 15.5 376 4.61
6 1 / 2.77 2.77 0.7 0.1 1.8 16.0 471 3.08
6 7 / 1.04 3.12 0.7 0.1 1.8 17.0 488 3.08
10 7 / 1.35 4.05 0.7 0.1 1.8 19.5 720 1.83
16 Compact 4.7 0.7 0.1 1.8 21.0 1005 1.15
25 round 5.9 0.9 0.1 1.8 25.5 1491 0.727
35 stranded 7.1 0.9 0.1 1.9 28.5 2005 0.524
50 8.1 1.0 0.1 2.0 32.0 2620 0.387

Page - 65
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, ALUMINIUM WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/AWA/PVC (acc. to IEC 60502-1)

1
Constructions :
2
1 Conductor (Annealed Copper)
3 2 Insulation (XLPE Compound)
4 3 Inner Covering (PVC Compound)

5 4 Round Aluminium Wire armour


5 Binding tape (Manufacturer's option)
6 6 Outer sheath (PVC Compound)

600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/SWA/PVC (acc. to IEC 60502-1)

Constructions :
1
1 Conductor (Annealed Copper)
2 2 Insulation (XLPE Compound)
3 3 Filler (Polyprophylene yarn,or extruded filler
4 up to request)
5 4 Binding tape (Manufacturer's option)
6 5 Inner Covering (PVC Compound)
6 Galvanized Round Steel Wire armour
7
7 Binding tape (Manufacturer's option)
8 Outer sheath (PVC Compound)
8

Note : Special application upon request


* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed

Page - 66
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, ALUMINIUM WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/AWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Inner covering : PVC Compound Maximum 90°C
Armour : Aluminium Wire
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black
Sheath - Black

SINGLE CORE
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- Diameter of of of Inner diameter of of of of Resistance
section of wire Conductor Insulation covering Aluminium Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) wire (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km

16 4.7 0.7 1.0 0.8 1.8 13.5 325 1.15

25 5.9 0.9 1.0 0.8 1.8 15.5 435 0.727

35 7.1 0.9 1.0 0.8 1.8 16.5 545 0.524

50 8.1 1.0 1.0 1.25 1.8 18.5 715 0.387

70 9.7 1.1 1.0 1.25 1.8 20.0 940 0.268

95 11.6 1.1 1.0 1.25 1.8 22.0 1215 0.193

120 12.9 1.2 1.0 1.6 1.8 24.5 1565 0.153

150 Compact 14.3 1.4 1.0 1.6 1.8 26.5 1865 0.124

185 round 16.0 1.6 1.0 1.6 1.8 28.5 2270 0.0991

240 stranded 18.3 1.7 1.0 1.6 1.9 31.0 2860 0.0754

300 20.7 1.8 1.0 1.6 1.9 34.0 3490 0.0601

400 23.4 2.0 1.2 2.0 2.1 38.5 4385 0.0470

500 26.5 2.2 1.2 2.0 2.2 42.0 5485 0.0366

630 30.3 2.4 1.2 2.0 2.3 46.5 6930 0.0283

800 34.3 2.6 1.4 2.5 2.5 52.5 8915 0.0221

1000 Round stranded 41.6 2.8 1.4 2.5 2.5 60.5 11315 0.0176

Page - 67
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/SWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Black
Sheath - Black

TWO CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- Diameter of of of Inner diameter of of of Resistance
section of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.7 1.0 0.8 1.8 13.5 314 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 1.8 14.0 325 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 1.8 14.5 355 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 1.8 15.0 372 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 1.8 15.5 422 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 1.8 16.0 437 4.61
6 1 / 2.77 2.77 0.7 1.0 0.8 1.8 16.5 485 3.08
6 7 / 1.04 3.12 0.7 1.0 0.8 1.8 17.0 511 3.08
10 7 / 1.35 4.05 0.7 1.0 1.25 1.8 20.0 757 1.83
16 4.7 0.7 1.0 1.25 1.8 21.0 907 1.15
25 5.9 0.9 1.0 1.6 1.8 25.0 1342 0.727
35 Compact 7.1 0.9 1.0 1.6 1.8 27.5 1630 0.524
50 round 8.1 1.0 1.0 1.6 1.8 30.0 1965 0.387
70 stranded 9.7 1.1 1.0 1.6 2.0 34.0 2549 0.268
95 11.6 1.1 1.2 2.0 2.1 39.0 3517 0.193
120 12.9 1.2 1.2 2.0 2.2 42.0 4159 0.153
150 14.3 1.4 1.2 2.0 2.3 46.0 4966 0.124
185 16.0 1.6 1.4 2.5 2.5 52.0 6435 0.0991
240 18.3 1.7 1.4 2.5 2.7 57.5 7894 0.0754
300 20.7 1.8 1.6 2.5 2.8 63.0 9543 0.0601

Page - 68
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/SWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow, Blue
Sheath - Black

THREE CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- Diameter of of of Inner diameter of of of Resistance
section of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.7 1.0 0.8 1.8 14.0 343 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 1.8 14.5 360 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 1.8 15.0 398 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 1.8 15.5 417 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 1.8 16.0 474 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 1.8 17.0 502 4.61
6 1 / 2.77 2.77 0.7 1.0 0.8 1.8 17.0 570 3.08
6 7 / 1.04 3.12 0.7 1.0 0.8 1.8 18.0 591 3.08
10 7 / 1.35 4.05 0.7 1.0 1.25 1.8 20.5 887 1.83
16 4.7 0.7 1.0 1.25 1.8 22.0 1087 1.15
25 5.9 0.9 1.0 1.6 1.8 26.5 1622 0.727
35 Compact 7.1 0.9 1.0 1.6 1.8 29.0 2015 0.524
50 round 8.1 1.0 1.0 1.6 1.9 31.5 2461 0.387
70 stranded 9.7 1.1 1.2 2.0 2.0 37.0 3522 0.268
95 11.6 1.1 1.2 2.0 2.2 41.5 4491 0.193
120 12.9 1.2 1.2 2.0 2.3 45.0 5381 0.153
150 14.3 1.4 1.4 2.5 2.5 50.0 6919 0.124
185 16.0 1.6 1.4 2.5 2.6 55.0 8285 0.0991
240 18.3 1.7 1.6 2.5 2.8 61.5 10398 0.0754
300 20.7 1.8 1.6 2.5 3.0 67.5 12550 0.0601

Page - 69
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/SWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow, Blue, Black
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- Diameter of of of Inner diameter of of of Resistance
section of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.7 1.0 0.8 1.8 15.0 384 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 1.8 15.5 398 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 1.8 16.0 455 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 1.8 16.5 471 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 1.8 17.0 550 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 1.8 18.0 575 4.61
6 7 / 2.77 2.77 0.7 1.0 1.25 1.8 19.0 755 3.08
6 7 / 1.04 3.12 0.7 1.0 1.25 1.8 19.5 792 3.08
10 7 / 1.35 4.05 0.7 1.0 1.25 1.8 22.0 1039 1.83
16 4.7 0.7 1.0 1.25 1.8 23.5 1292 1.15
25 5.9 0.9 1.0 1.6 1.8 28.5 1955 0.727
35 Compact 7.1 0.9 1.0 1.6 1.9 31.5 2440 0.524
50 round 8.1 1.0 1.0 1.6 2.0 34.5 3039 0.387
70 stranded 9.7 1.1 1.2 2.0 2.2 40.5 4345 0.268
95 11.6 1.1 1.2 2.0 2.3 45.0 5577 0.193
120 12.9 1.2 1.4 2.5 2.5 50.0 7191 0.153
150 14.3 1.4 1.4 2.5 2.6 55.0 8600 0.124
185 16.0 1.6 1.4 2.5 2.8 60.5 10388 0.0991
240 18.3 1.7 1.6 2.5 3.0 67.5 13059 0.0754
300 20.7 1.8 1.6 2.5 3.2 74.0 15807 0.0601

Page - 70
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/SWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- Diameter of of of Inner diameter of of of Resistance
section of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.7 1.0 0.8 1.8 16.0 427 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 1.8 16.5 447 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 1.8 17.0 510 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 1.8 17.5 531 7.41
4 1 / 2.26 2.26 0.7 1.0 1.25 1.8 19.0 727 4.61
4 7 / 0.85 2.55 0.7 1.0 1.25 1.8 19.5 763 4.61
6 1 / 2.77 2.77 0.7 1.0 1.25 1.8 20.5 905 3.08
6 7 / 1.04 3.12 0.7 1.0 1.25 1.8 21.0 908 3.08
10 7 / 1.35 4.05 0.7 1.0 1.25 1.8 24.0 1203 1.83
16 Compact 4.7 0.7 1.0 1.6 1.8 26.5 1666 1.15
25 round 5.9 0.9 1.0 1.6 1.8 30.5 2290 0.727
35 stranded 7.1 0.9 1.0 1.6 1.9 34.0 2878 0.524
50 8.1 1.0 1.2 2.0 2.1 39.0 3920 0.387

Page - 71
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (acc. to IEC 60502-1)

2
1 Conductor (Annealed Copper)
2 Insulation (XLPE Compound)
3
3 Filler (Polyprophylene yarn,or extruded filler
4 up to request)
4 Binding tape (Manufacturer's option)
5
5 Inner Covering (PVC Compound)
6 6 Galvanized Flat Steel Wire armour
7 Galvanized Steel Tape binding
7
8 Outer sheath (PVC Compound)

Note : Special application upon request


* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed

Page - 72
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Black
Sheath - Black

TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. thickness of of of Resistance
section of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.7 1.0 0.8 0.3 1.8 14.0 365 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 0.3 1.8 14.0 398 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 0.3 1.8 14.5 426 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 0.3 1.8 15.0 434 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 0.3 1.8 15.5 502 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 0.3 1.8 16.0 514 4.61
6 1 / 2.77 2.77 0.7 1.0 0.8 0.3 1.8 16.5 575 3.08
6 7 / 1.04 3.12 0.7 1.0 0.8 0.3 1.8 17.0 598 3.08
10 7 / 1.35 4.05 0.7 1.0 0.8 0.3 1.8 19.0 744 1.83
16 4.7 0.7 1.0 0.8 0.3 1.8 20.5 896 1.15
25 5.9 0.9 1.0 0.8 0.3 1.8 23.5 1187 0.727
35 Compact 7.1 0.9 1.0 0.8 0.3 1.8 26.0 1472 0.524
50 round 8.1 1.0 1.0 0.8 0.3 1.8 28.5 1804 0.387
70 stranded 9.7 1.1 1.0 0.8 0.3 1.9 32.0 2328 0.268
95 11.6 1.1 1.2 0.8 0.3 2.0 36.5 3031 0.193
120 12.9 1.2 1.2 0.8 0.3 2.1 39.5 3635 0.153
150 14.3 1.4 1.2 0.8 0.3 2.2 43.5 4381 0.124
185 16.0 1.6 1.4 0.8 0.3 2.4 48.5 5342 0.0991
240 18.3 1.7 1.4 0.8 0.3 2.6 54.0 6724 0.0754
300 20.7 1.8 1.6 0.8 0.3 2.7 60.0 8222 0.0601
400 23.4 2.0 1.6 0.8 0.3 3.0 66.5 10210 0.0470

Page - 73
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow, Blue
Sheath - Black

THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. thickness of of of Resistance
section of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.7 1.0 0.8 0.3 1.8 14.5 418 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 0.3 1.8 14.5 426 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 0.3 1.8 15.0 460 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 0.3 1.8 15.5 497 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 0.3 1.8 16.0 551 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 0.3 1.8 17.0 593 4.61
6 1 / 2.77 2.77 0.7 1.0 0.8 0.3 1.8 17.5 665 3.08
6 7 / 1.04 3.12 0.7 1.0 0.8 0.3 1.8 18.0 671 3.08
10 7 / 1.35 4.05 0.7 1.0 0.8 0.3 1.8 20.0 884 1.83
16 4.7 0.7 1.0 0.8 0.3 1.8 21.5 1087 1.15
25 5.9 0.9 1.0 0.8 0.3 1.8 25.0 1466 0.727
35 Compact 7.1 0.9 1.0 0.8 0.3 1.8 27.5 1841 0.524
50 round 8.1 1.0 1.0 0.8 0.3 1.8 30.0 2285 0.387
70 stranded 9.7 1.1 1.2 0.8 0.3 2.0 34.5 3070 0.268
95 11.6 1.1 1.2 0.8 0.3 2.1 39.0 3989 0.193
120 12.9 1.2 1.2 0.8 0.3 2.2 42.0 4816 0.153
150 14.3 1.4 1.4 0.8 0.3 2.3 46.5 5871 0.124
185 16.0 1.6 1.4 0.8 0.3 2.4 52.0 7162 0.0991
240 18.3 1.7 1.6 0.8 0.3 2.7 58.0 9123 0.0754
300 20.7 1.8 1.6 0.8 0.3 2.8 64.0 11130 0.0601

Page - 74
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow, Blue, Black
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. thickness of of of Resistance
section of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.7 1.0 0.8 0.3 1.8 15.0 446 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 0.3 1.8 15.5 483 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 0.3 1.8 16.0 532 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 0.3 1.8 16.5 544 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 0.3 1.8 17.0 637 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 0.3 1.8 18.0 659 4.61
6 1 / 2.77 2.77 0.7 1.0 0.8 0.3 1.8 18.5 645 3.08
6 7 / 1.04 3.12 0.7 1.0 0.8 0.3 1.8 19.0 783 3.08
10 7 / 1.35 4.05 0.7 1.0 0.8 0.3 1.8 21.5 1039 1.83
16 4.7 0.7 1.0 0.8 0.3 1.8 23.0 1295 1.15
25 5.9 0.9 1.0 0.8 0.3 1.8 27.0 1795 0.727
35 Compact 7.1 0.9 1.0 0.8 0.3 1.8 30.0 2263 0.524
50 round 8.1 1.0 1.0 0.8 0.3 1.9 32.5 2830 0.387
70 stranded 9.7 1.1 1.2 0.8 0.3 2.1 38.0 3838 0.268
95 11.6 1.1 1.2 0.8 0.3 2.2 42.5 5013 0.193
120 12.9 1.2 1.4 0.8 0.3 2.3 47.0 6144 0.153
150 14.3 1.4 1.4 0.8 0.3 2.5 51.5 7450 0.124
185 16.0 1.6 1.4 0.8 0.3 2.7 57.5 9123 0.0991
240 18.3 1.7 1.6 0.8 0.3 2.9 64.0 11666 0.0754
300 20.7 1.8 1.6 0.8 0.3 3.1 70.5 14268 0.0601

Page - 75
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : XLPE Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. thickness of of of Resistance
section of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.7 1.0 0.8 0.3 1.8 16.0 508 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 0.3 1.8 16.5 520 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 0.3 1.8 17.0 601 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 0.3 1.8 17.5 615 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 0.3 1.8 18.5 730 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 0.3 1.8 19.0 750 4.61
6 1 / 2.77 2.77 0.7 1.0 0.8 0.3 1.8 20.0 875 3.08
6 7 / 1.04 3.12 0.7 1.0 0.8 0.3 1.8 20.5 897 3.08
10 7 / 1.35 4.05 0.7 1.0 0.8 0.3 1.8 23.0 1196 1.83
16 Compact 4.7 0.7 1.0 0.8 0.3 1.8 25.0 1512 1.15
25 round 5.9 0.9 1.0 0.8 0.3 1.8 29.0 2100 0.727
35 stranded 7.1 0.9 1.0 0.8 0.3 1.9 32.5 2700 0.524
50 8.1 1.0 1.2 0.8 0.3 2.0 36.0 3432 0.387

Page - 76
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, ALUMINIUM TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DATA/PVC (acc. to IEC 60502-1)

1
Constructions :
2 1 Conductor (Annealed Copper)
2 Insulation (XLPE Compound)
3
3 Inner Covering (PVC Compound)
4
4 Double Aluminium Tape armour
5 Outer sheath (PVC Compound)
5

600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (acc. to IEC 60502-1)

Constructions :
1 1 Conductor (Annealed Copper)
2 Insulation (XLPE Compound)
2
3 Filler (Polyprophylene yarn,or extruded filler
3
up to request)
4
4 Binding tape (Manufacturer's option)
5
5 Inner Covering (PVC Compound)
6
6 Double Galvanized Steel Tape armour
7 Outer sheath (PVC Compound)

7
Note : Special application upon request
* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed

Page - 77
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, ALUMINIUM TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DATA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Inner covering : PVC Compound Maximum 90°C
Armour : Double Aluminium tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black
Sheath - Black

SINGLE CORE
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of of of of Resistance
section of wire Conductor Insulation covering Aluminium Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km

16 4.7 0.7 1.0 0.5 1.8 13.5 335 1.15


25 5.9 0.9 1.0 0.5 1.8 15.0 455 0.727
35 7.1 0.9 1.0 0.5 1.8 16.5 570 0.524
50 Compact 8.1 1.0 1.0 0.5 1.8 17.5 705 0.387
70 round 9.7 1.1 1.0 0.5 1.8 19.5 930 0.268
95 stranded 11.6 1.1 1.0 0.5 1.8 21.5 1210 0.193
120 12.9 1.2 1.0 0.5 1.8 23.0 1470 0.153
150 14.3 1.4 1.0 0.5 1.8 24.5 1760 0.124
185 16.0 1.6 1.0 0.5 1.8 27.0 2155 0.0991
240 18.3 1.7 1.0 0.5 1.8 29.5 2735 0.0754
300 20.7 1.8 1.0 0.5 1.9 32.0 3365 0.0601
400 23.4 2.0 1.2 0.5 2.0 35.5 4240 0.0470
500 26.5 2.2 1.2 0.5 2.1 39.5 5350 0.0366
630 30.3 2.4 1.2 0.5 2.3 44.0 6670 0.0283

Page - 78
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Black
Sheath - Black

TWO CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- Diameter of of of Inner thickness of of of Resistance
section of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.7 1.0 0.2 1.8 12.5 220 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.2 1.8 13.0 230 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.2 1.8 13.0 258 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.2 1.8 13.5 268 7.41
4 1 / 2.26 2.26 0.7 1.0 0.2 1.8 14.0 312 4.61
4 7 / 0.85 2.55 0.7 1.0 0.2 1.8 15.0 326 4.61
6 1 / 2.77 2.77 0.7 1.0 0.2 1.8 15.0 372 3.08
6 7 / 1.04 3.12 0.7 1.0 0.2 1.8 16.0 387 3.08
10 7 / 1.35 4.05 0.7 1.0 0.2 1.8 18.0 514 1.83
16 4.7 0.7 1.0 0.2 1.8 19.0 643 1.15
25 5.9 0.9 1.0 0.2 1.8 23.0 893 0.727
35 Compact 7.1 0.9 1.0 0.2 1.8 24.5 1134 0.524
50 round 8.1 1.0 1.0 0.2 1.8 27.0 1422 0.387
70 stranded 9.7 1.1 1.0 0.2 1.9 30.5 1905 0.268
95 11.6 1.1 1.2 0.2 2.0 35.0 2544 0.193
120 12.9 1.2 1.2 0.5 2.1 39.5 3505 0.153
150 14.3 1.4 1.4 0.5 2.3 43.5 4245 0.124
185 15.9 1.6 1.4 0.5 2.4 48.5 5180 0.0991
240 18.3 1.7 1.6 0.5 2.6 54.0 6530 0.0754
300 20.7 1.8 1.6 0.5 2.7 59.5 8004 0.0601

Page - 79
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow, Blue
Sheath - Black

THREE CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- Diameter of of of Inner thickness of of of Resistance
section of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.58 1.58 0.7 1.0 0.2 1.8 13.0 249 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.2 1.8 13.5 259 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.2 1.8 13.5 294 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.2 1.8 14.0 307 7.41
4 1 / 2.26 2.26 0.7 1.0 0.2 1.8 15.0 263 4.61
4 7 / 0.85 2.55 0.7 1.0 0.2 1.8 15.5 381 4.61
6 1 / 2.77 2.77 0.7 1.0 0.2 1.8 16.0 445 3.08
6 7 / 1.04 3.12 0.7 1.0 0.2 1.8 16.5 463 3.08
10 7 / 1.35 4.05 0.7 1.0 0.2 1.8 18.5 630 1.83
16 4.7 0.7 1.0 0.2 1.8 20.0 812 1.15
25 5.9 0.9 1.0 0.2 1.8 23.5 1150 0.727
35 Compact 7.1 0.9 1.0 0.2 1.8 26.0 1481 0.524
50 round 8.1 1.0 1.0 0.2 1.8 28.5 1882 0.387
70 stranded 9.7 1.1 1.2 0.2 1.9 33.0 2588 0.268
95 11.6 1.1 1.2 0.2 2.1 37.5 3456 0.193
120 12.9 1.2 1.2 0.5 2.2 42.0 4669 0.153
150 14.3 1.4 1.4 0.5 2.4 46.5 5708 0.124
185 15.9 1.6 1.4 0.5 2.5 51.5 6965 0.0991
240 18.3 1.7 1.6 0.5 2.7 58.0 8905 0.0754
300 20.7 1.8 1.6 0.5 2.9 64.0 10919 0.0601

Page - 80
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow, Blue, Black
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- Diameter of of of Inner thickness of of of Resistance
section of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.7 1.0 0.2 1.8 13.5 280 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.2 1.8 14.0 293 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.2 1.8 14.5 343 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.2 1.8 15.0 357 7.41
4 1 / 2.26 2.26 0.7 1.0 0.2 1.8 16.0 426 4.61
4 7 / 0.85 2.55 0.7 1.0 0.2 1.8 16.5 446 4.61
6 1 / 2.77 2.77 0.7 1.0 0.2 1.8 17.0 531 3.08
6 7 / 1.04 3.12 0.7 1.0 0.2 1.8 17.5 552 3.08
10 7 / 1.35 4.05 0.7 1.0 0.2 1.8 20.0 764 1.83
16 4.7 0.7 1.0 0.2 1.8 21.5 999 1.15
25 5.9 0.9 1.0 0.2 1.8 25.5 1434 0.727
35 Compact 7.1 0.9 1.0 0.2 1.8 28.5 1859 0.524
50 round 8.1 1.0 1.0 0.2 1.9 31.5 2383 0.387
70 stranded 9.7 1.1 1.2 0.2 2.0 36.0 3311 0.268
95 11.6 1.1 1.2 0.5 2.2 42.5 4872 0.193
120 12.9 1.2 1.4 0.5 2.4 46.5 5983 0.153
150 14.3 1.4 1.4 0.5 2.5 51.0 7274 0.124
185 15.9 1.6 1.4 0.5 2.7 57.0 8922 0.0991
240 18.3 1.7 1.6 0.5 2.9 64.0 11427 0.0754
300 20.7 1.8 1.6 0.5 3.1 70.5 14015 0.0601

Page - 81
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- Diameter of of of Inner thickness of of of Resistance
section of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km

1.5 1 / 1.38 1.38 0.7 1.0 0.2 1.8 14.5 319 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.2 1.8 15.0 333 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.2 1.8 15.5 390 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.2 1.8 16.0 405 7.41
4 1 / 2.26 2.26 0.7 1.0 0.2 1.8 17.0 496 4.61
4 7 / 0.85 2.55 0.7 1.0 0.2 1.8 17.5 520 4.61
6 1 / 2.77 2.77 0.7 1.0 0.2 1.8 18.5 620 3.08
6 7 / 1.04 3.12 0.7 1.0 0.2 1.8 19.0 645 3.08
10 7 / 1.35 4.05 0.7 1.0 0.2 1.8 22.0 900 1.83
16 Compact 4.7 0.7 1.0 0.2 1.8 23.5 1196 1.15
25 round 5.9 0.9 1.0 0.2 1.8 27.5 1720 0.727
35 stranded 7.1 0.9 1.0 0.2 1.9 31.0 2252 0.524
50 8.1 1.0 1.2 0.2 2.0 35.0 2946 0.387

Page - 82
CURRENT CARRYING CAPACITY FOR SINGLE CORE XLPE INSULATED CABLE
Current Carrying Capacity DC Alternating Minimum Conductor
1) Reactance2) (50 Hz) Inductance2) (50 Hz)
Conductor In Air ( 30°C ) In Ground Conductor Current Insulation Short
Nominal Flat Trefoil Trefoil Resistance resistance Nominal Resistance circuit
Area at 20°C at 90°C / Trefoil Flat Trefoil Flat Capacitance at 20°C current /
core to core core to core 1 sec
50 Hz

mm² A A A Ω / km Ω / km Ω / km Ω / km mH / km mH / km µF / km M Ω. km A

1.5 re/rm 22 21 22 12.1 15.43 0.1459 0.1603 0.4646 0.5108 0.0520 3000 212
2.5 re/rm 30 29 29 7.41 9.45 0.1339 0.1484 0.4264 0.4726 0.0571 2500 353
4 re/rm 42 40 37 4.61 5.88 0.1244 0.1391 0.3962 0.4424 0.0621 2000 564
6 re/rm 55 53 46 3.08 3.93 0.1160 0.1305 0.3693 0.4155 0.0665 2000 846
10 re/rm 77 74 61 1.83 2.34 0.1072 0.1217 0.3416 0.3878 0.0721 1500 1410

16 cm 105 101 79 1.15 1.47 0.1028 0.1172 0.3264 0.3726 0.0751 1500 2256
25 cm 141 135 101 0.727 0.927 0.0984 0.1130 0.3124 0.3586 0.0752 1500 3525
35 cm 176 169 122 0.524 0.669 0.0932 0.1077 0.2967 0.3429 0.0789 1000 4935
50 cm 216 207 144 0.387 0.494 0.0911 0.1056 0.2890 0.3353 0.0796 1000 7050
70 cm 279 268 178 0.268 0.343 0.0875 0.1023 0.2778 0.3240 0.0815 900 9870

95 cm 342 328 211 0.193 0.247 0.0845 0.0991 0.2674 0.3136 0.0848 800 13395
120 cm 400 383 240 0.153 0.196 0.0827 0.0974 0.2629 0.3091 0.0853 800 16920
150 cm 464 444 271 0.124 0.159 0.0829 0.0975 0.2626 0.3088 0.0846 800 21150
185 cm 533 510 304 0.0991 0.1272 0.0830 0.0976 0.2612 0.3074 0.0833 900 26085
240 cm 634 607 351 0.0754 0.0972 0.0814 0.0960 0.2565 0.3028 0.0848 800 33840

300 cm 736 703 396 0.0601 0.0779 0.0799 0.0944 0.2526 0.2988 0.0860 800 42300
400 cm 868 823 464 0.0470 0.0614 0.0728 0.0874 0.2500 0.2962 0.0865 700 56400

Section 4 - General Information


500 cm 998 946 525 0.0366 0.0482 0.0777 0.0923 0.2471 0.2933 0.0871 700 70500
630 cm 1151 1088 596 0.0283 0.0376 0.0770 0.0916 0.2447 0.2909 0.0880 700 88830
800 cm 1328 1252 679 0.0221 0.0310 0.0763 0.0908 0.2425 0.2887 0.0883 700 112800
1000 rm 1511 1420 767 0.0176 0.0258 0.0743 0.0889 0.2363 0.2825 0.0902 600 141000
Page - 83

1)
Note : re : Round solid conductor IEC 60228 class 1 Underground : Thermal resistivity of soil : 2.5 K.m / W Note : Reference methode of installation to be used to obtain current carrying
rm : Circular stranded conductor IEC 60228 class 2 Depth of laying : 80 cm capacity for : in cable ducting, in cables conduit, cables direct in the -
cm : Circular stranded compacted conductor IEC 60228 class 2 Base temperature : 20°C ground with / without added protection against mechanical damage
2)
The Inductance calculated for non armour cable.
Section 4 - General Information
Page - 84

CURRENT CARRYING CAPACITY FOR MULTICORE XLPE INSULATED CABLE

Current Carrying Capacity DC Alternating Minimum Conductor


Reactance (50 Hz) Inductance (50 Hz)
Conductor In Air ( 30°C ) Underground, Direct burial Conductor Current Insulation Short
Nominal Resistance resistance Nominal Resistance circuit
Area 2 3/4* 2 3/4* at 20°C at 90°C / 2/3 4 2/3 4 Capacitance at 20°C current /
Core Core Core Core 50 Hz Core Core Core Core core to core core to core 1 sec
mm² A A A A Ω / km Ω / km Ω / km Ω / km mH / km mH / km µF / km M Ω. km A

1.5 re/rm 26 23 26 22 12.1 15.43 0.0999 0.1125 0.3181 0.2498 0.0520 3000 212
2.5 re/rm 36 32 34 29 7.41 9.45 0.0961 0.1086 0.3057 0.2325 0.0571 2500 353
4 re/rm 49 42 44 37 4.61 5.88 0.0899 0.1025 0.2860 0.2128 0.0621 2000 564
6 re/rm 63 54 56 46 3.08 3.93 0.0853 0.0980 0.2714 0.1982 0.0665 2000 846

10 re/rm 86 75 73 61 1.83 2.34 0.0802 0.0930 0.2552 0.1819 0.0721 1500 1410
16 cm 115 100 95 79 1.15 1.47 0.0781 0.0910 0.2485 0.1752 0.0751 1500 2256
25 cm 149 127 121 101 0.727 0.927 0.0779 0.0908 0.2480 0.1748 0.0752 1500 3525
35 cm 185 158 146 122 0.524 0.669 0.0753 0.0883 0.2397 0.1664 0.0789 1000 4935

50 cm 225 192 173 144 0.387 0.494 0.0748 0.0877 0.2379 0.1646 0.0796 1000 7050
70 cm 289 246 213 178 0.268 0.343 0.0734 0.0864 0.2335 0.1602 0.0815 900 9870
95 cm 352 298 252 211 0.193 0.247 0.0711 0.0842 0.2262 0.1530 0.0848 800 13395
120 cm 410 346 287 240 0.153 0.197 0.0708 0.0839 0.2254 0.1521 0.0853 800 16920

150 cm 473 399 324 271 0.124 0.160 0.0712 0.0843 0.2267 0.1534 0.0846 800 21150
185 cm 542 456 363 304 0.0991 0.1281 0.0720 0.0851 0.2292 0.1559 0.0833 900 26085
240 cm 641 538 419 351 0.0754 0.0984 0.0711 0.0842 0.2264 0.1531 0.0848 800 33840
300 cm 741 621 474 396 0.0601 0.0799 0.0704 0.0835 0.2240 0.1507 0.0860 800 42300
400 cm 892 745 555 464 0.0470 0.0633 0.0701 0.0832 0.2231 0.1498 0.0865 700 56400

Note : re : Round solid conductor IEC 60228 class 1 Underground : Thermal resistivity of soil : 2.5 K.m / W 4* : 3 Phasa + Netral / Ground
rm : Circular stranded conductor IEC 60228 class 2 Depth of laying : 80 cm
cm : Circular stranded compacted conductor IEC 60228 class 2 Base temperature : 20°C
CURRENT CARRYING CAPACITY FOR SINGLE CORE PVC INSULATED CABLE
Current Carrying Capacity DC Alternating Minimum Conductor
1)
Reactance2) (50 Hz) Inductance 2) (50 Hz)
Conductor In Air ( 30°C ) In Ground Conductor Current Insulation Short
Nominal Flat Trefoil Trefoil Resistance resistance Nominal Resistance circuit
Area at 20°C at 70°C / Trefoil Flat Trefoil Flat Capacitance at 20°C current /
core to core core to core 1 sec
50 Hz

mm² A A A Ω / km Ω / km Ω / km Ω / km mH / km mH / km µF / km M Ω. km A

1.5 re/rm 18 17 18 12.1 14.4777 0.1476 0.1735 0.4697 0.5159 0.1391 50 174
2.5 re/rm 25 24 24 7.41 8.8661 0.1359 0.1621 0.4327 0.4789 0.1531 50 290
4 re/rm 34 33 31 4.61 5.5159 0.1291 0.1555 0.4110 0.4572 0.1553 50 464
6 re/rm 45 43 39 3.08 3.6853 0.1209 0.1475 0.3848 0.4310 0.1671 50 696
10 re/rm 63 60 52 1.83 2.1897 0.1112 0.1381 0.3538 0.4000 0.1827 50 1160

16 rm 85 82 67 1.15 1.3761 0.1034 0.1307 0.3292 0.3754 0.1966 40 1856


25 rm 114 110 86 0.727 0.87 0.0988 0.1263 0.3145 0.3607 0.2001 40 2900
35 rm 143 137 103 0.524 0.6272 0.0941 0.1218 0.2995 0.3457 0.2100 40 4060
50 rm 174 167 122 0.387 0.4634 0.0909 0.1188 0.2895 0.3357 0.2127 30 5800
70 rm 225 216 151 0.268 0.3212 0.0869 0.1150 0.2767 0.3229 0.2223 30 8120

95 rm 275 264 179 0.193 0.2317 0.0864 0.1145 0.2749 0.3212 0.2205 30 11020
120 rm 321 308 203 0.153 0.1841 0.0838 0.1121 0.2669 0.3131 0.2270 30 13920
150 rm 372 356 230 0.124 0.1497 0.0833 0.1116 0.2651 0.3113 0.2274 20 17400
185 rm 427 409 258 0.0991 0.1202 0.0828 0.1111 0.2634 0.3096 0.2279 20 21460
240 rm 507 485 297 0.0754 0.0924 0.0814 0.1098 0.2592 0.3054 0.2308 20 27840

300 rm 587 561 336 0.0601 0.0746 0.0807 0.1091 0.2567 0.3029 0.2323 20 34800
400 rm 689 656 394 0.0470 0.0597 0.0799 0.1084 0.2543 0.3005 0.2387 20 46400
500 rm 789 749 445 0.0366 0.0482 0.0790 0.1075 0.2513 0.2975 0.2355 20 58000

Section 4 - General Information


630 rm 905 855 506 0.0283 0.0395 0.0773 0.1059 0.2459 0.2921 0.2416 20 73080
800 rm 1037 971 577 0.0221 0.0334 0.0756 0.1044 0.2406 0.2868 0.2476 20 92800
1000 rm 1167 1079 652 0.0176 0.0290 0.0750 0.1038 0.2386 0.2848 0.2500 20 116000

1)
Note : re : Round solid conductor IEC 60228 class 1 Underground : Thermal resistivity of soil : 2.5 K.m / W Note : Reference methode of installation to be used to obtain current carrying
rm
Page - 85

: Circular stranded conductor IEC 60228 class 2 Depth of laying : 80 cm capacity for : in cable ducting, in cables conduit, cables direct in the -
Base temperature : 20°C ground with / without added protection against mechanical damage
2)
The Inductance calculated for non armour cable.
Section 4 - General Information
Page - 86

CURRENT CARRYING CAPACITY FOR MULTICORE PVC INSULATED CABLE

Current Carrying Capacity DC Alternating Minimum Conductor


Reactance (50 Hz) Inductance (50 Hz)
Conductor In Air ( 30°C ) Underground, Direct burial Conductor Current Insulation Short
Nominal Resistance resistance Nominal Resistance circuit
Area 2 3/4* 2 3/4* at 20°C at 70°C / 2/3 4 2/3 4 Capacitance at 20°C current /
Core Core Core Core 50 Hz Core Core Core Core core to core core to core 1 sec
mm² A A A A Ω / km Ω / km Ω / km Ω / km mH / km mH / km µF / km M Ω. km A

1.5 re/rm 22 18.5 22 18 12.1 14.4777 0.1075 0.1199 0.3421 0.2688 0.1391 50 174
2.5 re/rm 30 25 29 24 7.41 8.8661 0.0994 0.1120 0.3165 0.2433 0.1531 50 290
4 re/rm 40 34 38 31 4.61 5.5159 0.0983 0.1109 0.3130 0.2398 0.1553 50 464
6 re/rm 51 43 47 39 3.08 3.6853 0.0928 0.1054 0.2954 0.2221 0.1671 50 696

10 re/rm 70 60 63 52 1.83 2.1897 0.0865 0.0993 0.2754 0.2021 0.1827 50 1160


16 rm 94 80 81 67 1.15 1.3761 0.0818 0.0946 0.2604 0.1871 0.1966 40 1856
25 rm 119 101 104 86 0.727 0.8701 0.0807 0.0936 0.2569 0.1836 0.2001 40 2900
35 rm 148 126 125 103 0.524 0.6273 0.0778 0.0907 0.2478 0.1745 0.2100 40 4060

50 rm/sm 180 153 148 122 0.387 0.4635 0.0822 0.0950 0.2617 0.1884 0.2127 30 5800
70 rm/sm 232 196 183 151 0.268 0.3213 0.0789 0.0917 0.2510 0.1777 0.2223 30 8120
95 rm/sm 282 238 216 179 0.193 0.2318 0.0791 0.0920 0.2518 0.1785 0.2205 30 11020
120 rm/sm 328 276 246 203 0.153 0.1842 0.0772 0.0901 0.2457 0.1724 0.2270 30 13920

150 rm/sm 379 319 278 230 0.124 0.150 0.0775 0.0904 0.2466 0.1733 0.2274 20 17400
185 rm/sm 434 364 312 258 0.0991 0.1204 0.0769 0.0898 0.2447 0.1714 0.2279 20 21460
240 rm/sm 514 430 361 297 0.0754 0.0926 0.0759 0.0889 0.2417 0.1684 0.2308 20 27840
300 rm/sm 593 497 408 336 0.0601 0.0749 0.0756 0.0886 0.2407 0.1674 0.2323 20 34800

Note : re : Round solid conductor IEC 60228 class 1 Underground : Thermal resistivity of soil : 2.5 K.m / W 4* : 3 Phasa + Netral / Ground
rm : Circular stranded conductor IEC 60228 class 2 Depth of laying : 80 cm
sm : Sector shape stranded conductor IEC 60228 class 2 Base temperature : 20°C
Rating factor relating to open air temperature
Air temperature°C 10 15 20 25 30 35 40 45 50 55 60 65 70 80

PVC Insulation 1.22 1.17 1.12 1.06 1.00 0.94 0.87 0.79 0.71 0.61 0.50 - - -

XLPE Insulation 1.15 1.12 1.08 1.04 1.00 0.96 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.41

Rating factor relating to Ground temperature


Ground temp °C 10 15 20 25 30 35 40 45 50 55 60 65 70 80

PVC Insulation 1.10 1.05 1.00 0.95 0.89 0.84 0.77 0.71 0.63 0.55 0.45 - - -

XLPE Insulation 1.07 1.04 1.00 0.96 0.93 0.89 0.85 0.80 0.76 0.71 0.65 0.60 0.53 0.38

Rating factor relating to themal ground resistivity


Thermal Resistivity of soil K.m / W 1 1.5 2 2.5 3

Rating factors 1.18 1.1 1.05 1.00 0.96

Rating factor based on 3 core cable for size 1.5 ~ 10 mm²


Number of core
Under ground In Air

5 0.70 0.75

7 0.60 0.65

10 0.50 0.55

14 0.45 0.50

19 0.40 0.45

Section 4 - General Information


24 0.35 0.40

40 0.30 0.35

61 0.25 0.30
Page - 87
Section 4 - General Information

Reduction factors for group of more than one multi-core cable (note 1)
to be applied to reference ratings for multi-core cables in free air
Number Number of cables
Method of installation
of trays 1 2 3 4 6 9
Touching
1 1.00 0.88 0.82 0.79 0.76 0.73
2 1.00 0.87 0.80 0.77 0.73 0.68
3 1.00 0.86 0.79 0.76 0.71 0.66
≥ 20 mm
Perforated trays
(note 2) Spaced
D
1 1.00 1.00 0.98 0.95 0.91 -
2 1.00 0.99 0.96 0.92 0.87 -
3 1.00 0.98 0.95 0.91 0.85 -
≥ 20 mm

1 1.00 0.88 0.82 0.78 0.73 0.72



225 mm

2 1.00 0.88 0.81 0.76 0.71 0.70


Vertical
Perforated Touching

trays
(note 3)
1 1.00 0.91 0.89 0.88 0.87 -

225 mm
D
2 1.00 0.91 0.88 0.87 0.85 -

Spaced
Touching
1 1.00 0.87 0.82 0.80 0.79 0.78
2 1.00 0.86 0.80 0.78 0.76 0.73
Ladder 3 1.00 0.85 0.79 0.76 0.73 0.70
≥ 20 mm
supports,
cleats, etc. Spaced
D
(note 2) 1 1.00 1.00 1.00 1.00 1.00 -
2 1.00 0.99 0.98 0.97 0.96 -
3 1.00 0.98 0.97 0.96 0.93 -
≥ 20 mm

Factors apply to single layer groups of cables as shown above and do not apply when cables are installed in more than one layer touching each other.
Values for such installations may be significantly lower and shall be determined by an appropriate method.
NOTE 1 Values given are averages for the cable types and range of conductor sizes considered. The spread of values is generally less than ± 5 %.

NOTE 2 Values are given for vertical a spacing between trays of 300 mm and at least 20 mm between trays and wall. For closer spacing the factors
should be reduced.

NOTE 3 Values are given for horizontal spacing between trays of 225 mm with trays mounted back to back. For closer spacing the factors should be
reduced.

Page - 88
Section 4 - General Information

Reduction factors for groups of more than one circuit of single-core cables (Note 1)
to be applied to reference rating for one circuit of single-core cables in free air
Number of Use as a multiplier to
Method of installation
trays 1 2 3 rating for
Touching
Perforated 1 0.98 0.91 0.87 Three cables in
trays 2 0.96 0.87 0.81 horizontal
(Note 3) 3 0.95 0.85 0.78 formation
≥ 20 mm

Touching
Vertically

Perforated 225 mm 1 0.96 0.86 - Three cables
trays in vertcal
(note 4) 2 0.95 0.84 - formation

Touching
Ladder 1 1.00 0.97 0.96 Three cables in
supports,cleats etc. 2 0.98 0.93 0.89 horizontal
(Note 3) 3 0.97 0.90 0.86 formation
≥ 20 mm

D
≥ 2D 1 1.00 0.98 0.96
Perforated
trays 2 0.97 0.93 0.89
(Note 3) 3 0.96 0.92 0.86
≥ 20 mm


225 mm
Vertical 1 1.00 0.91 0.89 Three cables in
≥ 2D
perforated trays trefoil
(Note 4) 2 1.00 0.90 0.86 formation
D

Spaced

D
≥ 2D 1 1.00 1.00 1.00
Ladder
supports,cleats etc. 2 0.97 0.95 0.93
(Note 3) 3 0.96 0.94 0.90
≥ 20 mm

NOTE 1 Value given are averages for the cable types and range of conductor sizes considered. The spread of values is generally less than ± 5 %.

NOTE 2 For circuits having more than one cable in parallel per phase, each three phase set of conductors should be considered as a circuit for the
purpose of this table

NOTE 3 Values are given for vertical spacings between trays of 300 mm.For closer spacing the factors should be reduced.

NOTE 4 Values are given for horizontal spacings between trays of 225 mm with trays mounted back to back and at least 20 mm between the tray
and any wall. For closer spacing the factors should be reduced.

Page - 89
Section 4 - General Information
PERMISSIBLE PULLING TENSION
Pulling equipment Permissible pulling tension (kg)
PULLING EYE 7 x (Number of core) x (Cross section area of conductor)
CABLE NET About 500 kg, but the maximum tension shall not be more than one of
conductor (same calculation as using PULLING EYE)

Reference data on Aluminium conductor


Pulling equipment Permissible pulling tension (kg)
PULLING EYE 4 x (Number of core) x (Cross section area of conductor)
CABLE NET About 500 kg, but the maximum tension shall not be more than one of
conductor (same calculation as using PULLING EYE)
Note) Cable net shall be covered more than 500 mm in length

MINIMUM BENDING RADIUS D : Diameter of cable


Minimum bending radius
Type of cable Single core cable
Multi Core Cable
Round / Compacted Conductor Sector conductor
Medium Voltage Cable 10D 12D 8D

Reference data on other types of POWER cables


Minimum bending radius
Single core cable
Type of cable
Round/Compacted Multi core cable
Sector conductor
conductor
Sheild cable ( XLPE/PVC-S etc ) 10D 12D 8D
Non Sheild cable ( XLPE/PVC etc ) 8D 12D 6D
Triplex type cable ( CVT etc ) - - 8D
Wire armored cable ( XLPE/SWA/PVC etc) 10D 12D 10D
Tape armored cable (XLPE/DSTA/PVC etc) 10D 12D 10D
Flat tape armored (XLPE/FSWA/PVC etc) 10D 12D 10D

Reference data on other types of INSTRUMENT cables


Minimum bending radius
Type of cable
Multi core cable
Non shield cable ( XLPE/PVC etc ) 6D Note) Sheild tape shall be
Sheild cable (XLPE/PVC-S etc) 6D AL mylar tape

PERMISSIBLE SIDE WALL PRESSURE


300kg/m is suggested as permissible side wall pressure to the cable during installation.
Side wall pressure (T1) can be calculated with below formula.
T kg
T1 = Pulling tension (T) / Bending radius (r) r

CALCULATION OF CABLE PULLING TENSION DURING INSTALLATION

The cable pulling tension (T2) during installation can be calculated with below formula.

1) Horizontal straight part : T2 = µ * W * L W : Weight of cable (kg/m)


2) Horizontal curve part : T3 = T4 * e (µ θ ) L : Length of cable with straight part (m)
θ : Angle of curve part (rad)
µ : Friction factor Friction factor T2 : Pulling tension (kg)
on pulley 0.2 T3 : Pulling tension before curve part (kg)
underground 0.2 - 0.3 T4 : Pulling tension after curve part (kg)
in pipe 0.5 - 0.7
Page - 90
Section 4 - Contents & Information

Fire Performance Tests


Flame Propagation Tests
IEC 60332-1
Part 1 - Test on a single vertical insulated wire or cable
This is a relatively simple method for providing adequate indication of the flame-retardant characteristics of a single cable.
A 600 mm long cable sample is verticatlly suspended, placed in the middle of a three-sided metal screen.
This is subjected to the regulated flame of one (up to a cable diameter of 50 mm) or two (above 50 mm diameter) gas burners at an
angle of 45° to the cable. The flame is applied for a continuous time calculated according to an increasing with the cable weight
(from around 1-minute for a small control cable to about 7 minutes for a 4 core 300 mm² power cable). The test is passed if the cable
has self-extinguished and the charred or flame affected portion of the cable has not reached the top of the sample.

IEC 60332-3
Part 3 - Test on bunched wire or cables
This test was developed to obtain a method to determine the flame propagation characteristics of bunched cables.
It can not be assumed that because a single vertical cable complies with the requirements of IEC 60332 part 1 it will also behave in 1
a similar manner when bunched with others cables.
The propagation of a flame along a bunch of cables depends on a number of features, such as :
The volume of combustible material exposed to the fire
The geometrical configuration of the cables
The temperature at which it is possible to ignite any gases emitted from the cables
The quantity of combustible gas released from the cables
The volume of air passing through the cable installation
The test consists of a vertical chamber, 1 x 2 x 4 m. Openings air inlet and outlet are provided in the base and the top of the test
chamber for a controlled air flow rate during the test. The cable samples to be tested are 3.5 m long and fixed to a steel ladder mounted
150 mm from the rear wall vertically with the test chamber. The number of lengths of cables in the test depends on the test categoty
based on the volume of combustible material.
Test Category Volume of combustible material Time of flame application
A 7 litres / m 40 Minutes
B 3.5 litres / m 40 Minutes
C 1.5 litres / m 20 Minutes
A ribbon gas burner of a set size and heat flow rate, operating at 800°C is mounted horizontally in front of the cable samples at a set
distance and height. The test is passed if the charred or affected portion of the samples have not reached a height exceeding 2.5 m
above the bottom edge of the burner.

IEC 60331 - 21 (1999)


Fire resisting characteristics of electric cables Circuit Integrity Test
This test determines the circuit integrity of a cable during and after a prolonged fire :
A horizontally suspended sample 1200 mm long is placed 75 mm above a 610 mm long ribbon type gas burner, the flame temperature
of which is regulated to 750°C. The conductors of the sample are connected to an AC voltage source, at the operating voltage, via fuses.
The flame and test voltage shall be applied continuously for a period of 90 min. 12 hours after the flame has been extinguished the cable
is energised again.
The test is passed if no failure of any of the fuses occurs.

Page - 91
Section 4 - General Information

NOTES

Page - 92

You might also like