Professional Documents
Culture Documents
EFRIGERANT PROCESS
The best way to understand what is happening in a refrigerant-based dehumidifier is to keep in mind the impact pressure has on the boiling point of a fluid, and that energy will migrate from hot to cold. It is common knowledge that it takes longer to boil an egg at 5,000 feet (1,600 m) than it does at sea level. At higher altitudes there is less pressure, which lowers the point at which water boils. At 5,000 feet (1,600 m), water boils at 202F, (94C) while at sea level it boils at 212F (100C). Refrigerant behaves just like water in that the boiling point changes at different pressures. Refer to Table 1 for examples of R22's various boiling points. Pressure Temp. Pressure (PSI) (PSI) (F) 50 60 80 100 120 26 34 48 59 69 140 160 180 200 220 Temp. Pressure Temp. (F) (F) (PSI) 78 87 94 101 108 240 260 275 290 320 114 120 124 128 136
Liquid Only
Table 1 - R22 Pressure/Temperature Relationships
Liquid/Vapor
Condenser
Vapor Only
Supercooling
We will choose the starting point of the refrigeration cycle at the inlet of the thermal expansion valve (TXV). The TXV creates a pressure drop across its internal orifice, which separates the dehumidifier's refrigerant system into two halves: high side and low side. (Point A, Figures 1 and 3) As the refrigerant leaves the TXV, it starts to boil because the pressure is reduced to approximately 50 to 90 psi. The refrigerant is a mixture of cold saturated vapor and liquid as it
Pressure
A TXV
Evaporator
B C
Compressor D Superheat
Enthalpy
Figure 1 - Refrigeration Process
D EHUMIDIFICATION COMPONENTS
The optimization of dehumidification in the refrigeration process requires careful design and selection of the systems components. The design becomes more complicated when a wide range of inlet conditions occur and multiple condensers are used to allow year-round control.
Compressor
Desert Aire uses scroll technology in all of its units (except <2hp ) to provide the most favorable energy output for every electrical input. In addition, its design reduces the number of parts and provides long life. Compressors put out a variable amount of energy depending on the pressure differential of the high and low sides. The greater the differential, the harder the compressor must work to overcome the difference and the less it can output. Therefore, the designer must know the dynamics of the system before compressor performance can be determined. Refer to Figure 2 for an example of the significant variance in compressor capacity at typical conditions.
COLD 55% 100%
Outside Ambient
HOT
40% LOW
75%
A
EXPANSION VALVE
Internal Load
HIGH
RECEIVER TANK
A compressor is selected for the system to produce a given output at one design point. For example, to cool and dehumidify 1000 cfm of air from 95F db / 78F wb to 55F dewpoint, you need 82 MBH of energy. The compressor must provide this amount with the high and low pressures balanced by the evaporator and condenser coils.
CONDENSER COIL
D
Figure 3 - Refrigerant flow
TECHNICAL BULLETIN 1
Description
Cold, saturated liquid + vapor Superheated vapor Hot gas Hot liquid
Condenser Design
The condenser or combination of condensers must be sized for the total heat of rejection (THR) of the system. There are three (3) types used: reheat, remote air-cooled and watercooled. Remote Air-cooled condensers are placed outside the conditioned space to reject excess energy to the outdoors. A water-cooled condenser would use pool water, cooling-tower water or chilled water as the medium to reject the excess energy. These can be cost-effectively sized to optimize the condensing pressure/temperature for minimum energy usage. Air-cooled condensers must balance their physical size and air volume with a maximum condensing temperature. Generally, a maximum of 120F (49C) condensing temperature is used to balance first cost with operating efficiency. Most systems are sized to achieve a 25F (-3.9C) differential which would require a maximum outside air design of 95F (35C). When air temperatures go higher than 95F, the condensing coil must be designed with more surface area because the difference between ambient and 120F condensing temperature is smaller, yet the amount of energy to be rejected has not changed. Because dehumidifiers operate in many condensing modes, there needs to be a method of controlling the pressure of these elements. Desert Aire uses flooding control, which allows liquid refrigerant to back up into the condenser, thereby reducing the effective surface area of the coil. The colder the air or water entering a condenser, the less coil surface is required; conversely, the hotter the air or water, the more surface is required to maintain the desired pressure. This flooding control allows a dehumidifier to reject energy to an outdoor condenser in a range from 0F to 95F (-18C to 35C) and water temperature from 45F to 105F (7C to 40C).
Receivers
A receiver is just a storage vessel for liquid refrigerant. Since most dehumidifiers use several condensers, each with a variable requirement for refrigerant, there must be a place to store the liquid not in circulation. In addition, many dehumidifiers use outdoor condensers that may need to operate over a wide range of ambient temperatures, causing a significant change in the volume of liquid refrigerant required to operate. A dehumidifier without a receiver must be limited in its operational range or else experience many problems in controlling moisture removal.
OT GAS DEFROST
Hot gas defrost is used to intentionally freeze the evaporator coil and then defrost the ice and remove it from the system as water. Such a system measures the internal refrigerant temperatures and only defrosts on demand for a short duration. The drawback is that this technique does not dehumidify during the defrost cycle, and can therefore only be applied on re-circulation systems such as ice rinks.
ONCLUSION
OT GAS BYPASS
Hot gas bypass is a technique used to prevent a coil from freezing up at low load conditions. As a system reaches its minimum approach temperature, the refrigerant temperature drops below 32F (0C) and any water vapor in the air passing over the coil will freeze. By installing a small feeder tube from the discharge side of the compressor to the coil's inlet header, a small amount of hot gas can be metered into the coil to raise the refrigerant's temperature above the freezing point. This creates a false load on the system and reduces the efficiency of the system since part of the electrical energy used to run the compressor is short-circuited to create the load. However, this small electrical cost can save a major compressor failure should the coil continue to freeze up and starve the compressor into failure.
Dehumidifiers operate in many modes of operation in order to insure continuous moisture removal. To achieve this, the systems design incorporates many different critically sized components that must function seamlessly. Each mode can be explained by understanding how each refrigerant process moves along the pressure-enthalpy diagram of R22 shown in Figure 1.
8300 West Sleske Court Milwaukee, WI 53223 (414) 357-7400 FAX: (414) 357-8501 www.desert-aire.com
101 10/02