You are on page 1of 3

No.

Design calulation of 15 m height Steel Chimney at SIKORSKY project Step: 1 - DESIGN DATA Height of the steel chemney (H) = Diameter at the top (d) = Wind Intensity = up to 15m height 15.00 0.50 1.65 m m KN/m2 m m m

Step: 2 - DIMENSION IN FLARED PORTION Height of flared portion = H / 3 Adopt height of flared portion Diameterof conical flared portion at the Bottom = 5/4 x d 5.00 6.50 0.63

Step: 3 - INTENSITY OF WIND PRESSURE Wind Intensity at different height (Refer IS 875) Basic Wind speed Vb Risk factor k1 (for important building) Terrain factor k2 (for catogery II,Class C) up to 10m Terrain factor k2 (for catogery II,Class C) 10 m to 15 m height Topogarphy factor k3 Design Wind speed Vz up to 10m Design Wind speed Vz 10 m to 15 m height Design wind pressure Pz up to 10 m Design wind pressure Pz 0 m to 15 m height 0 to 15 m Shape factor for steel chimney circular in plan 44.00 1.00 0.93 0.97 1.00 40.92 42.68 1.005 1.093 1.093 0.70 KN/m2 KN/m2 KN/m2 m/s

Step : 4 P = 0.7 x p1 x d x h The intensity of wind pressure is adopted as the average value of those at upper and lower section .for calcaulations the maximum intensity at top is used Over -turning moment due to wind, Mw P = Total wind force Substituting the value of ( P) Mw = 0.7 x p1 x d1 x h x h/2 KN-m 43.04 KN-m 5.74

Step : 5 - THICKNESS OF CHIMNEY PLATE Select section at 15 m from top Diameter of steel chimney : Assume the thickness of steel plate : D / t ratio = Radius of gyration, k =0.7 x d/2 Effective height for axial stress h1 = Ratio h1/k = For bending stress = 1/2 (h1/k) 0.80 6.00 133.33 280.00 30000 107.14 53.57 mm mm m mm

No.

Design calulation of 15 m height Steel Chimney at SIKORSKY project Allowable stress in axial compression = Allowable stress in bending = Maximum tensile stress in windward side of steel chimney ( Mw / 250 d t) - 0.079 h < 1 x ft
2

125.00 153.00

N/mm2 N/mm
2

1 - Efficiency of the joint on the tension side Thickness (t) = Maximum compressure stress on leeward side = (Mw/ 250 d2t) + 0.079h + 0.002 h/t < 2 x ft 2 - Efficiency of the joint on the compression side Thickness t = Total thickness with corrosion allowance 5 Step 5 : MODULUS OF SECTION OF STEEL CHIMNEY Z = 0.77 d2 t 6 Step 6: SELF WEIGHT OF STEEL CHIMNEY Self weight of chimney at section 10% for stiffeners Area of cross section 7 Step 7: CHECK FOR STRESSES P/A + M/Z 49.04 25.49 8 Step : 8 - DESIGN OF BASE PLATE The maximum compressure force per unit circumferential length. F1 =( 4 Mw / d12 t)+(W S+W L / d1t)(t-1) Allowable bending stress of concrete = Where, W s = 79 d t h W L = 2dh Width of base plate = F1/ bcr a = l. (3 c/bc)1/2 Provided 300 mm width 25 mm thick base plate 9 Step : 9 - DESIGN OF ANCHOR BOLT ( HOLDING DOWN BOLTS) The maximum tensile force per unit length of circumference. 32.68 mm 163.38 4.00 N/mm N/mm
2

0.0020

mm

0.002 6.00

mm mm

1155000.00

mm3

177.47 195.22 15072.00

KN KN mm2

N/mm2 N/mm2

No.

Design calulation of 15 m height Steel Chimney at SIKORSKY project F1 =( 4 Mw / d12 t) - (W s / d1t ) (t-1) Assume of dia of bolts : Tensile strenght of bolts : 163.38 32.00 126.00 KN N/mm mm

No. of anchor bolts required = 2.00 Provid M32 anchor bolts of 1200 mm length at 250 l mm C/C Provide lug for greater stability