You are on page 1of 44

CT Saturation Tutorial

Presented by Tony Giuliante

Bushing CT

IS

IP

N Turns

Copyright ATG Consulting 2003

Physical Properties of Core


Length L Area A

B-H Characteristic

Copyright ATG Consulting 2003

B-H Characteristic
B

Flux to Volts per Turn


=

s B

dA

= B A sin (t) V = d = B A cos (t) N dt

Copyright ATG Consulting 2003

Flux to Volts per Turn

V = BA N

Electric Field to Ampere Turns


=

dL

= H L

Copyright ATG Consulting 2003

Convert B-H Characteristic


B V = BA N

= H L

V/N vs. NI
V N

NI

Copyright ATG Consulting 2003

CT Exciting Characteristic
2000:5

300:5

VS

IS

Simplified Bushing CT Circuit


IS

IP
N

REB

REB = RLEADS + RDEVICES

Copyright ATG Consulting 2003

Simplified Bushing CT Circuit


RCT IS

IP
N

XM IM

REB

Simplified Bushing CT Circuit


IS

IP
N

XM IM

V = IS RTB

RTB

Copyright ATG Consulting 2003

Flux vs Voltage
V = N d dt 1 = N 1 = N

dt

IS RTB

dt

Flux vs Voltage
1 = N

IS RTB

dt

Flux equals the AREA under the Voltage

Copyright ATG Consulting 2003

Voltage Demand IS RTB

Voltage & Flux Waveforms


IS RTB

Copyright ATG Consulting 2003

Flux Design Limits


+ S

- S

Secondary Current
No Saturation

Copyright ATG Consulting 2003

10

Increased Voltage Demand Five times IS RTB


5*IS RTB

Flux for Ideal CT


No Saturation

5*IS RTB

Copyright ATG Consulting 2003

11

Current Output for Ideal CT


No Saturation
Primary Current Secondary Current

Amperes

Time (Seconds)

Flux Design Limits


+ S - S

Copyright ATG Consulting 2003

12

Flux Design Limits


+ S - S

Flux Excursion

Copyright ATG Consulting 2003

13

Current vs Flux

AC Saturation

Copyright ATG Consulting 2003

14

AC Saturation
Large Fault Current Large Burden Low CT Kneepoint Voltage

AC Saturation
Relay Applications
Large Fault Current
Unit Auxiliary Transformers

Large Burden
High Impedance Bus Differentials

Low CT Kneepoint Voltage


Compact Distribution Switchgear

Copyright ATG Consulting 2003

15

Unit Auxiliary Transformers


G

87UAT

DC Offset
Transformer

Fault current includes a dc component, or offset, that makes the current asymmetrical. L/R = 100 ms X/R = 37.7

Copyright ATG Consulting 2003

16

Offset Current vs Flux


Primary Current Flux Sec. Amperes or Flux Density

Time (Seconds)

Secondary Current
Primary Current Secondary Current

Amperes

Time (Seconds)

Copyright ATG Consulting 2003

17

Secondary Current Observations


Secondary current is distorted due to the core flux saturation Secondary current distorts after a short time (time-to-saturation) Distortion slowly dissipates as primary dc offset decays

Secondary Current 100 Amps 50 0 -50 0 2 Tesla 1 0 -1 0 1 2 3 4 Cycles 5 6 7 I SEC 1 2 3 4 5 6 Magnetic Flux Density (B) 7 I PRIM

Copyright ATG Consulting 2003

18

Large Differential Current


Secondary Current Primary Current

Amperes

Differential Current

Time (Seconds)

DC Saturation Factors
Large DC Time Constant Large Burden Low CT Kneepoint Voltage High Remanent Flux

Copyright ATG Consulting 2003

19

Remanent Flux
Trapped magnetic flux in core if a previous offset current is interrupted before reaching a symmetrical state High X/R ratios make remanent flux more likely due to the slow decay rates of offset current

Remanent Flux Survey


Remanent flux in % of saturation 0 - 20 21 - 40 41 - 60 61 - 80 Percentage of cts 39 18 16 27

Copyright ATG Consulting 2003

20

Remanent Flux Example


CT data
1200:5, C800, burden = 1.6 +j 0.7 ohm

Fault current 24,000 amps with dc offset X/R ratio = 19 Display ct secondary output current for remanence of 0%, 50% and 75% of saturation

0% Remanent Flux
Primary Current Secondary Current

Amperes

Time (Seconds)

Copyright ATG Consulting 2003

21

50% Remanent Flux


Primary Current Secondary Current

Amperes

Time (Seconds)

75% Remanent Flux


Primary Current Secondary Current

Amperes

Time (Seconds)

Copyright ATG Consulting 2003

22

Remanent Flux Results


Remanent flux 0% 50% 75% Time-to-saturation 1+ cycles 1/2 cycle 1/3 cycle

IEEE Guide for the Application of Current Transformers Used for Protective Relaying Purposes C37.110-1996

Copyright ATG Consulting 2003

23

CT Classification

CT Accuracy Class
ANSI defines accuracy rating classes by a letter and number C100, C800 or T100, etc. Letter designates how the accuracy can be determined Number designates the minimum secondary terminal voltage under a standard burden

Copyright ATG Consulting 2003

24

Accuracy Class Letter


C means by Calculation
non-gapped cores with negligible leakage flux, such as bushing cts

T means by Test
cts with leakage flux, such as cts with wound primaries

Old classes H and L


H T and L C

Accuracy Class Number


Minimum secondary terminal voltage produced
at 20 times rated current into a standard burden without exceeding a 10% ratio correction factor

Copyright ATG Consulting 2003

25

What is a Standard Burden?


IEEE Standard Requirements for Instrument Transformers C57.13-1993 the standard relaying burdens are 1, 2, 4 and 8 ohms at a lagging 0.5 p.f. 20 times rated secondary current of 5 A is 100 A, and 100 A times the standard burdens yield C ratings of 100, 200, 400 and 800 V

CT Knee Point Voltages


45o Tangent A B 300:5 2000:5

VS

IS

Copyright ATG Consulting 2003

26

Knee Point Definitions


Point A is the ANSI knee point voltage
point tangent to 45 degree slope line

Point B is the IEC knee point


where a 10% increase in voltage causes a 50 % increase in current

IEC knee point is higher than ANSI knee point

CT Excitation Impedance
Excitation curve represents the exciting impedance in terms of voltage and current The ANSI knee point (A) represents the point of maximum permeability of the iron core

Copyright ATG Consulting 2003

27

Examples
Determine Accuracy Class Selecting CT Ratings Calculating Time to Saturation

Example - Find Accuracy Class


Find the approximate ct accuracy class from the excitation curve
the C class is defined for a 10% ratio correction factor at 20 times rated current
10% of (20 X 5 A) is 10 A for IE = 10 A, use the excitation curve to find VS as about 500 V

next find the ct terminal voltage by subtracting the internal voltage drop from VS
(continued)

Copyright ATG Consulting 2003

28

Example - Equivalent Circuit


IP VS = 500 IS = 100 A IE = 10 A VB = ? ZB

Example - continued
VB (voltage to the burden)
VB = VS - (IS X RS) VB = 500 - (100 X 0.61) VB = 439 V

The approximate ct accuracy class is the next lowest ANSI class number (C400)

Copyright ATG Consulting 2003

29

Examples
Determine Accuracy Class Selecting CT Ratings Calculating Time to Saturation

Avoiding CT Saturation
VX > IS ZTB (1 + X/R)
VX = saturation voltage IS = secondary current ZTB = total ct secondary burden

Copyright ATG Consulting 2003

30

CTs for Generator Differentials


For generators, typically cts cannot be sized to avoid saturation because of:
high fault current high X/R ratio

Common applications would:


select adequate ct primary rating select highest practical C class match manufacturer and types of cts

Examples
Determine Accuracy Class Selecting CT Ratings Calculating Time to Saturation

Copyright ATG Consulting 2003

31

Transient Response of Current Transformers


Power Systems Relaying Committee

Time to Saturate Equation

VK I F R TB

( I - KR )

TCT TS
T CT - T S

-t TCT

-e

-t TS

+1

Copyright ATG Consulting 2003

32

VK
VK 2000:5 Tangents Intersect 300:5

VS

IS

Saturation Parameters
R TB = RCT + R LEADS +R DEVICES I F = FAULT CURRENT (SEC RMS AMPS) KR =

.5 - .75 IRON CORE .1 AIR GAP

= 377
L TCT = M R TB

Copyright ATG Consulting 2003

33

VM & I M
45o Tangent VM 300:5 2000:5

VS

IM

IS

CT Inductance
LM TCT = RTB VM

XM =

IM
XM

LM =

Copyright ATG Consulting 2003

34

DC Offsets

DC Offset Current
Depends on where in the voltage wave the fault occurs. Fault time is defined as: F I A => Fault Initiation Angle

Copyright ATG Consulting 2003

35

Voltage Waveform
FIA

45

90 4.16

135 180 225 270 345 360 8.33 12.5

Degrees

60 Hz

16.67 Time ms

Voltage Waveform
FIA

45

90 5

135 180 225 270 345 360 10 15

Degrees

50 Hz

20 Time ms

Copyright ATG Consulting 2003

36

Power System
R L

Z = R2 + X2 = ARCTAN ( L / R)

Power System
R L

= Characteristic Angle

Copyright ATG Consulting 2003

37

Fault at FIA = No Offset


R L

Current Waveform No Offset FIA =


2 1

0 Current

-1

-2

-3 0 10 20 Time - Milliseconds 30 40 50

Copyright ATG Consulting 2003

38

Fault at FIA = 90 Max Offset


R L

Current Waveform Max Offset FIA = + 90


2 1

0 Current

-1

-2

-3 0 10 20 Time - Milliseconds 30 40 50

Copyright ATG Consulting 2003

39

Total Current
2 1

0 Current

-1

-2

-3 0 10 20 Time - Milliseconds 30 40 50

Equations
v(t) = Vmax * sin ( Wt + Close_Ang ) i (t) = i ss (t) + i trans (t) i ss (t) = [ Vmax / Z ] * sin ( Wt + Alpha ) Alpha = Close_Ang - ArcTan ( WL/R ) i trans (t) = [ e^ (-R/L) t ] * [ -Vmax / Z ] * sin ( Alpha )

Copyright ATG Consulting 2003

40

Power System Time Constants


L/R (MS) 1 2 5 10 30 100 200 400 1000 X/R 0.377 0.754 1.885 3.770 11.310 37.699 75.398 150.796 376.991 Ang (deg) 20.66 37.02 62.05 75.14 84.95 88.48 89.24 89.62 89.85 Power System High Fault Resistance Distribution Lines Subtransmission Lines EHV Lines Transformers Generators Large Generators

Subtransmission Line L/R = 10 ms


2 1

0 Current

-1

-2

-3 0 10 20 Time - Milliseconds 30 40 50

Copyright ATG Consulting 2003

41

Generator L/R = 200 ms


2 1

0 Current

-1

-2

-3 0 10 20 Time - Milliseconds 30 40 50

EHV Line L/R = 30 ms


2 1

0 Current

-1

-2

-3 0 10 20 Time - Milliseconds 30 40 50

Copyright ATG Consulting 2003

42

Distribution Line L/R = 5 ms


2 1

0 Current

-1

-2

-3 0 10 20 Time - Milliseconds 30 40 50

Copyright ATG Consulting 2003

43

You might also like