Person per household 6 NPUT

No of Houshold 35 OUTPUT
Design Population 210
Water Consumable Rate 120
LPD LPS
ADD 25200 0.291667
MDD 32760 0.379167
MHD 3150 0.036458
Household per Nodes 7
Nodes 5
Area No. of Nodes No of Household
1 0 0
2 1 7
3 1 7
4 1 7
5 1 7
6 1 7
LPD LPH LPS
Q1 0 0 0
Q2 5040 210 0.06
Q3 5040 210 0.06
Q4 5040 210 0.06
Q5 5040 210 0.06
Q6 5040 210 0.06
Pipe Length HH served Pipe Diameter(mm)
f 0 0 0
e 47.5 7 31
d 75 7 31
c 64 7 25
b 43.5 7 25
a 72 7 25
appendix o
QA
QB 0.3
QC 0.24
QD 0.18
QE 0.12
QF 0.06
table 9.1
Case 1
Pipe Q Dia(mm) h1/100 Length hf
f 0 0 0 0 0
e 0.3 31 0.67 47.5 0.32
d 0.24 31 0.48 75 0.36
c 0.18 25 0.77 64 0.49
b 0.12 25 0.36 43.5 0.16
a 0.06 25 0.1 72 0.07
Total Length 302 Friction Loss 1.4
Minimum Water Level above the water main 4
h1/100 0.33
Case 2 table 9.1
Pipe Q h1/100 Dia(mm)
f 0 0 0
e 0.3 0.33 38
d 0.24 0.33 31
c 0.18 0.33 31
b 0.12 0.33 25
a 0.06 0.33 19
Operating Time(hr) 12
Pump Capacity = MDD/Operating Time
= 0.379167 LPS
Case 3
Summary 0
Pipe Length(m) Case 1 Case 2 Selected Recommended
f 0 0 0 0 0
e 47.5 31 38 31 38
d 75 31 31 31 31
c 64 25 31 25 31
b 43.5 25 25 25 25
a 72 25 19 19 25
Design Of Reservoir And Pump
Criterion for Capacity = 1/4 ADD
6300 L 6.3 M^3
Radius 0.63 m
Height 2.52 m
Frequency Of Filling The Reservoir = 5.2 times per day
Reservoitr Filling Time = = 16615.38 sec
= 4.6 hrs