Air System Sizing Summary for AHU-13-GF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 2
Floor Area .............................................................. 374.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-13-GF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 143.3
Sensible coil load ................................................ 119.3
Coil L/s at Aug 1900 ............................................ 4683
Max block L/s at Aug 2000 ................................... 5016
Sum of peak zone L/s .......................................... 5019
Sensible heat ratio .............................................. 0.832
m/kW .................................................................... 2.6
W/m .................................................................. 383.3
Water flow @ 7.7 K rise ....................................... 4.46

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................ Aug 1900


OA DB / WB ................................................... 40.9 / 23.5
Entering DB / WB ........................................... 33.7 / 20.2
Leaving DB / WB ........................................... 12.0 / 10.8
Coil ADP .................................................................... 9.6
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 50
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 2 of 2
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 24.1 kW
Coil L/s at Des Htg ............................................... 1585 L/s
Max coil L/s ......................................................... 1585 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 64.5
Ent. DB / Lvg DB ............................................ 19.0 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Aug 2000 ................................. 5016 L/s
Standard L/s ........................................................ 4871 L/s
Actual max L/(s-m) ............................................ 13.41 L/(s-m)

Fan motor BHP ...................................................... 12.46 BHP


Fan motor kW .......................................................... 9.29 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................ 1375 L/s
L/(s-m) ................................................................. 3.68 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 5.00 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-12-GF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 6
Floor Area .............................................................. 730.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-12-GF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 138.4
Sensible coil load .................................................. 98.4
Coil L/s at Jul 1500 .............................................. 4824
Max block L/s at Aug 2000 ................................... 4880
Sum of peak zone L/s .......................................... 5043
Sensible heat ratio .............................................. 0.711
m/kW .................................................................... 5.3
W/m .................................................................. 189.6
Water flow @ 7.7 K rise ....................................... 4.30

kW
kW
L/s
L/s
L/s

L/s

Load occurs at .................................................. Jul 1500


OA DB / WB ................................................... 45.1 / 24.6
Entering DB / WB ........................................... 29.4 / 19.9
Leaving DB / WB ........................................... 12.0 / 11.2
Coil ADP .................................................................. 10.1
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 61
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 3 of 6
Max zone temperature deviation ................................ 0.9

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 22.5 kW
Coil L/s at Des Htg ............................................... 1621 L/s
Max coil L/s ......................................................... 1621 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 30.8
Ent. DB / Lvg DB ............................................ 20.2 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Aug 2000 ................................. 4880 L/s
Standard L/s ........................................................ 4739 L/s
Actual max L/(s-m) .............................................. 6.69 L/(s-m)

Fan motor BHP ...................................................... 12.12 BHP


Fan motor kW .......................................................... 9.04 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 873 L/s
L/(s-m) ................................................................. 1.20 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 3.31 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-11-GF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 9
Floor Area .............................................................. 657.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-11-GF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 179.8
Sensible coil load ................................................ 131.3
Coil L/s at Jul 1500 .............................................. 6181
Max block L/s at Jul 2000 .................................... 6263
Sum of peak zone L/s .......................................... 6467
Sensible heat ratio .............................................. 0.730
m/kW .................................................................... 3.7
W/m .................................................................. 273.6
Water flow @ 7.7 K rise ....................................... 5.59

kW
kW
L/s
L/s
L/s

L/s

Load occurs at .................................................. Jul 1500


OA DB / WB ................................................... 45.1 / 24.6
Entering DB / WB ........................................... 30.1 / 20.0
Leaving DB / WB ........................................... 12.0 / 11.2
Coil ADP .................................................................. 10.0
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 60
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 7 of 9
Max zone temperature deviation ................................ 0.9

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 28.8 kW
Coil L/s at Des Htg ............................................... 2075 L/s
Max coil L/s ......................................................... 2075 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 43.9
Ent. DB / Lvg DB ............................................ 20.1 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Jul 2000 ................................... 6263 L/s
Standard L/s ........................................................ 6082 L/s
Actual max L/(s-m) .............................................. 9.53 L/(s-m)

Fan motor BHP ...................................................... 15.55 BHP


Fan motor kW ........................................................ 11.60 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................ 1337 L/s
L/(s-m) ................................................................. 2.03 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 4.25 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-10-GF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 9
Floor Area .............................................................. 716.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-10-GF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 109.4
Sensible coil load .................................................. 86.2
Coil L/s at Jun 1500 ............................................. 4513
Max block L/s at Jul 1600 .................................... 4513
Sum of peak zone L/s .......................................... 4812
Sensible heat ratio .............................................. 0.789
m/kW .................................................................... 6.5
W/m .................................................................. 152.7
Water flow @ 7.7 K rise ....................................... 3.40

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Jun 1500


OA DB / WB ................................................... 44.5 / 24.6
Entering DB / WB ........................................... 28.3 / 18.7
Leaving DB / WB ........................................... 12.0 / 11.2
Coil ADP .................................................................. 10.2
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 53
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 1 of 9
Max zone temperature deviation ................................ 0.8

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 13.2 kW
Coil L/s at Des Htg ................................................ 993 L/s
Max coil L/s .......................................................... 993 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 18.4
Ent. DB / Lvg DB ............................................ 20.7 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Jul 1600 ................................... 4513 L/s
Standard L/s ........................................................ 4382 L/s
Actual max L/(s-m) .............................................. 6.30 L/(s-m)

Fan motor BHP ...................................................... 11.21 BHP


Fan motor kW .......................................................... 8.36 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 543 L/s
L/(s-m) ................................................................. 0.76 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 3.44 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-09-GF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones ........................................................ 10
Floor Area .............................................................. 934.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-09-GF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 155.8
Sensible coil load ................................................ 127.4
Coil L/s at Jun 2000 ............................................. 7406
Max block L/s at Oct 2000 ................................... 7585
Sum of peak zone L/s .......................................... 7948
Sensible heat ratio .............................................. 0.818
m/kW .................................................................... 6.0
W/m .................................................................. 166.8
Water flow @ 7.7 K rise ....................................... 4.84

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Jun 2000


OA DB / WB ................................................... 38.8 / 23.1
Entering DB / WB ........................................... 26.7 / 17.9
Leaving DB / WB ........................................... 12.0 / 11.2
Coil ADP .................................................................. 10.4
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 52
Design supply temp. ................................................ 12.0
Zone T-stat Check ............................................... 6 of 10
Max zone temperature deviation ................................ 0.6

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 19.3 kW
Coil L/s at Des Htg ............................................... 1578 L/s
Max coil L/s ......................................................... 1578 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 20.7
Ent. DB / Lvg DB ............................................ 21.5 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Oct 2000 .................................. 7585 L/s
Standard L/s ........................................................ 7365 L/s
Actual max L/(s-m) .............................................. 8.12 L/(s-m)

Fan motor BHP ...................................................... 18.84 BHP


Fan motor kW ........................................................ 14.05 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 608 L/s
L/(s-m) ................................................................. 0.65 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 2.79 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-08-GF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 8
Floor Area .............................................................. 641.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-08-GF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 156.8
Sensible coil load ................................................ 129.9
Coil L/s at Jun 1500 ............................................. 6939
Max block L/s at Jun 1500 ................................... 6939
Sum of peak zone L/s .......................................... 7289
Sensible heat ratio .............................................. 0.829
m/kW .................................................................... 4.1
W/m .................................................................. 244.6
Water flow @ 7.7 K rise ....................................... 4.87

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Jun 1500


OA DB / WB ................................................... 44.5 / 24.6
Entering DB / WB ........................................... 28.0 / 18.2
Leaving DB / WB ........................................... 12.0 / 11.1
Coil ADP .................................................................. 10.2
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 51
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 6 of 8
Max zone temperature deviation ................................ 0.3

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 21.0 kW
Coil L/s at Des Htg ............................................... 1618 L/s
Max coil L/s ......................................................... 1618 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 32.7
Ent. DB / Lvg DB ............................................ 21.0 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Jun 1500 .................................. 6939 L/s
Standard L/s ........................................................ 6737 L/s
Actual max L/(s-m) ............................................ 10.82 L/(s-m)

Fan motor BHP ...................................................... 17.23 BHP


Fan motor kW ........................................................ 12.85 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 930 L/s
L/(s-m) ................................................................. 1.45 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 3.99 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-07-GF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 8
Floor Area .............................................................. 888.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-07-GF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 126.4
Sensible coil load .................................................. 99.7
Coil L/s at Jun 1500 ............................................. 5438
Max block L/s at Jun 2000 ................................... 5438
Sum of peak zone L/s .......................................... 5682
Sensible heat ratio .............................................. 0.788
m/kW .................................................................... 7.0
W/m .................................................................. 142.4
Water flow @ 7.7 K rise ....................................... 3.93

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Jun 1500


OA DB / WB ................................................... 44.5 / 24.6
Entering DB / WB ........................................... 27.6 / 18.5
Leaving DB / WB ........................................... 12.0 / 11.2
Coil ADP .................................................................. 10.3
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 54
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 2 of 8
Max zone temperature deviation ................................ 0.8

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 18.4 kW
Coil L/s at Des Htg ............................................... 1456 L/s
Max coil L/s ......................................................... 1456 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 20.7
Ent. DB / Lvg DB ............................................ 21.2 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Jun 2000 .................................. 5438 L/s
Standard L/s ........................................................ 5280 L/s
Actual max L/(s-m) .............................................. 6.12 L/(s-m)

Fan motor BHP ...................................................... 13.50 BHP


Fan motor kW ........................................................ 10.07 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 510 L/s
L/(s-m) ................................................................. 0.57 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 2.49 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-06-GF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 8
Floor Area .............................................................. 519.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-06-GF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 116.9
Sensible coil load ................................................ 100.4
Coil L/s at Jul 2000 .............................................. 5723
Max block L/s at Aug 2000 ................................... 5927
Sum of peak zone L/s .......................................... 5993
Sensible heat ratio .............................................. 0.859
m/kW .................................................................... 4.4
W/m .................................................................. 225.2
Water flow @ 7.7 K rise ....................................... 3.63

kW
kW
L/s
L/s
L/s

L/s

Load occurs at .................................................. Jul 2000


OA DB / WB ................................................... 39.4 / 23.1
Entering DB / WB ........................................... 27.0 / 17.7
Leaving DB / WB ........................................... 12.0 / 11.2
Coil ADP .................................................................. 10.3
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 50
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 7 of 8
Max zone temperature deviation ................................ 0.1

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 12.9 kW
Coil L/s at Des Htg ............................................... 1090 L/s
Max coil L/s ......................................................... 1090 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 24.9
Ent. DB / Lvg DB ............................................ 21.9 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Aug 2000 ................................. 5927 L/s
Standard L/s ........................................................ 5755 L/s
Actual max L/(s-m) ............................................ 11.42 L/(s-m)

Fan motor BHP ...................................................... 14.72 BHP


Fan motor kW ........................................................ 10.98 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 450 L/s
L/(s-m) ................................................................. 0.87 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 3.41 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-05-GF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones ........................................................ 10
Floor Area .............................................................. 806.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-05-GF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 122.0
Sensible coil load ................................................ 103.9
Coil L/s at Sep 2000 ............................................ 5966
Max block L/s at Oct 2000 ................................... 6186
Sum of peak zone L/s .......................................... 6536
Sensible heat ratio .............................................. 0.851
m/kW .................................................................... 6.6
W/m .................................................................. 151.4
Water flow @ 7.7 K rise ....................................... 3.79

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Sep 2000


OA DB / WB ................................................... 38.2 / 22.5
Entering DB / WB ........................................... 26.9 / 17.7
Leaving DB / WB ........................................... 12.0 / 11.2
Coil ADP .................................................................. 10.3
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 51
Design supply temp. ................................................ 12.0
Zone T-stat Check ............................................... 8 of 10
Max zone temperature deviation ................................ 0.5

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 14.3 kW
Coil L/s at Des Htg ............................................... 1179 L/s
Max coil L/s ......................................................... 1179 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 17.7
Ent. DB / Lvg DB ............................................ 21.7 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Oct 2000 .................................. 6186 L/s
Standard L/s ........................................................ 6007 L/s
Actual max L/(s-m) .............................................. 7.68 L/(s-m)

Fan motor BHP ...................................................... 15.36 BHP


Fan motor kW ........................................................ 11.46 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 450 L/s
L/(s-m) ................................................................. 0.56 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 3.05 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-04-GF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 8
Floor Area .............................................................. 892.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-04-GF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 135.0
Sensible coil load ................................................ 109.3
Coil L/s at Oct 1700 ............................................. 6145
Max block L/s at Dec 2000 ................................... 6383
Sum of peak zone L/s .......................................... 6529
Sensible heat ratio .............................................. 0.810
m/kW .................................................................... 6.6
W/m .................................................................. 151.4
Water flow @ 7.7 K rise ....................................... 4.20

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Oct 1700


OA DB / WB ................................................... 41.7 / 23.2
Entering DB / WB ........................................... 27.2 / 18.1
Leaving DB / WB ........................................... 12.0 / 11.2
Coil ADP .................................................................. 10.3
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 54
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 4 of 8
Max zone temperature deviation ................................ 0.2

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 18.2 kW
Coil L/s at Des Htg ............................................... 1470 L/s
Max coil L/s ......................................................... 1470 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 20.4
Ent. DB / Lvg DB ............................................ 21.4 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Dec 2000 ................................. 6383 L/s
Standard L/s ........................................................ 6198 L/s
Actual max L/(s-m) .............................................. 7.16 L/(s-m)

Fan motor BHP ...................................................... 15.85 BHP


Fan motor kW ........................................................ 11.82 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 561 L/s
L/(s-m) ................................................................. 0.63 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 2.73 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-03-GF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 9
Floor Area .............................................................. 845.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-03-GF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 168.2
Sensible coil load ................................................ 137.7
Coil L/s at Jul 1500 .............................................. 7328
Max block L/s at Oct 2000 ................................... 7328
Sum of peak zone L/s .......................................... 8024
Sensible heat ratio .............................................. 0.819
m/kW .................................................................... 5.0
W/m .................................................................. 199.0
Water flow @ 7.7 K rise ....................................... 5.23

kW
kW
L/s
L/s
L/s

L/s

Load occurs at .................................................. Jul 1500


OA DB / WB ................................................... 45.1 / 24.6
Entering DB / WB ........................................... 28.0 / 18.3
Leaving DB / WB ........................................... 12.0 / 11.1
Coil ADP .................................................................. 10.2
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 52
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 7 of 9
Max zone temperature deviation ................................ 0.9

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 21.9 kW
Coil L/s at Des Htg ............................................... 1683 L/s
Max coil L/s ......................................................... 1683 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 25.9
Ent. DB / Lvg DB ............................................ 20.9 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Oct 2000 .................................. 7328 L/s
Standard L/s ........................................................ 7116 L/s
Actual max L/(s-m) .............................................. 8.67 L/(s-m)

Fan motor BHP ...................................................... 18.20 BHP


Fan motor kW ........................................................ 13.57 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 958 L/s
L/(s-m) ................................................................. 1.13 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 3.83 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-02-GF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 9
Floor Area .............................................................. 985.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-02-GF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 147.4
Sensible coil load ................................................ 119.3
Coil L/s at Jul 1600 .............................................. 6708
Max block L/s at Oct 2000 ................................... 6951
Sum of peak zone L/s .......................................... 7435
Sensible heat ratio .............................................. 0.809
m/kW .................................................................... 6.7
W/m .................................................................. 149.7
Water flow @ 7.7 K rise ....................................... 4.58

kW
kW
L/s
L/s
L/s

L/s

Load occurs at .................................................. Jul 1600


OA DB / WB ................................................... 44.7 / 24.5
Entering DB / WB ........................................... 27.2 / 18.1
Leaving DB / WB ........................................... 12.0 / 11.2
Coil ADP .................................................................. 10.3
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 53
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 5 of 9
Max zone temperature deviation ................................ 0.2

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 20.3 kW
Coil L/s at Des Htg ............................................... 1640 L/s
Max coil L/s ......................................................... 1640 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 20.6
Ent. DB / Lvg DB ............................................ 21.4 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Oct 2000 .................................. 6951 L/s
Standard L/s ........................................................ 6750 L/s
Actual max L/(s-m) .............................................. 7.06 L/(s-m)

Fan motor BHP ...................................................... 17.26 BHP


Fan motor kW ........................................................ 12.87 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 543 L/s
L/(s-m) ................................................................. 0.55 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 2.37 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-13-FF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 3
Floor Area .............................................................. 445.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-13-FF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 85.2
Sensible coil load .................................................. 71.8
Coil L/s at Jul 1900 .............................................. 3943
Max block L/s at Jun 1900 ................................... 4089
Sum of peak zone L/s .......................................... 4133
Sensible heat ratio .............................................. 0.843
m/kW .................................................................... 5.2
W/m .................................................................. 191.4
Water flow @ 7.7 K rise ....................................... 2.65

kW
kW
L/s
L/s
L/s

L/s

Load occurs at .................................................. Jul 1900


OA DB / WB ................................................... 40.9 / 23.5
Entering DB / WB ........................................... 27.5 / 18.0
Leaving DB / WB ........................................... 12.0 / 11.1
Coil ADP .................................................................. 10.3
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 52
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 2 of 3
Max zone temperature deviation ................................ 0.1

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ......................................................... 8.1 kW
Coil L/s at Des Htg ................................................ 670 L/s
Max coil L/s .......................................................... 670 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 18.2
Ent. DB / Lvg DB ............................................ 21.7 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Jun 1900 .................................. 4089 L/s
Standard L/s ........................................................ 3970 L/s
Actual max L/(s-m) .............................................. 9.19 L/(s-m)

Fan motor BHP ...................................................... 10.15 BHP


Fan motor kW .......................................................... 7.57 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 152 L/s
L/(s-m) ................................................................. 0.34 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 1.72 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-12-FF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 9
Floor Area .............................................................. 630.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-12-FF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 202.9
Sensible coil load ................................................ 164.2
Coil L/s at Jul 2000 .............................................. 7648
Max block L/s at Jul 2000 .................................... 8065
Sum of peak zone L/s .......................................... 8084
Sensible heat ratio .............................................. 0.809
m/kW .................................................................... 3.1
W/m .................................................................. 322.1
Water flow @ 7.7 K rise ....................................... 6.31

kW
kW
L/s
L/s
L/s

L/s

Load occurs at .................................................. Jul 2000


OA DB / WB ................................................... 39.4 / 23.1
Entering DB / WB ........................................... 30.3 / 19.2
Leaving DB / WB ........................................... 12.0 / 11.0
Coil ADP .................................................................. 10.0
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 54
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 9 of 9
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 27.1 kW
Coil L/s at Des Htg ............................................... 2125 L/s
Max coil L/s ......................................................... 2125 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 43.0
Ent. DB / Lvg DB ............................................ 21.1 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Jul 2000 ................................... 8065 L/s
Standard L/s ........................................................ 7831 L/s
Actual max L/(s-m) ............................................ 12.80 L/(s-m)

Fan motor BHP ...................................................... 20.03 BHP


Fan motor kW ........................................................ 14.94 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 963 L/s
L/(s-m) ................................................................. 1.53 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 4.19 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-11-FF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 9
Floor Area .............................................................. 677.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-11-FF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 220.3
Sensible coil load ................................................ 176.4
Coil L/s at Jul 2000 .............................................. 8029
Max block L/s at Jul 2000 .................................... 8464
Sum of peak zone L/s .......................................... 8478
Sensible heat ratio .............................................. 0.801
m/kW .................................................................... 3.1
W/m .................................................................. 325.4
Water flow @ 7.7 K rise ....................................... 6.85

kW
kW
L/s
L/s
L/s

L/s

Load occurs at .................................................. Jul 2000


OA DB / WB ................................................... 39.4 / 23.1
Entering DB / WB ........................................... 30.7 / 19.5
Leaving DB / WB ........................................... 12.0 / 11.0
Coil ADP .................................................................... 9.9
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 54
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 9 of 9
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 30.7 kW
Coil L/s at Des Htg ............................................... 2374 L/s
Max coil L/s ......................................................... 2374 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 45.3
Ent. DB / Lvg DB ............................................ 21.0 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Jul 2000 ................................... 8464 L/s
Standard L/s ........................................................ 8219 L/s
Actual max L/(s-m) ............................................ 12.50 L/(s-m)

Fan motor BHP ...................................................... 21.02 BHP


Fan motor kW ........................................................ 15.68 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................ 1139 L/s
L/(s-m) ................................................................. 1.68 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 4.43 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-10-FF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 7
Floor Area .............................................................. 756.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-10-FF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 128.5
Sensible coil load .................................................. 99.5
Coil L/s at Jul 1500 .............................................. 5212
Max block L/s at Oct 2000 ................................... 5212
Sum of peak zone L/s .......................................... 5626
Sensible heat ratio .............................................. 0.774
m/kW .................................................................... 5.9
W/m .................................................................. 169.9
Water flow @ 7.7 K rise ....................................... 3.99

kW
kW
L/s
L/s
L/s

L/s

Load occurs at .................................................. Jul 1500


OA DB / WB ................................................... 45.1 / 24.6
Entering DB / WB ........................................... 28.3 / 18.8
Leaving DB / WB ........................................... 12.0 / 11.2
Coil ADP .................................................................. 10.2
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 55
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 2 of 7
Max zone temperature deviation ................................ 0.7

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 17.0 kW
Coil L/s at Des Htg ............................................... 1324 L/s
Max coil L/s ......................................................... 1324 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 22.4
Ent. DB / Lvg DB ............................................ 21.1 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Oct 2000 .................................. 5212 L/s
Standard L/s ........................................................ 5061 L/s
Actual max L/(s-m) .............................................. 6.89 L/(s-m)

Fan motor BHP ...................................................... 12.94 BHP


Fan motor kW .......................................................... 9.65 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 651 L/s
L/(s-m) ................................................................. 0.86 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 3.60 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-09-FF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 9
Floor Area .............................................................. 852.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-09-FF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 126.7
Sensible coil load ................................................ 103.7
Coil L/s at Jun 1600 ............................................. 5840
Max block L/s at Oct 2000 ................................... 6083
Sum of peak zone L/s .......................................... 6428
Sensible heat ratio .............................................. 0.819
m/kW .................................................................... 6.7
W/m .................................................................. 148.7
Water flow @ 7.7 K rise ....................................... 3.94

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Jun 1600


OA DB / WB ................................................... 44.2 / 24.5
Entering DB / WB ........................................... 27.1 / 18.0
Leaving DB / WB ........................................... 12.0 / 11.2
Coil ADP .................................................................. 10.3
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 52
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 4 of 9
Max zone temperature deviation ................................ 0.9

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 16.1 kW
Coil L/s at Des Htg ............................................... 1314 L/s
Max coil L/s ......................................................... 1314 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 18.9
Ent. DB / Lvg DB ............................................ 21.5 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Oct 2000 .................................. 6083 L/s
Standard L/s ........................................................ 5907 L/s
Actual max L/(s-m) .............................................. 7.14 L/(s-m)

Fan motor BHP ...................................................... 15.11 BHP


Fan motor kW ........................................................ 11.27 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 461 L/s
L/(s-m) ................................................................. 0.54 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 2.50 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-08-FF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 9
Floor Area .............................................................. 807.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-08-FF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 155.1
Sensible coil load ................................................ 125.0
Coil L/s at Jun 1500 ............................................. 6371
Max block L/s at Jun 1500 ................................... 6371
Sum of peak zone L/s .......................................... 6651
Sensible heat ratio .............................................. 0.806
m/kW .................................................................... 5.2
W/m .................................................................. 192.2
Water flow @ 7.7 K rise ....................................... 4.82

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Jun 1500


OA DB / WB ................................................... 44.5 / 24.6
Entering DB / WB ........................................... 28.7 / 18.7
Leaving DB / WB ........................................... 12.0 / 11.1
Coil ADP .................................................................. 10.1
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 52
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 4 of 9
Max zone temperature deviation ................................ 0.8

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 22.9 kW
Coil L/s at Des Htg ............................................... 1711 L/s
Max coil L/s ......................................................... 1711 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 28.4
Ent. DB / Lvg DB ............................................ 20.6 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Jun 1500 .................................. 6371 L/s
Standard L/s ........................................................ 6186 L/s
Actual max L/(s-m) .............................................. 7.89 L/(s-m)

Fan motor BHP ...................................................... 15.82 BHP


Fan motor kW ........................................................ 11.80 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 983 L/s
L/(s-m) ................................................................. 1.22 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 3.79 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-07-FF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 8
Floor Area .............................................................. 888.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-07-FF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 122.5
Sensible coil load .................................................. 97.4
Coil L/s at Jun 1500 ............................................. 5343
Max block L/s at Jun 2000 ................................... 5343
Sum of peak zone L/s .......................................... 5587
Sensible heat ratio .............................................. 0.795
m/kW .................................................................... 7.2
W/m .................................................................. 138.0
Water flow @ 7.7 K rise ....................................... 3.81

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Jun 1500


OA DB / WB ................................................... 44.5 / 24.6
Entering DB / WB ........................................... 27.6 / 18.4
Leaving DB / WB ........................................... 12.0 / 11.2
Coil ADP .................................................................. 10.3
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 53
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 2 of 8
Max zone temperature deviation ................................ 0.8

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 17.5 kW
Coil L/s at Des Htg ............................................... 1398 L/s
Max coil L/s ......................................................... 1398 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 19.7
Ent. DB / Lvg DB ............................................ 21.3 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Jun 2000 .................................. 5343 L/s
Standard L/s ........................................................ 5188 L/s
Actual max L/(s-m) .............................................. 6.02 L/(s-m)

Fan motor BHP ...................................................... 13.27 BHP


Fan motor kW .......................................................... 9.89 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 470 L/s
L/(s-m) ................................................................. 0.53 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 2.42 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-06-FF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones ........................................................ 11
Floor Area .............................................................. 946.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-06-FF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 170.2
Sensible coil load ................................................ 142.9
Coil L/s at Jun 1500 ............................................. 7773
Max block L/s at Jun 2000 ................................... 8150
Sum of peak zone L/s .......................................... 8428
Sensible heat ratio .............................................. 0.840
m/kW .................................................................... 5.6
W/m .................................................................. 179.9
Water flow @ 7.7 K rise ....................................... 5.29

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Jun 1500


OA DB / WB ................................................... 44.5 / 24.6
Entering DB / WB ........................................... 27.7 / 18.1
Leaving DB / WB ........................................... 12.0 / 11.1
Coil ADP .................................................................. 10.3
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 51
Design supply temp. ................................................ 12.0
Zone T-stat Check ............................................... 8 of 11
Max zone temperature deviation ................................ 0.8

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 19.8 kW
Coil L/s at Des Htg ............................................... 1542 L/s
Max coil L/s ......................................................... 1542 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 20.9
Ent. DB / Lvg DB ............................................ 21.0 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Jun 2000 .................................. 8150 L/s
Standard L/s ........................................................ 7913 L/s
Actual max L/(s-m) .............................................. 8.61 L/(s-m)

Fan motor BHP ...................................................... 20.24 BHP


Fan motor kW ........................................................ 15.09 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 797 L/s
L/(s-m) ................................................................. 0.84 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 3.39 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-01-SF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones ........................................................ 12
Floor Area .............................................................. 985.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-01-SF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 233.9
Sensible coil load ................................................ 203.5
Coil L/s at Jul 2000 .............................................. 8992
Max block L/s at Jul 2000 .................................... 9155
Sum of peak zone L/s .......................................... 9477
Sensible heat ratio .............................................. 0.870
m/kW .................................................................... 4.2
W/m .................................................................. 237.4
Water flow @ 7.7 K rise ....................................... 7.27

kW
kW
L/s
L/s
L/s

L/s

Load occurs at .................................................. Jul 2000


OA DB / WB ................................................... 39.4 / 23.1
Entering DB / WB ........................................... 31.3 / 19.0
Leaving DB / WB ........................................... 12.0 / 10.9
Coil ADP .................................................................... 9.9
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 50
Design supply temp. ................................................ 12.0
Zone T-stat Check ............................................... 5 of 12
Max zone temperature deviation ................................ 0.1

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 17.3 kW
Coil L/s at Des Htg ............................................... 1569 L/s
Max coil L/s ......................................................... 1569 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 17.6
Ent. DB / Lvg DB ............................................ 22.6 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Jul 2000 ................................... 9155 L/s
Standard L/s ........................................................ 8889 L/s
Actual max L/(s-m) .............................................. 9.29 L/(s-m)

Fan motor BHP ...................................................... 22.74 BHP


Fan motor kW ........................................................ 16.95 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 665 L/s
L/(s-m) ................................................................. 0.68 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 3.30 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-05-FF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones ........................................................ 10
Floor Area .............................................................. 750.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-05-FF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 174.7
Sensible coil load ................................................ 151.9
Coil L/s at Sep 2000 ............................................ 8610
Max block L/s at Oct 2000 ................................... 9095
Sum of peak zone L/s .......................................... 9778
Sensible heat ratio .............................................. 0.870
m/kW .................................................................... 4.3
W/m .................................................................. 232.9
Water flow @ 7.7 K rise ....................................... 5.43

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Sep 2000


OA DB / WB ................................................... 38.2 / 22.5
Entering DB / WB ........................................... 27.1 / 17.6
Leaving DB / WB ........................................... 12.0 / 11.1
Coil ADP .................................................................. 10.3
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 50
Design supply temp. ................................................ 12.0
Zone T-stat Check ............................................... 8 of 10
Max zone temperature deviation ................................ 0.5

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 19.2 kW
Coil L/s at Des Htg ............................................... 1575 L/s
Max coil L/s ......................................................... 1575 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 25.7
Ent. DB / Lvg DB ............................................ 21.6 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Oct 2000 .................................. 9095 L/s
Standard L/s ........................................................ 8831 L/s
Actual max L/(s-m) ............................................ 12.13 L/(s-m)

Fan motor BHP ...................................................... 22.59 BHP


Fan motor kW ........................................................ 16.84 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 776 L/s
L/(s-m) ................................................................. 1.03 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 3.97 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-01-FF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones ........................................................ 10
Floor Area .............................................................. 859.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-01-FF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 152.3
Sensible coil load ................................................ 119.4
Coil L/s at Jul 1500 .............................................. 6300
Max block L/s at Jul 1600 .................................... 6300
Sum of peak zone L/s .......................................... 6580
Sensible heat ratio .............................................. 0.783
m/kW .................................................................... 5.6
W/m .................................................................. 177.3
Water flow @ 7.7 K rise ....................................... 4.73

kW
kW
L/s
L/s
L/s

L/s

Load occurs at .................................................. Jul 1500


OA DB / WB ................................................... 45.1 / 24.6
Entering DB / WB ........................................... 28.2 / 18.7
Leaving DB / WB ........................................... 12.0 / 11.2
Coil ADP .................................................................. 10.2
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 54
Design supply temp. ................................................ 12.0
Zone T-stat Check ............................................... 2 of 10
Max zone temperature deviation ................................ 0.3

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 20.2 kW
Coil L/s at Des Htg ............................................... 1583 L/s
Max coil L/s ......................................................... 1583 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 23.5
Ent. DB / Lvg DB ............................................ 21.1 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Jul 1600 ................................... 6300 L/s
Standard L/s ........................................................ 6118 L/s
Actual max L/(s-m) .............................................. 7.33 L/(s-m)

Fan motor BHP ...................................................... 15.65 BHP


Fan motor kW ........................................................ 11.67 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 752 L/s
L/(s-m) ................................................................. 0.88 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 3.55 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-04-FF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 8
Floor Area .............................................................. 888.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-04-FF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 134.7
Sensible coil load ................................................ 109.1
Coil L/s at Oct 1700 ............................................. 6136
Max block L/s at Dec 2000 ................................... 6374
Sum of peak zone L/s .......................................... 6520
Sensible heat ratio .............................................. 0.810
m/kW .................................................................... 6.6
W/m .................................................................. 151.7
Water flow @ 7.7 K rise ....................................... 4.19

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Oct 1700


OA DB / WB ................................................... 41.7 / 23.2
Entering DB / WB ........................................... 27.2 / 18.1
Leaving DB / WB ........................................... 12.0 / 11.2
Coil ADP .................................................................. 10.3
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 54
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 4 of 8
Max zone temperature deviation ................................ 0.2

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 18.2 kW
Coil L/s at Des Htg ............................................... 1466 L/s
Max coil L/s ......................................................... 1466 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 20.5
Ent. DB / Lvg DB ............................................ 21.4 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Dec 2000 ................................. 6374 L/s
Standard L/s ........................................................ 6189 L/s
Actual max L/(s-m) .............................................. 7.18 L/(s-m)

Fan motor BHP ...................................................... 15.83 BHP


Fan motor kW ........................................................ 11.80 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 560 L/s
L/(s-m) ................................................................. 0.63 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 2.74 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-03-FF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 9
Floor Area .............................................................. 834.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-03-FF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 156.1
Sensible coil load ................................................ 126.7
Coil L/s at Aug 1500 ............................................ 6573
Max block L/s at Oct 1900 ................................... 6614
Sum of peak zone L/s .......................................... 7389
Sensible heat ratio .............................................. 0.812
m/kW .................................................................... 5.3
W/m .................................................................. 187.2
Water flow @ 7.7 K rise ....................................... 4.85

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................ Aug 1500


OA DB / WB ................................................... 45.1 / 24.6
Entering DB / WB ........................................... 28.4 / 18.6
Leaving DB / WB ........................................... 12.0 / 11.1
Coil ADP .................................................................. 10.2
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 53
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 7 of 9
Max zone temperature deviation ................................ 0.9

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 22.0 kW
Coil L/s at Des Htg ............................................... 1671 L/s
Max coil L/s ......................................................... 1671 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 26.4
Ent. DB / Lvg DB ............................................ 20.8 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Oct 1900 .................................. 6614 L/s
Standard L/s ........................................................ 6422 L/s
Actual max L/(s-m) .............................................. 7.93 L/(s-m)

Fan motor BHP ...................................................... 16.43 BHP


Fan motor kW ........................................................ 12.25 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 952 L/s
L/(s-m) ................................................................. 1.14 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 3.88 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-02-FF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones ........................................................ 10
Floor Area .............................................................. 941.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-02-FF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 140.1
Sensible coil load ................................................ 113.6
Coil L/s at Aug 1600 ............................................ 6306
Max block L/s at Oct 2000 ................................... 6711
Sum of peak zone L/s .......................................... 7189
Sensible heat ratio .............................................. 0.811
m/kW .................................................................... 6.7
W/m .................................................................. 148.8
Water flow @ 7.7 K rise ....................................... 4.35

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................ Aug 1600


OA DB / WB ................................................... 44.7 / 24.5
Entering DB / WB ........................................... 27.4 / 18.2
Leaving DB / WB ........................................... 12.0 / 11.2
Coil ADP .................................................................. 10.3
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 53
Design supply temp. ................................................ 12.0
Zone T-stat Check ............................................... 6 of 10
Max zone temperature deviation ................................ 0.8

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 15.7 kW
Coil L/s at Des Htg ............................................... 1251 L/s
Max coil L/s ......................................................... 1251 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 16.7
Ent. DB / Lvg DB ............................................ 21.3 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Oct 2000 .................................. 6711 L/s
Standard L/s ........................................................ 6516 L/s
Actual max L/(s-m) .............................................. 7.13 L/(s-m)

Fan motor BHP ...................................................... 16.67 BHP


Fan motor kW ........................................................ 12.43 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 527 L/s
L/(s-m) ................................................................. 0.56 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 2.78 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-10-SF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones ........................................................ 10
Floor Area .............................................................. 864.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-10-SF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 197.9
Sensible coil load ................................................ 170.3
Coil L/s at Jul 2000 .............................................. 7249
Max block L/s at Jul 2000 .................................... 7398
Sum of peak zone L/s .......................................... 7404
Sensible heat ratio .............................................. 0.861
m/kW .................................................................... 4.4
W/m .................................................................. 229.1
Water flow @ 7.7 K rise ....................................... 6.15

kW
kW
L/s
L/s
L/s

L/s

Load occurs at .................................................. Jul 2000


OA DB / WB ................................................... 39.4 / 23.1
Entering DB / WB ........................................... 32.0 / 19.3
Leaving DB / WB ........................................... 12.0 / 10.9
Coil ADP .................................................................... 9.8
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 51
Design supply temp. ................................................ 12.0
Zone T-stat Check ............................................... 8 of 10
Max zone temperature deviation ................................ 0.1

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 25.4 kW
Coil L/s at Des Htg ............................................... 2066 L/s
Max coil L/s ......................................................... 2066 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 29.4
Ent. DB / Lvg DB ............................................ 21.5 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Jul 2000 ................................... 7398 L/s
Standard L/s ........................................................ 7183 L/s
Actual max L/(s-m) .............................................. 8.56 L/(s-m)

Fan motor BHP ...................................................... 18.37 BHP


Fan motor kW ........................................................ 13.70 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 580 L/s
L/(s-m) ................................................................. 0.67 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 3.15 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-09-SF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones ........................................................ 10
Floor Area .............................................................. 888.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-09-SF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 203.1
Sensible coil load ................................................ 180.6
Coil L/s at Jul 2000 .............................................. 8214
Max block L/s at Jul 2000 .................................... 8491
Sum of peak zone L/s .......................................... 8789
Sensible heat ratio .............................................. 0.889
m/kW .................................................................... 4.4
W/m .................................................................. 228.7
Water flow @ 7.7 K rise ....................................... 6.31

kW
kW
L/s
L/s
L/s

L/s

Load occurs at .................................................. Jul 2000


OA DB / WB ................................................... 39.4 / 23.1
Entering DB / WB ........................................... 30.8 / 18.7
Leaving DB / WB ........................................... 12.0 / 10.9
Coil ADP .................................................................... 9.9
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 49
Design supply temp. ................................................ 12.0
Zone T-stat Check ............................................... 8 of 10
Max zone temperature deviation ................................ 0.1

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 22.9 kW
Coil L/s at Des Htg ............................................... 1973 L/s
Max coil L/s ......................................................... 1973 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 25.8
Ent. DB / Lvg DB ............................................ 22.1 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Jul 2000 ................................... 8491 L/s
Standard L/s ........................................................ 8245 L/s
Actual max L/(s-m) .............................................. 9.56 L/(s-m)

Fan motor BHP ...................................................... 21.09 BHP


Fan motor kW ........................................................ 15.72 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 417 L/s
L/(s-m) ................................................................. 0.47 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 2.57 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-08-SF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 9
Floor Area .............................................................. 876.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-08-SF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 219.8
Sensible coil load ................................................ 187.2
Coil L/s at Jul 2000 .............................................. 8186
Max block L/s at Jun 2000 ................................... 8495
Sum of peak zone L/s .......................................... 8794
Sensible heat ratio .............................................. 0.852
m/kW .................................................................... 4.0
W/m .................................................................. 250.9
Water flow @ 7.7 K rise ....................................... 6.83

kW
kW
L/s
L/s
L/s

L/s

Load occurs at .................................................. Jul 2000


OA DB / WB ................................................... 39.4 / 23.1
Entering DB / WB ........................................... 31.5 / 19.2
Leaving DB / WB ........................................... 12.0 / 10.9
Coil ADP .................................................................... 9.8
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 51
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 9 of 9
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 32.8 kW
Coil L/s at Des Htg ............................................... 2553 L/s
Max coil L/s ......................................................... 2553 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 37.5
Ent. DB / Lvg DB ............................................ 21.0 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Jun 2000 .................................. 8495 L/s
Standard L/s ........................................................ 8249 L/s
Actual max L/(s-m) .............................................. 9.70 L/(s-m)

Fan motor BHP ...................................................... 21.10 BHP


Fan motor kW ........................................................ 15.73 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................ 1005 L/s
L/(s-m) ................................................................. 1.15 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 3.72 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-07-SF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones ........................................................ 10
Floor Area .............................................................. 806.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-07-SF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 173.6
Sensible coil load ................................................ 153.5
Coil L/s at Jun 2000 ............................................. 6737
Max block L/s at Jun 2000 ................................... 6951
Sum of peak zone L/s .......................................... 6963
Sensible heat ratio .............................................. 0.884
m/kW .................................................................... 4.6
W/m .................................................................. 215.3
Water flow @ 7.7 K rise ....................................... 5.39

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Jun 2000


OA DB / WB ................................................... 38.8 / 23.1
Entering DB / WB ........................................... 31.4 / 18.9
Leaving DB / WB ........................................... 12.0 / 10.9
Coil ADP .................................................................... 9.8
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 49
Design supply temp. ................................................ 12.0
Zone T-stat Check ............................................... 8 of 10
Max zone temperature deviation ................................ 0.1

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 21.0 kW
Coil L/s at Des Htg ............................................... 1771 L/s
Max coil L/s ......................................................... 1771 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 26.1
Ent. DB / Lvg DB ............................................ 21.9 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Jun 2000 .................................. 6951 L/s
Standard L/s ........................................................ 6749 L/s
Actual max L/(s-m) .............................................. 8.62 L/(s-m)

Fan motor BHP ...................................................... 17.26 BHP


Fan motor kW ........................................................ 12.87 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 399 L/s
L/(s-m) ................................................................. 0.49 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 2.65 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-06-SF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones ........................................................ 10
Floor Area .............................................................. 789.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-06-SF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 218.0
Sensible coil load ................................................ 195.0
Coil L/s at Jul 2000 .............................................. 9099
Max block L/s at Jun 2000 ................................... 9484
Sum of peak zone L/s .......................................... 9857
Sensible heat ratio .............................................. 0.894
m/kW .................................................................... 3.6
W/m .................................................................. 276.3
Water flow @ 7.7 K rise ....................................... 6.78

kW
kW
L/s
L/s
L/s

L/s

Load occurs at .................................................. Jul 2000


OA DB / WB ................................................... 39.4 / 23.1
Entering DB / WB ........................................... 30.3 / 18.5
Leaving DB / WB ........................................... 12.0 / 10.9
Coil ADP .................................................................. 10.0
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 48
Design supply temp. ................................................ 12.0
Zone T-stat Check ............................................... 8 of 10
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 25.3 kW
Coil L/s at Des Htg ............................................... 2112 L/s
Max coil L/s ......................................................... 2112 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 32.1
Ent. DB / Lvg DB ............................................ 21.8 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Jun 2000 .................................. 9484 L/s
Standard L/s ........................................................ 9209 L/s
Actual max L/(s-m) ............................................ 12.02 L/(s-m)

Fan motor BHP ...................................................... 23.55 BHP


Fan motor kW ........................................................ 17.56 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 735 L/s
L/(s-m) ................................................................. 0.93 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 3.96 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-05-SF(H


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones ........................................................ 10
Floor Area .............................................................. 713.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name .................................. AHU-05-SF(H


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 219.7
Sensible coil load ................................................ 195.1
Coil L/s at Aug 2000 ............................................ 9544
Max block L/s at Sep 2000 ................................. 10079
Sum of peak zone L/s ........................................ 10641
Sensible heat ratio .............................................. 0.888
m/kW .................................................................... 3.2
W/m .................................................................. 308.1
Water flow @ 7.7 K rise ....................................... 6.83

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................ Aug 2000


OA DB / WB ................................................... 39.4 / 23.1
Entering DB / WB ........................................... 29.4 / 18.3
Leaving DB / WB ........................................... 12.0 / 11.0
Coil ADP .................................................................. 10.1
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 49
Design supply temp. ................................................ 12.0
Zone T-stat Check ............................................... 9 of 10
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 24.7 kW
Coil L/s at Des Htg ............................................... 2082 L/s
Max coil L/s ......................................................... 2082 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 34.6
Ent. DB / Lvg DB ............................................ 21.9 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Sep 2000 ............................... 10079 L/s
Standard L/s ........................................................ 9786 L/s
Actual max L/(s-m) ............................................ 14.14 L/(s-m)

Fan motor BHP ...................................................... 25.03 BHP


Fan motor kW ........................................................ 18.66 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 761 L/s
L/(s-m) ................................................................. 1.07 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 4.10 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-04-SF(H


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 9
Floor Area .............................................................. 839.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name .................................. AHU-04-SF(H


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 181.9
Sensible coil load ................................................ 158.3
Coil L/s at Aug 2000 ............................................ 6920
Max block L/s at Oct 2000 ................................... 7377
Sum of peak zone L/s .......................................... 7810
Sensible heat ratio .............................................. 0.870
m/kW .................................................................... 4.6
W/m .................................................................. 216.8
Water flow @ 7.7 K rise ....................................... 5.65

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................ Aug 2000


OA DB / WB ................................................... 39.4 / 23.1
Entering DB / WB ........................................... 31.5 / 19.1
Leaving DB / WB ........................................... 12.0 / 10.9
Coil ADP .................................................................... 9.8
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 50
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 7 of 9
Max zone temperature deviation ................................ 0.1

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 22.5 kW
Coil L/s at Des Htg ............................................... 1888 L/s
Max coil L/s ......................................................... 1888 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 26.8
Ent. DB / Lvg DB ............................................ 21.8 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Oct 2000 .................................. 7377 L/s
Standard L/s ........................................................ 7164 L/s
Actual max L/(s-m) .............................................. 8.79 L/(s-m)

Fan motor BHP ...................................................... 18.32 BHP


Fan motor kW ........................................................ 13.66 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 467 L/s
L/(s-m) ................................................................. 0.56 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 2.84 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-03-SF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 9
Floor Area .............................................................. 901.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-03-SF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 220.7
Sensible coil load ................................................ 187.9
Coil L/s at Jul 2000 .............................................. 8192
Max block L/s at Oct 2000 ................................... 8517
Sum of peak zone L/s .......................................... 9231
Sensible heat ratio .............................................. 0.851
m/kW .................................................................... 4.1
W/m .................................................................. 245.0
Water flow @ 7.7 K rise ....................................... 6.86

kW
kW
L/s
L/s
L/s

L/s

Load occurs at .................................................. Jul 2000


OA DB / WB ................................................... 39.4 / 23.1
Entering DB / WB ........................................... 31.6 / 19.3
Leaving DB / WB ........................................... 12.0 / 10.9
Coil ADP .................................................................... 9.8
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 51
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 9 of 9
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 32.4 kW
Coil L/s at Des Htg ............................................... 2543 L/s
Max coil L/s ......................................................... 2543 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 36.0
Ent. DB / Lvg DB ............................................ 21.1 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Oct 2000 .................................. 8517 L/s
Standard L/s ........................................................ 8270 L/s
Actual max L/(s-m) .............................................. 9.45 L/(s-m)

Fan motor BHP ...................................................... 21.15 BHP


Fan motor kW ........................................................ 15.77 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 973 L/s
L/(s-m) ................................................................. 1.08 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 3.74 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-02-SF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 9
Floor Area .............................................................. 730.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-02-SF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 179.3
Sensible coil load ................................................ 156.8
Coil L/s at Aug 2000 ............................................ 7165
Max block L/s at Sep 2000 ................................... 7449
Sum of peak zone L/s .......................................... 7784
Sensible heat ratio .............................................. 0.875
m/kW .................................................................... 4.1
W/m .................................................................. 245.6
Water flow @ 7.7 K rise ....................................... 5.57

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................ Aug 2000


OA DB / WB ................................................... 39.4 / 23.1
Entering DB / WB ........................................... 30.7 / 18.8
Leaving DB / WB ........................................... 12.0 / 10.9
Coil ADP .................................................................... 9.9
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 50
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 8 of 9
Max zone temperature deviation ................................ 0.1

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 20.9 kW
Coil L/s at Des Htg ............................................... 1745 L/s
Max coil L/s ......................................................... 1745 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 28.7
Ent. DB / Lvg DB ............................................ 21.8 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Sep 2000 ................................. 7449 L/s
Standard L/s ........................................................ 7233 L/s
Actual max L/(s-m) ............................................ 10.20 L/(s-m)

Fan motor BHP ...................................................... 18.50 BHP


Fan motor kW ........................................................ 13.79 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 555 L/s
L/(s-m) ................................................................. 0.76 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 3.56 L/s/person

Page 1 of 1

Air System Sizing Summary for AHU-01-GF(H)


Project Name: UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
Prepared by: MZECH EGYPTIAN CONSULTING HOUSE

05/19
02:37PM

Air System Information


Number of zones .......................................................... 6
Floor Area .............................................................. 938.0 m
Location ...................................... Makkah, Saudi Arabia

Air System Name ................................. AHU-01-GF(H)


Equipment Class .......................................... CW AHU
Air System Type ......................................... 1FDDVAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 138.4
Sensible coil load ................................................ 114.0
Coil L/s at Jul 1500 .............................................. 5899
Max block L/s at Aug 2000 ................................... 5899
Sum of peak zone L/s .......................................... 6128
Sensible heat ratio .............................................. 0.824
m/kW .................................................................... 6.8
W/m .................................................................. 147.5
Water flow @ 7.7 K rise ....................................... 4.30

kW
kW
L/s
L/s
L/s

L/s

Load occurs at .................................................. Jul 1500


OA DB / WB ................................................... 45.1 / 24.6
Entering DB / WB ........................................... 28.5 / 18.5
Leaving DB / WB ........................................... 12.0 / 11.1
Coil ADP .................................................................. 10.2
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 51
Design supply temp. ................................................ 12.0
Zone T-stat Check ................................................. 0 of 6
Max zone temperature deviation ................................ 0.5

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ........................................................ 20.8 kW
Coil L/s at Des Htg ............................................... 1619 L/s
Max coil L/s ......................................................... 1619 L/s
Water flow @ 11.1 K drop ................................... N/A

Load occurs at ................................................... Des Htg


W/m ........................................................................ 22.1
Ent. DB / Lvg DB ............................................ 21.1 / 32.0 C

Supply Fan Sizing Data


Actual max L/s at Aug 2000 ................................. 5899 L/s
Standard L/s ........................................................ 5727 L/s
Actual max L/(s-m) .............................................. 6.29 L/(s-m)

Fan motor BHP ...................................................... 14.65 BHP


Fan motor kW ........................................................ 10.92 kW
Fan static ................................................................ 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 706 L/s
L/(s-m) ................................................................. 0.75 L/(s-m)

Hourly Analysis Program v.4.4

L/s/person ................................................................ 3.24 L/s/person

Page 1 of 1

5. Plant Thermal Load

1
HVAC Calculation Sheet

Cooling Plant Sizing Summary for Sample Plant01


UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
MZECH EGYPTIAN CONSULTING HOUSE

05/19/2011
04:50PM

1. Plant Information:
Plant Name ............................................................................ Sample Plant01
Plant Type .................................................................. Generic Chilled Water
Design Weather .......................................................... Makkah, Saudi Arabia
2. Cooling Plant Sizing Data:
Maximum Plant Load ............................................................................ 5740.3 kW
Load occurs at ................................................................................ Jul 2000
m/kW ......................................................................................................... 5.0 m/kW
Floor area served by plant .................................................................. 28589.0 m
3. Coincident Air System Cooling Loads for Jul 2000

Air System Name


AHU-01-FF(H)
AHU-01-GF(H)
AHU-01-SF(H)
AHU-02-FF(H)
AHU-02-GF(H)
AHU-02-SF(H)
AHU-03-FF(H)
AHU-03-GF(H)
AHU-03-SF(H)
AHU-04-FF(H)
AHU-04-GF(H)
AHU-04-SF(H
AHU-05-FF(H)
AHU-05-GF(H)
AHU-05-SF(H
AHU-06-FF(H)
AHU-06-GF(H)
AHU-06-SF(H)
AHU-07-FF(H)
AHU-07-GF(H)
AHU-07-SF(H)
AHU-08-FF(H)
AHU-08-GF(H)
AHU-08-SF(H)
AHU-09-FF(H)
AHU-09-GF(H)
AHU-09-SF(H)
AHU-10-FF(H)
AHU-10-GF(H)
AHU-10-SF(H)
AHU-11-FF(H)
AHU-11-GF(H)
AHU-12-FF(H)
AHU-12-GF(H)
AHU-13-FF(H)
AHU-13-GF(H)

Mult.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

System
Cooling
Coil Load
( kW )
146.7
133.7
233.9
138.0
143.5
179.1
145.6
158.6
220.7
124.7
124.9
181.5
173.0
120.8
219.0
167.7
116.9
218.0
119.2
122.8
173.2
146.2
147.8
219.8
125.5
155.6
203.1
124.1
105.2
197.9
220.3
170.1
202.9
132.3
85.1
142.9

System loads are for coils whose cooling source is ' Chilled Water ' or ' Any ' .

Hourly Analysis Program v.4.4

Page 1 of 1

Hourly Chiller Load Profiles for Sample Plant01


UMM AL-QURA UNIVERSITY ( FACULTY OF EDUCATION )
MZECH EGYPTIAN CONSULTING HOUSE

05/19/2011
07:11PM

1. Plant Information:
Plant Name ............................................................................ Sample Plant01
Plant Type .................................................................. Generic Chilled Water
Design Weather .......................................................... Makkah, Saudi Arabia
2. Chiller Load Profiles from July to July :

Hour
0000
0100
0200
0300
0400
0500
0600
0700
0800
0900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300

DESIGN MONTH: JULY


OA
TEMP
( C )
35.1
34.5
33.9
33.4
33.0
32.9
33.1
33.7
34.8
36.4
38.3
40.3
42.3
43.8
44.7
45.1
44.7
43.9
42.5
40.9
39.4
38.0
36.8
35.8
Total kWh

Hourly Analysis Program v.4.4

TOTAL
COOLING
( kW )
785.6
755.8
709.5
661.0
616.2
578.1
548.4
5248.5
5132.2
5098.6
5089.4
5122.2
5276.6
5382.1
5476.5
5558.6
5613.4
5647.0
5684.2
5720.6
5740.3
777.2
902.2
879.8
83003.8

Page 1 of 1

Ventilation Calculations

1
HVAC Calculation Sheet

GROUND FLOOR
Space

Area Height

m3

ft3

No of ACH

L/S

Toilet (G-300&301&303&304)

47.6

190.4 6723.913

212.446

Toilet (G-315&311)

33.8

135.2 4774.543

150.854

Toilet (G-306&307&309&310)

2.76

11.04

389.874

12.3183

Toilet (G-312&313)

3.7

14.8

522.6571

16.5137

Toilet (G-302)

5.5

22

776.9227

24.5473

ABLUTION (308)

22

88

3107.691

147.284

KITCHEN(316)

11.7

46.8

1652.727

10

130.547

WASHING(314)

8.4

33.6

1186.573

56.2357

STORES(G-829&835)

17

68

2401.398

151.747

STORES(G-830&836)

13.3

53.2

1878.74

118.72

STORES(G-837&843)

24

847.5521

53.5578

STORES(G-852)

13

52

1836.363

116.042

STORES(G-839)

40.8

163.2 5763.354

364.193

STORES(G-853)

17

68

2401.398

151.747

STORES(G-854)

18.8

75.2

2655.663

167.814

STORES(G-857)

30

120

4237.76

267.789

STORES(G-859)

30.8

123.2 4350.767

274.93

ELEC RM(G-801)

8.65

34.6

1221.888

12

115.819

ELEC RM(G-806)

55

220

7769.227

12

736.42

ELEC RM(G-818&G-822&G-824)

14

56

1977.622

12

187.452

ELEC RM(G-856&G-861)

12

48

1695.104

12

160.673

TRANS RM (G-804)

56.6

226.4 7995.241

15

947.303

MDB (G-805)

67.6

270.4 9549.087

15

1131.41

37

12

495.41

GENRATOR (G-802)

148

5226.571

FIRST FLOOR
Space

Area Height

ft3

No of ACH

L/S

Toilet (F-300&301&305)

51.4

205.6 7260.696

229.406

Toilet (F-302)

24.7

98.8

3489.089

110.24

Toilet (G-306&307&309&310)

2.76

11.04

389.874

12.3183

Toilet (G-312&313)

3.7

14.8

522.6571

16.5137

Toilet (F-306)

51.4

205.6 7260.696

229.406

Toilet (F-304)

16.8

67

2366.083

74.7578

Toilet (F-307&313)

2.7

10.8

381.3984

12.0505

Toilet (F-308&312)

4.3

17.2

607.4123

19.1915

KITCHEN(F-303)

6.6

26.4

932.3073

12

88.3704

Toilet (F-309&310)

34.7

138.8 4901.676

154.871

STORES(F-807)

6.5

26

918.1814

58.0209

STORES(F-822&832)

13.3

53.2

1878.74

118.72

STORES(F-831)

17

68

2401.398

151.747

STORES(F-833)

30.8

123.2 4350.767

274.93

STORES(F-837&843)

24

847.5521

53.5578

STORES(F-838)

40

160

5650.347

357.052

STORES(F-845)

13

52

1836.363

116.042

ABLUTION(F-311)

22

88

3107.691

10

245.473

ELEC RM(F-812)

12.6

50.4

1779.859

12

168.707

ELEC RM(F-813)

13.8

55.2

1949.37

12

184.774

ELEC RM(F-807)

5.7

22.8

805.1745

12

76.3199

ELEC RM(F-834)

15

60

2118.88

12

200.842

SECOND FLOOR
Space

Area Height

m3

ft3

No of ACH

L/S

Toilet (S-300)

4.3

17.2

607.4123

19.1915

Toilet (S-301)

24

96

3390.208

107.116

Toilet (S-303&311)

3.4

13.6

480.2795

15.1747

Toilet (S-304)

16

565.0347

17.8526

Toilet (S-308&309)

48

192

6780.417

214.231

Toilet (S-315&321)

3.8

15.2

536.783

16.96

Toilet (S-306)

13

52

1836.363

58.0209

ABLUTION (S-314)

22

88

3107.691

147.284

KITCHEN(S-312&324&318)

6.6

26.4

932.3073

10

73.642

Toilet (S-316&322)

33.8

135.2 4774.543

150.854

Toilet (S-317&323)

3.4

13.6

480.2795

15.1747

Toilet (S-313&320)

2.75

11

388.4614

18.4105

STORES(S-803)

10

40

1412.587

89.263

STORES(S-806&813)

45

180

6356.641

401.683

STORES(S-817&818&841)

13.7

54.8

1935.244

122.29

STORES(S-827&822)

30.8

123.2 4350.767

274.93

STORES(S-830&834)

24

847.5521

53.5578

STORES(S-840)

13.7

54.8

1935.244

122.29

STORES(S-831)

40

160

5650.347

357.052

ELEC RM(S-809&808)

13

52

1836.363

12

174.063

ELEC RM(S-826&821)

12

48

1695.104

12

160.673

ELEC RM(G-818&G-822&G-824)

14

56

1977.622

12

187.452

ELEC RM(G-856&G-861)

12

48

1695.104

12

160.673