Delta Star Power Manufacturing Corp.

Substation Engineers Transformers


937-1181 936-8621 936-3241

Consultants

1613 Samuel St., Jordan Plaines, Novaliches, Proper, Quezon City, M. M. Tel. Nos. : 939-5431 to 34 connecting all Departments
Fax: (632) 939-0278 CTR No. 10DS1120-482 : PSPC : Clark

Customer Location

c/o PTL
TRANSFORMER SPECIFICATIONS 7000 KVA 3 60 Hz OA 22900 Volts 6600 Volts YNd1 3 5.92% 65 oC Mineral Oil Hyundai 2010.10

Capacity Phase Frequency Cooling Class High Voltage Low Voltage Vector Diagram HV Tap Impedance Temperature Rise Insulating Liquid Brand Date Manufactured

CERTIFIED TEST RESULTS


1. Insulation Resistance/Dielectric Adsorption & Polarization Index of Windings (Megger Test): Test Voltage DC (in KV) 10 KV 2 KV 10 KV One-Minute (in Meg) 3500 Meg 4500 Meg 6000 Meg Ten-Minute (in Meg) 5000 Meg 7000 Meg 10000 Meg Polarization Index 1.43 1.56 1.67

Primary :Ground Secondary:Ground Primary : Secondary

Note: 1. The Minimum Insulation Resistance is two (2) Megohms/KV. 2. The Dielectric Adsorption/Polarization Index (P.I.) minimum of 1.0 is computed ten (10) minutes reading over one (1) minute Reading.

-over-

DSPMC Ref. CTR482 Page 2

2.

Transformer Turn-Ratio (TTR) Test: Tap HV Phase LV Phase Computed Ratio NU/uv As Found Ratio NV/vw NW/wu

13222

6600

2.003

2.001

2.000

2.001

Note: As found ratio must not exceed + 0.5% of Computed Ratio. 3. Transformer insulating oil Dielectric Breakdown Voltage (BDV) Test: Trials 1 2 3 Average As Found Ratio 54.1 KV 54.3 KV 46.8 KV 51.73KV

Note: The average Dielectric Breakdown Voltage of Transformer insulating oil should be 26 KV or Higher to be considered Satisfactorily Good. 4. Digital Low Resistance Ohmmeter (Winding Resistance Test) : Test Current 1A 1A As Found Resistance Phase A Phase B 175.4 m 175.1 m 23.30 m 23.27 m Phase C 174.6 m 23.19 m

HV Side LV Side

Note: The Winding Resistance readings should be compared to the factory test data or previous field test data. If previous factory or field data is not available, use the data to compare phases on a three-phase unit (approx. balanced) or another identical unit. The permissible deviation for this test is plus or minus five (5) percent of the factory test or previous field test values. 5. Exciting Current at Rated Voltage test (No Load test): Test Voltage 6600 V As Found Current UW UV 1.10 A 1.13 A VW 2.62 A

Note: Exciting Current at Rated Voltage of the transformer should not exceed 3% of Full Load Current.

-over-

DSPMC Ref.CTR482

TESTING INSTRUMENTS USED:


1. 2. 3. 4. 5. INSULATION RESISTANCE (MEGGER) TESTER; (Battery Operated), Output 1 KV DC; Megohm Range: 21000 Megohms at 1 KV, Accuracy +/- 5%. Brand: YEW, Japan. LIQUID DIELECTRIC OIL TESTER; 0-60 KV, ASTM Gap Automatic Brand: Hipotronic, U.S.A. TRANSFORMER TURN-RATIO TEST SET; Ratio 0 to 129.999. Brand: James G. Biddle Co., U.S.A. DIGITAL LOW RESISTANCE OHMMETER (DLRO); Lowest Resolution 0.1 Micro-ohms. Brand: Hipotronics, U.S.A. Assorted Standard Laboratory Type Ammeter, Voltmeter, Wattmeter, Heavy Duty Variac. Brand: Yokogawa Electric Works, Japan.

Tested by

: ____________________________ GABRIEL CORREA : ____________________________ MICHAEL P. CAPATI Safety Engineer : ____________________________ REYNALDO C. DAQUIGAN-PEE : November 12, 2010

Witnessed by

Certified by

Date of Test