ES-Visual-Flow-Control

For Residential or Commercial Radiant Heating and Snow Melt Applications


Job Name Job Location Engineer Approval Contractor Approval Contractors P.O. No. Representative

Visual Flow Control Setter


Non-Electric Visual Flow Indicator and Flow Setter
The Visual Flow Control (VFC) is designed to balance heating circuits in both light commercial and residential applications.
Flow Meter (gpm)

Specifications
The Watts VFC is a non-electric visual flow indicator and flow setter. Commercial quality brass casting is machined for precision fit and function. The visual flow indicator features a rotatable scale for added flexibility in mounting. Each VFC allows zone-by-zone control and flow optimization. Available with 1" (25.4 mm) MPT half unions or 1" (25.4 mm) FPT connections. Technical Data Maximum Operating Temperature Minimum Operating Temperature Maximum Admitted Operating Pressure Accuracy 194 F (90.0C) -4 F (-20.0 C) 164 psi (11.3 bar) +/- 10%
Flow Adjustment Screw

Visual Flow Control

b ar

psi

Installation Parameters
Install in accordance with the requirements of all applicable building codes, and regulations. -  The VFC will work in any position. Flow direction is indicated by the arrow on the brass housing. A straight piece of tube (the same length as the valve body) is recommended on the upstream side to provide accurate flow monitoring. - The flow meter indicates the flow rate in gallons per minute (GPM) and can be fully rotated, facilitating easy and exact reading. -P  art of the VFCs unique design places the meter outside the actual fluid flow, preventing damage by system debris and dirt. - The regulating valve can be set to the desired flow by using an Allen key tool. The actual flow rate can be seen on the visual flow indicator. Several turns are required to fully open the valve. The flow meter provides accurate flow measuring for both water and water/glycol solutions when fluid conditions are above 68F (20.0C).

(12) 174 (10) 145 (8) (6) (4) (2) 116 87 58 29 0 F C


68 (20) 86 (30) 104 (40) 122 (50) 140 (60) 158 (70) 176 (80) 194 (90) 212 230

(100) (110)

Qty

Description 0.5-4 GPM (0.03 L/sec -0.25 L/sec), 1" (25.4 mm) MPT Half Unions 0.5-4 GPM (0.03 L/sec -0.25 L/sec), 1" (25.4 mm) FPT Ends

Order # 0955319 0955320

CAUTION

This Engineering Sheet is not intended to provide full installation instructions and safety information. In order to avoid property damage or injury, please refer to the complete installation manual and product safety information provided with the product.
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
N

OT FOR

USA: No. Andover, MA Tel. (855) 699-2887 Fax: (978) 794-1848 radiant.watts.com Canada: Burlington, ONT. Tel. (905) 332-4090 Fax: (905) 332-7068 radiant.watts.com

TA

BLE

ES-Visual-Flow-Control 1145