INTRODUCTION
Infrastructure Alarm and Monitoring System (IAMS) is unique product, combination of IT & Embedded electronics, designed to meet the requirements of telecom service providers, infrastructure providers and operating & maintenance staff. In the telecom cell sites, there is a need to monitor the site data like EB,DG, Site alarms and Site environment conditions for better maintenance of the sites. IAMS collect periodic as well as alarm data and events data from BTS site for remote logging to server through GPRS in preferable mode or SMS in absence of GPRS.

MIMU

IAMS

Netwing Technologies Pvt. Ltd., India.

Page 1

IAMS
FEATURES/BENEFITS
1. IAMS monitor the site data like EB, DG, Site alarms and Site environment conditions for better maintenance of the sites. 2. IAMS collect periodic as well as alarm data and events data from BTS site for remote logging to server. 3. It is remotely logging through GPRS in preferable mode or SMS in absence of GPRS. 4. It has provision for two GPRS enabled SIMs. 5. Priority can be given to any GPRS/SMS while logging data to remote server. 6. It pickups and integrate the alarms and status which are already wired in the BTS site. 7. It provides alarms to BTS so that the existing alarm system continues as it was earlier. 8. It ensures that the existing system and BTS is not adversely affected. 9. We supply and install the sensors along with necessary wires, cables and all the accessories etc. whenever required and without any additional cost to capture the alarms from the BTS site. 10. The temperature sensor has accuracy of 0.5 degree whereas the accuracy of the other sensors is +/- 1%. 11. Beside this, IAMS controls and monitors the access of BTS panels to authorized person. 12. It allows ONLY authorized person to enter the restricted area and record the event all authorized and unauthorized event of access.

Netwing Technologies Pvt. Ltd., India.

Page 2

IAMS
SYSTEM ARCHITECTURE
Infrastructure Alarm and Monitoring System consists of three modules. 1) Multi Input Modem Unit 2) Access Control Unit 3) Alarm Monitoring Equipment

Netwing Technologies Pvt. Ltd., India.

Page 3

IAMS
TECHNICAL SPECIFICATIONS
Electrical Parameters monitored o EB Voltage for R, Y, B phase. o EB Current for R, Y, B phases. o EB Power factor for R, Y, B phases. o EB KWH, RunHrs and Frequency. o DG Voltage for R, Y, B phases. o DG Current for R, Y, B phases. o DG Power factor for R, Y, B phases. o DG KWH, RunHrs and Frequency. o BTS (Power Plant) Battery voltages and RunHrs. o DG Battery voltages. o Room Temperature. o Diesel Level in DG Tank. Electrical Parameters Ranges o Input Voltage : 240V Phase Current : 100 A Frequency : 50 Hz o Phase : Three o Accuracy : class 1.0. o Remote output : RS232/RS485. o Display : 16 X 2 LCD. o Meter Base : Metal o Terminal block Cover : Extended. o Diesel Level in DG Tank : 25%, 50%, 75%, 100%.

Alarms Monitored o BTS Site NOT on MAINS/DG/Battery alarm. o DG Battery low voltage alarm. o DG Low Lube Oil Pressure alarm. o DG Fail to Start alarm. o DG Fail to stop alarm. o DG fuel low level alarm. o DG High Canopy Temperature/High Water Temperature alarm. o Power Plant Battery (BTS battery) voltage below threshold alarm o High Room temp alarm. o Fire alarm. o Power Plant Battery (BTS battery) voltage output fail alarm. o Shelter door open/close alarm. o BTS door open/close alarm. o DG door open/close alarm. Page 4

Netwing Technologies Pvt. Ltd., India.

IAMS
Power Supply requirements Supply voltage range Internal protections Communication Modem User Interface (In each Unit) Display Keypad

: :

36 to 60 VDC. reverse polarity, over current.

Dual SIM modem

: :

2 X 16, characters Alphanumeric LCD. Keypad 4 X1 keys.

Environment Working temperature : 0 deg. To 70 deg. Humidity : RH 0 - 95% Cooling : Natural convection. Suitable for both Shelter and Outdoor applications. Input/output Connections Connections/Terminations : rated 300V, 10A . Industrial grade, touch proof and safety approved, with easy monitoring access. Installation System can be installed in a working cell site or new site without interrupting the BTS communication. It can be fixed on the PMU or SMPS or Battery. Enclosure : Each module has separate enclosure. Dust proof enclosure suitable for outdoor or shelter installation. For MIMU: Dimensions : L X W X H = 260 X 300 x 90 in mm. 19 rack mountable. Material: MS Weight: less than 2Kg. For AME: Dimensions : L X W X H = 215 X 225 x 55 in mm. Weight : Less than 2Kg. For ACU Dimensions : L X W X H = 130 X 110 X 40 mm. Weight : Less than 1Kg.