Generator Automatic Voltage Regulator Operation Manual

Self Excited Automatic Voltage Regulator Using IGBTs Insulated- Gate Bipolar Transistors

For use in Marathon* generators with PMG


* Use only for reference purpose only. This is not a Marathon Product

The EA08A-2000 is an Analog Voltage Regulator that uses IGBTs Power Devises in its power output, resembling the power stage of digital regulators. This design gives us the flexibility to use the output power from the Marathon* PMG to power the AVR. In addition, it has A1 and A2 terminals for use in remote biasing; biasing is required in automatic parallel ing and load sharing applications.

1. Specifications
Sensing Input Terminals

External Volts Adjustment 10% @ 1K PMG Input 200v Max 2 wire PMG Thermal Drift 0.05% per Degree Cchange in AVR ambient Analog Voltage Input 10% generator voltage per 1VDC Current Compensation 5 Amp CT (S2 to S1) 1 Amp CT (S2 to S3) Maximum 4% @ P.F. = 0.8 Dimensions 150mm L * 135mm W * 55.3mm H Weight 600g 2%

From E1 to 110v terminal (95 to 140 Volts) From E1 to 220v terminal (170 to 260 Volts) From E1 to 480v terminal (340 to 520 Volts) Under/Frequency 50 or 60 Hz DIP Switch selectable
Voltage Regulation < 0.5% using a

4% engine governor

Voltage Build-up Residual Volt. 5 VAC Output Voltage Maximum 90VDC @220VAC Output Current Continuous 8 A

Max 12 A for 10 sec

150.0 130.0

55.3 21.5

PMG

PMG

E2 220

F+ F-

110

E1

480

380

A1 A2 VR VR S1 S2 S3

135.0

115.0

xx/1 CT xx/5 CT

Generator Under Freguency LED indicator

UFRO UF
ON
1 2 3

STAB

DIP

DROOP VOLT

TRIM

ON
1 2 3

1-ON LARGER 500KW OFF LESS 500KW 2-ON 90-500KWOFF Less then 90Kw 3-ON 60HZOFF 50HZ

Do Not use a Megger with the AVR connected

______________________________________________________________________________________ 2
EA08A-2000

2. WIRING
1. E1 to 110V

3. ADJUSTMENTS
VOLT:

E1 to 220V E1 to 480V Sensing Input terminals


2. F+ & F- To Field
3. Connect the two PMG Capacitorn the circuit i

Generator output Volts adjust DROOP: Droop adjustment


DIP: Load Acceptance Adjustment (LAN) STAB: Stability Adjustment UFRO: Change knee point DIP Switches: Set generator reaction time DIP Switch1
ON = Larger then 500 kw OFF = Less then 500 kw .

5 Amp CT use terminals S1 & S2 4. S1-S2-S3: 1 Amp CT use terminals S2 & S3


5.

VR-VR Remote voltage adjustment 1k 1 watts Do not use for PF correction

6. A1 & A2 Provided Connection to PF controller or other devices, designed to work with signals up to +/- 5 Volts. Inputs must be fully floating. TRIM Adjustable

Warning: A leaking capacitor on the PMG circuit makes this AVR to run eratically and will not develop full output voltage. Remove the capacitor to fix . You can run the AVR without this capacitor temporally untill you preplace it with a new one.
PMG
Exciter field Armature

DIP Switch 2
ON = From 90 to 500kw OFF = Less then 90kw .

DIP Switch 3

ON = 60Hz OFF = 50Hz

Stator wires

C.T xxx:1A or xxx:5A

230VAC max 50 to 500 Hz

R L1 S L2 T L3

Connection to PF controller or PLC Paralleling control Use TRIM Pot to adjust sensibility

+/-5v
1k

Use original spare (10A) fuse for replacement. Products specification and appearance may be modified without prior notice. ______________________________________________________________________________________ EA08A-2000 3

1 2 3

ON
ON
1

PMG

1-ON LARGER 500KW OFF LESS 500KW 2-ON 90-500KWOFF Less then 90Kw 3-ON 60HZOFF 50HZ

2 3

UFRO STAB DIP DROOP VOLT TRIM


VR VR A2 S2 S1 S3 A1

PMG

F+ FE1
110V 220V
380/480v

S2 to S1=5A CT S2 to S3=1A CT