TUTORIAL SCOPE
1. FUNDAMENTALS 2. CHARACTERISTICS 3. POLARIZATION 4. ZONES SETTING CRITERIA 5. MHO VS QUADRILATERAL 6. SWITCH ON TO FAULT 7. POWER SWING BLOCKING/TRIPPING
20 December 2010 Protection Courses 2
TUTORIAL SCOPE
8. LOAD ENCROACHMENT 9. LOSS OF POTENTIAL 10. UNIT PROTECTION 11. PERMISSIVE UNDER REACH 12. PERMISSIVE OVER REACH 13. CARRIER BLOCKING 14. CURRENT REVERSAL
20 December EXTENSION Protection Courses 15. ZONE 1 2010 3
TUTORIAL SCOPE
16. WEAK IN-FEED 17. SERIES COMPENSATION 18. MUTUAL COMPENSATION 19. AUTO RECLOSER 20. STUB PROTECTION 21. CCVT TRANSIENT 22. DIRECTIONAL EARTH FAULT
20 December 2010 Protection Courses 4
MHO
MHO CHARACTERISTICS
20 December 2010 Protection Courses 5
MHO CHARACTERISTICS
20 December 2010
Protection Courses
Quadrilateral
QUADRILATERAL CHARACTERISTICS
20 December 2010 Protection Courses 7
20 December 2010
Protection Courses
20 December 2010
Protection Courses
POLARIZATION METHODS
SELF POLARIZATION Terminal faults will not cover CROSS POLARIZATION Use other healthy phase voltages Terminal three phase fault will not cover MEMORY POLARIZATION Covers all type of faults
20 December 2010 Protection Courses 10
POLARIZATION METHODS
20 December 2010
Protection Courses
11
Time
Relay A
Relay B
Relay C
Relay D
Zone 3R
Zone 1
Zone 2
Zone 3F
Zone 2
Zone 3R Zone 1
Zone 3R
Zone 1
Zone 2
Zone 3
Zone 2
Zone 1
Zone 3R
20 December 2010
Protection Courses
12
X
A B C
20 December 2010
Protection Courses
13
SWITCH ON TO FAULT
SWITCH ON TO FAULT. Failure to remove Earth Clamps after CB Maintenance Practically Zero Impedance in fault path. Fault Point is at the Origin - Boundary condition for Zones 1 & 2 For a 3-Phase fault, cross-polarising will have no effect
20 December 2010
Protection Courses
14
SOTF ALGORITHMS
AC SOTF - Used where VT is on LINE SIDE of the CB IF Current and Voltage have been Dead for 10 Secs AND the Current Rises ABOVE 30% of Nominal AND Voltage remains BELOW 20% of Nominal THEN Remove the Time Delay from Zone 3 AND Allow tripping on Overcurrent only FOR 200ms DC SOTF - Used where VT is on BUSBAR SIDE of the CB When Circuit Breaker Manual Close Handle is Operated Remove the Time Delay from Zone 3 FOR 400ms (Longer delay allows for CB Closing time)
20 December 2010 Protection Courses 15
Power Swing Outer boundary If the System Impedance Remains in the Power Swing Detection Zone for longer than the PSD Transit Time (Nominally 50 ms) POWER SWING ALARM will Operate Power Swing Inner
Zone 3
Zone 2
Zone 1
20 December 2010
16
20 December 2010
Protection Courses
17
LOAD ENCROACHMENT
20 December 2010
Protection Courses
18
LOSS OF POTENTIAL
20 December 2010
Protection Courses
19
Operation of Zone 1 sends signal to remote end Instantaneous trip if Zone 1 Operation Zone 2 + Signal from Remote end
S/Stn 1
Relay A
Signalling Channel
Zone 2 Carrier Aided Trip
Relay B
Relay C
Time
Distance
Zone 2
Zone 1
Distance
Instantaneous Operation of Zone 2 sends signal to remote end Instantaneous trip if Zone 1 Operation Zone 2 + Signal from Remote end
SIGNALLING CHANNEL REQUIRED BETWEEN ENDS
Signalling Channel
Zone 2 Carrier Aided Trip
Relay B
Relay C
Time
Distance
Zone 2
Distance
Operation of Zone 4 sends blocking signal to remote end Instantaneous trip if Zone 1 Operation Zone 2 + No blocking Signal from Remote end WITHIN the Permissive Trip Time
S/Stn 1
BLOCKING SCHEME
SIGNALLING CHANNEL REQUIRED BETWEEN ENDS
S/Stn 2
Relay A
Signalling Channel
Zone 2 Carrier Aided Trip
Relay B
Relay C
Time
Distance
Zone 2
Zone 1
Zone 4 - Blocking
Distance
Operation of Zone 4 sends blocking signal to remote end Instantaneous trip if Zone 1 Operation Zone 2 + NO BLOCKING SIGNAL from Remote End WITHIN the Permissive Trip Time
S/Stn 1
BLOCKING SCHEME
Signalling Channel
Zone 2 Carrier Aided Trip
S/Stn 2
Relay A
Relay B
Relay C
Time
Distance
Zone 2
Zone 1
Distance
CURRENT REVERSAL
20 December 2010
Protection Courses
24
CURRENT REVERSAL
20 December 2010
Protection Courses
25
CURRENT REVERSAL
20 December 2010
Protection Courses
26
No Signalling used between ends Used with Auto-Recloser only Results in More Breaker Operations
S/Stn 1
Gives improved fault clearance time for fault @ this position
S/Stn 2
S/Stn 3
Relay A
Relay B
Relay C
Relay C
Time
Trip Reclose
Zone 1 Ext
Distance
Zone 1
Zone 2
Zone 3F
Distance
20 December 2010
Protection Courses
28
SERIES COMPENSATION
Used to increase load capacity Improve power system stability Improve load division on parallel paths Reduce transmission losses
20 December 2010
Protection Courses
29
Voltage reversal
SERIES COMPENSATION
20 December 2010
Protection Courses
30
Ib
MUTUAL COMPENSATION 1
20 December 2010 Protection Courses 31
MUTUAL COMPENSATION 2
When one of the lines is out of service and earthed at both ends Energise a Status Input SWITCH TO ALTERNATE SETTINGS group
ALTERNATE SETTING GROUP uses Increased Earth Fault Compensation Factor to take account of the Zero Sequence Mutual Coupling due to the parallel line
20 December 2010
Protection Courses
32
CCVT TRANSIENT
20 December 2010
Protection Courses
33
Distance element may over reach CCVT Trans. Reduce the fundamental component of the fault voltage results in decrease in the calculated impedance High capacitance reduced transient effect Passive Ferro-resonance reduced transient effect
CCVT TRANSIENT
20 December 2010
Protection Courses
34
CCVT TRANSIENT
20 December 2010 Protection Courses 35
Unrestricted Characteristic Operates for any fault current above setting in selected direction
X
Detects high impedance earth faults Operate quantity - residual current Polarising quantity - residual voltage Line Angle
Line Angle
Reverse DEF
20 December 2010
Protection Courses
37
If no Signalling Channel is available OR Signalling Channel fails RELAY CAN OPERATE AS BACK-UP TIME GRADED OVER CURRENT
20 December 2010 Protection Courses 38