Air-Cooled Liquid Chillers

30XA 252-1702
Nominal cooling capacity 270-1700 kW
The Aquaforce liquid chillers are the premium solution for industrial and commercial applications where installers, consultants and building owners require optimal performances and maximum quality. The Aquaforce liquid chillers are designed to meet current and future requirements in terms of energy efficiency and operating sound levels. They use the best technologies available today: - Twin-rotor screw compressors with a variable capacity valve. - Single refrigerant R134a. - Low-noise generation IV Flying Bird fans made of composite material. - Aluminium micro-channel heat exchangers (MCHX). - Touch-screen Pro-Dialog control system. To meet to all environmental and economic requirements, the Aquaforce is available in two versions: One offers an extremely low noise level while at the same time boasting superior energy efficiency. The other offers unequalled energy efficiency to satisfy the most stringent demands of building owners wanting to reduce operating costs to the minimum. This version is also recommended for applications in geographical zones where the air temperature is very high.

Features and advantages Very economical operation

Extremely high full load and part load energy efficiency: - Eurovent energy efficiency class A, average EER above 3.20 kW/kW (high-efficiency option) - Average ESEER above 4 kW/kW - New twin-rotor screw compressor equipped with a highefficiency motor and a variable capacity valve that permits exact matching of the cooling capacity to the load. - All aluminium condenser with micro-channels that is more efficient than a copper/aluminium coil. - Flooded shell-and-tube evaporator to increase the heat exchange efficiency. - Electronic expansion device permitting operation at a lower condensing pressure and improved utilisation of the evaporator heat exchange surface (superheat control). - Economizer system with electronic expansion device for increased cooling capacity

Low operating sound levels

Compressors - Discharge dampers integrated in the oil separator (Carrier patent). - Silencer on the economiser return line. - Acoustic compressor and oil separator enclosure reducing radiated noise Condenser section - Condenser coils in V-shape with an open angle, allowing quieter air flow across the coil - Low-noise 4th generation Flying Bird fans, made of a composite material (Carrier patent) are now even quieter and do not generate intrusive low-frequency noise - Rigid fan mounting preventing start-up noise (Carrier patent)

Absolute reliability

Easy and fast installation

Integrated hydronic module (option) - Centrifugal low or high-pressure water pump (as required), based on the pressure loss of the hydronic installation - Single or dual pump (as required) with operating time balancing and automatic changeover to the back-up pump if a fault develops - Water filter protecting the water pump against circulating debris - High-capacity membrane expansion tank ensures pressurisation of the water circuit - Thermal insulation and aluminium protection - Pressure sensor to check filter pollution and for direct numerical display of the water flow rate with an estimate of the instantaneous cooling capacity at the control interface - Water flow control valve Simplified electrical connections - Main disconnect switch with high trip capacity - Transformer to supply the integrated control circuit (400/24 V) Fast commissioning - Systematic factory operation test before shipment - Quick-test function for step-by-step verification of the instruments, expansion devices, fans and compressors

Screw compressors - Industrial-type screw compressors with oversized bearings and motor cooled by suction gas. - All compressor components are easily accessible on site minimising down-time. - Protection increased by an electronic board. Air condenser - All aluminium micro-channel heat exchanger (MCHX) with a corrosion resistance that is 3.5 times higher than for a traditional coil. The all aluminium design eliminates the formation of galvanic currents between aluminium and copper that cause coil corrosion in saline or corrosive environments. Evaporator - Thermal insulation with aluminium sheet finish for perfect resistance to external aggression (mechanical and UV protection). Auto-adaptive control - Control algorithm prevents excessive compressor cycling (Carrier patent) - Automatic compressor unloading in case of abnormally high condensing pressure. If condenser coil fouling or fan failure occurs, the Aquaforce continues to operate, but at reduced capacity Exceptional endurance tests - Partnerships with specialised laboratories and use of limit simulation tools (finite element calculation) for the design of critical components. - Transport simulation test in the laboratory on a vibrating table. The test is based on a military standard and equivalent to 4000 km by truck. - Salt mist corrosion resistance test in the laboratory for increased corrosion resistance Pro-Dialog combines intelligence with operating simplicity. The control constantly monitors all machine parameters and precisely manages the operation of compressors, electronic expansion devices, fans and of the evaporator water pump for optimum energy efficiency.

Pro-Dialog control

Environmental care

R134a refrigerant - Refrigerant of the HFC group with zero ozone depletion potential - 30% reduction in the refrigerant charge through the use of micro-channel heat exchangers Leak-tight refrigerant circuit - Reduction of leaks as no capillary tubes and flare connections are used - Verification of pressure transducers and temperature sensors without transferring refrigerant charge - Liquid line service valve for simplified maintenance

Energy management - Internal time schedule clock: controls chiller on/off times and operation at a second set-point - Set-point reset based on the outside air temperature or the return water temperature - Master/slave control of two chillers operating in parallel with operating time equalisation and automatic changeover in case of a unit fault Ease-of-use - User interface with large touch screen (120 x 99 mm) for intuitive access to the operating parameters. The information is in clear text and can be displayed in local language (please contact your distributor).

Remote management (standard)

Aquaforce is equipped with an RS485 serial port that offers multiple remote control, monitoring and diagnostic possibilities. Carrier offers a vast choice of control products, specially designed to control, manage and supervise the operation of an air conditioning system. Please consult your Carrier representative for more information. Aquaforce also communicates with other building management systems via optional communication gateways. A connection terminal allows remote control of the Aquaforce by wired cable: - Start/stop: opening of this contact will shut down the unit - Dual set-point: closing of this contact activates a second set-point (example: unoccupied mode) - Demand limit: closing of this contact limits the maximum chiller capacity to a predefined value - Heat reclaim (option): closing of this contact allows heat reclaim mode operation - Water pump 1 and 2 control*: these outputs control the contactors of one or two evaporator water pumps - Water pump on reversal*: these contacts are used to detect a water pump operation fault and automatically change over to the other pump - Operation indication: this volt-free contact indicates that the chiller is operating (cooling load) or that it is ready to operate (no cooling load) - Alert indication: this volt-free contact indicates the necessity to carry out a maintenance operation or the presence of a minor fault - Alarm indication: this volt-free contact indicates the presence of a major fault that has led to the shut-down of one or several refrigerant circuits * not available for units with the hydronic module option

Remote management (EMM option)

The Energy Management Module offers extended remote control possibilities: - Room temperature: permits set-point reset based on the building indoor air temperature (with Carrier thermostat) - Set point reset: ensures reset of the cooling set-point based on a 4-20 mA or 0-5 V signal - Demand limit: permits limitation of the maximum chiller power or current based on a 0-10 V signal - Demand limit 1 and 2: closing of these contacts limits the maximum chiller power or current to two predefined values. - User safety: this contact can be used for any customer safety loop; opening of the contact generates a specific alarm - Ice storage end: when ice storage has finished, this input permits return to the second set-point (unoccupied mode) - Time schedule override: closing of this contact cancels the time schedule effects - Out of service: this signal indicates that the chiller is completely out of service - Chiller capacity: this analogue output (0-10 V) gives an immediate indication of the chiller capacity

New generation 06T screw compressor

The new generation of the Carrier 06T screw compressors benefits from Carriers long experience in the development of twin-rotor screw compressors. The compressor is equipped with bearings with oversized rollers, oil pressure lubricated for reliable and durable operation, even at maximum load. A variable control valve controlled by the oil pressure permits infinitely variable cooling capacity. This system allows optimal adjustment of the compressor cooling capacity and ensures exceptionally high stability of the chilled water leaving temperature.

Among the other advantages: if a fault occurs e.g. if the condenser is fouled or at very high outside temperature, the compressor does not switch off, but continues operation with a reduced capacity (unloaded mode). The compressor is equipped with a separate oil separator that minimises the amount of oil in circulation in the refrigerant circuit and with its integrated silencer considerably reduces discharge gas pulsations for much quieter operation. 3

All-aluminium micro-channel heat exchanger (MCHX)

Already utilised in the automobile and aeronautical industries for many years, the MCHX used in the Aquaforce is entirely made of aluminium. This one-piece concept significantly increases its corrosion resistance by eliminating the galvanic currents that are created when two different metals (copper and aluminium) come into contact in traditional heat exchangers. Unlike traditional heat exchangers the MCHX heat exchanger can be used in moderate marine and urban environments.

From an energy efficiency point-of-view the MCHX heat exchanger is approximately 10% more efficient than a traditional coil and allows a 30% reduction in the amount of refrigerant used in the chiller. The low thickness of the MCHX reduces air pressure losses by 50% and makes it less susceptible to fouling (e.g. by sand) than a traditional coil. Cleaning of the MCHX heat exchanger is very fast using a high-pressure washer.

Pro-Dialog operator interface with touch-screen

The Aquaforce operator interface is very user-friendly. It is a large-format touch-screen, and the information is easily accessible: clear text in the selected language allows

consultation of all operating parameters. Up to eight screens can be personalised.

Options and accessories


Options Corrosion protection, traditional coils Corrosion protection, traditional coils Low temperature glycol solution Very low temperature glycol solution Unit equipped for air discharge ducting IP 54 control box Tropical applications Grilles Enclosure panels Winter operation Evaporator frost protection Evaporator and hydronic module frost protection Heat reclaim Single power connection point Service valve Discharge valve Evaporator with one pass more Evaporator with one pass less 21 bar evaporator Reversed water connections High-pressure single-pump hydronic module High-pressure dual-pump hydronic module Low-pressure single-pump hydronic module Low-pressure dual-pump hydronic module Direct-expansion free-cooling system High energy efficiency JBus gateway BacNet gateway LON gateway Energy Management Module EMM High pressure switch to comply with German (VBG 20) and Dutch (RLK) standards Dual safety valve installed with three-way valve Swiss code compliance in addition to PED code Russian code compliance (GOST) Australian code compliance Unit without enclosure Traditional coils (Cu/Al) Traditional coils (Cu/Al) without slots Suction piping insulation Low sound level Very low sound level (second attenuation level) MCHX anti-corrosion protection Accessories CCN JBus gateway CCN BacNet gateway CCN LON Talk gateway Connection sleeve Energy Management Module EMM Lead-lag kit Anti-vibration mountings No. 2B 3A 5 6 10 20A 22 23 23A 28 41A 41B 50 81 92 93A 100A 100C 104 107 116B 116C 116F 116G 118A 119 148B 148C 148D 156 193 194 197 199 200 253 254 255 256 257 258 263

Description Factory application of Blygold Polual treatment on the copper/ aluminium coils Fins made of pre-treated aluminium (polyurethane and epoxy) Low temperature chilled water production down to -6C with ethylene glycol and -3C with propylene glycol Low temperature chilled water production down to -12C with ethylene glycol (limited to -10C for certain sizes) and -8C with propylene glycol (limited to -6C for certain sizes) Fans with available pressure equipped with discharge connection flanges Increased leak tightness of control boxes Unit control box suitable for tropical applications Metallic grilles on the unit front, rear and sides Side panels at each end of the coil Fan speed control via frequency converter Resistance heater on the evaporator Resistance heater on the evaporator and the hydronic module Complete recovery of the heat rejected by the condenser Power connection of the machine via one main supply connection Shut-off valves on the compressor suction piping, the economiser line and the compressor discharge piping Shut-off valves on the compressor discharge piping Evaporator with one pass more, water-side Evaporator with one pass less, water-side Reinforced evaporator for extension of the maximum water-side service pressure range to 21 bar Evaporator with reversed water inlet/outlet See hydronic module chapter See hydronic module chapter See hydronic module chapter See hydronic module chapter Chilled water production without the use of the compressors, using direct-expansion heat exchange on the condensers Improved condenser performance Two-directional communications board, complies with JBus protocol Two-directional communications board, complies with BacNet protocol Two-directional communications board, complies with LON protocol See chapter Energy Management Module One PZH/PZHH high-pressure switch per compressor Three-way valve upstream of the safety valves on the evaporator and the oil separator Additional tests on the water heat exchangers. Additional supply of PED documents, supplementary certificates and test certificates. GOST certification Heat exchanger approved in accordance with the Australian code. Compressors not equipped with acoustic enclosure Coils made of copper tubes with aluminium fins Coils made of copper tubes with aluminium fins without slots Thermal insulation of the suction piping with flexible, anti-UV insulant Sound insulation of certain unit refrigerant circuit components (suction, evaporator and economiser piping) Additional sound insulation

Advantages Improved corrosion resistance, recommended for industrial, rural and marine environments Improved corrosion resistance, recommended for moderate marine and urban environments Covers specific applications such as ice storage and industrial processes Covers specific applications such as ice storage and industrial processes Facilitates connection to the discharge ducts Increased control box protection Reduced relative humidity in the control box for operation in tropical environments (hot and humid) Enhanced aesthetics, protection against intrusion to the unit interior Enhanced aesthetics Stable unit operation when the air temperature is between -10C and -20C Evaporator frost protection down to -20C outside temperature Evaporator and hydronic module frost protection down to -20C outside temperature Free hot-water production as well as cold-water production Quick and easy installation Simplified maintenance Simplified maintenance Increased water inlet and outlet pressure loss on opposite sides Reduced water inlet and outlet pressure loss on opposite sides Covers applications with a high water column (high buildings) Simplification of the water piping Easy and fast installation Easy and fast installation, operating safety Easy and fast installation Easy and fast installation, operating safety Very economical chilled water production at low outdoor temperatures Energy cost reduction, full load operation at higher air temperatures Easy connection by communication bus to a building management system Easy connection by communication bus to a building management system Easy connection by communication bus to a building management system Easy connection by wired connection to a building management system Conformance with German and Dutch regulations Valve replacement and inspection facilitated without refrigerant loss. Conforms to European standard EN378/BGVD4 Conformance with Swiss regulations in addition to PED code Conformance with Russian regulations (GOST) Conformance with Australian regulations More economical Possibility to add specialised condenser treatment Recommended for the Middle East, sand storms. Possibility to add specialised condenser treatment. Prevents condensation on the suction piping Unit sound power level reduction of -3 dB(A)

Use 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1502 30XA 252-1002 30XA 252-1502 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1002 30XA 252-1702 30XA 252-1702 30XA 252-502 30XA 252-502 30XA 252-502 30XA 252-502 30XA 252-1002 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702 30XA 252-1702

Unit sound power level reduction of -1 to -3 dB(A), depending on unit size, compared to option 257 Carrier factory treatment of the MCHX heat exchanger for The Super Enviro-Shield option was developed to extend the applications in aggressive environments application range of MCHX heat exchangers in severe environmental conditions: this option is compulsory in industrial and coastal environments. Description Advantages See option 148B See option 148B See option 148C See option 148C See option 148D See option 148D Piping to be welded with Victaulic connection Ease-of-installation See controls manual Easy connection by wired connection to a building management system Additional water outlet temperature sensor kit, field-installed, allows Optimised operation of two chillers connected in parallel with master/slave operation of two chillers connected in parallel. operating time balancing. Elastomeric anti-vibration mountings for each unit weight Absorption of vibrations, linked to the unit operation (essentially distribution point compressor)

Use See option 148B See option 148C See option 148D 30XA 252-1702 30XA 252-1702 30XA 252-1502 30XA 252-1702

Hydronic module (option 116)


Typical hydronic circuit diagram
Legend

2 9 9

15

C
12

D 9

A 9 4 12 5

13

16

17

10

A B C D 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 ----

Components of unit and hydronic module Pressure sensor (A-B = p evaporator) Pressure sensor Pressure sensor (C-D = p water filter) Pressure sensor Victaulic screen filter Expansion tank Safety valve Available pressure pump Drain valve Water flow control valve Evaporator Evaporator defrost heater (option) Hydronic module defrost heater Air vent (evaporator) Water purge (evaporator) Expansion compensator (flexible connections) Flow switch Water temperature sensor System components Air vent Flexible connection Shut-down valves Charge valve Hydronic module (option)

16 18

17

B 9 14

11

Low-pressure pump (hydronic module option)


200

Available static system pressure

High-pressure pump (hydronic module option)


400 375 350 325 300 275 250 225 200 175 150 125 100 75 50

150 125 100 75 50 25 0 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 Water flow rate, l/s

1 2

Available static pressure, kPa)

Available static pressure, kPa

175

1 2

3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 Water flow rate, l/s

Legend 1. 30XA 252-302 2. 30XA 352 3. 30XA 402 4. 30XA 452-502

Legend 1. 30XA 252 2. 30XA 302-352 3. 30XA 402 4. 30XA 452-502

Suitable for heating, domestic hot water preparation, agriculture and food industry, industrial processes and other hot-water requirements. With the total heat reclaim option it is possible to reduce the energy consumption bill considerably compared to conventional heating equipment such as fossil fuel boilers or electric water tanks.

Condenser leaving water temperature, C

Total heat reclaim (option 50)

65 60 55 50 45 40 35 30 25 20 0 5 10 15

Operating principle

If hot water production is required, the compressor discharge gases are directed towards the heat reclaim condenser. The refrigerant releases its heat to the hot water that leaves the condenser at a temperature of up to 60C. In this way 100% of the heat rejected by the liquid chiller can be used to produce hot water. When the demand for heat is satisfied, the hot gas is again directed towards the air condenser where the heat is rejected to the outside air by the fans. Hot water temperature control is ensured by the chiller Pro-Dialog control that independently controls the reclaim operation of each refrigerant circuit. Note: Heat reclaim is only possible, if the unit produces cold water at the same time.
Condenser water temperature (C) Entering temperature at start-up Entering temperature during operation Leaving temperature during operation Evaporator water temperature (C) Entering temperature at start-up Entering temperature during operation Leaving temperature during operation Minimum 12.5* 20 25 6.8 3.3 Maximum 55 55 60 45 21 15

Evaporator leaving water temperature, C

Full load Part load limit, approx. 60% Minimum load limit, approx. 30%

Part load operating limits (evaporator leaving water temperature = 7C)


Maximum condenser leaving water temperature, C

60 55 50 45 40 100 90 80 70 60 50 40 30

* The entering water temperature at start-up must not fall below 12.5C. For installations with a lower temperature a three-way valve must be used.

Note: If the evaporator leaving water temperature is below 4C, a glycol-water solution or the frost protection option must be used.

In part-load operation, the limitation of the condenser leaving water temperature is due to the operating range of the screw compressor. If the condenser leaving water temperature is above the limit value given in the curves on the right, the unit will automatically change over to the mode without heat recovery:

Unit load, %

These are the same as for the standard unit except:


30XA heat reclaim mode Cooling capacity* Heating capacity in heat reclaim mode Total power input (unit)* Total energy efficiency ratio (EER) Total energy efficiency ratio (COP) Operating weight** Refrigerant charge Circuit A Circuit B Heat reclaim condenser Water volume Water connection Diameter Outside diameter kW kW kW kW/kW kW/kW kg kg kg l inch mm 252 261 336 82 3,16 4,07 4230 302 291 373 90 3,22 4,13 4270

Physical data

352 311 401 99 3,15 4,06 4280

402 379 481 113 3,36 4,27 5260

452 438 554 128 3,40 4,31 5380

502 493 620 140 3,53 4,46 5880 62 39 68

602 603 760 172 3,52 4,44 7000 62 62

702 665 832 183 3,63 4,55 7100 62 66

752 707 894 206 3,43 4,35 7470 70 62

802 775 974 219 3,53 4,45 7680 74 69

852 814 1027 234 3,48 4,40 8320 77 68

902 875 1105 253 3,45 4,38 8670 74 77

1002 971 1229 283 3,42 4,35 9280 96 94

* Entering and leaving water temperature: evaporator 12C/7C; heat reclaim condenser: 40C/45C ** Weights are for guidance only

36 37 37 53 54,5 38 38 39 37 39 Flooded shell-and-tube condenser 38 38 38 55 68 Type Victaulic 3 3 3 4 4 88.9 88.9 88.9 114.3 114.3

55 + 55 55 + 55 55 + 68 55 + 68 55 + 68 68 + 68 68 + 68 4 114.3 4 114.3 4 114.3 4 114.3 4 114.3 4 114.3

4 4 114.3 114.3

The DX free cooling option permits significant energy savings for all applications that require cooling in winter. In the free cooling mode the compressors are stopped and only the fan and cooling micro-pump are running. The changeover from compressor cooling mode to free cooling mode is automatically controlled by the Pro-Dialog control, based on the chiller heat load and the temperature difference between chilled water and ambient air. Important: In order to optimise chiller performances, it is recommended to use the leaving water set point reset function.

DX free cooling system (option 118A)

Advantages of the DX free cooling system

Operating principle

When the chilled water-air temperature difference exceeds a threshold value, the Pro-Dialog control carries out a comparison between the instantaneous chiller cooling capacity and the available free cooling capacity. If the operating conditions allow free cooling operation, the compressors are stopped, a set of valves on the suction piping connects the evaporator with the condenser, allowing the migration of the refrigerant vapours to the condenser. The refrigerant condenses in the condenser coils, and the cooling micro-pump transports the liquid to the evaporator. The cooling capacity in free cooling mode is controlled by the opening of the electronic expansion valve (EXV). Operation in combined FC (free-cooling) and MC (mechanical cooling) mode is possible in the two independent refrigerant circuits. This can optimise the free-cooling operations and at the same time ensures that the cooling requirements of the system are met.

Operation without glycol Unlike traditional hydronic free-cooling systems that require the use of a glycol solution, the Aquaforce DX free cooling chiller works with pure water. The evaporator is protected against frost down to -20C by an electric resistance heater (option). Low water pressure losses The Aquaforce DX free cooling chiller does not include a three-way valve nor free cooling coils connected in series with the evaporator. The Aquaforce free cooling chiller has the same water pressure losses as a standard chiller. Weight and dimensions gain - The DX free cooling option has practically no impact on the weight of the liquid chiller. - The Aquaforce free cooling chiller has the same dimensions as a standard chiller. Increased energy efficiency - In free cooling mode only the fans and the cooling micropump run. At an air-water temperature difference of 10 K for example the average chiller energy efficiency (EER) is 23 (kW/kW). - In the mechanical cooling mode chiller thermal and energy performances are not reduced by the use of a water-glycol solution. - As the pressure losses of the water circuit are low, the water pumps use less energy.

30XA 252-1002 in free-cooling mode

Cooling capacities

EER

FC mode Circuit 1: FC Circuit 2: FC Mixed mode Circuit 1: MC Circuit 2: FC MC mode Circuit 1: MC Circuit 2: MC Delta T (K)

Condenser entering air temperature, C LWT 0 -5 Cap Unit EER Cap Unit EER C kW kW kW/kW kW kW kW/kW 252 10 146 6 24.3 186 6 30.8 302 146 6 24.5 186 6 31 352 146 6 24.6 186 6 31 402 188 8 23.1 261 8 31.9 452 191 8 24 266 8 33.2 502 214 9 24 299 9 33.2 602 260 11 24 382 11 34.3 702 280 12 23.4 412 12 34.1 752 282 12 24.1 414 12 35.1 802 282 12 23.6 412 12 34.3 852 326 14 23.4 480 14 34.1 902 330 14 23.9 485 14 34.7 1002 370 15 24.1 544 15 35
Legend LWT Cap kW Unit kW EER kW/kW Leaving water temperature Cooling capacity Unit power input (compressors, fans, control) Energy efficiency ratio

-10 Cap kW 189 190 189 281 286 323 425 459 461 459 534 540 605

Unit kW 6 6 6 8 8 9 11 12 12 12 14 14 16

EER kW/kW 31 31.3 31.3 33.9 35.4 35.5 37.8 37.6 38.7 37.8 37.6 38.3 38.6

Legend MC Mechanical cooling (compressors) FC Free cooling Delta T Difference between the leaving water temperature and the entering air temperaure (K)

Operating limits
Evaporator water temperature, C Minimum leaving water temperature Maximum leaving water temperature Condenser water temperature, C Minimum leaving air temperature Maximum leaving air temperature

Free-cooling mode 3.3 25 -20 20

Mechanical cooling mode (compressors) 3.3 15 -20* 55

* For operation at an air temperature below -10C option 28 (winter operation) is required.

Physical data
30XA Nominal cooling capacity* Standard unit Power input EER Eurovent class cooling ESEER Nominal cooling capacity* Unit with option 119 Power input EER Eurovent class cooling ESEER Operating weight** Standard unit + option 119*** Option 254*** Sound levels Standard-efficiency unit Sound power level**** dB(A) Sound pressure level at 10 m dB(A) Standard unit + option 257 Sound power level**** dB(A) Sound pressure level at 10 m dB(A) Standard unit + option 258 Sound power level**** dB(A) Sound pressure level at 10 m dB(A) High-efficiency unit (option 119) Sound power level**** dB(A) Sound pressure level at 10 m dB(A) Unit with options 119 + 257 Sound power level**** dB(A) Sound pressure level at 10 m dB(A) Compressors Circuit A Circuit B Circuit C Circuit D Refrigerant** Standard unit + option 119*** Circuit A kg Circuit B kg Circuit C kg Circuit D kg Option 254*** Circuit A kg Circuit B kg Circuit C kg Circuit D kg Capacity control Minimum capacity % Condensers Fans Qty. standard unit + option 119 Qty. option 254**** Standard total air flow l/s Standard speed r/s Evaporator Water content l Without hydronic module Water connections, inlet/outlet Diameter in Outside diameter mm Max. water-side pressure kPa With hydronic module (option 116) Water connections, inlet/outlet Diameter in Outside diameter mm Expansion tank volume l Max. water-side pressure kPa Chassis paint colour * ** *** **** 252 kW kW kW/kW kW/kW kW kW kW/kW kW/kW kg 268 86.7 3.09 B 4.11 274 87.5 3.13 A 3.93 3740 4160 302 293 98 2.99 B 4.29 300 96.2 3.12 A 4.03 3780 4190 352 320 106 3.02 B 4.31 326 105 3.11 A 408 3820 4710 402 382 122 3.13 A 4.22 393 120 3.28 A 4.01 4673 5190 452 437 142 3.08 B 4.37 451 140 3.21 A 4.18 4743 5260 502 492 161 3.04 B 4.34 508 154 3.29 A 4.19 5174 5830 602 605 198 3.06 B 4.13 616 191 3.23 A 4.02 6097 6870 702 653 208 3.14 A 4.21 677 203 3.33 A 4.18 6247 7030 752 706 235 3.00 B 4.00 726 233 3.12 A 3.99 6547 7820 802 764 258 2.96 B 3.95 792 249 3.18 A 4.10 6847 8140 852 802 265 3.03 B 3.93 838 257 3.26 A 4.14 7308 8260 902 869 297 2.93 B 3.91 899 286 3.14 A 3.91 7648 9010 1002 1102 1202 1302 1352 1402 1502 1702 952 321 2.97 B 3.91 1000 310 3.23 A 3.95 8226 9260 1116 363 3.07 B 4.11 1147 348 3.30 A 4.24 1216 405 3.00 B 4.02 1247 388 3.21 A 4.10 1297 445 2.91 B 4.03 1354 425 3.19 A 4.23 1382 504 2.74 C 3.83 1442 463 3.11 A 4.15 1426 473 3.01 B 4.10 1468 451 3.25 A 4.13 1478 493 3.00 B 4.11 1523 470 3.24 A 4.12 4143/ 8637 4650/ 9340 97 64 94 61 92 59 100 67 99 66 1 1 1 92 95 100 140 129 135 10 24 24 82000 11.7 240 6/8 168.3/ 219.1 1000 1605 528 3.04 B 3.86 1675 513 3.27 A 4.04 7348/ 7348 8270/ 8270 97 64 94 61 92 58 101 67 99 65 1 1 1 1 77 66 77 66 130 95 130 95 8 28 28 95667 11.7 240 6/6 168.3 168.3 1000 -

10170 10610 10990 11350 4128/ 8141 11470 11890 12250 12640 4650/ 9180 96 63 93 60 91 58 99 66 98 65 1 1 1 69 66 100 102 92 135 10 19 19 64917 11.7 168 96 63 93 60 92 59 100 67 98 65 1 1 1 85 66 100 112 92 135 10 20 20 68333 11.7 182 96 63 93 60 91 58 99 66 98 65 1 1 1 87 68 100 112 92 135 10 20 20 68333 11.7 203 97 64 94 61 92 59 100 67 98 65 1 1 1 87 80 96 112 98 122 10 20 20 68333 11.7 224 97 64 94 61 92 59 101 68 99 66 1 1 1 100 85 100 140 103 135 10 24 24 82000 11.7 230 6/8 168.3/ 219.1 1000 -

89 57 86 54 94 62

89 57 86 54 94 62

89 57 86 54 94 62

92 60 89 57 95 63

93 61 90 58 88 56 95 63

93 61 90 58 88 55 95 63

93 62 91 59 88 57 96 65

92 61 90 57 88 55 96 64 95 62 1 1 62 66 100 95 15 12 12 41000 11.7 94

95 63 92 60 89 56 98 65 96 63 1 1 70 62 129 88 15 12 13 41000 11.7 98

95 63 92 59 89 56 98 66 96 63 1 1 70 57 112 95 15 12 13 41000 11.7 119

94 62 91 58 89 56 98 65 96 63 1 1 77 66 130 95 15 14 14 47833 11.7 119

96 63 93 60 89 57 99 66 97 64 1 1 70 75 129 103 15 14 15 47833 11.7 130

95 63 92 59 90 57 98 65 97 64 1 1 80 84 140 129 15 16 16 54667 11.7 140

92 92 92 94 94 94 96 60 60 60 62 62 62 64 06T semi-hermetic screw compressors, 50 r/s 1 1 1 1 1 1 1 1 1 1 1 1 1 1 R134a 36 38 37 38 37 39 53 37 55 39 62 39 62 62 -

60 64 70 85 85 102 102 64 64 56 56 56 56 88 PRO-DIALOG, electronic expansion valve (EXV) 15 15 15 15 15 15 15 Aluminium micro-channel heat exchanger Axial Flying Bird 4 with rotating shroud 6 6 6 8 8 9 11 6 6 7 8 8 9 11 20500 20500 20500 27333 27333 30750 37583 11.7 11.7 11.7 11.7 11.7 11.7 11.7 Flooded shell-and-tube type 58 61 61 66 70 77 79

Victaulic 5 5 5 5 5 5 5 6 6 6 6 6 8 6 6 6 6/8 141.3 141.3 141.3 141.3 141.3 141.3 141.3 168.3 168.3 168.3 168.3 168.3 219.1 168.3 168.3 168.3 168.3/ 219.1 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 Victaulic 4 4 4 4 114.3 114.3 114.3 114.3 50 50 50 50 400 400 400 400 Colour code: RAL7035 4 114.3 50 400 4 114.3 80 400 -

Standard Eurovent LCP/A/P/C/AC conditions in cooling mode: evaporator entering/leaving water temperature 12C/7C, outside air temperature 35C, evaporator fouling factor 0.18 x 10-4 (m2 K)/W. Weights are guidelines only. The refrigerant charge is also given on the unit nameplate. Options: 119 = high energy efficiency; 254 = traditional Cu/Al coils. 10-12 W - In accordance with ISO 9614-1 and certified by Eurovent Average sound pressure level, unit in a free field on a reflective surface Weight and diameters of connection modules 1 and 2 for sizes 1402 to 1702. Notes: 1. Unit sizes 30XA 1402 to 1702 are supplied in two field-assembled modules. 2. Option 119 (high energy efficiency can be used together with options 254 and 255. 3. Contact your Carrier representative to obtain the performances

Electrical data
30XA 252 302 352 402 Power circuit Nominal power supply V-ph-Hz 400-3-50 Voltage range V 360-440 Maximum supply cable section 2 x 240 2 x 240 2 x 240 2 x 240 Circuits A + B mm2 Circuits C + D mm2 2 Option 81 mm Short circuit holding current (TN system)* Circuits A + B kA 38 38 38 38 Circuits C + D kA Option 81 kA Control circuit 24 V via internal transformer Standard unit Maximum start-up current** Circuits A + B A 269 269 287 402 Circuits C + D A Option 81 A Nominal start-up current*** Circuits A + B A 245 245 262 378 Circuits C + D A Option 81 A Cosine Phi (maximum)**** 0.88 0.88 0.87 0.88 Cosine Phi (nominal) 0.85 0.85 0.84 0.84 Maximum power input Circuits A + B kW 121 131 141 165 Circuits C + D kW Option 81 kW Nominal unit current draw Circuits A + B A 151 167 184 210 Circuits C + D A Option 81 A Maximum unit current draw (Un) Circuits A + B A 198 215 233 270 Circuits C + D A Option 81 A Maximum unit current draw (Un 10%)**** Circuits A + B A 208 232 251 290 Circuits C + D A Option 81 A High energy efficiency version (option 119) Maximum start-up current** Circuits A + B A 274 274 292 407 Circuits C + D A Option 81 A Nominal start-up current*** Circuits A + B A 246 246 261 379 Circuits C + D A Option 81 A Cosine Phi (maximum)**** 0.88 0.87 0.87 0.88 Cosine Phi (nominal) 0.84 0.84 0.83 0.83 Maximum power input Circuits A + B kW 126 136 147 172 Circuits C + D kW Option 81 kW Nominal unit current draw Circuits A + B A 151 167 182 210 Circuits C + D A Option 81 A Maximum unit current draw (Un) Circuits A + B A 208 226 243 284 Circuits C + D A Option 81 A Maximum unit current draw (Un 10%)**** Circuits A + B A 219 243 262 305 Circuits C + D A Option 81 A 452 502 602 702 752 802 852 902 1002 1102 1202 1302 1352 1402 1502 1702
2 x 240 2 x 240 4 x 240 4 x 240 4 x 240 4 x 240 4 x 240 6 x 240 6 x 240 4 x 240 4 x 240 4 x 240 6 x 240 6 x 240 6 x 240 4 x 240 2 x 240 2 x 240 2 x 240 2 x 240 2 x 240 2 x 240 4 x 240 8 x 240 8 x 240 8 x 240 8 x 240 8 x 240 8 x 240 -

38 -

38 -

50 -

50 -

50 -

50 -

50 -

50 -

50 -

50 50 50

50 50 50

50 50 50

50 50 50

50 50 50

50 50 50

50 50 -

505 480 0.88 0.86 185 240 303 326 510 479 0.88 0.85 192 237 316 340 -

505 480 0.88 0.86 204 266 335 360 510 479 0.88 0.85 212 264 350 376 -

574 536 0.88 0.87 247 322 404 435 583 535 0.88 0.86 257 320 423 455 -

606 562 0.88 0.87 267 349 436 469 616 561 0.88 0.86 278 346 457 491 -

773 735 0.86 0.84 293 406 492 529 782 734 0.86 0.84 304 404 512 551 -

803 759 0.86 0.85 312 431 522 561 812 757 0.86 0.84 323 427 542 583 -

805 761 0.87 0.85 343 452 572 615 815 760 0.86 0.84 356 446 596 640 -

893 845 0.85 0.83 359 516 611 657 905 845 0.85 0.82 372 516 635 683 -

941 865 0.86 0.84 420 556 707 760 954 860 0.86 0.82 435 546 734 790 -

574 587 991 536 587 909 0.88 0.85 247 210 457 322 278 600 404 354 758 435 380 815 583 587 1010 535 587 907 0.88 0.84 257 217 475 320 273 593 423 367 790 455 395 850

773 587 1079 735 587 993 0.86 0.84 293 210 503 406 278 684 492 354 845 529 380 909 782 587 1099 734 587 991 0.86 0.83 304 217 522 404 273 678 512 367 879 551 395 946

803 587 1155 759 587 1036 0.87 0.85 342 210 552 449 278 727 568 354 922 611 380 991 812 587 1175 757 587 1026 0.87 0.83 353 217 570 439 273 712 588 367 956 633 395 1028

891 587 1242 859 587 1156 0.85 0.83 388 209 597 569 292 861 655 352 1007 705 378 1083 901 587 1265 846 587 1124 0.85 0.83 400 216 615 537 275 812 678 364 1041 729 391 1120

893 587 1248 845 587 1125 0.85 0.83 390 210 600 538 278 816 661 354 1015 711 380 1091 905 587 1275 845 587 1122 0.85 0.82 405 217 622 535 273 808 688 367 1056 740 395 1135

941 587 1294 865 587 1143 0.86 0.84 420 210 630 556 278 834 707 354 1061 760 380 1141 954 587 1321 860 587 1133 0.86 0.82 435 217 652 546 273 820 734 367 1102 790 395 1185

805 805 761 761 0.87 0.85 343 343 452 452 572 572 615 615 815 815 760 760 0.86 0.84 356 356 712 446 446 893 596 596 1191 640 640 1281

* kA eff: efficiency value: rms for English version ** Instantaneous start-up current (operating current of the smallest compressor + fan current + locked rotor current in star connection of the largest compressor). Values obtained at operation with maximum unit power input. *** Instantaneous start-up current (operating current of the smallest compressor + fan current + locked rotor current in star connection of the largest compressor). Values obtained at standard Eurovent unit operating conditions: air 35C, water 12/7C **** Values obtained at operation with maximum unit power input. Circuit D for size 1702 only Values obtained at standard Eurovent unit operating conditions: air 35C, water 12/7C Values obtained at operation with maximum unit power input. Values given on the unit name plate Notes: Motor and fan electrical data if the unit operates at Eurovent conditions (motor ambient temperature 50C); 1.9 A for standard unit; 3.6 A for unit with option 119 Start-up current: 8.4 A for standard unit; 20 A for unit with option 119 Power input: 760 W for standard unit; 1650 W for unit with option 119 Unit sizes 30XA 1102 to 1702 have two power connection points (circuits A + B and circuits C + D).

10

Hydronic module (option 116)*


30XA Single or dual low-pressure pump Motor power Power input Max. current draw Single or dual high-pressure pump Motor power Power input Max. current draw kW kW A kW kW A

Electrical data

252 2.2 2.8 4.7 4 5.1 8.2

302 2.2 2.8 4.7 5.5 7.2 11.7

352 3 3.9 6.4 5.5 7.2 11.7

402 4 5.1 8.2 7.5 9.2 15

452 5.5 7.2 11.7 11 13.2 21.2

502 5.5 7.2 11.7 11 13.2 21.2

* Additional power and current.

Electrical data notes and operating conditions 30XA 30XA 252-1002 units have a single power connection point located immediately upstream of the two main disconnect switches. 30XA 1102-1702 units have two power connection points located upstream of the main disconnect switches. The control box includes: - One main disconnect switch per circuit - Starter and motor protection devices for each compressor, the fans and the pump - Control devices Field connections: All connections to the system and the electrical installations must be in full accordance with all applicable local codes. The Carrier 30XA units are designed and built to ensure conformance with these codes. The recommendations of European standard EN 60 204-1 (corresponds to IEC 60204-1) (machine safety - electrical machine components - part 1: general regulations) are specifically taken into account, when designing the electrical equipment.

1.

2. 3. 4. 5. 6,

Notes: Generally the recommendations of IEC 60364 are accepted as compliance with the requirements of the installation directives. Conformance with EN 60204 is the best means of ensuring compliance with the Machines Directive 1.5.1. Annex B of EN 60204-1 describes the electrical characteristics used for the operation of the machines.

The operating environment for the 30XA units is specified below: Environment* Environment as classified in EN 60721 (corresponds to IEC 60721) : - outdoor installation* - ambient temperature range: minimum temperature 20C to +55C, class 4K4H* - altitude: lower than or equal to 2000 m - presence of hard solids, class 4S2 (no significant dust present) - presence of corrosive and polluting substances, class 4C2 (negligible) Power supply frequency variation: 2 Hz. The neutral (N) line must not be connected directly to the unit (if necessary use a transformer). Overcurrent protection of the power supply conductors is not provided with the unit. The factory installed disconnect switch(es)/circuit breaker(s) is (are) of a type suitable for power interruption in accordance with EN 60947-3 (corresponds to IEC 60947-3). The units are designed for simplified connection on TN(s) networks (IEC 60364). For IT networks derived currents may interfere with network monitoring elements, and it is recommended to create an IT type divider for the system units that require this and/or a TN type divider for Carrier units. Please consult the appropriate local organisations to define the monitoring and protection elements and carry out the electrical installation.

NOTE: If particular aspects of an actual installation do not conform to the conditions described above, or if there are other conditions which should be considered, always contact your local Carrier representative. * The required protection level for this class is IP43B (according to reference document IEC 60529). All 30XA units are protected to IP44CW and fulfil this protection condition.

11

Part load performances


With the rapid increase in energy costs and the care about environmental impacts of electricity production, power consumption of air conditioning equipment has become an important topic. The energy efficiency of a liquid chiller at full load is rarely representative of the actual performance of the units, as on average a chiller works less than 5% of the time at full load.

The heat load of a building depends on many factors, such as the outside air temperature, the exposure to the sun and the building occupancy. Consequently it is preferable to use the average energy efficiency, calculated at several operating points that are representative for the unit utilisation.

IPLV (in accordance with ARI 550/590-98)

The IPLV (integrated part load value) allows evaluation of the average energy efficiency based on four operating conditions defined by the ARI (American Refrigeration Institute). The IPLV is the average weighted value of the energy efficiency ratios (EER) at different operating conditions, weighted by the operating time.

ESEER (in accordance with EUROVENT)

The ESEER (European seasonal energy efficiency ratio) permits evaluation of the average energy efficiency at part load, based on four operating conditions defined by Eurovent. The ESEER is the average value of energy efficiency ratios (EER) at different operating conditions, weighted by the operating time.

IPLV (integrated part load value)


Load % 100 75 50 25 Air temperature C 35 26.7 18.3 12.8 Energy efficiency EER1 EER2 EER3 EER4 Operating time % 1 42 45 12

ESEER (European seasonal energy efficiency ratio)


Load % 100 75 50 25 Air temperature C 35 30 25 20 Energy efficiency EER1 EER2 EER3 EER4 Operating time % 3 33 41 23

ESEER = EER1 x 1% + EER2 x 42% + EER3 x 45% + EER4 x 12%

ESEER = EER1 x 3% + EER2 x 33% + EER3 x 41% + EER4 x 23%

Part load performances


30XA standard IPLV kW/kW ESEER kW/kW 252 4.53 4.11

302 4.63 4.29

352 4.81 4.31

402 4.50 4.22

452 4.58 4.37

502 4.75 4.34

602 4.61 4.13

702 4.67 4.21

752 4.48 4.00

802 4.42 3.95

852 4.46 3.93

902 4.35 3.91

1002 1102 1202 1302 1352 1402 1502 1702 4.39 4.64 4.53 4.56 4.35 4.61 4.58 4.31 3.91 4.11 4.02 4.03 3.83 4.10 4.11 3.86

12

Operating limits

Evaporator water temperature Water entering temperature at start-up Water entering temperature during operation Water leaving temperature during operation

Minimum 6.8 3.3

Maximum 45* 21 15

Evaporator water flow rate (l/s)


30XA 252 302 352 402 452 502 602 702 752 802 852 902 1002 1102 1202 1302 1352 1402 1502 1702 Minimum 3.6 4.0 4.3 5.3 6.0 6.7 8.1 8.9 9.6 10.4 11.0 11.8 13.1 15.1 16.4 17.5 18.8 19.3 19.9 22.0

Note: If the leaving water temperature is below 4C, a glycol/water solution or the frost protection option must be used.

Condenser air temperature C Storage Operation: Standard unit With winter operation option (option 28) With high energy efficiency option (option 119)***

Minimum Maximum -20 68 -10 -20 -10 55** 55** 55****

Maximum* 37.5 40.5 40.5 34.1 36.9 42.0 45.0 56.1 59.1 67.1 67.1 73.9 83.9 87.8 92.9 96.1 107.4 107.4 109.4 107.4

Note: If the air temperature is below 0C, a glycol/water solution or the frost protection option must be used. * ** *** **** Based on the installation type and the air temperature Part load, based on the water temperature Recommended for operation above 46C Part-load operation

The maximum water flow rate corresponds to a pressure drop of 100 kPa.

30XA standard unit

Operating range

30XA unit with option 119

Air entering temperature, C

Evaporator leaving water temperature, C

Air entering temperature, C

Evaporator leaving water temperature, C

Legend Operating range, unit equipped with option 28 (winter operation) Below 0C air temperature the unit must either be equipped with the evaporator frost protection option (41A or 41B), or the water loop must be protected against frost by using a frost protection solution (by the installer). Part load average

13

30XA 252-352 - MCHX heat exchanger (standard) 30XA 252-302 - Cu/Al heat exchanger (option 254/255)

Dimensions/clearances

Legend All dimensions are given in mm.

1 2

Required clearances for maintenance and air flow Recommended space for evaporator tube removal Water inlet Water outlet Air outlet do not obstruct Power supply connection

Control circuit connection

30XA 402-452 - MCHX heat exchanger (standard) 30XA 352-452 - Cu/Al heat exchanger (option 254/255)

NOTE: Drawings are not contractually binding. Before designing an installation, consult the certified dimensional drawings, available on request.

14

30XA 502 - MCHX heat exchanger (standard) 30XA 502 - Cu/Al heat exchanger (option 254/255)

Dimensions/clearances

30XA 602-802 - MCHX heat exchanger (standard) 30XA 602-702 - Cu/Al heat exchanger (option 254/255)

Legend All dimensions are given in mm.

1 2

Required clearances for maintenance and air flow Recommended space for evaporator tube removal Water inlet Water outlet Air outlet do not obstruct Power supply connection

Control circuit connection

NOTE: Drawings are not contractually binding. Before designing an installation, consult the certified dimensional drawings, available on request.

15

30XA 852-902 - MCHX heat exchanger (standard) 30XA 752-852 - Cu/Al heat exchanger (option 254/255)

Dimensions/clearances

Legend All dimensions are given in mm.

1 2

Required clearances for maintenance and air flow Recommended space for evaporator tube removal Water inlet Water outlet Air outlet do not obstruct Power supply connection

Control circuit connection

30XA 1002 - MCHX heat exchanger (standard) 30XA 902-1002 - Cu/Al heat exchanger (option 254/255)

NOTE: Drawings are not contractually binding. Before designing an installation, consult the certified dimensional drawings, available on request.

16

30XA 1102-1352 - MCHX heat exchanger (standard) 30XA 1102-1352 - Cu/Al heat exchanger (option 254/255)

Dimensions/clearances

Legend All dimensions are given in mm.

1 2

Required clearances for maintenance and air flow Recommended space for evaporator tube removal Water inlet Water outlet Air outlet do not obstruct Power supply connection

Control circuit connection

NOTE: Drawings are not contractually binding. Before designing an installation, consult the certified dimensional drawings, available on request.

17

30XA 1402-1502 module 1/2 - MCHX heat exchanger (standard) 30XA 1402-1502 module 1/2 - Cu/Al heat exchanger (option 254/255))

Dimensions/clearances

Module 2

Legend All dimensions are given in mm.

1 2

Required clearances for maintenance and air flow Recommended space for evaporator tube removal Water inlet

Water outlet (to be connected to the water inlet of module 2) Air outlet do not obstruct Power supply connection

30XA 1402-1502 module 2/2 - MCHX heat exchanger (standard) 30XA 1402-1502 module 2/2 - Cu/Al heat exchanger (option 254/255)

Control circuit connection

Module 1

Water inlet (to be connected to the water outlet of module 1)

NOTE: Drawings are not contractually binding. Before designing an installation, consult the certified dimensional drawings, available on request. Unit sizes 1402-1502 are supplied in two field-assembled modules (connection pipe completion to be done by the installer).

18

30XA 1702 module 1/2 - MCHX heat exchanger (standard) 30XA 1702 module 1/2 - Cu/Al heat exchanger (option 254/255)

Dimensions/clearances

Module 2

1 2
30XA 1702 module 2/2 - MCHX heat exchanger (standard) 30XA 1702 module 2/2 - Cu/Al heat exchanger (option 254/255)
C

Legend All dimensions are given in mm. Required clearances for maintenance and air flow Recommended space for evaporator tube removal Water inlet Water outlet (to be connected to the water inlet of module 2) Air outlet do not obstruct Power supply connection Control circuit connection

Module 1

NOTE: Drawings are not contractually binding. Before designing an installation, consult the certified dimensional drawings, available on request. Unit size 1702 is supplied in two field-assembled modules (connection pipe completion to be done by the installer).

Water inlet (to be connected to the water outlet of module 1).

19

20

Standard unit - LWT = 5C Air temperature, C 25 CAP COMP UNIT 30XA kW kW kW

Standard unit

Cooling capacities

252 302 352 402 452 502 602 702 752 802 852 902 1002 1102 1202 1302 1352 1402 1502 1702

272 300 329 386 444 499 613 662 717 779 815 885 968 1133 1236 1323 1413 1452 1505 1631

66 75 81 95 113 124 153 161 182 201 205 230 248 280 314 345 392 366 382 408

71 80 85 101 119 131 161 170 191 210 216 241 260 295 329 360 407 384 400 429

COOL COOL l/s kPa 73 82 89 104 124 136 167 176 199 220 224 252 271 307 343 378 429 400 417 446 77 87 93 110 130 143 175 185 208 229 235 262 283 321 358 393 444 418 436 467 12 14 15 18 20 23 28 30 33 36 37 41 45 52 57 61 65 67 69 75 13 13 16 30 33 32 41 32 33 31 34 32 31 37 39 41 38 41 42 50 252 277 302 360 413 464 569 616 667 722 757 821 899 1053 1149 1226 1308 1348 1397 1516 80 90 98 113 136 149 183 192 218 240 245 276 297 335 375 414 470 438 457 488 84 95 102 120 142 156 191 201 227 249 256 286 309 350 390 429 485 455 475 509 12 13 14 17 20 22 27 29 32 34 36 39 43 50 55 58 62 64 67 72 12 12 14 28 30 30 38 30 31 29 31 30 29 35 36 38 36 38 39 46 241 263 287 346 396 444 546 590 639 691 726 787 862 1009 1102 1173 1251 1291 1339 1453 87 99 107 124 149 164 200 211 239 263 269 302 326 367 411 454 516 480 501 535 92 103 111 130 154 170 208 219 248 272 279 312 338 381 426 469 530 497 519 556 11 13 14 16 19 21 26 28 30 33 35 37 41 48 52 56 60 61 64 69 11 11 13 26 28 27 35 28 29 27 29 28 27 32 33 35 33 35 36 43 227 247 268 328 374 419 515 557 605 644 686 737 814 953 1035 1017 922 1191 1252 1367 97 111 120 138 166 183 224 235 267 290 301 333 365 410 455 451 420 518 553 595 102 115 124 144 172 190 231 244 275 298 311 343 377 424 470 466 434 535 571 616 11 12 13 16 18 20 25 27 29 31 33 35 39 45 49 48 44 57 60 65 10 10 12 24 25 25 31 25 26 23 26 25 24 29 30 27 19 30 32 38

13 14 16 18 21 24 29 32 34 37 39 42 46 54 59 63 67 69 72 78

14 14 17 32 35 34 43 34 35 33 36 34 33 40 41 44 41 44 45 53

30 CAP kW COMP UNIT kW kW COOL COOL l/s kPa COMP UNIT kW kW COOL COOL l/s kPa COMP UNIT kW kW COOL COOL l/s kPa COMP UNIT kW kW COOL COOL l/s kPa

262 289 316 373 429 482 591 640 693 751 787 854 935 1094 1194 1276 1362 1401 1452 1575

35 CAP kW

40 CAP kW

46 CAP kW

Standard unit - LWT = 6C Air temperature, C 25 CAP COMP UNIT 30XA kW kW kW 252 280 67 72 302 309 77 81 352 338 83 87 402 398 96 102 452 457 115 121 502 514 127 133 602 632 156 164 702 683 164 173 752 739 186 195 802 802 205 214 852 840 209 220 902 911 235 246 1002 998 253 265 1102 1167 286 300 1202 1273 320 335 1302 1362 353 368 1352 1454 400 415 1402 1496 373 391 1502 1550 390 408 1702 1678 415 437 COMP kW 74 84 91 105 126 139 171 179 203 224 228 257 277 312 350 385 438 408 426 454
Unit power input (compressors, fans and control circuit)) Evaporator water flow rate Evaporator pressure drop

COOL l/s 13 15 16 19 22 25 30 33 35 38 40 43 48 56 61 65 69 71 74 80

COOL kPa 14 15 18 34 36 36 46 36 37 35 38 36 35 42 44 46 43 46 47 56

30 CAP kW 270 297 325 385 442 497 610 659 714 773 810 879 962 1127 1229 1313 1401 1443 1495 1621 UNIT kW 78 88 95 112 132 145 179 188 212 233 239 267 289 327 365 400 453 426 444 475 COOL l/s 13 14 15 18 21 24 29 31 34 37 39 42 46 54 59 63 67 69 71 77 COOL kPa 14 14 16 32 34 34 43 34 35 32 35 34 33 39 41 43 40 43 44 52 COMP kW 81 92 100 115 138 152 187 196 222 245 250 281 303 342 383 422 480 446 466 497 UNIT kW 86 96 104 121 144 159 195 205 231 254 261 291 315 356 398 437 494 464 484 518 COOL l/s 12 14 15 18 20 23 28 30 33 35 37 40 44 52 56 60 64 66 68 74 COOL kPa 13 13 15 30 32 31 40 31 33 30 33 31 31 36 38 40 37 40 41 49 COMP kW 89 101 109 126 151 167 204 214 243 268 274 308 332 374 419 463 526 489 511 545

35 CAP kW 260 285 311 371 425 478 587 634 687 743 780 845 925 1084 1182 1261 1345 1387 1437 1560

40 CAP kW 248 272 295 356 407 457 563 608 658 711 747 810 887 1039 1134 1207 1286 1329 1377 1495

UNIT kW 93 105 113 132 157 173 212 223 252 277 284 318 344 388 434 478 541 506 529 566
Application data: Standard units, refrigerant R134a Evaporator temperature rise: 5 K

COOL l/s 12 13 14 17 19 22 27 29 31 34 36 39 42 50 54 57 61 63 66 71

COOL kPa 12 12 14 28 30 29 37 29 30 28 31 29 28 34 35 37 34 37 38 45

46 CAP kW 234 255 276 338 385 431 531 573 615 655 705 735 831 981 1057 1039 956 1200 1258 1401

COMP kW 99 113 122 140 169 187 228 240 267 290 307 324 368 418 458 453 427 511 544 602

UNIT kW 103 117 126 146 175 193 236 248 275 299 317 335 379 432 473 467 441 528 561 622

COOL l/s 11 12 13 16 18 21 25 27 29 31 34 35 40 47 50 50 46 57 60 67

COOL kPa 10 10 12 25 27 26 33 26 27 24 28 24 25 30 31 28 20 31 32 40
Evaporator fluid: chilled water Fouling factor: 0,18 x10-4 (m2 K) / W Performances in acordance with EN 14511

Legend LWT CAP kW COMP kW

Leaving water temperature Cooling capacity Compressor power input

UNIT kW COOL l/s COOL kPa

Standard unit

Cooling capacities

Standard unit - LWT =7C Air temperature, C 25 CAP COMP UNIT 30XA kW kW kW 252 289 68 73 302 318 78 82 352 349 85 89 402 410 98 104 452 471 117 123 502 530 129 136 602 651 159 167 702 703 167 176 752 761 190 198 802 825 209 218 852 864 213 224 902 938 240 250 1002 1027 258 270 1102 1202 292 306 1202 1311 327 342 1302 1401 360 375 1352 1496 409 424 1402 1539 381 399 1502 1596 398 416 1702 1728 424 445 COMP kW 75 86 93 107 129 141 174 182 207 228 233 262 282 319 357 393 447 416 434 463 UNIT kW 80 90 97 113 134 148 182 191 216 237 243 272 294 333 372 408 462 434 452 484 COOL l/s 13 15 16 19 22 24 30 32 35 38 40 43 47 55 60 64 69 71 73 80 COOL kPa 14 15 17 33 36 35 45 35 37 34 37 35 34 41 43 45 42 45 46 55 35 CAP kW 268 293 320 382 437 492 605 653 706 764 802 869 952 1116 1216 1297 1382 1426 1478 1605 COMP kW 82 94 102 117 141 155 190 200 226 250 255 286 309 348 390 430 490 455 475 507 UNIT kW 87 98 106 123 147 161 198 208 235 258 265 297 321 363 405 445 504 473 493 528 COOL l/s 13 14 15 18 21 23 29 31 34 36 38 41 45 53 58 62 66 68 70 77 COOL kPa 13 13 16 31 33 33 42 33 34 32 35 33 32 38 40 42 39 42 43 51 COMP kW 90 103 111 128 154 170 208 218 248 273 279 313 338 381 427 472 537 498 520 555 UNIT kW 94 107 115 134 160 176 216 227 256 282 289 324 350 395 441 487 551 516 538 576 COOL l/s 12 13 14 17 20 22 28 30 32 35 37 40 43 51 56 59 63 65 68 73 COOL kPa 12 12 14 29 31 30 39 30 32 29 32 30 30 35 37 39 36 39 39 47 COMP kW 100 115 125 142 172 190 232 244 267 284 308 321 359 412 448 451 434 485 513 605 UNIT kW 105 119 129 148 178 197 240 253 275 293 318 331 370 426 462 465 448 502 530 625 COOL l/s 11 12 14 17 19 21 26 28 30 31 34 35 40 47 50 50 47 56 58 68 COOL kPa 11 11 13 26 28 27 35 27 27 24 28 25 25 30 31 29 21 29 30 41 40 CAP kW 256 279 304 367 419 470 580 626 677 731 769 832 912 1069 1166 1240 1320 1366 1416 1539 46 CAP kW 241 262 284 347 396 444 547 590 625 658 719 741 830 989 1057 1055 990 1174 1222 1429

COOL l/s 14 15 17 20 22 25 31 34 36 39 41 45 49 57 62 67 71 73 76 82

COOL kPa 15 16 19 35 38 38 48 38 39 36 40 38 37 44 46 49 45 48 49 59

30 CAP kW 279 306 335 397 455 511 629 679 734 795 834 904 990 1160 1265 1350 1440 1484 1538 1668

Standard unit - LWT = 10C Air temperature, C 25 COMP kW 79 90 98 113 136 149 184 193 219 242 247 278 300 338 378 418 477 442 461 491
Unit power input (compressors, fans and control circuit)) Evaporator water flow rate Evaporator pressure drop

30XA 252 302 352 402 452 502 602 702 752 802 852 902 1002 1102 1202 1302 1352 1402 1502 1702

CAP kW 316 348 381 447 513 578 710 766 829 897 941 1020 1118 1308 1425 1522 1622 1674 1736 1881

COMP kW 72 82 89 103 124 137 169 177 201 222 226 255 275 310 347 384 437 405 423 450

UNIT kW 77 87 94 109 130 143 177 186 210 231 237 265 287 324 362 399 452 423 441 471

COOL l/s 15 17 18 21 24 28 34 37 40 43 45 49 53 62 68 73 77 80 83 90

COOL kPa 18 18 22 41 44 43 55 43 45 42 46 44 42 50 53 56 52 55 57 68

30 UNIT kW 83 94 102 119 142 156 192 202 228 251 258 288 312 352 393 433 492 460 480 512 COOL l/s 15 16 17 21 24 27 33 35 38 41 43 47 51 60 66 70 75 77 80 87 COOL kPa 16 17 20 38 41 40 52 41 42 39 43 41 39 47 49 52 48 52 53 63 CAP kW 292 320 348 417 476 535 659 711 768 829 872 943 1034 1213 1321 1406 1496 1548 1606 1745 COMP kW 86 99 107 123 148 163 201 211 239 265 270 303 327 369 413 457 521 482 504 536 UNIT kW 91 103 111 129 154 170 209 220 248 273 280 314 339 383 428 472 536 500 522 557 COOL l/s 14 15 17 20 23 26 31 34 37 40 42 45 49 58 63 67 71 74 77 83 COOL kPa 15 16 18 36 38 38 48 38 39 36 40 38 37 44 46 48 44 48 49 59 CAP kW 280 305 331 400 456 512 632 681 736 793 835 903 989 1162 1265 1331 1374 1481 1536 1671

CAP kW 304 335 366 433 495 557 686 739 799 864 908 983 1077 1261 1374 1466 1561 1612 1672 1815

35

40

COMP kW 94 108 118 134 162 179 219 231 261 289 295 331 358 403 451 492 534 527 551 587

UNIT kW 99 112 122 140 168 186 227 239 270 298 306 341 370 417 466 507 549 545 569 608
Application data: Standard units, refrigerant R134a Evaporator temperature rise: 5 K

COOL l/s 13 15 16 19 22 24 30 33 35 38 40 43 47 55 60 64 66 71 73 80

COOL kPa 14 14 17 33 35 35 45 35 36 33 37 35 34 40 42 43 38 44 45 54

46

CAP kW 263 285 309 378 422 483 588 642 599 631 702 674 760 969 990 1023 1047 1135 1186 1455

COMP kW 104 121 132 149 176 201 239 257 233 248 279 261 299 374 381 404 434 431 459 578

UNIT kW 109 125 136 155 182 207 247 266 242 257 289 272 310 388 395 418 448 449 476 598

COOL l/s 13 14 15 18 20 23 28 31 29 30 33 32 36 46 47 49 50 54 57 69

COOL kPa 13 13 15 30 31 31 39 31 25 22 27 20 21 29 27 27 23 27 28 42
Evaporator fluid: chilled water Fouling factor: 0,18 x10-4 (m2 K) / W Performances in acordance with EN 14511

Legend LWT CAP kW COMP kW

Leaving water temperature Cooling capacity Compressor power input

UNIT kW COOL l/s COOL kPa

21

22

Unit with option 119 (high energy efficiency)

Cooling capacities

Unit with option 119 - LWT = 5C Air temperature,C 25 CAP COMP UNIT COOL 30XA kW kW kW l/s 252 277 63 73 13 302 305 70 79 15 352 333 77 86 16 402 395 88 101 19 452 455 103 115 22 502 513 113 127 24 602 620 141 158 29 702 682 148 168 32 752 732 173 193 35 802 799 185 206 38 852 846 189 212 40 902 908 213 237 43 1002 1009 228 257 48 1102 1156 257 288 55 1202 1257 287 320 60 1302 1367 317 350 65 1352 1460 348 379 70 1402 1482 333 373 71 1502 1540 347 388 73 1702 1691 377 424 80 COMP kW 70 77 84 97 113 124 154 163 190 202 206 232 249 281 314 346 380 363 379 413 UNIT kW 79 86 93 109 125 138 171 182 209 223 230 256 278 312 347 379 411 404 420 459 COOL l/s 13 14 15 18 21 24 29 31 34 37 39 42 46 53 58 63 67 68 71 78 COOL kPa 13 14 16 31 34 34 42 34 35 33 36 34 34 39 40 44 41 43 44 53 35 CAP kW 257 282 307 369 425 479 579 637 684 746 789 848 942 1080 1174 1275 1360 1383 1436 1578 COMP kW 76 84 93 106 125 136 169 178 208 222 226 254 272 307 344 379 417 397 415 452 UNIT kW 85 93 102 118 136 150 186 197 226 242 249 278 301 338 376 412 448 437 455 498 COOL l/s 12 13 15 18 20 23 28 30 33 36 38 40 45 51 56 61 65 66 68 75 COOL kPa 12 13 15 30 32 32 39 32 32 31 34 32 32 36 38 41 38 40 41 50 COMP kW 84 93 101 116 137 149 185 195 228 243 248 279 299 336 377 416 457 436 455 495 UNIT kW 93 102 110 128 148 163 202 214 246 263 271 302 327 367 409 449 488 475 495 541 COOL l/s 12 13 14 17 19 22 26 29 31 34 36 39 43 49 54 58 62 63 66 72 COOL kPa 12 12 14 28 30 29 36 30 30 28 32 30 30 34 35 38 35 37 38 46 COMP kW 93 104 114 130 153 167 206 218 254 272 277 312 334 376 421 466 512 487 509 554 UNIT kW 102 112 123 141 164 180 223 237 273 291 299 334 362 405 452 498 542 526 548 599 COOL l/s 11 12 13 16 18 21 25 28 30 32 34 37 41 47 51 55 59 60 62 69 COOL kPa 10 10 12 25 27 26 33 27 28 26 29 27 27 31 32 35 32 34 35 42 40 CAP kW 247 269 292 356 408 460 556 613 658 718 759 815 905 1039 1130 1226 1306 1330 1380 1518 46 CAP kW 233 253 273 338 387 435 528 581 625 681 720 774 859 985 1073 1163 1238 1263 1309 1440

COOL kPa 14 15 17 33 36 36 44 36 37 35 39 36 36 41 43 47 44 45 47 57

30 CAP kW 268 294 321 382 440 497 600 660 708 773 818 879 976 1119 1216 1322 1411 1434 1489 1636

Unit with option 119 - LWT = 6C Air temperature,C 25 CAP COMP UNIT COOL 30XA kW kW kW l/s 252 286 64 74 14 302 315 71 80 15 352 344 78 87 16 402 407 90 102 19 452 469 105 117 22 502 529 115 129 25 602 640 143 160 30 702 704 151 171 34 752 755 177 196 36 802 824 188 209 39 852 872 192 216 42 902 937 217 241 45 1002 1041 232 261 50 1102 1192 261 292 57 1202 1296 293 326 62 1302 1409 322 356 67 1352 1505 355 386 72 1402 1529 339 379 73 1502 1587 354 395 76 1702 1742 384 431 83 COMP kW 71 78 86 98 115 126 157 165 193 206 210 237 253 286 319 352 388 370 386 420
Unit power input (compressors, fans and control circuit)) Evaporator water flow rate Evaporator pressure drop

COOL kPa 15 15 18 35 38 38 47 38 39 36 41 38 38 43 45 49 46 48 49 60

30 CAP kW 276 303 330 395 454 512 619 681 730 797 843 906 1007 1153 1254 1363 1454 1478 1535 1685 UNIT kW 80 87 95 110 127 140 174 185 212 226 233 260 282 316 352 386 419 410 427 466 COOL l/s 13 14 16 19 22 24 29 32 35 38 40 43 48 55 60 65 69 70 73 80 COOL kPa 14 14 17 33 36 35 44 36 36 34 38 36 36 41 42 46 43 45 46 56 COMP kW 77 86 94 107 127 138 172 181 211 225 230 259 277 312 349 386 425 404 422 459 UNIT kW 86 95 103 120 138 152 189 200 230 245 253 282 306 343 382 419 455 444 463 505 COOL l/s 13 14 15 18 21 24 28 31 34 37 39 42 46 53 58 63 67 68 70 77 COOL kPa 13 13 16 31 34 33 41 33 34 32 36 33 33 38 40 43 40 42 43 53 COMP kW 85 94 103 118 139 151 188 198 231 247 252 283 304 342 383 423 466 443 463 503

35 CAP kW 266 291 316 381 438 493 598 657 705 769 814 873 971 1113 1210 1314 1401 1426 1479 1626

40 CAP kW 255 278 301 367 421 474 575 632 678 740 782 839 933 1070 1164 1263 1346 1371 1421 1563

UNIT kW 94 103 112 130 150 165 205 217 250 267 275 306 332 372 415 456 496 483 503 549
Application data: Standard units, refrigerant R134a Evaporator temperature rise: 5 K

COOL l/s 12 13 14 17 20 23 27 30 32 35 37 40 44 51 55 60 64 65 68 74

COOL kPa 12 12 14 29 31 31 38 31 32 30 33 31 31 35 37 40 37 39 40 49

46 CAP kW 240 261 282 349 399 448 545 599 644 702 742 797 885 1016 1105 1198 1275 1301 1348 1483

COMP kW 95 105 116 131 155 169 210 221 258 276 281 316 340 382 427 473 521 495 517 562

UNIT kW 104 114 124 143 167 183 226 240 277 295 304 339 367 412 459 505 551 534 557 607

COOL l/s 11 12 13 17 19 21 26 29 31 33 35 38 42 48 53 57 61 62 64 71

COOL kPa 11 11 13 26 28 28 35 28 29 27 30 28 28 32 33 36 34 36 36 44
Evaporator fluid: chilled water Fouling factor: 0,18 x10-4 (m2 K) / W Performances in acordance with EN 14511

Legend LWT CAP kW COMP kW

Leaving water temperature Cooling capacity Compressor power input

UNIT kW COOL l/s COOL kPa

Unit with option 119 (high energy efficiency)

Cooling capacities

Unit with option 119 - LWT = 7C Air temperature,C 25 CAP COMP UNIT COOL 30XA kW kW kW l/s 252 295 65 75 14 302 325 72 82 15 352 354 79 89 17 402 420 91 103 20 452 483 107 119 23 502 545 117 131 26 602 660 146 163 31 702 726 154 173 35 752 778 180 199 37 802 849 192 212 40 852 899 196 219 43 902 965 221 244 46 1002 1073 236 265 51 1102 1229 266 297 59 1202 1336 298 331 64 1302 1452 328 362 69 1352 1550 362 393 74 1402 1575 345 386 75 1502 1636 360 401 78 1702 1795 391 438 86 COMP kW 72 79 87 99 117 128 159 168 196 209 214 241 258 291 325 359 395 376 393 427 UNIT kW 81 89 96 112 129 142 177 188 215 230 237 264 286 322 358 392 426 417 434 474 COOL l/s 14 15 16 19 22 25 30 33 36 39 41 44 49 57 62 67 71 73 75 83 COOL kPa 15 15 18 35 38 37 46 37 38 36 40 38 37 43 45 49 45 47 48 59 35 CAP kW 274 300 326 393 451 508 616 677 726 792 838 899 1000 1147 1247 1354 1442 1468 1523 1675 COMP kW 78 87 96 109 129 140 174 184 215 229 234 263 282 318 355 393 433 411 430 467 UNIT kW 88 96 105 121 141 154 191 203 233 249 257 286 310 348 388 425 463 451 470 513 COOL l/s 13 14 16 19 22 24 29 32 35 38 40 43 48 55 59 65 69 70 73 80 COOL kPa 14 14 16 33 35 35 43 35 36 34 37 35 35 40 42 46 42 44 45 55 COMP kW 86 95 105 119 141 154 191 201 235 251 256 288 309 348 389 430 474 450 471 512 UNIT kW 95 104 114 131 153 168 208 221 254 271 279 311 337 378 421 463 504 490 511 557 COOL l/s 13 14 15 18 21 23 28 31 33 36 38 41 46 53 57 62 66 67 70 77 COOL kPa 13 13 15 31 33 32 40 33 33 31 35 33 33 37 39 42 39 41 42 51 COMP kW 96 107 118 133 157 172 213 225 262 280 286 321 345 388 434 481 530 503 526 572 UNIT kW 105 116 126 145 169 186 229 244 281 300 308 344 373 418 466 513 560 542 565 616 COOL l/s 12 13 14 17 20 22 27 29 32 34 36 39 43 50 54 59 62 64 66 73 COOL kPa 11 12 13 28 30 29 37 30 30 28 32 30 30 34 35 38 35 37 38 46 40 CAP kW 263 286 310 378 433 488 593 651 698 762 805 864 961 1103 1199 1301 1385 1411 1463 1610 46 CAP kW 248 269 291 359 411 462 562 617 663 723 764 820 911 1046 1138 1233 1311 1339 1387 1527

COOL kPa 16 16 19 37 40 39 49 40 41 38 43 40 40 46 47 52 48 50 52 63

30 CAP kW 285 313 341 407 468 527 638 702 753 821 869 933 1037 1189 1292 1404 1497 1523 1581 1736

Unit with option 119 - LWT = 10C Air temperature,C 25 CAP COMP UNIT COOL 30XA kW kW kW l/s 252 323 68 78 15 302 355 76 85 17 352 387 84 93 19 402 460 95 107 22 452 527 113 125 25 502 595 123 138 28 602 722 154 171 34 702 793 162 182 38 752 851 190 209 41 802 929 202 223 44 852 981 207 230 47 902 1055 233 257 50 1002 1173 250 279 56 1102 1341 281 312 64 1202 1458 315 348 70 1302 1586 347 381 76 1352 1691 384 415 81 1402 1721 365 405 82 1502 1786 381 422 85 1702 1959 413 460 94 COMP kW 75 83 92 104 124 135 168 177 207 220 225 254 272 307 343 379 419 397 415 450
Unit power input (compressors, fans and control circuit)) Evaporator water flow rate Evaporator pressure drop

COOL kPa 18 19 22 43 46 46 57 46 47 44 49 46 46 53 55 60 56 58 60 73

30 CAP kW 312 342 372 446 510 575 699 767 823 898 948 1019 1133 1297 1410 1532 1632 1663 1724 1894 UNIT kW 84 93 101 116 136 149 185 197 226 241 249 277 301 337 376 412 450 438 456 497 COOL l/s 15 16 18 21 24 27 33 37 39 43 45 49 54 62 67 73 78 79 82 90 COOL kPa 17 18 21 41 44 43 54 43 44 42 46 43 43 50 52 56 52 55 56 69 COMP kW 82 91 101 113 135 147 183 193 226 241 246 277 297 335 374 414 458 434 453 492 UNIT kW 91 100 110 126 147 162 200 213 245 261 269 300 326 365 407 447 489 474 494 538 COOL l/s 14 16 17 21 23 26 32 35 38 41 44 47 52 60 65 70 75 76 79 87 COOL kPa 16 16 19 38 41 40 50 41 41 39 43 41 40 46 48 53 49 51 52 64

35 CAP kW 300 328 356 430 492 554 674 740 793 865 914 981 1091 1251 1359 1476 1571 1602 1660 1826

40 CAP kW 287 313 339 414 472 532 648 711 762 832 878 942 1048 1202 1306 1418 1506 1538 1594 1754

COMP kW 90 100 110 124 148 162 200 211 247 263 269 303 325 365 409 453 501 474 496 538

UNIT kW 99 109 119 136 160 176 217 231 266 283 292 326 353 396 441 486 531 513 536 584
Application data: Standard units, refrigerant R134a Evaporator temperature rise: 5 K

COOL l/s 14 15 16 20 23 25 31 34 36 40 42 45 50 57 62 68 72 73 76 84

COOL kPa 15 15 17 35 38 37 47 38 39 36 40 38 38 43 45 49 45 47 48 59

46 CAP kW 271 294 318 393 448 504 614 673 723 789 832 893 993 1140 1239 1322 1351 1458 1509 1663

COMP kW 100 112 124 138 165 181 223 236 275 293 300 337 363 407 456 494 517 528 553 600

UNIT kW 109 121 133 150 177 194 240 255 293 313 323 360 390 437 487 525 547 567 592 645

COOL l/s 13 14 15 19 21 24 29 32 35 38 40 43 47 54 59 63 65 70 72 79

COOL kPa 13 13 15 32 34 34 42 34 35 33 36 34 34 39 41 43 37 43 44 54
Evaporator fluid: chilled water Fouling factor: 0,18 x10-4 (m2 K) / W Performances in acordance with EN 14511

Legend LWT CAP kW COMP kW

Leaving water temperature Cooling capacity Compressor power input

UNIT kW COOL l/s COOL kPa

23

Carrier is participating in the Eurovent Certification Programme for liquid chilling packages. Certified data of certified models are as listed in the Eurovent Directory of Certified Products or on the Internet site www.eurovent-certification.com. This programme covers air-cooled chillers up to 600 kW and watercooled chillers up to 1500 kW.

Order No.: 13450-20, 10.2009. Supersedes order No.: 13450-20, 10.2007 Manufacturer reserves the right to change any product specifications without notice.

Manufactured by: Carrier SCS, Montluel, France. Printed in the Netherlands.