Diseo de Subestaciones
Elctricas



Universidad Nacional
de Ingeniera
Facultad de electrotecnia y computacin
<Departamento de ingeniera elctrica>

Diseo de Subestaciones Elctricas



1
- Contenido
1. I. TEMA ................................................................................................................3
2. II. INTRODUCCIN ............................................................................................4
3. III. OBJETIVOS......................................................................................................5
1. Objetivo General ............................................................................................................... 5
2. Objetivos Especficos ........................................................................................................ 5
4. IV. INFORMACIN GENERAL ..........................................................................6
3. Breve Resea Histrica ..................................................................................................... 7
4. Tabla De Valores V11 ....................................................................................................... 8
5. Estudio De Cargas ............................................................................................................. 9
6. Graficas de Consumo ...................................................................................................... 10
5. V. CALCULO DE COEFICIENTES .................................................................20
7. Coeficiente de demanda .................................................................................................. 20
8. Coeficiente de Diversidad ............................................................................................... 21
9. Coeficiente DEL factor de Cargas .................................................................................. 22
10. Factor de Perdida ......................................................................................................... 23
11. Hora Equiuvalente ....................................................................................................... 24
6. VI. LOCALIZACION DE LA SUB ESTACION ELECTRICA ......................25
12. Centros de la Elipse ..................................................................................................... 26
13. La Dispersin: ............................................................................................................. 26
14. Momento de Correlacin ............................................................................................. 27
15. ngulos de los ejes de Simetra de la Elipse ............................................................... 27
16. Exactitud de los nuevos ejes: ...................................................................................... 28
17. VISTA DE LA ELIPSE .............................................................................................. 29
7. VII. SELECCIN DE TRANSFORMADOR DE POTENCIA .........................30
1. Factor de carga del la variante:........................................................................................ 31
2. Perdidas en los transformadores de potencia .................................................................. 35
3. Graficas de Perdidas ........................................................................................................ 42
5. Intercepcin de graficas .................................................................................................. 45
8. VIII. TIEMPO DE COMPENSACION DE INVERSION EN COMPRA DE
TRANSFORMADOR DE POTENCIA. ............................................................... 47
4. Evaluacin Econmica de la Variantes ........................................................................... 48
5. Conexin de los transformadores .................................................................................... 48
9. IX. DISEO DE BARRAS COLECTORAS ......................................................49
Diseo de Subestaciones Elctricas



2
1. Calibre mnimo de la barra .............................................................................................. 49
2. Calculo de momento de inercia ....................................................................................... 50
3. Calculo del claro y la flecha para la seleccin mxima: ................................................. 51
4. Tensin critica de flameo ................................................................................................ 52
5. Distancias mnimas ......................................................................................................... 53
6. Cargas horizontales en las barras tubulares ..................................................................... 54
7. Resistencia del aislador ................................................................................................... 57
8. Longitud del claro mximo entre dos apoyos considerando la fuerza horizontal mxima
58
9. Seleccin de aisladores para las barras. ........................................................................... 59
10. Calculo de apartarrayo ................................................................................................ 60
10. X. DETERMINAR LA TENSIN NOMINAL Vn (KV) ................................60
11. XI. ENCONTRAR CON LAS CORRIENTES DE DESCARGAS Id(KA) .....61
11. Localizar la distancia del apartarrayo .......................................................................... 63
12. Distancias de diseo .................................................................................................... 65
12. XII. DISTANCIAS DE SEGURIDAD ..................................................................67
13. XIII.ZONAS DE LA SUB ESTACIN ................................................................69
13. Zona de circulacin del personal ................................................................................. 69
14. Zona de circulacin de vehculo .................................................................................. 69
15. Zonas de trabajo .......................................................................................................... 69
14. XIV.CONCLUSIONES ..........................................................................................70
15. XV. ANEXOS ..........................................................................................................71








Diseo de Subestaciones Elctricas



3









I. DISEO DE UNA SUB ESTACION EN EL
MUNICIPIO DE DIRIAMBA, CARAZO
VARIANTE (V11)











Diseo de Subestaciones Elctricas



4



II. INTRODUCCIN

Una Sub estacin elctrica es una instalacin destinada a modificar y establecer los
niveles de tensin de una infraestructura elctrica, con el fin de facilitar el transporte y
distribucin de la energa elctrica. Su equipo principal es el transformador.
Como norma general, se puede hablar de subestacin elctricas elevadoras, situadas en
las inmediaciones de las centrales generadoras de energa elctrica, cuya funcin es
elevar el nivel de tensin, hasta 132.220 o incluso 400 kv, antes de entregar la energa a
la red de transporte. Las subestaciones elctricas reductoras, reducen el nivel de tensin
hasta valores que oscilan, habitualmente entre 13.2, 15, 20, 45 66 kv y entregan la
energa a la red de distribucin. Posteriormente, los centros de transformacin reducen
los niveles de tensin hasta valores comerciales baja tensin apta para el consumo
domstico e industriales, tpicamente 400.
La razn tcnica que explica porque el transporte y la distribucin en energa elctrica
se realizan a tensiones elevadas, y en consecuencia, porque necesarias las subestaciones
elctricas es la siguiente:
Por tanto, cuanto mayor sea el nivel de tensin, menor deber ser el de intensidad para
transmitir la misma potencia y en consecuencia menores sern las prdidas por efecto
joule.

Diseo de Subestaciones Elctricas



5





III. OBJETIVOS
1. Objetivo General

Realizar el diseo elctrico de una sub estacin para los equipos mayores 1000
volts en el primer semestre 2012



2. Objetivos Especficos

- Disear el sistema elctrico correspondiente a la sub estacin reductora
de voltaje de la ciudad de Diriamba.
- Disear un plano de la sub estacin antes mencionada.
- Plasmar en un documento los clculos del proyecto.
- Aplicar los conocimientos adquiridos en la asignatura de diseo de sub
estaciones elctricas.









Diseo de Subestaciones Elctricas



6
IV. INFORMACIN GENERAL

- Nombre del Departamento: Carazo
- Nombre del Municipio: Diriamba
- Fecha de fundacin: 6 de Octubre de 1984
- Coordenadas Geogrficas: Se encuentra ubicada entre los 115longitud
norte 86 14 de longitud oeste.
-
Extensin Territorial: 348.88 km
2
- Lmites: Al norte con el municipio de San Marcos
Al sur con el Ocano Pacifico
Al este con los municipios de Jinotepe y Dolores
Al oeste con los municipios de San Rafael del Sur y el Ocano
Pacifico
- Altitud: 580.13 mts
- Referencia Geogrfica: A 41 km de Managua y a 5 km de Jinotepe
- Clima: El rea corresponde a la denominada Bosque Hmedo Tropical, se
caracteriza por tener un clima hmedo, relativamente fresco.
- Temperatura: La temperatura anual oscila entre los 22 y en poca de
invierno bajo hasta los 18 .
- Precipitacin: La precipitacin alcanza entre 1,200 y 1400, mm
- Humedad Relativa. La humedad relativa es de 89.2%
- Vientos: La velocidad de los vientos oscila entre 5m/seg y 2 m/seg
- Topografa: Se caracteriza por tener una topografa tipo altiplanicie, que
descienden hasta el Oeste con porcentaje no mayores al 8%.
- Morfologa: Corresponde a una zona de montaas de poca alturas con perfiles
accidentales por la depresin irregular de la Mesetas de los Pueblos.
- Hidrologa: Se localiza en la parte media de la micro cuenca del rio Amayo, los
principales ros que cruzan el municipio son rio Grande, rio Limn, rio Amayito,
rio la Flor y rio la Maquina. Las aguas subterrneas se encuentran a una
profundidad que vara entre 254m y 291m.
- Geologa: Se localiza dos falla geolgicas no confirmadas: La primera ubicada
en el sector noroeste de la ciudad, y la segunda, al suroeste de la misma.
- Tipos de Suelos: Se logran a identificar tres materiales geolgicos en el territorio
urbano: arcilla, cantera de la composicin pomcea y caliza, suelo franco
arcilloso limoso


Diseo de Subestaciones Elctricas



7




3. Breve Resea Histrica

No se con precisin el donde se fund la antigua Diriamba, aunque algunos
historiadores opina que estaba situada hacia la regin suroeste de lo que ms tarde se
llam Pueblo Nuevo y su fundacin se le atribuye al Cacique Diriangen, descendiente
de la tribu de los Dirianes que poblaron las altura de los departamentos de Managua,
Masaya y Carazo.
Durante la colonizacin se le conoce como un pequeo poblado con 335 personas que
hilaban el algodn las casas eran de paja y las calles de tierra. La propiedad raz
estaba reducida al solar en que se hallaban las casa y las pequeas huertas destinada a
sembrar lo indispensable, las tierras se adquiran por simple ocupacin, sin otro ttulo;
en el ao 1984 Diriamba fue destruida por un incendio, desde ese entonces de adopt un
nuevo tipo de construccin: al adobe con techos de madera y tejas de barro.
En 1870 fue introducido el cultivo de caf a Diriamba y con ello, las comunicaciones
con las ciudades vecinas se facilitaron, gracias a la utilizacin del ferrocarril, Es
atraves del caf que Diriamba alcanza su mejor momento econmico. La villa de
Diriamba fue elevada a cuidad durante el gobierno de Jos Santos Zelaya, segn decreto
legislativo del 6 de octubre de 1984.
La primera mitad del siglo XX fue para Diriamba un tiempo de prosperidad,
convirtindose en una de las ciudades ms importantes del pas: contaba con colegios de
gran prestigio, club social, hoteles, sala de cines, restaurante alumbrado pblico, calles
pavimentadas etc. Sin embargo, despus de 1979, las fluctuaciones en el precio del caf
y en el mal manejo de los recursos, Diriamba al igual que el resto del pas quedo
sumergida en un estacionamiento que ha perdurado hasta el da de hoy, siendo
actualmente el comercio la principal fuente de ingreso de la ciudad.





Diseo de Subestaciones Elctricas



8
Con el presente trabajo a realizar estaremos utilizando la tabla de cargas especificada a
continuacin, donde estas cagas representan la demanda de potencia de nuestra sub
estacin a disear las cuales proyectaremos a presentar un incremento de potencia anual
pero lo reflejaremos cada 10 aos hasta los 20 aos que es el tiempo de vida til de
nuestra sub estacin elctrica. Cada una de estas representara carga nuestro sistema de
las cuales preveremos suplir todas sus demandas de potencia brindando servicio
continuo.
4. Tabla De Valores V11

VARIANTE 11
POTENCIAS S*100KVA
CARGAS
Tiempo.TH C E P Q V W Y Z Smax Smed Smin
1 5 30 49 60 55 68 65 4 336 68 42 4
2 5 30 51 65 59 68 65 4 347 68 43.375 4
3 5 35 51 65 58 68 68 5 355 68 44.375 5
4 8 35 55 68 57 72 68 5 368 72 46 5
5 8 37 59 68 56 72 68 6 374 72 46.75 6
6 9 36 58 68 55 47 72 6 351 72 43.875 6
7 10 36 57 72 52 47 72 7 353 72 44.125 7
8 11 38 56 72 25 39 58 7 306 72 38.25 7
9 12 42 58 58 37 41 58 8 314 58 39.25 8
10 13 47 59 58 37 45 62 10 331 62 41.375 10
11 14 47 60 62 48 51 67 11 360 67 45 11
12 15 39 68 67 48 40 67 9 353 68 44.125 9
13 15 41 62 67 35 31 59 10 320 67 40 10
14 15 45 64 59 30 31 47 15 306 64 38.25 15
15 15 51 55 47 58 24 47 15 312 58 39 15
16 15 40 52 47 58 39 39 17 307 58 38.375 15
17 11 31 25 39 62 39 41 15 263 62 32.875 11
18 11 31 37 41 67 43 45 11 286 67 35.75 11
19 10 31 37 45 67 43 51 9 293 67 36.625 9
20 11 29 48 51 59 38 12 9 257 59 32.125 9
21 10 30 25 39 38 59 26 7 234 59 29.25 7
22 8 30 37 41 42 58 26 5 247 58 30.875 5
23 5 30 37 45 47 57 38 4 263 57 32.875 4
24 5 30 48 51 55 68 65 4 326 68 40.75 4
246 871 1208 1355 1205 1188 1286 203 7562
Smax 15 51 68 72 67 72 72 17 374
Smed 10.25 36.291 50.333 56.458 50.208 49.5 53.583 8.4583 315.8033
Smin 5 29 25 39 25 24 12 4 234

Diseo de Subestaciones Elctricas



9

5. Estudio De Cargas

Como objetivo principal de este centro de distribucin energtica es cumplir con el
servicio continuo de energa a todos los usuarios y con la calidad requerida. Las
necesidades que presentan los consumidores son distintas a cada hora del da
ocasionado que haya variaciones en el sistema elctrico o cmo podemos decir que
aumento o disminuya la demanda de potencia en dependencia del uso de la energa
refirindose si es de uso domiciliar o industrial. Para poder darnos cuenta de las
variaciones de las cargas tenemos que realizar los siguientes estudios:
1. Obtener el valor mximo de su demanda.
2. Hacer un estudio de cargas individuales, es decir apreciar cul es su
contribucin a la demanda total del conjunto del cual forma parte.
3. Determinar el consumo de energa en tiempo dado.
4. Determinar la variacin de la carga durante las distintas horas del da
El trabajo realizado comprende los estudios de demanda mxima, factor de demanda,
factor de diversidad, factor de carga, factor de prdidas, horas equivalentes y los
respectivos grficos que comprenden estos estudios
- Demanda Mxima: Es la demanda mxima que presenta la carga en funcin de
un determinado tiempo.
- Factor de Demanda: Por carga instalada se asume la sumatoria de las potencias
de todos los equipos existentes en el lugar para el que se calcula el factor de
demanda, el cual no puede ser mayor a la unidad.
- Factor de Diversidad: Es la forma que se expresa la relacin que existe en la
coincidencia de los valores de demandas mximas.
- Factor de carga: Es la manera de valorar el grado de utilizacin de un sistema.
Esta dado por la siguiente formula:
- Factor de Perdida: Es la relacin entre el valor medio y el valor mximo de
potencias disipadas en prdidas en un intervalo de tiempo dado. Es uno de los
ndices ms representativos al analizar la energa perdida en un periodo de
tiempo de las lneas de transmisin o distribucin.
- Horas Equivalentes: Es el nmero de horas en que se debe mantener el valor
pico de las perdidas y de las cargas, para que se produzcan unas prdidas iguales
a las que se producen las cargas con sus variaciones.
Diseo de Subestaciones Elctricas


10
6. Graficas de Consumo
Grafica corresponde a la variante V11, nombre de la carga C
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
C 5 5 5 8 8 9 10 11 12 13 14 15 15 15 15 15 11 11 10 11 10 8 5 5

Diseo de Subestaciones Elctricas


11
Grafica corresponde a la variante V11, nombre de la carga E

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
E 30 30 35 35 37 36 36 38 42 47 47 39 41 45 51 40 31 31 31 29 30 30 30 30


Diseo de Subestaciones Elctricas


12
Grafica corresponde a la variante V11, nombre de la carga P

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
P 49 51 51 55 59 58 57 56 58 59 60 68 62 64 55 52 25 37 37 48 25 37 37 48
Diseo de Subestaciones Elctricas


13
Grafica corresponde a la variante V11, nombre de la carga Q


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Q 60 65 65 68 68 68 72 72 58 58 62 67 67 59 47 47 39 41 45 51 39 41 45 51
Diseo de Subestaciones Elctricas


14
Grafica corresponde a la variante V11, nombre de la carga V


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
V 55 59 58 57 56 55 52 25 37 37 48 48 35 30 58 58 62 67 67 59 38 42 47 55
Diseo de Subestaciones Elctricas


15
Grafica corresponde a la variante V11, nombre de la carga W


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
W 68 68 68 72 72 47 47 39 41 45 51 40 31 31 24 39 39 43 43 38 59 58 57 68

Diseo de Subestaciones Elctricas


16
Grafica corresponde a la variante V11, nombre de la carga Y


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Y 65 65 68 68 68 72 72 58 58 62 67 67 59 47 47 39 41 45 51 12 26 26 38 65

Diseo de Subestaciones Elctricas


17
Grafica corresponde a la variante V11, nombre de la carga Z

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Z 4 4 5 5 6 6 7 7 8 10 11 9 10 15 15 17 15 11 9 9 7 5 4 4

Diseo de Subestaciones Elctricas


18




























1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
336 347 335 368 374 351 353 306 314 331 360 353 320 306 312 307 263 286 293 257 234 247 263 326
0
50
100
150
200
250
300
350
400
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
S
*
1
0
0
K
V
A

Tiempo,TH
Sumatoria
Smax=374*100KVA
Smin=234*100KVA
Smed=314*100KVA
100%
62.56%
83.95%
Diseo de Subestaciones Elctricas


19

Diseo de Subestaciones Elctricas



20

V. CALCULO DE COEFICIENTES

7. Coeficiente de demanda

Kdem= Coeficiente de demanda

-

<1




= 0.060




= 0.058




= 0.056


= 0.053


= 0.055


= 0.060




= 0.055




= 0.083




= 0.049






Diseo de Subestaciones Elctricas



21

15
+
15

15
=1

12
+
12
83
12
=1


8. Coeficiente de Diversidad
Kdiv= Factor de Diversidad
Kdiv=




Carga C Carga E











Carga Q
Carga P




Carga W

Carga V

Carga Y
l

12
+7
8

8
=1.05

16
+
18

18
=1.05

12
+
5

5
=1.09

12
+
7

7
=1.06

16
+
16

16
=1

15
+
12
9
14
=1.09

15
+
8

8
=1.12

15
+
18
109
15
=1.08

15
+
5
9
5
=1.13

15
+
7

11
=1.08

15
+
16

15
=1.12

12
+
8

12
=1.04

12
+
18
11
12
=1.16

12
+
5

5
=1.07

12
+
7

12
=1.04

12
+
16
9
14
=1.08

7
+
18

4
=1.11

7
7
+
5

5
=1.03

7
+
7

7
=1

8
+
16
9
8
=1.13

18
+
4
9
4
=1.93

18
+
6

6
=1.09

5
+
5

5
=1.03

5
+
16

5
=1.14

7
+
16
9
7
=1.13
Diseo de Subestaciones Elctricas



22


9. Coeficiente DEL factor de Cargas

F
Carga
=Coeficiente de carga
F
CARGA
=

=0.784 =78.4%

=0.7492 =74.92%

=0.6875 =68.75%




=0.8429 =89.29%


=0.6833 =68.33%

=0.7115 =71.15%

=0.74 =74%

=0.7441 =74.41%

=0.4941 =49.41%

Diseo de Subestaciones Elctricas



23

10. Factor de Perdida

Fperd= factor de perdida
- Factor de Perdidas en Cargas Domiciliares
Fperd= 0.78Fc
2
+ 0.22Fc
Fperd C= 0.78 (0.683)
2
+ 0.22 (0.683)= 0.5141
Fperd E= 0.78 (0.7115)
2
+ 0.22 (0.7115)=0.5513
Fperd P= 0.78 (0.74)
2
+ 0.22 (0.74)=0.5899
Fperd Q= 0.78 (0.784)
2
+ 0.22 (0.784)=0.6519
Fperd V= 0.78 (0.7492)
2
+ 0.22 (0.7492)=0.6026
Fperd W= 0.78 (0.6875)
2
+ 0.22 (0.6875)=0.5199
Fperd Y= 0.78 (0.7441)
2
+ 0.22 (0.7441)=0.5955
Fperd Z= 0.78 (0.4941)
2
+ 0.22 (0.4941)=0.2991
Fperd= 0.78 (0.8395)
2
+ 0.22 (0.8395)=0.7344
- Factor de Prdidas en Carga industriales
Fperd= 0.5Fc
2
+ 0.5Fc
Fperd C= 0.5 (0.683)
2
+ 0.5 (0.683)=0.5747
Fperd E= 0.5 (0.7115)
2
+ 0.5 (0.7115)=0.6088
Fperd P= 0.5 (0.74)
2
+ 0.5 (0.74)=0.6438
Fperd Q= 0.5 (0.784)
2
+ 0.5 (0.784)=0.6993
Fperd V= 0.5 (0.7492)
2
+ 0.5 (0.7492)=0.6552
Fperd W= 0.5 (0.6875)
2
+ 0.5 (0.6875)=0.58
Fperd Y= 0.5 (0.7441)
2
+ 0.5 (0.7441)=0.6488
Fperd Z= 0.5 (0.4941)
2
+ 0.5 (0.4941)=0.3691
Fperd= 0.5 (0.8395)
2
+ 0.5 (0.8395)=0.7721

Diseo de Subestaciones Elctricas



24
11. Hora Equiuvalente

Formula General:

24*F
carga

Para C:


Para E:

Para P:

Para Q:

Para V:

Para W:

Para Y:

Para Z:

Para :







=24*0.6833=16.3992= 16:23:57


=24*0.7115=17.076= 17:4:33


=24*0.74=17.76= 17:45:36


=24*0.784=18.816= 18:48:57


=24*0.7492=17.9808=17:58:50


=24*0.6875=16.5=16:30


=24*0.7455 =17.892= 17:53:31


=24*0.4941=11.8584=11:51:30


=24*0.8429=20.2299=20:13:46

Diseo de Subestaciones Elctricas



25
VI. LOCALIZACION DE LA SUB ESTACION ELECTRICA

Ejes de la Coordenada:

COORDENADAS

CARGAS X[m] Y[m]
C 2028.1028 1841.6189
E 2272.163 600.1404
P 2872.8946 1889.2775
Q 2163.391 1351.4599
V 2772.6623 1237.435
W 858.9664 961.2779
Y 2244.3871 2334.5108
Z 2663.5844 3300.6334

Centros eventuales de carga
X
i
=

1
Y
i
=

1

Dnde:
P
ij
: Potencia de cada consumidor a la hora x
Coordenadas da cada consumidor
n: Numero de consumidor
CEC X[Km] Y[Km] CEC X[Km] Y[Km]
C
1
2131.9236 1446.5581 C
13
2279.2897 1471.122
C
2
2144.0338 1445.3289 C
14
2285.6928 1411.5202
C
3
2146.3792 1437.4533 C
15
2348.9103 1378.9238
C
4
2137.7551 1440.3259 C
16
2278.515 1347.5503
C
5
2146.0447 1437.3259 C
17
2229.3505 1325.9574
C
6
2234.2863 1484.2757 C
18
2240.3605 1375.774
C
7
2227.7305 1480.5287 C
19
2237.2277 1402.8759
C
8
2212.2005 1470.5723 C
20
2270.6865 1302.8133
C
9
2232.9997 1451.8064 C
21
2041.367 1285.4465
C
10
2221.0402 1437.4077 C
22
2094.4522 1321.7569
C
11
2217.3818 1433.252 C
23
2118.5261 1367.2812
C
12
2269.4974 1485.2937 C
24
2128.782 1447.8255

Diseo de Subestaciones Elctricas



26
12. Centros de la Elipse
a
x
=

a
y
=


Dnde:
m: Es el nmero de horas
a
x
a
y
: Esperanzas matemticas
Centros de la Elipse
a
x
2203.1014
a
y
1412.0406

13. La Dispersin:
D
x
=

D
y
=


Est comprobado que al tratar de deducir resultados generales a partir de una pequea
muestra, como nuestro caso, las dispersiones obtenidas al dividir simplemente
entremson ligeramente menores a las verdaderas, por bello se sugiere modificar el
denominador a m-1, osea como se presenta.
De modo que la dimensin de la dispersin esta dada por;


Obtenindose las medidas de exactitud con las variables X,Y
h
x
=

h
y
=


DISPERSIN DESVIASIN EXACTITUD
D
X

5426.5331

73.665 h
x

0.0095
D
Y

3595.9999



59.9666
h
y

0.0117


Diseo de Subestaciones Elctricas



27
14. Momento de Correlacin
C
xy=


Este caracteriza adems la dependencia entre las magnitudes X,Y la dispersin. Se
aprecia que se hizo la misma consideracin referente al divisor.
Coeficiente de correlacin
r=


Siempre que r0 una magnitud bidimensional ser correlacionada, en caso contrario no
habr correlacin. Es decir si r0 X,Y son dependientes y si r=0 son independientes
entre s.
15. ngulos de los ejes de Simetra de la Elipse

1




CORRELACIN RADIO ANGULO DMC DEL SISTEMA(
Cxy 739.0123
R

171.288

0.1672 19.4591

181.993

Desviaciones medias- cuadrticas del sistema de coordenadas

=
2
Cos
2
+r

x

2
y
Sen2+

Sen
2

=
2
Sen
2
+r

x

2
y
Sen2+

Cos
2


-Estas se expresan por medio de las desviaciones medio-cuadrticas del sistema original
de coordenadas

Diseo de Subestaciones Elctricas



28
16. Exactitud de los nuevos ejes:





Asumiendo que el 95 % de los centros eventuales de carga ocurren dentro de la elipse
se obtiene 2 ~ 3, por lo tanto

h
R

3
=

h
R

3
=


EXACTITUD
DEL SISTEMA
(,)
RADIOS DE LA ELIPSE DEL
SISTEMA (,)
H 0.011589 R 149.4529
H 0.006402 R 270.5388



Con los siguientes datos podemos determinar la ubicacin de nuestra sub estacin
elctrica:
Necesarios para la ubicacin de la sub estacin elctrica.





h

= 1/ ( 2 )

= 1/( 2)


ESPERANZA MAT DISPERSION DESV EXACTITUD
Ax 2029.1478 Dx 5454.2951

x 73.8531 hx 0.009574
Ay 1194.785 Dy 3456.8543 y 58.795 hy 0.012026
CORRELACION RADIO ANGULO DMC DEL SISTEMA (,)
Cxy r 57.9653
905.56223 0.2085492 21.099652 61.48709
Diseo de Subestaciones Elctricas


29
17. VISTA DE LA ELIPSE






Diseo de Subestaciones Elctricas



30
VII. SELECCIN DE TRANSFORMADOR DE POTENCIA

Ecuaciones a utilizar



Sf= Potencia final proyectada a n aos, MVA
Si= Potencia inicial, MVA
r= Crecimiento a n aos, MVA
n= Aos de proyeccin

Para realizar la seleccin de transformadores de potencia debemos de asegurar la
calidad de alimentacin elctrica en el punto de ubicacin y categora de los
transformadores. Esto se realiza con el objetivo de brindar continuidad en el servicio
elctrico para los consumidores.
La cantidad de transformadores a instalar va a depender de la clasificacin de los
consumidores que tengamos ya que si tenemos consumidores de primera categora
tenemos la obligacin de brindar servicio continuo y por medio de 2 redes, por lo tanto
nos obliga a instalar 2 transformadores de potencia en una sola sub estacin. Debemos
de tomar en cuenta que instalar un solo transformador tenemos la ventaja de reducir los
costos de construccin.
Los transformadores de potencia que podemos utilizar en dependencia de su tipo de
aislamiento son los siguientes:
Transformadores de dos bobinas trifsicos:
1*63MVA aceite con sistema de ventilacin.
1*32MVA aceite con sistema de ventilacin.
2*32MVA aceite con sistema de ventilacin.
En las siguientes tablas presentaremos el incremento de las carga en dependencia del
paso de los aos. Esto se mostrara en 10 aos y 20 aos observaremos el incremento
total de las cargas, as procedemos a la seleccin de nuestro transformador de potencia.
La seleccin de los transformadores estar en dependencia de la categora de los
consumidores que existan; en este caso se tienen consumidores de categora I, II, III.
Por ende se instalaran dos transformadores; por la existencia de consumidores de
categora I, II los cuales deben estar siempre alimentados .Desde luego si la red de
( )
n
i f
r S S + = 1
Diseo de Subestaciones Elctricas



31
distribucin lo permite. Una vez planteadas las variantes y despus de haber analizado
ciertos criterios se determin: 2) transformador de 32MVA. Los cuales suplirn la
demanda en los 20 aos en la que fue proyectada.

1. Factor de carga del la variante:


TABLA DE INCREMENTO PARA DETERMINAR LAS VARIANTES DEL
TRANSFORMADOR.



10 AOS 20 AOS
PARES IMPAR PARES IMPARES
2.5% 3.25% 2.25% 3.5%






Coordenadas
Incremento
Cargas Categoras Coordenadas en X Coordenadas en Y 10 AOS 20 AOS
C 1
2028.1028 1841.6189
+25% +15%
E 3
2272.163 600.1404
-27% +10%
P 3
2872.8946 1889.2775
+25% -17%
Q 3
2163.391 1351.4599
-27% +28%
V 2
2772.6623 1237.435
+30% +15%
W 2
858.9664 961.2779
+25% -22.5%
Y 3
2244.3871 2334.5108
+15% +18%
Z 3
2663.5844 3300.6334
-20% +15%
( )
n
i f
r S S + = 1
Diseo de Subestaciones Elctricas


32


Tabla De Cargas Para El Primer Ao



1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
C
o
n
s
u
m
i
d
o
r
,
1
0
0
K
V
A

C 5 5 5 8 8 9 10 11 12 13 14 15 15 15 15 15 11 11 10 11 10 8 5 5
E 30 30 35 35 37 36 36 38 42 47 47 39 41 45 51 40 31 31 31 29 30 30 30 30
P 49 51 51 55 59 58 57 56 58 59 60 68 62 64 55 52 25 37 37 48 25 37 37 48
Q 60 65 65 68 68 68 72 72 58 58 62 67 67 59 47 47 39 41 45 51 39 41 45 51
V 55 59 58 57 56 55 52 25 37 37 48 48 35 30 58 58 62 67 67 59 38 42 47 55
W 68 68 68 72 72 47 47 39 41 45 51 40 31 31 24 39 39 43 43 38 59 58 57 68
Y 65 65 68 68 68 72 72 58 58 62 67 67 59 47 47 39 41 45 51 12 26 26 38 65
Z 4 4 5 5 6 6 7 7 8 10 11 9 10 15 15 17 15 11 9 9 7 5 4 4
336 347 355 368 374 351 353 306 314 331 360 353 320 306 312 307 263 286 293 257 234 247 263 326
Diseo de Subestaciones Elctricas


33


Tabla De Cargas Para Los 10 Aos






1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
6.8845 6.8845 6.88 11.02 11.02 12.39 13.769 15.1 16.523 17.9 19.28 20.65 20.653 20.653 20.7 20.65 15.15 15.1 13.77 15.1 13.8 11 6.8845 6.8845
38.403 38.403 44.8 44.8 47.36 46.08 46.083 48.6 53.764 60.16 60.16 49.92 52.483 57.604 65.3 51.2 39.68 39.7 39.68 37.1 38.4 38.4 38.403 38.403
67.468 70.222 70.2 75.73 81.24 79.86 78.483 77.1 79.86 81.24 82.61 93.63 85.367 88.121 75.7 71.6 34.42 50.9 50.95 66.1 34.4 50.9 50.945 66.091
76.805 83.205 83.2 87.05 87.05 87.05 92.166 92.2 74.245 74.24 79.37 85.77 85.766 75.525 60.2 60.16 49.92 52.5 57.6 65.3 49.9 52.5 57.604 65.284
75.729 81.237 79.9 78.48 77.11 75.73 71.599 34.4 50.945 50.95 66.09 66.09 48.191 41.307 79.9 79.86 85.37 92.3 92.25 81.2 52.3 57.8 64.714 75.729
87.046 87.046 87 92.17 92.17 60.16 60.164 49.9 52.483 57.6 65.28 51.2 39.683 39.683 30.7 49.92 49.92 55 55.04 48.6 75.5 74.2 72.965 87.046
89.498 89.498 93.6 93.63 93.63 99.14 99.136 79.9 79.86 85.37 92.25 92.25 81.237 64.714 64.7 53.7 56.45 62 70.22 16.5 35.8 35.8 52.322 89.498
5.1203 5.1203 6.4 6.4 7.681 7.681 8.9606 8.96 10.241 12.8 14.08 11.52 12.801 19.201 19.2 21.76 19.2 14.1 11.52 11.5 8.96 6.4 5.1203 5.1203
446.95 461.62 472 489.3 497.2 468.1 470.36 406 417.92 440.3 479.1 471 426.18 406.81 416 408.9 350.1 382 391 342 309 327 348.96 434.06
Diseo de Subestaciones Elctricas


34


Tabla De Cargas Para Los 20 Aos


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
9.9489 9.9489 9.95 15.92 15.92 17.91 19.898 21.9 23.877 25.87 27.86 29.85 29.847 29.847 29.8 29.85 21.89 21.9 19.9 21.9 19.9 15.9 9.9489 9.9489
46.815 46.815 54.6 54.62 57.74 56.18 56.178 59.3 65.541 73.34 73.34 60.86 63.981 70.223 79.6 62.42 48.38 48.4 48.38 45.3 46.8 46.8 46.815 46.815
97.5 101.48 101 109.4 117.4 115.4 113.42 111 115.41 117.4 119.4 135.3 123.37 127.35 109 103.5 49.74 73.6 73.62 95.5 49.7 73.6 73.622 95.51
93.631 101.43 101 106.1 106.1 106.1 112.36 112 90.51 90.51 96.75 104.6 104.55 92.07 73.3 73.34 60.86 64 70.22 79.6 60.9 64 70.223 79.586
109.44 117.4 115 113.4 111.4 109.4 103.47 49.7 73.622 73.62 95.51 95.51 69.643 59.694 115 115.4 123.4 133 133.3 117 75.6 83.6 93.52 109.44
106.11 106.11 106 112.4 112.4 73.34 73.344 60.9 63.981 70.22 79.59 62.42 48.376 48.376 37.5 60.86 60.86 67.1 67.1 59.3 92.1 90.5 88.949 106.11
129.34 129.34 135 135.3 135.3 143.3 143.26 115 115.41 123.4 133.3 133.3 117.4 93.52 93.5 77.6 81.58 89.5 101.5 23.9 51.7 51.7 75.612 129.34
6.242 6.242 7.8 7.803 9.363 9.363 10.924 10.9 12.484 15.61 17.17 14.04 15.605 23.408 23.4 26.53 23.41 17.2 14.04 14 10.9 7.8 6.242 6.242
599.03 618.77 632 655 665.6 631 632.85 542 560.83 589.9 642.9 635.9 572.77 544.48 562 549.5 470.1 515 528.1 457 408 434 464.93 582.99
Diseo de Subestaciones Elctricas



35
2. Perdidas en los transformadores de potencia
Para ello es necesario el uso de un conjunto de ecuaciones tales como:
Coeficiente de llenado.


Kll a 1 Ao

3108 100
37 100
08
Kll
1
=0.8424

19 100
97 100
08
Kll
10
=0.8426.

100
100
083
Kll
20
=0.8443.
Sobre carga del transformador
VARIABLE 1. 1.3 (1*32MVA)=32 MVA
VARIABLE 2. 1.3 (2*32MVA)=64 MVA
VARIABLE 3. 1.3 (1*63MVA)=63 MVA.
Sobre carga admisible permisible.
VARIABLE 1.
Sap=

(1-KLL) 0.3
1 3 1 087 03
Sap=1.20 MVA.
VARIABLE 2.
Sap=

(1-KLL) 0.3
3 1 087 03
Diseo de Subestaciones Elctricas



36
Sap=2.41 MVA.
VARIABLE 3.
31 087 03
Sap=2.37 MVA
Al realizar el clculo de las prdidas totales del transformador debemos de considerar las prdidas que se
generan en este con carga y sin carga para obtener un valor total.
Siendo:
AP
SC
: Prdidas referidas del transformador sin carga, consideran las prdidas de potencia activa, tanto
del transformador como las creadas por los elementos del sistema debido a la potencia reactiva
demandada por el mencionado transformador (KW)
AP
CCTO
: Anlogamente, Prdidas referidas de cortocircuito
k
C
: Coeficiente de Carga
S
C
: Carga real del transformador o de clculo (kVA)
S
N
: Potencia nominal o de chapa del transformador
AP
SC
: Prdidas de potencia sin carga, aproximadamente iguales a las prdidas del ncleo del
transformador (Kw)
AP
CCTO
: Prdidas de potencia de cortocircuito o prdidas del cobre (KW)
k
ip
: Coeficiente incremental de prdidas, dado por el sistema de energa para la planta en cuestin
en correspondencia con su localizacin. Esta entre 0.02 0.12 (Kw/Kvar)
AQ
SC
: Potencia reactiva del trasformador sin carga (Kvar)
AQ
CC
: Potencia reactiva demandada por el transformador a plena carga (Kvar)
I
SC
: Corriente del transformador sin carga.
V
CCTO
: Voltaje de cortocircuito del transformador.

Donde


Prdidas referidas al transformador sin carga.
Diseo de Subestaciones Elctricas



37
P
SC
= P
SC
+ K
ip
Q
SC
Prdidas referidas al transformador con carga.
P
CC
= P
CC
+ K
ip
Q
CC

Esto se resume en:
P
CT
= P
SC
+ P
CC
S
2
C

S
2
N
Caracterstica de los transformadores
Tipo


TVC 32000/138 10.5 40.0 145.0 0.7 76.0
TCFC 64000/138 10.5 70.0 245.0 0.60 110.0



PRIMER VARIABLE DE TRANSFORMADOR 1*32MVA

3000
07
100

3000
10
100
330
Diseo de Subestaciones Elctricas



38

0 008 79

1 008330 138

79
138
3000

79 001 10


SEGUNDA VARIABLE DE TRANSFORMADOR 2*32MVA


7
138
3000

1180810



TERCERA VARIABLE DE TRANSFORMADOR 63MVA

3000

378

70008378 100

0081 7

100
7
3000

1000187 10

S
P P P
N
S
C
CC sc
2
2
2 2 32 * 2 A A ' A
+ =
Diseo de Subestaciones Elctricas



39
Tabla de perdidas para el 1 ao


TRANFORMADOR DE 63*MVA TRANFORMADOR DE 32*MVA 2 TRANFORMADORES DE 32*MVA
Escalones
Sc
MVA
H/Ao Kc P't, kw Perd kw-H Costo Perd $ Kc P't, kw Perd kw-H Costo Perd $ Kc = 0.5 P't, kw Perd kw-H Costo Perd $
0 0 0 0 100.24 0 0 0 57.92 0 0 115.84 0 0
1 23.4 365 5.794 207.048 75572.52 9295.41996 0.731 279.189852 101904.296 12534.22839 0.3656 226.474926 82663.3479 10167.59179
2 24.7 365 5.794 219.24521 80024.5016 9843.013697 0.772 304.458322 111127.288 13668.65638 0.3859 239.109161 87274.8438 10734.80579
3 25.7 365 5.794 229.076321 83612.85716
10284.38143
0.803 324.825041 118561.14
14583.02022
0.4016 249.292521 90991.77
11191.98771
4 26.3 730 11.587 235.162247 171668.4402
10557.60908
0.822 337.43301 246326.097
15149.05497
0.4109 255.596505 186585.449
11475.00509
5 28.6 365 5.794 259.792691 94824.33235
11663.39288
0.894 388.458914 141787.504
17439.86295
0.4469 281.109457 102604.952
12620.40907
6 29.3 350 5.556 267.698543 93694.49012
24036.65219
0.916 404.83715 147765.56
36350.32773
0.4578 289.298575 105593.98
25976.11907
7 30.6 730 11.587 282.888 206508.24
12700.25676
0.956 436.304539 318502.314
19587.89228
0.4781 305.03227 222673.557
13694.42374
8 30.7 365 5.794 284.083728 103690.5609
25507.87797
0.959 438.781682 160155.314
39398.20719
0.4797 306.270841 111788.857
27500.0588
9 31.2 365 5.794 290.120889 105894.1244
13024.97731
0.975 451.288625 164720.348
20260.60282
0.4875 312.524313 114071.374
14030.77901
10 31.4 365 5.794 292.563062 106785.5175
13134.61866
0.981 456.347977 166567.011
20487.74241
0.4906 315.053988 114994.706
14144.3488
11 32 365 5.794 299.98321 109493.8716 13467.74621 1.000 471.72 172177.8 21177.8694 0.5000 322.74 117800.1 14489.4123
12 32.6 365 5.794 307.543802 112253.4879 13807.17901 1.019 487.382977 177894.786 21881.05873 0.5094 330.571488 120658.593 14841.00697
13 33.1 365 5.794 313.95158 114592.3268 14094.8562 1.034 500.657713 182740.065 22477.02802 0.5172 337.208856 123081.233 15138.99161
14 33.6 365 5.794 320.456889 116966.7644 14386.91203 1.050 514.1345 187659.093 23082.06838 0.5250 343.94725 125540.746 15441.51179
15 34.7 365 5.794 335.111877 122315.8349
15044.8477
1.084 544.49465 198740.547
24445.08733
0.5422 359.127325 131081.474
16123.02126
16 35.1 365 5.794 340.558 124303.67
15289.35141
1.097 555.777166 202858.666
24951.61587
0.5484 364.768583 133140.533
16376.28553
17 35.3 730 11.587 343.304469 250612.2625
15412.65414
1.103 561.466916 409870.849
25207.05719
0.5516 367.613458 268357.824
16504.0062
18 35.5 365 5.794 346.066543 126314.2883
15536.65746
1.109 567.188994 207023.983
25463.94989
0.5547 370.474497 135223.191
16632.45255
19 36 365 5.794 353.04 128859.6
15849.7308
1.125 581.635625 212297.003
26112.53138
0.5625 377.697813 137859.702
16956.74329
20 36.8 365 5.794 364.400395 133006.1442
16359.75574
1.150 605.1705 220887.233
27169.1296
0.5750 389.46525 142154.816
17485.0424
21 37.4 365 5.794 373.084543 136175.8583
16749.63057
1.169 623.161102 227453.802
27976.81765
0.5844 398.460551 145438.101
17888.88643


2597169.693 306047.5212

4077020.7 479403.8088

2799579.15 329412.8892

Diseo de Subestaciones Elctricas



40
Tabla de perdidas para el 10 ao

Transformador de 63*MVA TRAFORMADOR DE*32 MVA 2 TRANFORMADORES DE 32*MVA

Escalones
Sc
MVA
H/Ao Kc P't, kw Perd kw-H
Costo Perd
$
Perd kw-H
Costo Perd
$
Kc = 0.5 P't, kw Perd kw-H Costo Perd $
0 0 0 0 100.24 0
0
0 57.92 0
0
0 115.84 0
0
1 30.91 365 0.491 286.607457 104611.7216
12867.242
0.966 444.009988 21140.8
2600.318
0.483 308.884994 112743.023
13867.392
2 32.71 365 0.519 308.945145 112764.9781
13870.092
1.022 490.286083 162063.646
19933.828
0.511 332.023041 121188.41
14906.174
3 34.15 365 0.542 327.725377 119619.7624
14713.231
1.067 529.192334 178954.42
22011.394
0.534 351.476167 128288.801
15779.523
4 34.89 365 0.554 337.691002 123257.2158
15160.638
1.090 549.837722 193155.202
23758.090
0.545 361.798861 132056.584
16242.960
5 35.01 365 0.556 339.32718 123854.4207
15234.094
1.094 553.227326 200690.768
24684.965
0.547 363.493663 132675.187
16319.048
6 38.15 365 0.606 384.137228 140210.0884
17245.841
1.192 646.058506 201927.974
24837.141
0.596 409.909253 149616.877
18402.876
7 39.10 365 0.621 398.452321 145435.0972
17888.517
1.222 675.71451 235811.355
29004.797
0.611 424.737255 155029.098
19068.579
8 40.62 730 0.645 422.088809 154062.4152
18949.677
1.269 724.681274 246635.796
30336.203
0.635 449.220637 163965.533
20167.761
9 40.89 365 0.649 426.381669 155629.3091
19142.405
1.278 733.57462 264508.665
32534.566
0.639 453.66731 165588.568
20367.394
10 41.63 365 0.661 438.293074 319953.9443
19677.168
1.301 758.251001 267754.736
32933.833
0.650 466.005501 170092.008
20921.317
11 41.79 365 0.663 440.896602 160927.2598
19794.053
1.306 763.644626 276761.615
34041.679
0.653 468.702313 171076.344
21042.390
12 42.61 365 0.676 454.396434 165854.6985
20400.128
1.332 791.611687 278730.288
34283.825
0.666 482.685843 176180.333
21670.181
13 43.40 365 0.689 467.650469 170692.4212
20995.168
1.356 819.069539 288938.266
35539.407
0.678 496.41477 181191.391
22286.541
14 44.03 365 0.699 478.394645 174614.0453
21477.528
1.376 841.327817 298960.382
36772.127
0.688 507.543908 185253.527
22786.184
15 44.70 365 0.709 489.903701 178814.8509
21994.227
1.397 865.170668 307084.653
37771.412
0.698 519.465334 189604.847
23321.396
16 46.10 365 0.732 514.787136 187897.3046
23111.368
1.441 916.720682 315787.294
38841.837
0.720 545.240341 199012.724
24478.565
17 46.81 365 0.743 527.654597 192593.928
23689.053
1.463 943.377686 334603.049
41156.175
0.731 558.568843 203877.628
25076.948
18 47.03 365 0.747 531.681608 194063.7868
23869.846
1.470 951.720282 344332.855
42352.941
0.735 562.740141 205400.151
25264.219
19 47.10 365 0.748 532.966889 194532.9144
23927.548
1.472 954.382947 347377.903
42727.482
0.736 564.071474 205886.088
25323.989
20 47.20 365 0.749 534.806321 195204.3072
24010.130
1.475 958.193625 348349.776
42847.022
0.738 565.976813 206581.537
25409.529
21 47.91 365 0.760 547.978469 200012.1411
24601.493
1.497 985.481836 349740.673
43018.103
0.749 579.620918 211561.635
26022.081
22 48.93 365 0.777 567.246042 207044.8054
25466.511
1.529 1025.39769 359700.87
44243.207
0.765 599.578847 218846.279
26918.092
23 49.72 365 0.789 582.447885 212593.4782
26148.998
1.554 1056.89074 374270.159
46035.230
0.777 615.325372 224593.761
27625.033


3934244.894 464234.954

6197281.14 762265.581

4010310.33 493268.171
Diseo de Subestaciones Elctricas



41

TABLA DE PERDIDAS PARA EL 20 AO

TRANFORMADOR DE 63*MVA TRANSFORMADOR DE 32*MVA 2TRANSFORMADOR DE 32*MVA

Escalones
Sc
MVA
H/Ao Kc P't, kw Perd kw-H
Costo Perd
$
Kc P't, kw Perd kw-H Costo Perd $ Kc = 0.5 P't, kw Perd kw-H Costo Perd $
0 0 0 0 100.24 0
0
0 57.92 0
0
0 115.84 0
0
1 40.76 365 0.647 424.311186 154873.583
19049.4507
1.274 729.285284 21140.8
2600.318
0.6369 451.522642 164805.764
20271.109
2 43.39 365 0.689 467.481175 170630.6289
20987.56735
1.356 818.718819 266189.129
32741.263
0.678 496.23941 181127.385
22278.668
3 45.68 365 0.725 507.267974 185152.8106
22773.79571
1.428 901.143536 298832.369
36756.381
0.714 537.451768 196169.895
24128.897
4 46.49 365 0.738 521.830834 190468.2545
23427.59531
1.453 931.312829 328917.391
40456.839
0.726 552.536415 201675.791
24806.122
5 47.01 365 0.746 531.314736 193929.8785
23853.37505
1.469 950.960247 339929.183
41811.289
0.735 562.360124 205261.445
25247.158
6 51.49 365 0.817 617.391575 225347.9249
27717.79476
1.609 1129.28218 347100.49
42693.360
0.805 651.521092 237805.199
29250.039
7 52.8 365 0.838 644.040889 235074.9244
28914.21571
1.650 1184.4905 412187.998
50699.124
0.825 679.12525 247880.716
30489.328
8 54.19 365 0.860 673.049708 245663.1436
30216.56666
1.693 1244.58691 432339.033
53177.701
0.847 709.173454 258848.311
31838.342
9 54.44 365 0.864 678.347097 247596.6905
30454.39293
1.701 1255.5613 454274.222
55875.729
0.851 714.660648 260851.137
32084.690
10 54.95 365 0.872 689.229377 251568.7224
30942.95286
1.717 1278.10568 458279.873
56368.424
0.859 725.932839 264965.486
32590.755
11 56.08 365 0.890 713.702582 260501.4423
32041.67741
1.753 1328.80584 466508.573
57380.554
0.876 751.282918 274218.265
33728.847
12 56.2 365 0.892 716.330765 261460.7294
32159.66971
1.756 1334.25054 485014.13
59656.738
0.878 754.00527 275211.923
33851.067
13 57.27 365 0.909 740.013776 270105.0281
33222.91845
1.790 1383.31368 487001.447
59901.178
0.895 778.536841 284165.947
34952.411
14 58.29 365 0.925 763.005936 278497.1665
34255.15148
1.822 1430.94562 504909.494
62103.868
0.911 802.352809 292858.775
36021.629
15 58.99 365 0.936 779.019723 284342.199
34974.09047
1.843 1464.12074 522295.15
64242.304
0.922 818.94037 298913.235
36766.328
16 59.9 365 0.951 800.123432 292045.0527
35921.54148
1.872 1507.84045 534404.07
65731.701
0.936 840.800224 306892.082
37747.726
17 61.87 365 0.982 846.916185 309124.4077
38022.30214
1.933 1604.77912 550361.763
67694.497
0.967 889.269559 324583.389
39923.757
18 63.1 365 1.002 876.899728 320068.4009
39368.41331
1.972 1666.89482 585744.378
72046.559
0.986 920.327411 335919.505
41318.099
19 63.21 365 1.003 879.609936 321057.6265
39490.08806
1.975 1672.50945 608416.61
74835.243
0.988 923.134725 336944.175
41444.133
20 63.28 365 1.004 881.337071 321688.0308
39567.62779
1.978 1676.08749 610465.949
75087.312
0.989 924.923743 337597.166
41524.451
21 63.58 365 1.009 888.76073 324397.6664
39900.91297
1.987 1691.46678 611771.932
75247.948
0.993 932.613392 340403.888
41869.678
22 64.29 365 1.020 906.469936 330861.5265
40695.96776
2.009 1728.15423 617385.376
75938.401
1.005 950.957117 347099.348
42693.220
23 65.49 365 1.040 936.848069 341949.5451
42059.79405
2.047 1791.0874 630776.296
77585.484
1.023 982.423698 358584.650
44105.912
24 66.56 365 1.057 964.409023 352009.2935
43297.1431
2.080 1848.18432 653746.899
80410.869
1.040 1010.97216 369004.838
45387.595


6368414.677 783315.0052

11227992.6 1381043.084

6701788.32 824319.963
Diseo de Subestaciones Elctricas



42
0
100
200
300
400
500
600
700
0 5 10 15 20 25 30 35 40
Exponencial (1x63MVA, AO1)
Exponencial (1X32MVA, AO1)
Exponencial (2X32MVA, AO1)
3. Graficas de Perdidas
TABLA CON PRDIDAS DEL PRIMER AO
`


Diseo de Subestaciones Elctricas



43
0
200
400
600
800
1000
1200
1400
0 10 20 30 40 50 60
Exponencial (1X63MVA, 10AO)
Exponencial (1x32MVA, 10AO)
Exponencial (2X32MVA, 10 AO)
Tabla con prdidas de 10 aos

`


Diseo de Subestaciones Elctricas



44
0
500
1000
1500
2000
2500
0 10 20 30 40 50 60 70
Exponencial (1X63MVA, 20 AO)
Exponencial (1X32MVA, 20AO)
Exponencial (2X32MVA, 20AOS)
Tabla con perdidas de 20 aos

`


Diseo de Subestaciones Elctricas



45
5. Intercepcin de graficas
PRIMERA VARIANTE
Intercepcin de los transformadores de 1*32MVA y 1*63MVA:
(a1*32+b1*32S
2
c) = (a2*32+b2*32S
2
c)

(
1 3 3
3 1 3
)
(
79 100
00 7 01 7
)

(
79
00 7
) 198
Para los siguientes aos:

n: nmero de aos
i: incremento porcentual

Para los siguientes aos: proyectaremos la respuesta a cada uno de los aos de la vida til de la subestacin.


191

198
S
20aos


191

39







Diseo de Subestaciones Elctricas



46
SEGUNDA VARIANTE
Transformadores de los transformadores de 1*32MVA y 2*32MVA:
(a1*32+b1*32S
2
c) = (a1*63+b1*63S
2
c)

(
1 3 1 3
1 3 1 3
)
(
79 118
190 7 01 7
)

(
3
090 7
) 1
Para los siguientes aos:

n: nmero de aos
i: incremento porcentual


Para los siguientes aos:


11

39
S
20aos


1 3


11

87
Diseo de Subestaciones Elctricas



47
VIII. TIEMPO DE COMPENSACION DE INVERSION EN COMPRA DE
TRANSFORMADOR DE POTENCIA.

Este es el tiempo en el que se recupera la inversin que se realiz en la compra del transformador de
potencia para la sub estacin elctrica.
Tiempo de compensacin:

C C
K K
T
A B
B A
CO

=

Gastos anuales de explotacin (miles de dlares):

C C C p a
+ =


K
A
= Costo de capital para la variante A
K
B
= Costo capital para la variante B
Ca=costos por amortizacin.
Cp= costos de las prdidas totales.

COSTO DE LOS
TRANSFORMADORES

Primera
2*32MVA
Segunda
1*63MVA

32 63
COSTO $ 76,500 110,000
COSTO TOTAL $ 153000 110,000


Gastos anules de explotacin CA, CB
Ca=0.10K
Cp=E*$KWH





Diseo de Subestaciones Elctricas



48

4. Evaluacin Econmica de la Variantes
















La bibliografa de Suministros Elctricos de Empresas Industriales, nos indica que en la comparacin de dos
equipos de Transformacin el rgimen econmico debe ser menor de siete aos, o su recuperacin
econmica debe ser menor de siete aos. Dicha condicin se cumple en el anlisis de nuestras variantes. .
5. Conexin de los transformadores
La conexin a utilizar en el diseo depende en gran parte de la finalidad u objeto de la subestacin. En este
caso ser: Reduccin de Voltaje. Una conexin muy frecuente es A - Y Aterrizado debido a las siguientes
razones: Al aterrizar el neutro del secundario se aslan las corrientes de tierra de secuencia cero. Se eliminan
tensiones de tercera armnica, ya que la corriente magnetizaste de sta se queda circulando dentro de la delta
del lado primario.
La conexin estrella se usa con aislamiento graduado hasta el valor de la tensin del neutro.



TABLA DE PRIMER AO
VARIANTES Primera 2*32MVA Segunda 1*63MVA
K $ 153000 110000
Ca $ 15300 11000
Cp $ 329412.88 306047.52
C $ 344712.88 317047.52
Tco 1.554290275
TABLA DECIMO AO
VARIANTES Primera 2*32MVA Segunda 1*63MVA
K $ 153000 110000
Ca $ 15300 11000
Cp $ 493268.17 464234.95
C $ 508568.17 475234.95
Tco 1.290004386
TABLA VIGESIMO AO
VARIANTES Primera 2*32MVA Segunda 1*63MVA
K $ 153000 110000
Ca $ 15300 11000
Cp $ 824319.96 783315.000
C $ 839619.96 794315.00
Tco 0.95
Diseo de Subestaciones Elctricas



49
IX. DISEO DE BARRAS COLECTORAS

Clculo para la seleccin de barras colectoras de la Subestacin de la ciudad de Rivas, departamento
de Rivas.

Nivel de voltaje de la SEE
Voltaje en lado Primario 69kV
Voltaje en el lado secundario Secundario 13.8kV
Potencia de Cortocircuito S
ccsist
= 15,000 MVA
Potencia instalada SNT = 63MVA
Potencia mxima del sistema= 55.12MVA

1. Calibre mnimo de la barra

Frmula para la determinacin de la seccin del conductor de las barras del lado de alta tensin y el
lado de media tensin.


Donde la corriente nominal I
N



I < 1,200A, entonces J = 1.5A/mm2
I > 1,200A, entonces J = 0.75A/mm2
I = Corriente nominal en la barra
J = Densidad de corriente para la barra

Tenemos que



Donde
NT
S
= Potencia nominal del transformador = 52.435MVA
V
A
= Tensin de lnea

Para el lado de alta tensin:




V
S
I
LL
N
N
3
3 . 1
=
,
I
Seccin
N
=
3 69
12 . 55 * 3 . 1
kV
MVA
I
Nsc
= A 57 . 599 =
3
. 3 . 1
A
Max
N
V
S
I =
Diseo de Subestaciones Elctricas



50
Para el lado de Baja tensin:




Entonces con los niveles de corriente ya calculados podemos determinar secciones de los conductores:

Para el lado de alta tensin:






Para el lado de baja tensin:





Seccin a utilizar la determinaremos con el uso del libro Diseo de sub estaciones elctricas de Ral
Martin.

Valores de la barra obtenidos de la Tabla 3.7 del libro Diseo de sub Estaciones de Ral Martin.
Para el lado de alta alta:
Se utilizara una barra de: 3/4

Para el lado de baja tensin:
Se utilizar una barra: 2 barras de 4 pulgadas.

2. Calculo de momento de inercia





t : Constante
I: Momento de Inercia de la Seccin (cm
4
)
D: Dimetro de la barra a utilizar (
2
cm )
Nota: Estos clculos se realizan tanto para el lado de alta como para el lado de baja
3 8 . 13
12 . 55 * 3 . 1
kV
MVA
I
Nsc
=
A 870 . 2997 =
2
2
71 . 399
5 . 1
57 . 599
mm
mm
A
A
I
Seccin
N
A
= = =
,
2
2
16 . 3997
75 . 0
870 . 2997
mm
mm
A
A
I
Seccin
N
B
= = =
,
( )
64
t D D
I
INTERIOR EXTERIOR

=
Diseo de Subestaciones Elctricas



51

Momento de inercia para los cables de potencia del lado alta tensin:
I=
4
0779 . 3 cm
Momento de inercia para los cables de potencia del lado de baja tensin:
I=
4
32 . 249 cm


3. Calculo del claro y la flecha para la seleccin mxima:

La determinacin del Claro se realiza con la formula siguiente:


Donde
L: Claro (cm/mts)
E: Mdulo de Elasticidad (Kg / cm
2
)
I: Momento de Inercia de la Seccin (cm
4
)
W: Peso Unitario del Tubo (Kg / cm)

En la tabla 3.7 del libro Diseo de sub Estaciones de Ral Martin, se establece el momento de inercia
correspondiente a cada una de las barras. Y a la tabla de propiedades de los materiales de Enrquez Harper
Gilberto en la pgina 582.
Para nuestro calculo en el lado de alta tensin:
L: Claro (cm/mts)
E: 700000 (Kg / cm
2
)
I: 3.078 (cm
4
)
W: 0. 016338(Kg / cm)

3
016338 . 0 * 750
078 . 3 700000 608 , 4 - -
=
L


mts L 323 . 9 =
Para nuestro calculo en el lado de baja tensin:
L: Claro (cm/mts)
E: 700000 (Kg / cm
2
)
I: 249.32 (cm
4
)
W: 0.016338 (Kg / cm)

3
750
608 , 4
W
I E
L
- -
=
Diseo de Subestaciones Elctricas



52
3
016338 . 0 * 750
32 . 249 700000 608 , 4 - -
=
L


mts L 34 . 40 =
L= 40mts


Calculo de Flecha para el lado de alta y el lado de baja tensin:

1
10

L=10mts

L: Claro (cm/mts)
F: Flecha (cm/mts)

Para nuestro calculo en el lado de alta tensin:


1
10
10 00


Para nuestro calculo en el lado de baja tensin:


1
10
0 89
4. Tensin critica de flameo

Es una tensin que se obtiene de forma experimental, y que representa una probabilidad de flameo del 50 %.
La TCF se adquiere de la manera siguiente:

961 . 0
NBI
TCFNORMAL
=


De la tabla 8.4 del libro Diseo de Subestaciones de Enriquez Harper

TENSIN NBI
69 kV 350 kV
13.8 kV 110 kV


Para el lado de alta tensin:
Diseo de Subestaciones Elctricas



53
KV
kV
TCFNORMAL
20 . 364
961 . 0
350
= =



Para el lado de baja tensin:
KV
KV
TCFNORMAL
46 . 114
961 . 0
110
= =




Donde
TCF
NORMAL
: TCF en condiciones normales de temperatura presin y humedad.
NBI: Nivel de Aislamiento al Impulso segn el nivel de tensin.
K
h
: Factor de Humedad Atmosfrica, igual a la uno en este caso.

Para el lado de alta tensin
KV
KV
TCFDISEO
74 . 347
06 . 1
015 . 1 * 20 . 364
= =

Para el lado de baja tensin
KV
KV
TCFDISEO
15 . 121
06 . 1
015 . 1 * 46 . 114
= =


5. Distancias mnimas

Son las distancias dielctricas mnimas que deben de haber entre Fase Tierra y Fase Fase. A partir del
uso de la siguiente expresin se pueden definir estas distancias.
d K TCFDISEO -
=

Siendo
K: Gradiente de Tensin; vara entre 500 600 kV/m
d: Distancia de Fase a Tierra (mts)

Utilizando el valor promedio del gradiente de tensin, la Distancia Fase Tierra queda:
550
TCF
d
DISEO
T F
=


Para el lado de alta tensin:
m
m KV
KV
m KV
TCF
d
DISEO
T F
63 . 0
/ 550
74 . 347
/ 550
= = =


o
h NORMAL
DISEO
K TCF
TCF
*
=
Diseo de Subestaciones Elctricas



54
Distancia a usar en el diseo 1.5mts

Para el lado de baja tensin:
m
m KV
KV
m KV
TCF
d
DISEO
T F
220 . 0
/ 550
15 . 121
/ 550
= = =



Distancia a usar en el diseo 1m.
Los Valores encontrados de distancias cumplen con la tabla de distancia mnimas del libro de Sub
estaciones, Enrquez Harper Gilberto en la pgina 355.

Para la distancia dielctrica entre fases se tiene en cuenta que la mxima tensin que puede aparecer entre
fases, es igual al NBI ms el valor de cresta de la onda de tensin a tierra, de frecuencia fundamental,
correspondiente a las condiciones fundamentales de operacin.

Por ello la Distancias Fase Fase es:
d d T F F F
=
8 . 1

Para alta tensin
m
d F F
134 . 1 63 . 0 * 8 . 1 = =



Distancia Final: 2mts = 6.56pies =78.74 Pulg.

Para baja tensin
m
d F F
396 . 0 220 . 0 * 8 . 1 = =


Distancia Final: 1mt = 3.2pies = 39.37 Pulg.


Los Valores encontrados de distancias cumplen con la tabla de distancia mnimas del libro de Sub
estaciones, Enrquez Harper Gilberto en la pgina 355.

6. Cargas horizontales en las barras tubulares

Aqu se considera la Fuerza Horizontal Mxima a la que estn sujetas las barras. Generalmente para efectos
de clculo se considera que es la sumatoria de:
- Fuerza Horizontal debida a Corto Circuito F
CC
(Lbs)
- Fuerza del Viento FV (Lbs)

F F F V CC MX
+ =
Diseo de Subestaciones Elctricas



55
L
D
I
F
CCTO
CC - -

=
10 2 . 43
7
2

Dnde:
I
CCTO
: Corriente de Cortocircuito (A)
D: Distancia entre Centro de las Fases (Pulg)
L: Longitud del Claro (Pies)
Para encontrar esos valores nos vamos a la tabla de transformadores y del Ral Martn se tiene:

MVA
BASE
MVA
CCTO
V
CCTO

100 15,000 10.5

X
S
: Reactancia del Sistema (p.u.)
X
T
: Reactancia del Transformador (p.u.)
V
CCTO
%: Voltaje de Corto Circuito del Transformador.


S
BASE
= 100MVA
Voltaje de prueba de cortocircuito = V
cc
= 10.5%
Primeramente procedemos a calcular la reactancia del sistema XS referida a la SEE

Reactancia del sistema

100
10000
0007
Reactancia de transformador

001

001 10 (
100
3
) 017
Potencia de Cortocircuito:


MVA
MVA
MVA
CCTO
80 . 576
1667 . 0 006667 . 0
100
=
+
=
Corriente de Cortocircuito:


Diseo de Subestaciones Elctricas



56
Para el lado de alta tensin:
A
KV
MVA
ICCTO
156 . 2413
138 *
80 . 576
3
= =

Para el lado de baja tensin:
A
KV
MVA
I CCTO
56 . 24131
8 . 13 *
80 . 576
3
= =


Fuerza de Cortocircuito:
L
D
I
F
CCTO
CC - -

=
10 2 . 43
7
2

Para el lado de alta tensin:

3
131

787
10

380 107

I
CCTO
: Corriente de Cortocircuito (A)=2413.1516A
D: Distancia entre Centro de las Fases = 2mts = 6.56pies =78.74 Pulg.
L: Longitud del Claro = 10mts =32.80 Pies

Para el lado de baja tensin:

3
1311

3937
10

918 8 10



I
CCTO
: Corriente de Cortocircuito (A)=24131.15A
D: Distancia entre Centro de las Fases = 1mt = 3.2pies = 39.37 Pulg.
L: Longitud del Claro =28mts = 91.8Pies

Ahora calcularemos la fuerza del viento ejercida en la barra de alta tensin:
d L P FV - -
=


Si
10 43 . 1
3 2
-

=
V P

Diseo de Subestaciones Elctricas



57
Sabiendo que
V: Velocidad del Viento (Pies/seg)=9 Km/H=2.5 mts/s=8.20 pies/s
Entonces
13 80

10

9 10

Lb / Pies
2

Con el valor de la presin=P debida a la fuerza del viento podemos calcular el valor de la fuerza de viento
ejercida en las barras:
En el lado de alta tensin:
d: Dimetro Nominal del tubo (Pies)=3/4 pulg=62.5*10
-3
Ft
L: Longitud del Claro = 10mts = 32.80 Pies
Lbs
FV
20 . 0 10 * 5 . 62 * 80 . 32 * 10 * 96
3 3
= =


En el lado de baja tensin:

d: Dimetro Nominal del tubo (Pies) =4 pulgadas = 0.33Pies
L: Longitud del Claro = 28mts = 91.8Pies

Lbs
FV
91 . 2 33 . 0 * 8 . 91 * 10 * 96
3
= =


Con las fuerzas del viento y de cortocircuito calculadas ambos lados podemos determinar la fuerza total en
cada barra:
F F F V CC MX
+ =
Para el lado de alta tensin:
Lbs
FMX
92 . 10 20 . 0 72 . 10 = + =
Para el lado de Baja tensin:
Lbs
FMX
3 3
10 * 66 . 867 . 5 9 . 2 10 * 86566 . 5 = + =

7. Resistencia del aislador

Es la resistencia mecnica que tendr el aislador tomando en cuenta la fuerza horizontal mxima aplicada a
la barra. Para que haya mayor seguridad se aplica un factor a la fuerza horizontal mxima, quedando la
resistencia de este modo:
F R MX A 25 . 1
=

Para el lado de alta tensin:
Diseo de Subestaciones Elctricas



58
Lbs R
A
65 . 13 92 . 10 * 25 . 1 = =

Donde
F
max
: Fuerza mxima en lbs de lado de alta 13.65Lbs
Para el lado de baja tensin:
Donde
Lbs R
A
3 3
10 * 07 . 332 . 7 10 * 867 . 5 * 25 . 1 = =


F
max
: Fuerza mxima en lbs de lado de baja tensin 2.515*10
3
Lbs
8. Longitud del claro mximo entre dos apoyos considerando la fuerza horizontal mxima

Esta longitud est dada por:
|
|
.
|

\
|
+
=


d V
D
I
R
L
CCTO
A
2 4
2
7
10 19 . 1 10 2 . 43 25 . 1

Siendo
R
A
: Resistencia del Aislador en Cantilever (Lbs)
d:dimetro Nominal del Tubo (Pulg)
I
cco
: intensidad de cortocircuito
V: Velocidad del viento.
. D: Distancia entre Centro de las Fases (pulg)

Para el lado de alta tensin:
R
A
=13.625Lbs
d=3/4 pulg=62.5*10
-3
Ft
I
cco
: =2413.135A
V=9 Km/H=2.5 mts/s=8.20 Pies/s
D: Distancia entre Centro de las Fases =2mts = 6.56pies =78.74 Pulg.

Pies
L
064 . 34
10 * 5 . 62 * ) 20 . 8 ( * 10 * 19 . 1
74 . 78
) 135 . 2413 (
* 10 * 2 . 43 25 . 1
625 . 13
3 2 4
2
7
=
(

+
|
|
.
|

\
|
=


Longitud en metros: 10.35 mts.
Para el lado de baja tensin:
Diseo de Subestaciones Elctricas



59
R
A
:=7.33207*10
3
Lbs
d:=4
I
cco
: =24131.56A
V=9 Km/H=2.5 mts/s=8.20 Ft/s
D: Distancia entre Centro de las Fases1mt = 3.2pies = 39.37 Pulg.
.
Pies
L
629 . 9141
333 . 0 * ) 20 . 8 ( * 10 * 19 . 1
37 . 39
) 135 . 2413 (
* 10 * 2 . 43 25 . 1
10 * 3320 . 7
2 4
2
7
3
=
(

+
|
|
.
|

\
|
=


Longitud en metros: 24.98mts
9. Seleccin de aisladores para las barras.
Los aisladores son los encargados de asegurar las barras conductoras a la estructura. Adems de esto
proporciona el aislamiento requerido para resguardar el sistema de cualquier evento que concierna a esto. La
adecuada seleccin del tipo de aislador va en dependencia de muchos factores los cuales mencionaremos a
continuacin:
- El tipo de barra que se utilizara.
- Condiciones ambientales a la que este estar sometido.
- Esfuerzos mecnicos que va soportar debido al peso de la barra o conductor que este sosteniendo.
A criterio del diseador escoger el aislador ms conveniente y que cumpla con las exigencias que est
demandando en la construccin de su sistema elctrico cumpliendo con todos los acpites mencionados
anteriormente.
EFECTO CORONA EN LAS BARRAS.
Podemos definir el efecto corona como una descarga provocada por la ionizacin del aire que se produce en
los conductores de las lneas de alta tensin y se presenta en forma de halo luminoso a su alrededor a la vez
provoca un silbido. Este fenmeno provoca perdida de energa a la misma vez corrosin en los conductores
debido al acido producido(cido nitroso). Para reducir este efecto debemos de aumentar la seccin circular
del conductor, Dado que el conductor suele ser de seccin circular el fenmeno o halo adquiere forma de
corona, de aqu se deriva el nombre de este fenmeno.
Para nuestros estudios realizados no consideraremos el efecto corona ya que este se produce en tensiones de
230KV o mayor aeste. Pero en caso alguno el clculo se realiza determinando la tensin critica disruptiva
del fluido que rodea al conductor (V
0
) y se divide entre la tensin a tierra de este, si dicho valor C
s
>= 1 no
existir efecto corona.
Entonces la ecuacin a utilizar es la siguiente:

1

RADIO DE INTERFERENCIA
Diseo de Subestaciones Elctricas



60
Este fenmeno es producido por ondas electromagnticas errantes de alta frecuencia las cuales se propagan
por lo largo de la lnea y los espacios cercanos a ella. Este efecto se obtiene en un recepcin de radios,
cuando la relacin de la intensidad de campo deseada a la intensidad de campo indeseable (RUIDOS
PROVOCADOS, ATMOSFERICOS, SEAL DE RADIO), es menor que el valor detectado por el odo
humano en la frontera de lo satisfactorio y lo contrario.
Par saber si se produce una seal de ruido arriba de un nivel tolerable, se calcula la tensin a tierra del
sistema para un nivel seguro de ruido y comparando este con la tensin real de fase a tierra de la
subestacin, se logra saber si los conductores seleccionados causan o no RADIO DE INTERFERENCIA.
10. Calculo de apartarrayo
El apartarrayo es un dispositivo elctrico que se utiliza para drenar a tierra las sobretensiones que se
presentan en el sistema debido las descargas atmosfricas, operacin de interruptores o desbalanceo del
sistema, con el fin de resguardar los equipos y sigan operando nominalmente.
Los equipos que se encuentran operando bajo tensiones de 230KV son afectadas en su mayora por
sobretensiones de tipo externas y en otras para sistemas que operan con mayores tensiones se ven afectadas
por desrdenes elctricos internos.
Estos elementos se instalan en cada una de las fases, uno de sus extremos a la lnea y el otro directamente a
tierra con el objetivo de drenar las sobre tensiones producidas en el sistema y dejar la tensiones permisibles
para que los equipos de la subestacin elctrica puedan operar nominalmente.
Existen 3 caractersticas principales que cumplen los apartarrayo las cuales son:
Comportarse como un aislador siempre y cuando la tensin aplicada no exceda el valor
predeterminado.
Cumplir con la funcin de conduccin cuando se exceda el valor predeterminado.
Interrumpir la corriente del arco cuando el efecto haya pasado.
Los apartarrayos brindan su mayor proteccin a los elementos de las subestacin siempre que estos se
encuentren dentro del radio de cobertura estipulado por el dispositivo y los puntos donde se deben ubicar,
pero debemos considerar los factores que definen la separacin de los apartarrayos o elementos a proteger,
como lo son:
Magnitud y pendiente del frente de la onda de tensin incidente.
Caracterstica de proteccin del apartarrayo.
Magnitud y forma de la onda de tensin que puede soportar el transformador.
Impedancia caracterstica de las lneas y buses
Para realizar los clculos de los apartarrayo necesitamos de las siguientes ecuaciones:
X. DETERMINAR LA TENSIN NOMINAL Vn (KV)
V K V MX e N -
=
Ke = coeficiente de aterrizamiento, en dependencia del sistema de puesta a tierra.
Diseo de Subestaciones Elctricas



61
Vmax= tensin mxima en la que los equipos puedan operar sin fallas.
Podemos verlos en los siguientes diagramas


Ke
0.8
Slidamente
a Tierra
1
Alta
Impedancia

Ke nos indica que la sub estacin elctrica tiene un neutro conectado slidamente a tierra.
- Lado de alta de la sub estacin 69KV
Vmax del apartarrayo ser de 72.45 KV.
KV
VN
45 . 72 8 . 0
-
=

=
VN
57.96KV (voltaje nominal).

- Lado de baja de la sub estacin 13.8KV
Vmax del apartarrayo ser de 14.4 KV.
KV
VN
4 . 14 8 . 0
-
=

=
VN
11.52KV (voltaje nominal).
XI. ENCONTRAR CON LAS CORRIENTES DE DESCARGAS Id(KA)
Z
NBI
K I r d
0
2
=
Kr= coeficiente determinado de acuerdo donde consideremos que se dar la onda.
Zo= impedancia caracterstica del apartarrayo.
NBI= nivel de aislamiento al impulso segn el nivel de tensin (tomado de la tabla 8.4 del libro de
diseo de sub estaciones de Enrquez Harper.)

Diseo de Subestaciones Elctricas



62




- Lado de alta de la sub estacin 69KV
NBI= 650
Z
0
(ohm)=250/m
Kr= 2
KA
I d
6 . 5
300
250 * 2
1600 = =

= ) (KA
Id
5.6 KA
- Lado de baja de la sub estacin 13.8KV

NBI= 110
Z
0
(ohm)= 200
Kr= 2
4127 . 12698
4 . 50
200 * 2
1600 = =
KV
Id

= ) (KA
Id
12.69KA
Definir el margen de proteccin.
Dimensin de proteccin del apartarrayo para los dispositivos de la subestacin.
% 100 -

=
V
V NBI
M
d
d
P

Vd= tensin mxima de cresta.
- Lado de alta de la sub estacin 138KV.
NBI= 350KV
La tensin de descarga con una onda de impulso de 1,2/50micro seg.

3


30
3
007
Kr Distancia (mts)
3 700
2 1,600
1 3,200

NBI
69KV 350KV
13.8KV 110KV
Diseo de Subestaciones Elctricas



63
% 100
07 . 202
07 . 202 350
-

=
MP

Mp= 73.20%

- Lado de baja de la sub estacin 13.8KV.
NBI= 110KV
La tensin de descarga con una onda de impulso de 1,2/50micro seg.

3


110
3
3
% 100
63
63 110
-

=
MP

Mp= 74.60%
11. Localizar la distancia del apartarrayo

( )
S
V V
d
d MX

=
'
150

Dnde:
NBI V Mx 8 . 0
=
'

V S N
12
100
=
S= pendiente de frente de onda.
Un= tensin nominal segn tabla.
- Lado de alta de la sub estacin 69KV.
Vmax=0.8*NBI
Vmax= 0.8*350
Vmax=280kv

V S N
12
100
=
KV
S
96 . 57
12
100
=
S= 483 KV

Diseo de Subestaciones Elctricas



64
( )
483
07 . 202 280
150

=
KV
d

d= 24.20mts

- Lado de baja de la sub estacin 13.8KV.
Vmax=0.8*NBI
Vmax= 0.8*110
Vmax=88kv

V S N
12
100
=
KV
S
52 . 11
12
100
=
S= 96 KV

( )
96
63 88
150

=
KV
d

d= 39.06mts


Seccin del conductor a tierra del apartarrayo.
Conductor de cobre:
V Seccin N 4 . 0 24
+ =
Conductor de aluminio:
V Seccin N 6 . 0 40
+ =


El material del conductor a utilizar en puesta a tierra de los apartarrayo ser de aluminio.
- Lado de alta de la sub estacin 138KV.
V Seccin N 6 . 0 40
+ =

) 96 . 57 * 6 . 0 ( 40 KV
Seccin
+ =

Seccin= 74.776mm
2
En este caso hemos de utilizar un conductor de aluminio desnudo calibre 133.1mcm o 2/0.

- Lado de baja de la sub estacin 13.8KV.
Diseo de Subestaciones Elctricas



65
V Seccin N 6 . 0 40
+ =
) 52 . 11 * 6 . 0 ( 40 KV
Seccin
+ =
Seccin= 47mm
2
En este caso hemos de utilizar un conductor de aluminio desnudo calibre 3/0.

12. Distancias de diseo

Estos clculos comprenden las distancias que deben existir entre las lneas energizadas y los dems
dispositivos dentro de la sub estacin elctrica y tiene que cumplir con la siguiente secuencia:
- Distancia entre fases.
- Distancia entre fases y tierras.
- Altura de los equipos sobre el nivel del suelo.
- Altura de las barras colectoras sobre el nivel del suelo.
- Altura de remate de las lneas de transmisin que llegan a la sub estacin.
- Distancia de seguridad.
Los primeros 2 puntos fueron calculados con anterioridad por lo siguiente procedemos al clculo del tercer
acpite en adelante.

ALTURA DE LOS EQUIPOS SOBRE EL NIVEL DEL SUELO hs(mts)
Esto comprende clculo de altura de los siguientes elementos: apartarrayo, transformador de tensin,
transformador de corriente, cuchillas, interruptor.
Si en cualquier caso los equipos no se encontraran dentro de una barrera de aislamiento tendrn que ser
colocados a una altura mnima de 3mts de la base de los aisladores que soportan partes vivas y no siendo
inferior a los 2.25mts.
hs se calcula de la siguiente manera:
kV hS 0105 . 0 30 . 2
+ =
Kv= tensin mxima del equipo.
- Lado de alta de la sub estacin 138KV.
kV hS 0105 . 0 30 . 2
+ =

) 138 * 0105 . 0 ( 30 . 2 KV
hS
+ =

=
hS
3.749mts

Diseo de Subestaciones Elctricas



66
- Lado de baja de la sub estacin 13.8KV.
kV hS 0105 . 0 30 . 2
+ =

) 8 . 13 * 0105 . 0 ( 30 . 2 KV
hS
+ =

=
hS
2.44mts

Altura de las barras colectoras sobre el nivel del suelo hb (mts).
Este clculo se realiza con el objetivo de reducir la sensacin del campo magntico hacia el personal de
trabajo que se encuentra dentro de la subestacin elctrica y tambin como medida de seguridad.
Se utiliza la siguiente ecuacin:
kV hb 0125 . 0 5
+ =
- Lado de alta de la sub estacin 69KV.
KV
hb
0125 . 0 5+ =

) 69 * 0125 . 0 ( 5 KV
hb
+ =

=
hb
5.862mts.

- Lado de baja de la sub estacin 13.8KV.
KV
hb
0125 . 0 5+ =

) 8 . 13 * 0125 . 0 ( 5 KV
hb
+ =

=
hb
5.17mts.
Altura de remate de las lneas de trasmisin en la subestacin elctrica hl (mts).
Los conductores elctricos que entran o salen de la sub estacin no deben de presentar una altura de remate
inferior a los 6mts. Para poder determinar esta altura recurrimos a utilizar la siguiente ecuacin.
kV hL 006 . 0 5
+ =
- Lado de alta de la sub estacin 69KV.
KV
hl
006 . 0 5+ =

) 69 * 006 . 0 ( 5 KV
hl
+ =

Diseo de Subestaciones Elctricas



67
=
hl
5.414mts.

- Lado de baja de la sub estacin 13.8KV.
KV
hl
006 . 0 5+ =
) 8 . 13 * 006 . 0 ( 5 KV
hl
+ =

=
hl
5.082mts.

XII. DISTANCIAS DE SEGURIDAD

Esta es la distancia que debe presentar algunas de las partes de la subestacin para que el personal circule
dentro de ella y pueda realizar maniobras en el tiempo que lo amerite, brindando seguridad.
Ecuaciones a utilizar.
9 . 0
+ =
d d T F h

25 . 2
+ =
d d T F V

dh= distancia horizontal.
dv= distancia vertical.

- Lado de alta de la sub estacin 138KV.
Distancia de seguridad horizontal
9 . 0
+ =
d d T F h

9 . 0 94 . 0 + =
dh

mts
dh
84 . 1 =
Distancia de seguridad vertical
25 . 2
+ =
d d T F V

25 . 2 94 . 0 + =
dV


mts
dV
19 . 3 =
Diseo de Subestaciones Elctricas



68
- Lado de baja de la sub estacin 13.8KV.
Distancia de seguridad horizontal
9 . 0
+ =
d d T F h

9 . 0 46 . 0 + =
dh

mts
dh
36 . 1 =
Distancia de seguridad vertical
25 . 2
+ =
d d T F V

25 . 2 46 . 0 + =
dV

mts
dV
71 . 2 =

Zona de circulacin de vehculo:
vehiculo de ancho
d d T F culo zonadevehi
, , ) 7 . 0 ( * 2 + + =


mts
mts
d
d
culo zonadevehi
culo zonadevehi
52 . 5
2 . 2 ) 7 . 0 96 . 0 ( * 2
=
+ + =

mts
mts
d
d
culo zonadevehi
culo zonadevehi
52 . 4
2 . 2 ) 7 . 0 46 . 0 ( * 2
=
+ + =







Diseo de Subestaciones Elctricas



69


XIII. ZONAS DE LA SUB ESTACIN

13. Zona de circulacin del personal

Estas distancias deben estar especificadas de acuerdo a la altura mnima que presente los dispositivos desde
el suelo hasta las partes vivas, considerando la libre circulacin del personal de trabajo.
Al instalar barandales deben presentar una distancia de 1.2mts de altura y quedar a una distancia de la parte
viva igual a la dft ms 0.9mts como mnimo.
Las cercas deben tener una altura de 2.25mts y estar alejadas de las partes vivas a una distancia de igual al
df-t
14. Zona de circulacin de vehculo
La distancia horizontal a las partes vivas ser 0.7 metros ms la d
F-T
, para tener en cuenta las maniobras y la
impresin del conductor. La distancia vertical ser por lo menos igual a la d
F-T
para conexiones rgidas, y
para barras flexibles de d
ft-T
ms 0.5 metros, para absorber los movimientos de los cables.
S hay vehculos con carga pesada se considerar las dimensiones exteriores del vehculo de mayor tamao
que piense utilizar, incluido el transformador ms voluminoso que se instale en la subestacin.
15. Zonas de trabajo
Se debe asegurar la seguridad total de los trabajadores de la sub estacin sin temor alguno a recibir alguna
descarga elctrica. Presentando una distancia de trabajo no menor a los 3metros.








Diseo de Subestaciones Elctricas



70






XIV. CONCLUSIONES



Durante los clculos y estudio realizado pudimos llegar a la conclusin de la importancia de una subestacin
elctrica para suministrar el servicio energtico a todos los consumidores que necesiten de este, a la vez
demostramos las habilidades adquiridas durante el periodo de clases y poner en prctica durante este diseo.
Se realizaron los clculos necesarios parta determinar la potencia demandada por nuestros consumidores
despus de un periodo de 10,20 aos, tomando estos datos pudimos hacer la seleccin correcta de nuestro
transformador.
Ya que no contamos con consumidores de primera categora optamos por la selecciona de un solo
transformador, adems de esto reducir los cost del montaje de toda la subestacin, otro razn por la que
decidimos utilizar un solo transformador son las reduccin de prdidas ya que son menores en cambio que
utilizar dos transformadores nos aumentara las perdidas y costo de construccin.








Diseo de Subestaciones Elctricas



71












XV. ANEXOS
Diseo de Subestaciones Elctricas



72
NOTA:
Todos los clculos realizados en el presente trabajo fueron con objetivos de obtener la informacin necesaria
para realizar el diseo de una subestacin en el Municipio de Diriamba.

TRANSFORMADOR PARA LA SUB ESTACIN









CARACTERISTICAS:
- Transformador de potencia de 2.5 hasta 100MVA.
- Sumergidos en aceite y con sistema de enfriamiento por ventiladores.
- Tensiones de 69KV, 115KV, 138KV, 245KV.
- Verificado bajos normas tcnicas de CIE, ANSI, UNE, EN.
- Tanque de expansin.


Los
Diseo de Subestaciones Elctricas



73
clculos fueron en base a montaje de una subestacin a la intemperie la cual tendr todos los dispositivos
necesarios para su funcionamiento, pero con el avance de la tecnologa y la mejora de los dispositivos elctricos
optamos utilizar por mdulos (encapsulados) elctricos en el rea de baja tensin de nuestra subestacin
elctrica. Estos dispositivos nos brindan la ventaja de reducir el tamao del local a construir y no solo eso sino
todos los seccionadores, TC, TV, que sean de utilizar en el lado de bajo estarn en un solo modulo reduciendo el
riesgo de accidentes y obtener mayor maniobrabilidad del sistema.
A continuacin presentaremos las caractersticas de los mdulos que utilizaremos:
DESCRIPCION DE MODULOS A UTILIZAR
APLICACIONES:
Las instalaciones 8BK20 para mdulos
Extrables con interruptor de potencia para montaje
En locales interiores son apropiadas para:
- Tensiones nominales de 7,2 kV a 24 Kv
- Intensidad nominal de corte en cortocircuito de 31,5 kA a 50 kA
- Intensidad nominal de servicio de las barras colectoras hasta 4000 A
- Intensidad nominal de servicio de las derivaciones hasta 4000 A

UTILIZACION:
Centrales trmicas, estaciones de transformacin y Centros de distribucin de las compaas elctricas.
- Industria del cemento
- Industria del automvil
- Plantas siderrgicas
- Trenes de laminacin
- Minera
- Industrias de fibras y de productos alimenticios
- Industria qumica
- Industrias de aceites minerales
- Instalaciones de oleoductos
- Plataformas offshore
- Electroqumica
- Petroqumica
- Alimentaciones ferroviarias
- Industria naval
- Centrales diesel elctricas
- Plantas de emergencia
-
MANIOBRAS A PUERTA CERRADAS:
Aumento de la proteccin para personas mediante:
- Cierre y apertura del aparato de maniobra
- en posicin de seccionamiento o de servicio
- mecnica o elctricamente
- con la puerta cerrada
Diseo de Subestaciones Elctricas



74
- Obtencin del tramo de seccionamiento por desplazamiento del mdulo extrable, con accionamiento
manual o por motor, con la puerta cerrada.
- Verificacin de la ausencia de tensin. Segn VDE 0105 Parte 1, se ofrecen 3
Posibilidades:
- cierre de un interruptor rpido de puesta a tierra con la puerta cerrada
- verificacin de los polos con indicador de tensin capacitivo con la puerta cerrada.
- Verificacin con comprobador usual de tensin segn VDE0681 Parte 4, pero con la puerta abierta
- Cierre y apertura del interruptor rpido de puesta a tierra con la puerta cerrada
- en la derivacin y en la barra
Colectora: accionamiento manual

Enclavamiento puerta mdulo extrable:

La puerta est integrada como sigue en el concepto de enclavamiento:
- La apertura slo es posible con el mdulo extrable en posicin de seccionamiento enclavada
- El desplazamiento del mdulo extrable desde la posicin de seccionamiento a la posicin de servicio slo es
posible con la puerta cerrada.

Proteccin contra contactos directos y contra la penetracin de cuerpos extraos
- Las instalaciones 8BK20 garantizan tanto proteccin exterior como tambin interior.
- La proteccin exterior est garantizada mediante blindaje completo de las celdas en todos los estados de
servicio
- La proteccin interior est garantizada mediante la compartimentacin metlica interior con obturadores de
accin forzada; blindaje del compartimiento de barras colectores resistente a arcos Internos a eleccin
- las paredes de separacin de celda a celda, a eleccin, resistente a arcos internos Grado de proteccin.
- ejecucin estndar IP4X /IP3XD.
- Los grados de proteccin ms elevadas como, por ejemplo, IP31D, IP50 e IP51 se pueden alcanzar mediante
medidas aditivas.

Blindaje en chapa de acero

Compartimentacin de chapa de acero a prueba de arcos internos
Las instalaciones 8BK20 estn probadas respecto a las repercusiones de un arco interno que pueda surgir, de
acuerdo con las normas en vigor, para Proteccin hacia el exterior como seguridad para el personal de servicio.

A eleccin, resistencia interna contra arcos internos (superando las normas), es decir, las repercusiones de un arco
interno se limitan como sigue:

- no transmisin de la presin hacia las celdas contiguas
- no transmisin de la presin desde el compartimiento del mdulo extrable o de conexin hacia el
compartimiento de las barras colectoras (slo vale para intensidades nominales de hasta 2500 A)
- no transmisin de la presin desde el compartimiento de las barras colectoras hacia el compartimiento del
mdulo extrable o de conexin (slo vale para intensidades nominales de hasta 2500 A)
- Presos tato
- limitacin de la duracin del arco interno a un mximo de 100 ms
- limitacin de los daos y de Las repercusiones de un arco interno a un mnimo
- empleo recomendado con tiempos de escalonamiento > 0,5 s
- es posible la comprobacin del funcionamiento del presos tato sin interrupcin del servicio
- disparo del interruptor de alimentacin cuando acta el presos tato


Diseo de Subestaciones Elctricas



75
Proteccin contra maniobras errneas:

Todos los enclavamientos estn ejecutados como enclavamiento interrogatorio, es decir:
La palanca de maniobra slo se puede encajar, cuando se cumplen las condiciones del enclavamiento
Por ello, no hay esfuerzos excesivos sobre las piezas mecnicas del enclavamiento

Resistencia a la tensin:

La resistencia a la tensin de las celdas 8BK20 se asegura con las siguientes medidas:
Distancias de aire suficientemente grandes entre los conductores y a tierra
Formas favorables de los electrodos Con esto se puede renunciar a cualquier aislamiento de los conductores.

Mxima independencia del medio ambiente

Se consigue una mxima independencia del medio ambiente mediante:
Empleo de aisladores nervados de resina colada con elevada resistencia a capas extraas
Blindaje cerrado en todos los estados de servicio

Mantenimiento:

El reducido gasto en mantenimiento se consigue gracias a:
Blindaje cerrado en todos los estados de servicio
Empleo de acreditados aparatos de maniobra al vaco, exentos de mantenimiento

Disponibilidad

Adquisicin sencilla de piezas para ampliaciones y reparaciones debido al empleo de:
Aisladores normalizados
Transformadores normalizados
Aparatos al vaco de serie
Perfiles de cobre usuales en el comercio
Armario de baja tensin desmontable de hasta 15 kV con sistema de conexin de clavija

CELDA CON MDULO EXTRABLE CON INTERRUPTOR DE POTENCIA AL VACO CELDA CON MDULO EXTRABLE DE
SECCIONADOR


Diseo de Subestaciones Elctricas



76
CONTRUCCIONES BASICAS DE LAS CELDAS

Celda de barras colectoras simple
Montaje en una fila
1 Armario de baja tensin
2 Mdulo extrable con interruptor de potencia al vaco
3 Conexin del cable
4 Transformador de tensin
5 Interruptor rpido de puesta a tierra
6 Transformador de intensidad
7 Barras colectoras
8 Canal para descarga de la presin en el lado posterior

CONTRUCCION MECANICA
Construccin
- Perfiles y chapas de acero atornillados
- Guas para recibir el mdulo extrable
- Cubierta inferior suministrable a eleccin
- Tratamiento superficial
- perfiles y chapas de acero galvanizados
- puertas y marcos frontales con recubrimiento de pintura en polvo,
color gris (RAL 7032) paredes laterales de cierre de las celdas con
recubrimiento de pintura en polvo, color gris(RAL 7032)


Diseo de Subestaciones Elctricas



77






PAREDES DE SEPARACION:

Estas son las encargadas de separar las celdas contiguas.
Construccin
Chapa de acero galvanizada
Con escotadura para barras colectoras pasantes
Placa de paso con pasatapas de resina colada como compartimentacin transversal de las barras colectoras
suministrable a eleccin
Grado de proteccin respecto a las celdas contiguas: IP4X/IP3XD
Opcionalmente en ejecucin resistente a los arcos internos.






PARTES DE ALTA TENSION

Compartimentacin:

- Chapas de acero atornilladas en ejecucin galvanizada subdividen la celda en compartimiento de barras
colectoras
- compartimiento del mdulo extrable
- compartimiento de conexin
- Grado de proteccin entre los diferentes compartimientos: IP4X/IP3XD
- Compartimentacin completa tambin con mdulo extrable en posicin de servicio gracias a pasatapas de
vaso incorporados
- Contra contactos superiores e inferiores sujetos en los pasatapas de vaso
- Obturadores metlicos de maniobra forzosa para la apertura o cierre de los pasatapas de vaso al desplazar el
mdulo extrable
- Obturadores metlicos que se pueden bloquear cuando el mdulo extrable est sacado
- Tabique superior (acceso a las barras colectoras) e inferior (acceso a los cables), desatornillables
independientes entre s
- Opcionalmente, compartimiento de barras colectoras resistente a arcos internos

Diseo de Subestaciones Elctricas



78




BARRAS COLECTORAS:

- pletina de cobre, comercial Sujecin de las barras colectoras
- Sobre aisladores nervados de resina colada, comerciales
- Barras colectoras atornilladas, longitud de las barras colectoras de acuerdo con el ancho de la celda
Compartimentacin
- Tabiques de metal a los compartimientos de mdulo extrable y de conexin con grado de proteccin.
IP4X/IP3XD

- Compartimiento de barras colectoras pasante a lo largo de toda la instalacin; son posibles tabiques
transversales respecto a las celdas contiguas
- Opcionalmente, compartimiento de barras colectoras resistente a arcos internos posible



Aislamiento:

No es necesario aislamiento de las barras colectoras, pues la resistencia a la tensin tambin est garantizada sin
aislamiento
Opcionalmente, el aislamiento de las barras colectoras hasta los contra contactos superiores posible

Dispositivos en barras colectoras:
(A eleccin, se pueden suministrar los siguientes dispositivos en las barras colectoras al lado est representado un
ejemplo de celda con mdulo extrable y con interruptor de potencia al vaco sin afectar a la descarga de presin:
Transformador de tensin 4MR
Aislado con resina colada
Mx. 3 unidades unipolares o
2 unidades bipolares
Interruptor rpido de puesta a tierra
Con accionamiento manual
A eleccin, bloqueable o enclavable electromagnticamente
Conduccin superior de las barras colectoras
Diseo de Subestaciones Elctricas



79
Intensidad nominal de servicio de acuerdo con la intensidad nominal de servicio mxima de las barras colectoras
Barras de conexin sujetas en 3 aisladores
Se puede adaptar el canal necesario para las barras
Conexin superior del cable
Cable VPE unifilar de
2 x 500 mm2 como mximo por fase 1)
Con cajas de conexin de cables y portacables

















Detalles de los elementos dentro del modulo 8BK20, usado en el diseo de la sub estacin.




Diseo de Subestaciones Elctricas



80



PARARRAYOS