You are on page 1of 36

Horizontal Series

FAN COIL TECHNICAL CATALOG

BUILD YOUR REPUTATION ON OURS

Horizontal Series

International Environmental Corporation (IEC) works continually to improve its products. As a result, the design and specifications of each product may be changed without notice and may not be as described herein. Please contact IEC for information regarding current design and product specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties but are merely IECs opinion or commendation of its products. Manufacturers standard limited warranty applies.

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
TAbLE OF CONTENTS
3 Table of Contents 4 Portfolio 6 Features & Benefits 7 Unit Model Key 8 Ratings & Listings 9 Air Delivery 10 Electric Heating 11 Motor Data 13 Physical Data 27 Standard Features & Options 32 Piping Packages (Typical) 33 Mechanical Specifications

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
POrTFOLIO

CHY - Horizontal Hideaway 200 CFM to 1200 CFM


The Horizontal Hideaway (CHY) fan coil unit is designed specifically to meet the many varied requirements for a ceiling hideaway installation. The low-silhouette styling of the CHY makes this unit ideally suited for drop-ceiling and over-closet applications. Standard CHY units are provided with a galvanized finish.

CBY - Horizontal Telescoping Hideaway 200 CFM to 1200 CFM


The Horizontal Telescoping Hideaway (CBY) fan coil unit is mounted fully-recessed for ceiling-recessed applications. The CBYs telescoping frame with hinged panel adapts to any ceiling type and ensures exact alignment of the panel with the ceiling. The hinged-bottom panel provides easy access to all internal components. Standard CBY units are provided with a galvanized finish on the cabinet and powder-coat paint finish on the bottom-access panel.

CPY - Horizontal Hideaway with Plenum 200 CFM to 1200 CFM


The Horizontal Hideaway with Plenum (CPY) fan coil unit provides the same basic features of the CHY plus a return air plenum for above-ceiling mounting in closets, hallways or bathroom areas. The CPY design enables the unit to be adapted to installations requiring return air ducts or to be used as a return-air plenum with a unit-mounted filter and filter-rack assembly. CPY units are shipped from the factory ready for installation with the plenum section in place. No field fabrication is required. CPY units are designed with interchangeable panels so that the unit may be modified on site to accommodate a rear or bottom return. Standard CPY units are provided with a galvanized finish.

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
POrTFOLIO, Contd.

CXB - Horizontal Cabinet 200 CFM to 1200 CFM


The Horizontal Cabinet (CXB) fan coil unit is designed specifically for exposed mounting in hotels, motels, hospitals, nursing homes, offices or other commercial establishments. With the CXB, valuable floor space is not required, and its slim, attractively-styled cabinet blends with all types of decor. Since there is no requirement for duct work or structure modifications, the CXB is ideal for retrofit applications. Standard CXB units are provided with a powder-coat paint finish.

BHY - Horizontal Hi-Static Hideaway 400 CFM to 1000 CFM


The Horizontal Hi-Static Hideaway (BHY) fan coil unit is suited for above-ceiling applications with space limitations. The BHY unit is furnished with larger diameter wheels to achieve higher static pressures required for ductwork applications. Standard BHY units are provided with a galvanized finish.

BPY - Horizontal Hi-Static Hideaway with Plenum 400 CFM to 1000 CFM
The Horizontal Hi-Static Hideaway with Plenum (BPY) fan coil unit is designed for installations requiring a return-air plenum with a unit-mounted filter and filter-rack assembly. The BPY plenum is constructed of galvanized steel and lined with glass-fiber insulation. BPY units are designed with interchangeable panels so that the unit may be modified on site to accommodate a rear or bottom return. Standard BPY units are provided with a galvanized finish.
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
FEATurES & bENEFITS

Application Fit
Multiple cabinet choices are available in 7 nominal CFM sizes for application in a variety of room layouts.
o

Optional airflow configuration (front supply, bottom supply, rear return or bottom return) to meet certain design limitations.

Horizontal Cabinet units (CXB) with aesthetically pleasing cabinetry offer capacities that are ideal for air conditioning in dormitories, small apartments, schools and many other applications. Front supply, bottom or rear return are available.

Outside air connections are available to meet ventilation requirements and reduce field labor (CXB/ CBY/CPY/BPY).

Wide variety of factory assembled valve packages to meet desired controls specifications. Optional condensate overflow switch to address latest building codes where required. Wide variety of optional insulation materials are available to address IAQ concerns.

Horizontal Telescoping Hideaway units with painted access panel (CBY) allows smooth fit up to plaster or sheet rock ceilings. Standard units include bottom louvered return air with the filter located in the access panel.

Horizontal Hideaway models (CHY/BHY) units are installed above the ceiling with or without ducted supply air and open soffit return with an optional ceiling-mounted filter-grille.

Ease of Installation
Factory assembled valve packages minimize piping work at the job site (shipped loose for field mounting). Optional unit mounted controls, service switches and fusing minimize the electrical work required on site. Units are tagged at the factory for clear identification on job site. Opposite end connection units may minimize the piping work on renovation jobs.

Horizontal Hideaway models with plenum (CPY/ BPY) units are installed above the ceiling with or without ducted supply air and ducted return air. The return air filter is either mounted on the unit plenum or installed in an optional ceiling filtergrille.

Design Flexibility
Easy to use ratings program to speed up project design. Standard and high capacity hydronic coils and DX coils are available to match the heating and cooling loads of the space. Optional powder-paint finish colors and grille selections will complement most dcors (exposed units). CXB and CBY units ordered with optional rear return are constructed with a solid bottom panel. Customizable cabinetry makes these units ideal for renovation jobs or where special sizes are required to fit oversized valves and control packages.

Ease of Service
All components are accessible by simply removing the access panel. Filters can be replaced without tools or by opening the bottom panels on exposed units. Blower assembly easily removed from the rear of coil for service and cleaning.

Quality and Safety


Every unit is tested and inspected at the factory for trouble free start-up. ETL and CETL listed. AHRI certified.

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
uNIT MOdEL KEy
Code Items Code 01 C B
UNIT

02 Y
VINTAGE

03 0 4
SIZE

04 A Y Y Y
COILS

04a C B Y Y
ELECTRIC HEAT

05 C 2

06 R 5

07 C P B
CONTROLS

HAND/ MOTOR ARRANGEMENT

CHY CPY CBY CXB BHY BPY

Horizontal Hideaway Horizontal Hideaway with Plenum Horizontal Telescoping Hideaway Horizontal Cabinet Horizontal Hi-Static Hideaway Horizontal Hi-Static Hideaway with Plenum

02 03 04 06 08 10

200 CFM 300 CFM 400 CFM 600 CFM 800 CFM 1000 CFM

Voltage C 115-1-60 D 208-1-60 E 230-1-60 F 277-1-60 V 220-1-50* U 240-1-50*

Type 2 Permanent Split Capacitor

12 1200 CFM

Hand*** R Right L Left

Arrangement 5 6 6
CHY, BHY

Two-pipe Cooling and Heating or Four-pipe Cooling A 3 Row B 4 Row D 2 Row R 3 Row, AAV S 4 Row, AAV

Four-pipe Heating Y None 6 1 Row 7 2 Row

Coil Connection Y None S Same End O Opposite End

Coil Construction Y Std S SS Wrapper

6
CPY, BPY

5 Voltage C D E F V U 120 V 208 V 240 V 277 V 220 V (50)* 240 V (50)* kW** AY BY CY DY FY GY 0.50 1.00 1.50 2.00 3.00 4.00 HY JY KY LY NY YY 5.00 6.00 7.00 8.00 10.00 None Stages Y Single Stage Only 5 6
CXB

6
CBY

Y None

Voltage B C D E F V U * ** 24 V 120 V 208 V 240 V 277 V 220 V (50)* 240 V (50)*

System Manual Fan Operation A Standard Wall Mount (Switch Only) Valve Cycle Control G H J K L M N P Q R 2-Pipe Heat Only 2-Pipe Cool Only 2-Pipe Heat and Cool, MCO 2-Pipe Heat and Cool, ACO 2-Pipe Heat and Cool w/ Aux. Elec. Heat, MCO 2-Pipe Heat and Cool w/ Aux. Elec. Heat, ACO 2-Pipe Cool w/ Total Elec. Heat, MCO 2-Pipe Cool w/ Total Elec. Heat, ACO 4-Pipe Heat and Cool, MCO 4-Pipe Heat and Cool, ACO Thermostat 4 A B P N Basic Wall Series Horizontal Wall Series Vertical Wall Series 24 V Programmable Wall Series 24 V Non-Programmable Wall Series

Consult factory for 50Hz applications. Note that kWs depend on voltage and unit size.

*** Standing in front of the unit, hand is determined by looking into the air supply and assigning the hand to match the location of the cooling coil connections.

NOTE: MCO controls (J, L, N, Q) not available with Standard Unit Mount Thermostat

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
rATINGS & LISTINGS

AHRI Certification
IECs Horizontal Series units are certified in compliance with Air-Conditioning, Heating, and Refrigeration Institute (AHRI) industry standard AHRI-440 for room fan coil units. Approved standard ratings are tabulated below.

C-ETL US Listing
IECs Horizontal Series units are listed by ETL. The C-ETL-US listing signifies that IECs fan coil units have been examined by ETL and are in compliance with both the U.S. and Canadian applicable standards.

3061627
HEATING AND COOLING EQUIPMENT

Standard Ratings
Unit Type Unit Cell Nominal Size CFM 02-A 03-A CHY CPY CXB CBY 04-A 06-A 08-A 10-A 12-A 02-B 03-B CHY CPY CXB CBY 04-B 06-B 08-B 10-B 12-B 04-B BHY 06-B 08-B 10-B 200 300 400 600 800 1000 1200 200 300 400 600 800 1000 1200 400 600 800 1000 Cooling Capacity Total MBH 6.0 9.0 12.1 17.3 22.6 27.5 32.8 6.9 9.8 13.8 19.6 25.5 31.0 37.2 16.0 21.8 26.5 37.2 Sensible MBH 4.4 6.3 8.8 13.0 16.2 21.0 25.0 4.3 6.5 9.8 14.3 18.8 22.0 27.7 11.6 16.0 19.6 27.6 Power Input Watts PSC 87 85 165 225 235 305 435 87 85 145 220 235 300 425 170 205 225 355

NoTeS: 1. Ratings are based on 80F DB and 67F WB EAT, 45F

EWT, 10F water temperature rise, high fan speed, motor voltage 115/1/60, and air flow under dry coil conditions. 2. For all application ratings, use IECs computer selection program, the quick-selection ratings provided in this catalog, or contact your local IEC representative. 3. For additional information, please consult AHRIs website at www.ahrinet.org.

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
AIr dELIvEry

Air Delivery (60 Hz)


Model Coil Unit Size 02 03 04 06 08 10 12 02 03 04 06 08 10 12 02 03 04 06 08 10 12 02 03 04 06 08 10 12 04 06 08 10 04 06 08 10 04 06 08 10 04 06 08 10 CFM@ 0.0 eSP For Fan Speed Low 175 250 220 330 335 490 705 165 240 215 295 330 480 690 150 215 205 280 335 485 540 145 205 200 220 325 475 530 515 545 630 1210 505 525 615 1180 485 540 545 1060 420 525 535 1035 Med 195 295 360 540 590 665 950 190 285 305 530 585 655 930 175 270 275 450 565 630 900 170 260 270 440 550 615 880 600 705 715 1350 585 680 705 1315 535 640 660 1195 525 625 645 1165 High 220 330 510 760 870 1100 1425 215 320 500 745 860 1085 1400 190 300 470 690 835 1045 1300 185 290 460 675 815 1020 1275 665 830 930 1445 650 800 905 1410 570 720 800 1295 555 700 780 1260 0.05 205 300 480 720 840 1060 1370 200 290 470 700 825 1040 1345 180 275 445 655 800 995 1240 180 270 435 635 780 970 1215 630 780 870 1360 620 750 840 1320 540 680 750 1216 520 660 725 1175 0.10 185 265 450 670 800 1010 1310 175 250 440 650 780 970 1280 170 250 415 615 760 940 1180 160 240 400 595 740 915 1150 595 725 810 1275 575 700 780 1230 505 635 695 1130 485 610 670 1090 High Speed CFM @ eSP Indicated 0.15 160 225 415 620 760 930 1240 140 205 400 590 730 895 1205 145 215 380 560 710 880 1110 125 195 355 535 658 850 1075 550 670 750 1185 530 640 720 1140 465 585 640 1045 445 560 615 1005 0.20 170 370 560 700 845 1160 150 340 525 665 800 1115 165 320 500 650 805 1025 300 465 615 765 980 500 610 685 1095 465 585 655 1050 420 530 580 960 390 500 555 915 0.25 290 475 620 730 1055 240 430 575 670 990 250 410 570 710 920 210 355 515 645 850 430 550 615 1000 395 520 580 945 360 460 515 865 330 430 485 810 0.30 840 815 350 480 540 880 300 440 495 810 285 385 440 700 340 395 700

3 Row

CHY

4 Row

3 Row CBY CPY CXB 4 Row

3 Row BHY 4 Row

3 Row BPY 4 Row

NoTeS: 1. Tabled values are standard CFM at sea level, 70F with dry coil.

2. Ratings include factory-installed filter and/or grille, where applicable. 3. Consult factory for 50 Hz applications.

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
ELECTrIC HEATING

Electric Resistance Heating


Electric heaters are available on IEC Horizontal Series fan coil units for the following applications.

Electric Heater Selection


Voltage kW 0.5 1.0 120 V 1.5 2.0 3.0 0.5 1.0 1.5 2.0 208 V 3.0 4.0 5.0 6.0 8.0 0.5 1.0 1.5 2.0 3.0 240 V 277 V 4.0 5.0 6.0 8.0 10.0 02

Total Electric Heat


Total electric heat eliminates the requirement for a boiler. Heating and/or cooling may be available on an individual basis throughout the year. Two-pipe chilled water is used for cooling; and the electric heater is used for heating. Individual room controls can be supplied for either manual or automatic changeover.

03

04 -

Unit Size 06 08 -

10 -

12 -

Auxiliary Electric Heat


Auxiliary electric heat is ideal for tempering room air between seasons and during the cooling season when chilled water is being circulated. Individual room controls are supplied to provide electric heat only when chilled water is being circulated. During regular heating season, heating is provided by hot water being circulated in the system.

Note 6 Note 6
-

Note 6
-

Note 6
-

Note 6
-

Construction
The heater coils of high-grade resistance wire are supported by ceramic insulators on plated steel brackets. These heat elements are suspended directly in front of the fan outlet between the blower and the coil. High limit thermal cutouts protect the heater in the event of air failure. There are many special applications and control sequences for electric heat. For special applications, please consult the factory.

Note 6 Note 6
-

Note 6
-

Note 6
-

Note 6 Note 6

NoTeS: 1. All heaters are single stage and single phase.

2. Heaters over 48 Amps are subdivided and fused. 3. Electric Heating Capacities (BTUH) = Heater kW x 3413. 4. Electric Heater Amperage = (Heater kW x 1000)/Applied Voltage) 5. Consult factory for 50 Hz applications. 6. High and medium speed only.

10

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
MOTOr dATA

Thermal Overload Protection and ETL Listing


All permanently lubricated split-capacitor motors furnished by IEC contain internal thermaloverload protection. The overload automatically resets when the temperature returns to a safe limit. Electronics Testing Laboratories, Inc. approves the motor and thermal overload combination at locked rotor conditions only.

Motor Performance Data - CHY, CPY, CXB, CBY


Unit Size Voltage Fan Speed Nominal HP Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts 02 1/30 0.53 87 0.31 55 0.27 35 0.48 86 0.29 60 0.15 28 0.48 103 0.31 70 0.15 33 0.35 80 0.26 64 0.16 40 03 1/30 0.83 85 0.50 55 0.34 35 0.48 89 0.29 60 0.15 28 0.48 106 0.32 73 0.15 33 0.35 80 0.26 66 0.16 43 04 1/12 1.40 165 0.70 80 0.45 50 0.69 115 0.43 89 0.22 45 0.69 135 0.45 105 0.24 53 0.69 150 0.43 110 0.25 60 06 1/12 1.40 165 0.72 80 0.45 50 0.69 130 0.47 100 0.24 48 0.69 155 0.52 115 0.28 60 0.69 155 0.43 110 0.35 90 08 1/6 2.50 235 1.50 160 1.20 120 1.30 195 0.69 135 0.47 90 1.30 210 0.70 150 0.50 105 0.91 240 0.62 160 0.35 90 10 (2) 1/12 2.80 305 1.40 150 0.90 100 1.38 260 0.94 190 0.46 90 1.38 290 1.00 220 0.50 110 1.38 270 0.80 200 0.25 75 12 (2) 1/6 5.00 435 2.80 305 1.20 130 2.60 340 1.33 255 0.94 180 2.60 380 1.34 285 1.00 210 1.82 440 1.20 300 0.66 175

High 115 V 60 Hz 1 Phase Low High 208 V 60 Hz 1 Phase Low High 230 V 60 Hz 1 Phase Low High 277 V 60 Hz 1 Phase Low Medium Medium Medium Medium

NoTeS: 1. Total unit motor Amps and Watts are shown.

2. Consult factory for 50 Hz applications.

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

11

Horizontal Series
MOTOr dATA, Contd.

Motor Performance Data - BHY, BPY


Voltage Fan Speed High 115 V 60 Hz 1 Phase Medium Low High 208 V 60 Hz 1 Phase Medium Low High 230 V 60 Hz 1 Phase Medium Low High 277 V 60 Hz 1 Phase Medium Low Unit Size Nominal HP Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts 04 1/8 1.70 170 1.65 160 1.45 135 0.76 135 0.60 120 0.54 105 0.76 150 0.58 128 0.55 115 0.64 145 0.45 125 0.36 90 06 1/8 1.70 205 1.65 175 1.45 140 0.76 150 0.66 130 0.57 110 0.76 160 0.66 145 0.60 127 0.64 155 0.48 130 0.36 90 08 1/8 1.70 225 1.70 195 1.45 165 0.76 160 0.67 135 0.57 110 0.76 170 0.67 135 0.57 127 0.64 170 0.54 145 0.39 100 10 (2) 1/8 3.40 355 3.37 345 2.95 290 1.52 280 1.25 250 1.05 205 1.52 300 1.30 260 1.05 205 1.28 310 0.95 265 0.74 195

NoTeS: 1. Total unit motor Amps and Watts are shown.

2. Consult factory for 50 Hz applications.

12

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
PHySICAL dATA

CHY - Horizontal Hideaway


4 (102) 4 (102) FLEXIBLE METAL CONDUIT 1 (25)

7/8"(22) O.D. CONDENSATE DRAIN OPTIONAL 5/8"(16) O.D. TELL-TALE DRAIN CONNECTION, AVAILABLE ON STANDARD AND EXTENDED DRAIN PANS

JUNCTION BOX (REMOTE MOUNT)

6 (152) 1-1/2 (38)

1-1/8 (29) 2-1/4 (64) B A 3 (76) A'

D'

OPTIONAL EXTENDED DRAIN PAN (SEE NOTE 2)

TOP VIEW
RESILIENT MOUNTING GROMMET W/ 3/8"(10) DIA. HOLES (TYP. OF 4) H 3/4 (19) E MTG. HOLES 3/4 (19) CHILLED/HOT WATER SUPPLY & RETURN CONNECTIONS 1"(25) SUPPLY DUCT COLLAR 7/8 (22) 17-1/2 (445) 1 (25) 8-3/8 (213) AIR VENT

G OPTIONAL DRIP LIP SHIPPED LOOSE (NOTE 5)

SUPPLY AIR

FRONT VIEW
Unit Model
CHY02 CHY03 CHY04 CHY06 CHY08 CHY10 CHY12

16 (406)

RIGHT SIDE VIEW


Quantity/Unit F
6-1/4 (159) 6-1/4 (159) 6-1/4 (159) 7-1/2 (191) 7-1/2 (191) 7-1/2 (191) 7-1/2 (191)

Dimensions - Inches (Millimeters) A


21-1/4 (540) 25-1/4 (641) 31-1/4 (794) 36-1/4 (921) 43-1/4 (1099) 57-1/4 (1454) 65-1/4 (1657)

A
31-1/4 (794) 36-1/4 (921) 43-1/4 (1099) 43-1/4 (1099) 57-1/4 (1454) 65-1/4 (1657) 75-1/4 (1911)

B
16 (406) 20 (508) 26 (660) 31 (787) 38 (965) 52 (1321) 60 (1524)

D
13 (330) 14 (356) 15 (381) 10 (254) 17 (432) 11 (279) 13 (330)

e
18-1/4 (464) 22-1/4 (565) 28-1/4 (718) 33-1/4 (845) 40-1/4 (1022) 54-1/4 (1378) 62-1/4 (1581)

Blower
1 1 2 2 2 4 4

Motor
1 1 1 1 1 2 2

Unit Weight*
36 39 49 59 64 95 107

8-3/4 (222) 19-3/4 (502) 8-3/4 (222) 23-3/4 (603) 8-3/4 (222) 29-3/4 (756) 10 (254) 34-3/4 (883) 10 (254) 41-3/4 (1060) 10 (254) 55-3/4 (1416) 10 (254) 63-3/4 (1619)

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components.

1. 2. 3. 4. 5. 6.

RH shown, LH opposite. Optional drip lip not required with optional extended drain pan. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drip lip recommended. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

13

Horizontal Series
PHySICAL dATA, Contd.

CHY - Horizontal Hideaway with Electric Heat


CONTROL BOX (REMOTE MOUNT) 5-3/8 (137) STD. 6 (152) STD. FLEXIBLE METAL CONDUIT STRIP HEATER HIGH LIMIT ELECTRIC STRIP HEATER ELEMENT 1 (25) OPTIONAL 5/8"(16) O.D. TELL-TALE DRAIN CONNECTION, AVAILABLE ON STANDARD AND EXTENDED DRAIN PANS

6 (152) 1-1/2 (38) 1-1/8 (29) 2-1/4 (64)

7/8"(22) O.D. CONDENSATE DRAIN OPTIONAL EXTENDED DRAIN PAN (SEE NOTE 2)

E MTG. HOLES B A 3 (76)

D' A'

TOP VIEW
RESILIENT MOUNTING GROMMET W/ 3/8"(10) DIA. HOLES (TYP. OF 4) H 3/4 (19) 3/4 (19) CHILLED/HOT WATER SUPPLY & RETURN CONNECTIONS 21-1/2 (546) 1" SUPPLY DUCT COLLAR 7/8 (22) 1 (25) 12-3/8 (314) AIR VENT

SUPPLY AIR

FRONT VIEW
Unit Model
CHY02 CHY03 CHY04 CHY06 CHY08 CHY10 CHY12

16 (406)

OPTIONAL DRIP LIP SHIPPED LOOSE (NOTE 5)

RIGHT SIDE VIEW


Quantity/Unit Unit Weight*
38 41 51 61 66 97 109

Dimensions - Inches (Millimeters) A


21-1/4 (540) 25-1/4 (641) 31-1/4 (794) 36-1/4 (921) 43-1/4 (1099) 57-1/4 (1454) 65-1/4 (1657)

A
31-1/4 (794) 36-1/4 (921) 43-1/4 (1099) 43-1/4 (1099) 57-1/4 (1454) 65-1/4 (1657) 75-1/4 (1911)

B
16 (406) 20 (508) 26 (660) 31 (787) 38 (965) 52 (1321) 60 (1524)

D
13 (330) 14 (356) 15 (381) 10 (254) 17 (432) 11 (279) 13 (330)

e
18-1/4 (464) 22-1/4 (565) 28-1/4 (718) 33-1/4 (845) 40-1/4 (1022) 54-1/4 (1378) 62-1/4 (1581)

F
6-1/4 (159) 6-1/4 (159) 6-1/4 (159) 7-1/2 (191) 7-1/2 (191) 7-1/2 (191) 7-1/2 (191)

Blower
1 1 2 2 2 4 4

Motor
1 1 1 1 1 2 2

8-3/4 (222) 19-3/4 (502) 8-3/4 (222) 23-3/4 (603) 8-3/4 (222) 29-3/4 (756) 10 (254) 34-3/4 (883) 10 (254) 41-3/4 (1060) 10 (254) 55-3/4 (1416) 10 (254) 63-3/4 (1619)

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components.

1. 2. 3. 4. 5. 6.

RH shown, LH opposite. Optional drip lip not required with optional extended drain pan. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drip lip recommended. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.

14

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
PHySICAL dATA, Contd.

CPY - Horizontal Hideaway with Plenum


JUNCTION BOX 3 (76) 3-1/4 (83) 4 (102) 15-1/4 (387) 7/8" (22) O.D. CONDENSATE DRAIN 1-1/2 (38) A' 1-1/8 (29) 2-1/4 (57) C MTG. HOLES B BOTTOM ACCESS PANEL INSULATED PLENUM H REAR MTG. HOLES 1-1/2 (38) OPTIONAL 5/8" (16) O.D. TELL-TALE DRAIN CONNECTION, AVAILABLE ON STANDARD AND EXTENDED DRAIN PANS

1 (25)

OPTIONAL EXTENDED DRAIN PAN (SEE NOTE 2) D'

1" (25) FILTER RETURN AIR 1" (25) RETURN DUCT COLLAR FILTER RETAINER CLIP FILTER REMOVAL

3 (76)

TOP VIEW

OPTIONAL REAR RETURN

3/4 (19)

E RESILIENT MOUNTING GROMMET W/ 3/8" (10) DIA. HOLES (TYP. OF 4)

3/4 (19)

CHILLED/HOT WATER SUPPLY & RETURN CONNECTIONS

1" (25) SUPPLY DUCT COLLAR 7/8 (22)

1 (25)

20 (508) 19 (483) 11-3/8 (289) AIR VENT

10-1/2 (267)

SUPPLY F AIR REAR ACCESS PANEL

16 (406)

OPTIONAL DRIP LIP SHIPPED LOOSE (NOTE 5)

1"(25) FILTER RETURN AIR FILTER REMOVAL

FRONT VIEW
Unit Model
CPY02 CPY03 CPY04 CPY06 CPY08 CPY10 CPY12

RIGHT SIDE VIEW


Unit Blower Motor Weight*
1 1 2 2 2 4 4 1 1 1 1 1 2 2 55 60 70 82 95 135 154

Dimensions - Inches (Millimeters) A


21-1/4 (540) 25-1/4 (641) 31-1/4 (794) 36-1/4 (921) 43-1/4 (1099) 57-1/4 (1454) 65-1/4 (1657)

Quantity/Unit

A
31-1/4 (794) 36-1/4 (921) 43-1/4 (1099) 43-1/4 (1099) 57-1/4 (1454) 65-1/4 (1657) 75-1/4 (1911)

B
16 (406) 20 (508) 26 (660) 31 (787) 38 (965) 52 (1321) 60 (1524)

C
18-1/4 (464) 22-1/4 (565) 28-1/4 (718) 33-1/4 (845) 40-1/4 (1022) 54-1/4 (1378) 62-1/4 (1581)

D
13 (330) 14 (356) 15 (381) 10 (254) 17 (432) 11 (279) 13 (330)

e
19-3/4 (502) 23-3/4 (603) 29-3/4 (756) 34-3/4 (883) 41-3/4 (1060) 55-3/4 (1416) 63-3/4 (1619)

6-1/4 (159) 8-3/4 (222) 15-3/8 (391) 6-1/4 (159) 8-3/4 (222) 19-3/8 (883) 6-1/4 (159) 8-3/4 (222) 25-3/8 (645) 7-1/2 (190) 10 (254) 30-3/8 (772) 7-1/2 (190) 10 (254) 37-3/8 (949) 7-1/2 (190) 10 (254) 51-3/8 (1305) 7-1/2 (190) 10 (254) 59-3/8 (1508)

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components.

1. 2. 3. 4. 5. 6. 7.

RH shown, LH opposite. Optional drip lip not required with optional extended drain pan. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drip lip recommended. Threaded fittings must be field tightened and leak tested. Control box size and position may vary (consult factory).

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

15

Horizontal Series
PHySICAL dATA, Contd.

CPY - Horizontal Hideaway with Plenum with Electric Heat


CONTROL BOX 3-1/4 (83) 5-3/8 (137) STD. INSULATED PLENUM H REAR MTG. HOLES 1-1/2 (38) OPTIONAL 5/8" (16) O.D. TELL-TALE DRAIN CONNECTION, AVAILABLE ON STANDARD AND EXTENDED DRAIN PANS

6 (152) STD. 19-1/4 (489)

ELECTRIC STRIP HEATER ELEMENT 1 (25)

OPTIONAL EXTENDED DRAIN PAN (SEE NOTE 2)

1" (25) FILTER RETURN AIR 1" (25) RETURN DUCT COLLAR FILTER RETAINER CLIP FILTER REMOVAL

7/8" (22) O.D. CONDENSATION DRAIN STRIP HEATER HIGH LIMIT 1-1/2 (38) 1-1/8 (29) 2-1/4 (57) C FRONT MTG. HOLES B A A'

D' BOTTOM ACCESS PANEL

3 (76)

TOP VIEW
1" (25) SUPPLY 7/8 DUCT (22) COLLAR SUPPLY F AIR

OPTIONAL REAR RETURN


24 (610) 23 (584)

3/4 (19)

3/4 (19) RESILIENT MOUNTING GROMMET W/ 3/8" (10) DIA. HOLES (TYP. OF 4)

3/4 (19)

CHILLED/HOT WATER SUPPLY & RETURN CONNECTIONS OPTIONAL DRIP LIP SHIPPED LOOSE (NOTE 5)

11-3/8 (289) AIR VENT

10-1/2 (267)

REAR ACCESS 1" (25) FILTER RETURN FILTER REMOVAL AIR

ELECTRICAL KNOCKOUTS IN TOP & BOTTOM OF CONTACTOR BOX

16 (406)

FRONT VIEW
Unit Model
CPY02 CPY03 CPY04 CPY06 CPY08 CPY10 CPY12

RIGHT SIDE VIEW


Unit Blower Motor Weight*
1 1 2 2 2 4 4 1 1 1 1 1 2 2 57 62 72 84 97 137 156

Dimensions - Inches (Millimeters) A


21-1/4 (540) 25-1/4 (641) 31-1/4 (794) 36-1/4 (921) 43-1/4 (1099) 57-1/4 (1454) 65-1/4 (1657)

Quantity/Unit

A
31-1/4 (794) 36-1/4 (921) 43-1/4 (1099) 43-1/4 (1099) 57-1/4 (1454) 65-1/4 (1657) 75-1/4 (1911)

B
16 (406) 20 (508) 26 (660) 31 (787) 38 (965) 52 (1321) 60 (1524)

C
18-1/4 (464) 22-1/4 (565) 28-1/4 (718) 33-1/4 (845) 40-1/4 (1022) 54-1/4 (1378) 62-1/4 (1581)

D
13 (330) 14 (356) 15 (381) 13 (330) 17 (432) 11 (279) 13 (330)

e
19-3/4 (502) 23-3/4 (603) 29-3/4 (756) 34-3/4 (883) 41-3/4 (1060) 55-3/4 (1416) 63-3/4 (1619)

6-1/4 (159) 8-3/4 (222) 15-3/8 (391) 6-1/4 (159) 8-3/4 (222) 19-3/8 (883) 6-1/4 (159) 8-3/4 (222) 25-3/8 (645) 7-1/2 (190) 10 (254) 30-3/8 (772) 7-1/2 (190) 10 (254) 37-3/8 (949) 7-1/2 (190) 10 (254) 51-3/8 (1305) 7-1/2 (190) 10 (254) 59-3/8 (1508)

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components.

1. 2. 3. 4. 5. 6. 7.

RH shown, LH opposite. Optional drip lip not required with optional extended drain pan. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drip lip recommended. Threaded fittings must be field tightened and leak tested. Control box size and position may vary (consult factory).

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.

16

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
PHySICAL dATA, Contd.

CBY - Horizontal Telescoping Hideaway


1 1-1/2 (25) (38) JUNCTION BOX

OPTIONAL "L" SHAPE DRIP LIP, SHIPPED LOOSE (NOTE 5) CHILLED/HOT WATER SUPPLY & RETURN CONNECTION RESILIENT MOUNTING GROMMETS WITH 3/8"(10) DIA. HOLE (TYP. OF 4) 7/8"(22) KNOCKOUT 1 (25) 1-1/2 (38) 1 (25) 6-1/8 (156)

26 (660)

20-3/4 (527)

1-1/2(38) KNOCKOUT (TYPICAL)

1 (25)

PARTIAL REAR VIEW


(TYPICAL BOTH SIDES)

TOP VIEW

6-1/8 (156) 1-1/2 (38) 12(305) 11-1/4 MIN. (286) 14(356) MAX. B

1-1/2 (38) A C 1-1/2 (38) 1-1/4 (32) 24 (610) 20-3/4 (527)

1-1/2 (38) OPTIONAL DUCTED REAR RETURN

SUPPLY AIR

1"(25) SUPPLY DUCT COLLAR HINGED BOTTOM RETURN AIR PANEL 7/8"(22) O.D. CONDENSATE DRAIN CONNECTION

RETURN AIR

STAMPED RETURN AIR GRILLE & 1"(25) FILTER

FRONT VIEW
Unit Model
CBY02 CBY03 CBY04 CBY06 CBY08 CBY10 CBY12

RIGHT SIDE VIEW


Quantity/Unit Blower Motor
1 1 2 2 2 4 4 1 1 1 1 1 2 2

A
35 (889) 35 (889) 41 (1041) 53 (1346) 53 (1346) 75 (1905) 75 (1905)

Dimensions - Inches (Millimeters) C D


12-3/4 (324) 8-3/4 (222) 8-3/4 (222) 15-3/4 (400) 8-3/4 (222) 16-3/4 (425) 8-3/4 (222) 37 (940) 37 (940) 43 (1092) 55 (1397) 55 (1397) 77 (1956) 77 (1956)

F
6 (152) 6 (152) 6 (152) 7 (178) 7 (178) 7 (178) 7 (178)

Unit Weight*
115 120 135 150 155 227 241

16 (406) 20 (508) 26 (660) 31 (787) 38 (965) 52 (1321) 60 (1524)

32 (813) 32 (813) 38 (965) 50 (1270) 50 (1270) 72 (1829) 72 (1829)

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components.

1. 2. 3. 4. 5. 6.

RH shown, LH opposite. Internal factory valve packages and drains may not align w/cabinet knockouts. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drip lip required for units with valves. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

17

Horizontal Series
PHySICAL dATA, Contd.

CBY - Horizontal Telescoping Hideaway with Electric Heat


1 (25) 1-1/2 (38) CONTROL BOX STRIP HEATER HIGH LIMIT ELECTRIC STRIP HEATER ELEMENT

OPTIONAL "L" SHAPE DRIP LIP, SHIPPED LOOSE (NOTE 5) 26 (660) 20-3/4 (527) CHILLED/HOT WATER SUPPLY & RETURN CONNECTION RESILIENT MOUNTING GROMMETS WITH 3/8"(19) DIA. HOLE (TYP. OF 4)

1 1-1/2 (25) (38) 1 (25)

7/8"(22) KNOCKOUT E 6-1/8 (156) 1 (25) 1-1/2(38) KNOCKOUT (TYPICAL)

TOP VIEW

PARTIAL REAR VIEW


(TYPICAL BOTH SIDES)

1-1/2 (38) 11-1/4 12(305) (286) MIN. 14(356) MAX.

6-1/8 (156)

A B C 1-1/2 (38)

1-1/4 (32)

1-1/2 (38)

24 (610) 20-3/4 (527)

1-1/2 (38) OPTIONAL DUCTED REAR RETURN

SUPPLY AIR

1"(25) SUPPLY DUCT COLLAR HINGED BOTTOM RETURN AIR PANEL 7/8"(22) O.D. CONDENSATE DRAIN CONNECTION

RETURN AIR

STAMPED RETURN AIR GRILLE & 1"(25) FILTER

FRONT VIEW
Unit Model
CBY02 CBY03 CBY04 CBY06 CBY08 CBY10 CBY12

RIGHT SIDE VIEW


Quantity/Unit Blower Motor
1 1 2 2 2 4 4 1 1 1 1 1 2 2

A
35 (889) 35 (889) 41 (1041) 53 (1346) 53 (1346) 75 (1905) 75 (1905)

Dimensions - Inches (Millimeters) C D


12-3/4 (324) 8-3/4 (222) 8-3/4 (222) 15-3/4 (400) 8-3/4 (222) 16-3/4 (425) 8-3/4 (222) 37 (940) 37 (940) 43 (1092) 55 (1397) 55 (1397) 77 (1956) 77 (1956)

F
6 (152) 6 (152) 6 (152) 7 (178) 7 (178) 7 (178) 7 (178)

Unit Weight*
117 122 137 152 157 229 243

16 (406) 20 (508) 26 (660) 31 (787) 38 (965) 52 (1321) 60 (1524)

32 (813) 32 (813) 38 (965) 50 (1270) 50 (1270) 72 (1829) 72 (1829)

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components.

1. 2. 3. 4. 5. 6.

RH shown, LH opposite. Optional drip lip not required with optional extended drain pan. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drip lip required for units with valves. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.

18

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
PHySICAL dATA, Contd.

CBY - Horizontal Telescoping Hideaway with Bottom Supply


1 (25) 1-1/2(38) JUNCTION BOX OPTIONAL "L" SHAPE DRIP LIP, SHIPPED LOOSE (NOTE 5) CHILLED/HOT WATER SUPPLY & RETURN CONNECTION 30-3/4 (781) RESILIENT MOUNTING GROMMETS WITH 3/8"(10) DIA. HOLE (TYP. OF 4) 1 (25) 1-1/2(38) E 1-1/2 (38) 1 (25)

36 (914)

7/8"(22) KNOCKOUT 1-1/2(38) KNOCKOUT (TYPICAL)

1-1/2 (38) 1 (25)

TOP VIEW

PARTIAL REAR VIEW


(TYPICAL BOTH SIDES) 1-1/2(38)

A 1-1/2 (38) 11-1/4 12"(305) (286) MIN. 14"(356) MAX. HINGED BOTTOM RETURN AIR PANEL 6" (152) E 1-1/2 (38)

34(864) 30-3/4 (781)

1-1/2(38) OPTIONAL DUCTED REAR RETURN 7/8"(22) O.D. CONDENSATE DRAIN CONNECTION

FRONT VIEW

SUPPLY AIR

STAMPED SUPPLY AIR GRILLE RETURN AIR

STAMPED RETURN AIR GRILLE & 1"(25) FILTER

RIGHT SIDE VIEW


Unit Model
CBY02 CBY03 CBY04 CBY06 CBY08 CBY10 CBY12

A
35 (889) 35 (889) 41 (1041) 53 (1346) 53 (1346) 75 (1905) 75 (1905)

Dimensions - Inches (Millimeters) D e


37 (940) 37 (940) 43 (1092) 55 (1397) 55 (1397) 77 (1956) 77 (1956) 32 (813) 32 (813) 38 (965) 50 (1270) 50 (1270) 72 (1829) 72 (1829)

F
6 (152) 6 (152) 6 (152) 7 (178) 7 (178) 7 (178) 7 (178)

Quantity/Unit Blower Motor


1 1 2 2 2 4 4 1 1 1 1 1 2 2

Unit Weight*
115 120 135 150 155 227 241

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components.

1. 2. 3. 4. 5. 6.

RH shown, LH opposite. Internal factory valve packages and drains may not align w/cabinet knockouts. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drip lip required for units with valves. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

19

Horizontal Series
PHySICAL dATA, Contd.

CBY - Horizontal Telescoping Hideaway with Bottom Supply with Electric Heat
1(25) 1-1/2(38) CONTROL BOX STRIP HEATER HIGH LIMIT ELECTRIC STRIP HEATER ELEMENT OPTIONAL "L" SHAPE DRIP LIP, SHIPPED LOOSE (NOTE 5) 36 (914) CHILLED/ HOT WATER SUPPLY & RETURN CONNECTION

30-3/4 (781)

RESILIENT MOUNTING GROMMETS WITH 3/8"(10) DIA. HOLE (TYP. OF 4) 1(25) 7/8"(22) KNOCKOUT 1-1/2(38) KNOCKOUT (TYPICAL)

1-1/2(38) 1-1/2(38) 1(25)

1-1/2(38) 1(25) A E

PARTIAL REAR VIEW (TYPICAL BOTH SIDES) *DRAWING NOT TO SCALE*


34 (864) 1-1/2 (38) 30-3/4 (781) 1-1/2(38) OPTIONAL DUCTED REAR RETURN 7/8"(22) O.D. CONDENSATE DRAIN CONNECTION SUPPLY AIR STAMPED SUPPLY AIR GRILLE RETURN AIR STAMPED RETURN AIR GRILLE & 1"(25) FILTER

TOP VIEW
1-1/2(38) 11-1/4 (286) 12"(305) MIN. 14"(356) MAX. D 1-1/2 (38)

HINGED BOTTOM RETURN AIR PANEL 6"(152)

FRONT VIEW

RIGHT SIDE VIEW

Unit Model
CBY02 CBY03 CBY04 CBY06 CBY08 CBY10 CBY12 NoTeS: *

Dimensions - Inches (Millimeters) D e


37 (940) 37 (940) 43 (1092) 55 (1397) 55 (1397) 77 (1956) 77 (1956) 32 (813) 32 (813) 38 (965) 50 (1270) 50 (1270) 72 (1829) 72 (1829)

Quantity/Unit Blower Motor


1 1 2 2 2 4 4 1 1 1 1 1 2 2

Unit Weight*
117 122 137 152 157 229 243

35 (889) 35 (889) 41 (1041) 53 (1346) 53 (1346) 75 (1905) 75 (1905)

1. 2. 3. 4. 5. 6.

Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. RH shown, LH opposite. Internal factory valve packages and drains may not align w/cabinet knockouts. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drawing is not to scale and is provided for Drip lip required for units with valves. reference only. Dimensions may vary with Threaded fittings must be field tightened and leak tested. options ordered. Consult IeC web site for up to date drawings.

20

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
PHySICAL dATA, Contd.

CXB - Horizontal Cabinet


CONTROL BOX 3 1/2 (89) 1-1/2"(38) KNOCKOUT (TYP. OF 5) 7/8" (22) KNOCKOUT (TYP. OF 2) OPTIONAL STAMPED RETURN AIR GRILLE & 1" (25) FILTER OPTIONAL "L" SHAPED DRIP LIP, SHIPPED LOOSE (NOTE 5)

18 (457)

2 (51) 2 (51)

E A CHILLED/HOT WATER SUPPLY & RETURN CONNECTIONS

2 (51)

PARTIAL REAR VIEW


(TYPICAL BOTH SIDES)

TOP VIEW
C B

23-1/2 (597) C 1-1/2 (38) SUPPLY AIR AIR VENT

7/8" (22) O.D. CONDENSATE DRAIN CONNECTION

OPTIONAL RETURN AIR LOCATION 5-3/4 (146)

STANDARD STAMPED SUPPLY AIR GRILLE

RESILIENT MOUNTING GROMMETS WITH 3/8" (10) DIA. HOLE (TYP. OF 4)

APPROX. 2 REF. (51) REMOVABLE HINGED R.A./ACCESS PANEL

RETURN AIR

STANDARD STAMPED RETURN AIR GRILLE & 1" (25) FILTER

FRONT VIEW

RIGHT SIDE VIEW

Unit Model
CXB02 CXB03 CXB04 CXB06 CXB08 CXB10 CXB12 NoTeS: *

Dimensions - Inches (Millimeters) A


38 (965) 42 (1067) 48 (1219) 53 (1346) 60 (1524) 74 (1880) 82 (2083)

Quantity/Unit F G
11 (279) 11 (279) 11 (279) 12 (305) 12 (305) 12 (305) 12 (305)

B
17-1/8 (435) 21-1/2 (546) 25-7/8 (657) 34-5/8 (879) 39 (991) 52-1/8 (1324) 60-7/8 (1546)

C
10-7/16 (265) 10-1/4 (260) 11-1/16 (281) 9-3/16 (233) 10-1/2 (267) 10-15/16 (262) 10-9/16 (268)

e
34 (864) 38 (965) 44 (1118) 49 (1245) 56 (1422) 70 (1778) 78 (1981)

Blower
1 1 2 2 2 4 4

Motor
1 1 1 1 1 2 2

Unit Weight*
98 118 126 168 176 215 245

5-3/4 (146) 5-3/4 (146) 5-3/4 (146) 6-3/4 (171) 6-3/4 (171) 6-3/4 (171) 6-3/4 (171)

1. 2. 3. 4. 5. 6.

Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. RH shown, LH opposite. Internal factory valve packages and drains may not align w/cabinet knockouts. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drawing is not to scale and is provided for Drip lip required for units with valves. reference only. Dimensions may vary with Threaded fittings must be field tightened and leak tested. options ordered. Consult IeC web site for up to date drawings.

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

21

Horizontal Series
PHySICAL dATA, Contd.

CXB - Horizontal Cabinet with optional Electric Heat


CONTROL BOX OPTIONAL STAMPED RETURN AIR GRILLE & 1" (25) FILTER OPTIONAL "L" SHAPED DRIP LIP, SHIPPED LOOSE (NOTE 5) 3-1/2 (89) OPTIONAL ELECTRIC STRIP HEATER ELEMENT

1-1/2"(38) KNOCKOUT (TYP. OF 5)

7/8" (22) KNOCKOUT (TYP. OF 2) 18 (457)

2 (51) 2 (51)

E A CHILLED/HOT WATER SUPPLY & RETURN CONNECTIONS

2 (51)

TOP VIEW

PARTIAL REAR VIEW


(TYPICAL BOTH SIDES) 23-1/2 (597) 7/8" (22) O.D. CONDENSATE DRAIN CONNECTION

1-1/2 (38)

AIR VENT

OPTIONAL RETURN AIR LOCATION 5-3/4 (146)

SUPPLY AIR F

STANDARD STAMPED SUPPLY AIR GRILLE

APPROX. 2 REF. (51) RESILIENT MOUNTING GROMMETS WITH 3/8" (10) DIA. HOLE (TYP. OF 4) REMOVABLE HINGED R.A./ACCESS PANEL

RETURN AIR

STANDARD STAMPED RETURN AIR GRILLE & 1" (25) FILTER

FRONT VIEW
Unit Model
CXB02 CXB03 CXB04 CXB06 CXB08 CXB10 CXB12 NoTeS: *

RIGHT SIDE VIEW


Quantity/Unit F
5-3/4 (146) 5-3/4 (146) 5-3/4 (146) 6-3/4 (171) 6-3/4 (171) 6-3/4 (171) 6-3/4 (171)

Dimensions - Inches (Millimeters) A


38 (965) 42 (1067) 48 (1219) 53 (1346) 60 (1524) 74 (1880) 82 (2083)

B
17-1/8 (435) 21-1/2 (546) 25-7/8 (657) 34-5/8 (879) 39 (991) 52-1/8 (1324) 60-7/8 (1546)

C
10-7/16 (265) 10-1/4 (260) 11-1/16 (281) 9-3/16 (233) 10-1/2 (267) 10-15/16 (262) 10-9/16 (268)

e
34 (864) 38 (965) 44 (1118) 49 (1245) 56 (1422) 70 (1778) 78 (1981)

G
11 (279) 11 (279) 11 (279) 12 (305) 12 (305) 12 (305) 12 (305)

Blower
1 1 2 2 2 4 4

Motor
1 1 1 1 1 2 2

Unit Weight*
100 120 128 170 178 217 247

1. 2. 3. 4. 5. 6.

Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. RH shown, LH opposite. Internal factory valve packages and drains may not align w/cabinet knockouts. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drawing is not to scale and is provided for Drip lip required for units with valves. reference only. Dimensions may vary with Threaded fittings must be field tightened and leak tested. options ordered. Consult IeC web site for up to date drawings.

22

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
PHySICAL dATA, Contd.

BHY - Horizontal Hi-Static Hideaway


4 (102) 4 (102) FLEXIBLE METAL CONDUIT

1 (25)

JUNCTION BOX (REMOTE MOUNT) 6 (152)

7/8"(22) O.D. CONDENSATE DRAIN

OPTIONAL 5/8"(16) O.D. TELL-TALE DRAIN CONNECTION, AVAILABLE ON STANDARD AND EXTENDED DRAIN PANS

1-1/2 (38) 1-1/8 (29) 2-1/4 (57)

E MTG. HOLES B A

D' 3 (76) A'

OPTIONAL EXTENDED DRAIN PAN (SEE NOTE 2)

TOP VIEW
RESILIENT MOUNTING GROMMET W/ 3/8"(10) DIA. HOLES (TYP. OF 4) 3/4 (19) H E 3/4 (19)

*DRAWING NOT TO SCALE*


1"(25) SUPPLY DUCT COLLAR 7/8 (22) 1 (25) 19-3/4 (502) 8-3/8 (213)

CHILLED/HOT WATER SUPPLY & RETURN CONNECTIONS G

AIR VENT

SUPPLY AIR

11-1/4 (286)

FRONT VIEW

16 (406)

OPTIONAL DRIP LIP SHIPPED LOOSE (NOTE 5)

RIGHT SIDE VIEW

Unit Model
BHY04 BHY06 BHY08 BHY10 NoTeS: *

Dimensions - Inches (Millimeters) A


31-1/4 (794) 36-1/4 (921) 43-1/4 (1099) 57-1/4 (1454)

Quantity/Unit G
8-3/4 (222) 10 (254) 10 (254) 10 (254)

A
43-1/4 (1099) 43-1/4 (1099) 57-1/4 (1454) 65-1/4 (1657)

B
26 (660) 31 (787) 38 (965) 52 (1321)

D
15 (381) 10 (254) 17 (432) 11 (279)

e
28-1/4 (718) 33-1/4 (845) 40-1/4 (1022) 54-1/4 (1378)

F
6-1/4 (159) 7-1/2 (191) 7-1/2 (191) 7-1/2 (191)

H
29-3/4 (756) 34-3/4 (883) 41-3/4 (1060) 55-3/4 (1416)

Blower
2 2 2 4

Motor
1 1 1 2

Unit Weight*
62 73 82 128

1. 2. 3. 4. 5. 6.

Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. RH shown, LH opposite. Optional drip lip not required with optional extended drain pan. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drip lip recommended. Threaded fittings must be field tightened and leak tested. Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

23

Horizontal Series
PHySICAL dATA, Contd.

BHY - Horizontal Hi-Static Hideaway with Electric Heat


CONTROL BOX (REMOTE MOUNT) 5-3/8 (137) STD. 6 (152) STD. FLEXIBLE METAL CONDUIT OPTIONAL 5/8"(16) O.D. TELL-TALE DRAIN CONNECTION, AVAILABLE ON STANDARD AND EXTENDED DRAIN PANS

STRIP HEATER 1 (25)

6 (152) 1-1/2(38) 1-1/8 (29) 2-1/4 (57) E MTG. HOLES B A

7/8"(22) O.D. CONDENSATE DRAIN

D' 3 (76) A'

OPTIONAL EXTENDED DRAIN PAN (SEE NOTE 2)

TOP VIEW
RESILIENT MOUNTING GROMMET W/ 3/8"(10) DIA. HOLES (TYP. OF 4) H 3/4 (19) E 3/4 (19) 1"(25) SUPPLY 1 DUCT (25) COLLAR 7/8 (22) 23-3/4 (603) 12-3/8 (314) AIR VENT

CHILLED/HOT WATER SUPPLY & RETURN CONNECTIONS

SUPPLY AIR

11-1/4 (286)

FRONT VIEW
Unit Model
BHY04 BHY06 BHY08 BHY10 NoTeS: *

16 (406)

OPTIONAL DRIP LIP (NOTE 5) SHIPPED LOOSE

RIGHT SIDE VIEW

Dimensions - Inches (Millimeters) A


31-1/4 (794) 36-1/4 (921) 43-1/4 (1099) 57-1/4 (1454)

Quantity/Unit G
8-3/4 (222) 10 (254) 10 (254) 10 (254)

A
43-1/4 (1099) 43-1/4 (1099) 57-1/4 (1454) 65-1/4 (1657)

B
26 (660) 31 (787) 38 (965) 52 (1321)

D
15 (381) 10 (254) 17 (432) 11 (279)

e
28-1/4 (718) 33-1/4 (845) 40-1/4 (1022) 54-1/4 (1378)

F
6-1/4 (159) 7-1/2 (191) 7-1/2 (191) 7-1/2 (191)

H
29-3/4 (756) 34-3/4 (883) 41-3/4 (1060) 55-3/4 (1416)

Blower
2 2 2 4

Motor
1 1 1 2

Unit Weight*
64 75 84 130

1. 2. 3. 4. 5. 6.

Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. RH shown, LH opposite. Optional drip lip not required with optional extended drain pan. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drip lip recommended. Threaded fittings must be field tightened and leak tested. Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.

24

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
PHySICAL dATA, Contd.

BPY - Horizontal Hi-Static Hideaway with Plenum


JUNCTION BOX 3 (76) H REAR MTG. HOLES 3 (76) INSULATED PLENUM 2 (51) 1 (25) PLENUM HANGER CLIPS (SEE NOTE 4) 1 (25) OPTIONAL EXTENDED DRAIN PAN (SEE NOTE 2) OPTIONAL 5/8"(16) O.D. TELL-TALE DRAIN CONNECTION, AVAILABLE ON STANDARD AND EXTENDED DRAIN PANS 1"(25) FILTER RETURN AIR 1"(25) RETURN DUCT COLLAR BOTTOM ACCESS PANEL FILTER RETAINER FILTER CLIP REMOVAL

4 (102) 18 (457)

7/8"(22) O.D. CONDENSATE DRAIN D' A' C MTG. HOLES B A 3 (76)

1-1/2(38) 1-1/8 (29) 2-1/4 (57)

TOP VIEW
1"(25) SUPPLY DUCT 7/8 (22) COLLAR CHILLED/HOT WATER SUPPLY & RETURN CONNECTIONS SUPPLY AIR G F OPTIONAL DRIP LIP (NOTE 6) SHIPPED LOOSE A 16 (406)

OPTIONAL REAR RETURN


22-1/2 (572) 21-1/2 (546) 13-15/16 (354) AIR VENT 1/2(13)

3/4 (19)

E C RESILIENT MOUNTING GROMMET W/ 3/8"(10) DIA. HOLES (TYP. OF 4)

3/4 (19)

12-3/4 (324)

REAR ACCESS PANEL 1"(25) FILTER RETURN AIR FILTER REMOVAL

FRONT VIEW
Unit Model A A
43-1/4 (1099) 43-1/4 (1099) 57-1/4 (1454) 65-1/4 (1657)

RIGHT SIDE VIEW


Dimensions - Inches (Millimeters) C D e
28-1/4 (718) 33-1/4 (845) 40-1/4 (1022) 54-1/4 (1378) 15 (381) 29-3/4 (756) 10 (254) 34-3/4 (883) 17 (432) 41-3/4 (1060) 11(279) 55-3/4 (1416)

H
30-1/4 (768) 35-1/4 (895) 42-1/4 (1073) 56-1/4 (1429)

Quantity/Unit Unit Weight* Blower Motor


2 2 2 4 1 1 1 2 84 97 110 163

BPY04 31-1/4 (794) BPY06 36-1/4 (921) BPY08 43-1/4 (1099) BPY10 57-1/4 (1454) NoTeS: *

26 (660) 34 (787) 38 (965) 52 (1321)

6-1/4 (159) 8-3/4 (223) 7-1/2 (190) 10 (254) 7-1/2 (190) 10 (254) 7-1/2 (190) 10 (254)

1. 2. 3. 4. 5. 6. 7. 8.

Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. RH shown, LH opposite. Optional drip lip not required with optional extended drain pan. All dimensions are +/- 1/4" (6). Plenum hanger clip location may vary depending on unit accessories. Product specifications are subject to change without notice. Drip lip recommended. Control box size and position may vary (consult factory). Threaded fittings must be field tightened and leak tested. Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

25

Horizontal Series
PHySICAL dATA, Contd.

BPY - Horizontal Hi-Static Hideaway with Plenum with Electric Heat


CONTROL BOX 5-3/8 (137) STD. INSULATED PLENUM H REAR MTG. HOLES 3 (76) 2 (51) 1 (25)

PLENUM HANGER CLIPS (SEE NOTE 4)

6 (152) STD. 22 (559)

ELECTRIC STRIP HEATER ELEMENT 1 (25)

OPTIONAL 5/8"(16) O.D. TELL-TALE DRAIN CONNECTION,AVAILABLE ON STANDARD AND EXTENDED DRAIN PANS 1"(25) FILTER OPTIONAL EXTENDED DRAIN PAN (SEE NOTE 2) D' BOTTOM ACCESS PANEL RETURN AIR 1"(25) RETURN DUCT COLLAR FILTER RETAINER FILTER CLIP REMOVAL

7/8"(22) O.D. CONDENSATE DRAIN

1-1/2 (38)

1-1/8 (29) 2-1/4 (57)

C MTG. HOLES B A

A' 3 (76)

TOP VIEW

OPTIONAL REAR RETURN


26-1/2 (673) 25-1/2 (648) 13-15/16 (354) AIR VENT

3/4 (19)

3/4 (19) MAX.

E RESILIENT MOUNTING GROMMET W/ 3/8"(10) DIA. HOLES (TYP. OF 4)

3/4 (19) CHILLED/HOT WATER SUPPLY & RETURN CONNECTIONS

1"(25) SUPPLY 7/8 DUCT (22) COLLAR

1/2 (13)

12-3/4 (324) OPTIONAL DRIP LIP (NOTE 6) SHIPPED LOOSE

SUPPLY G F AIR 16 (406) REAR ACCESS PANEL RETURN AIR FILTER REMOVAL

A ELECTRICAL KNOCKOUTS IN TOP & BOTTOM OF CONTACTOR BOX

1"(25) FILTER

FRONT VIEW

RIGHT SIDE VIEW

Unit Model
BPY04 BPY06 BPY08 BPY10

Dimensions - Inches (Millimeters) A


31-1/4 (794) 36-1/4 (921) 43-1/4 (1099) 57-1/4 (1454)

A
43-1/4 (1099) 43-1/4 (1099) 57-1/4 (1454) 65-1/4 (1657)

B
26 (660) 34 (787) 38 (965) 52 (1321)

C
28-1/4 (718) 33-1/4 (845) 40-1/4 (1022) 54-1/4 (1378)

D
15 (381) 10 (254) 17 (432) 11 (279)

e
29-3/4 (756) 34-3/4 (883) 41-3/4 (1060) 55-3/4 (1416)

H
30-1/4 (768) 35-1/4 (895) 42-1/4 (1073) 56-1/4 (1429)

Unit Blower Motor Weight*


2 2 2 4 1 1 1 2 86 99 112 165

Quantity/Unit

6-1/4 (159) 8-3/4 (223) 7-1/2 (190) 10 (254) 7-1/2 (190) 10 (254) 7-1/2 (190) 10 (254)

NoTeS: *

1. 2. 3. 4. 5. 6. 7. 8.

Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. RH shown, LH opposite. Optional drip lip not required with optional extended drain pan. All dimensions are +/- 1/4" (6). Plenum hanger clip location may vary depending on unit accessories. Product specifications are subject to change without notice. Drip lip recommended. Control box size and position may vary (consult factory). Threaded fittings must be field tightened and leak tested. Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.

26

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
STANdArd FEATurES & OPTIONS
Factory Installed option
X (Rear) X X X X X X X X X X X X X X X X X X X (CXB X (CXB) X X X X X X

Features And options


Air Flow Arrangement Front Supply/Rear Return (CHY, BHY) Front Supply/Rear or Bottom Return (CPY, BPY, CBY, CXB) Coils 2 Rows 2-Pipe (CHY, CPY, CBY, CXB) 3 Rows 2-Pipe (CHY, BHY, CPY, BPY, CBY, CXB) 4 Rows 2-Pipe (CHY, BHY, CPY, BPY, CBY, CXB) 3/1, 3/2, 4/1 Rows 4-Pipe (CHY, BHY, CPY, BPY, CBY, CXB) Manual Air Vent Automatic Air Vent DX Coils Steam Coils Connection Right or Left (Same End) Right or Left (Opposite End) Drain Pan Galvanized Internally Coated with 2-part closed Cell Foam Stainless Steel Externally Coated Drip Lip (recommended with motorized valves) Extended Drain Pans (CHY, CPY, BHY, BPY) Secondary Drain Connection Fin Material Aluminum with Galvanized End Sheets Copper with Stainless End Sheets & Bottom Coil Baffle Nichrome Wire Strip electric Heater (Total and Auxiliary) Filters 1" Throwaway non-woven synthetic filter 1" Permanent 1" Pleated MERV 8 Insulation 1/2" Standard Fiberglass 1/2" Premium IAQ Fiberglass 1/2" Foil Face 1/4" Closed Cell Motor Type PSC Motors with Quick Connect Plug Motor Voltage 120/1/60 3-Speed 208/230/277/1/60 3-Speed (Optional Voltage) Supply/Return Air Grilles Louvered Stamped Supply Grille (CXB) Double Deflection, Aluminum Finish Supply Grille Double Deflection, Integral Supply Grille - painted Stamped Return Grille (CBY, CXB) Hinged Bar-Type, Aluminum-finish Return Grille with Throwaway Filter - F.O. Controls Service Switch with Lockout Tabs Single Point Power Connection Incoming Power Fusing 24 V Controls Condensate Overflow Switch 3-Speed Switch Thermostats Custom Control (DDC)

Standard
X X (Bottom) X X X X X X X X X X X X

Field Installed option


X X (CHY, CPY, CBY) X (CHY, CPY, CBY) X X

Factory Special Quote


X v X X X (CHY, CPY, CBY) X (CHY, CPY, CBY) X

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

27

Horizontal Series
STANdArd FEATurES & OPTIONS, Contd.
As detailed in the table on page 29, we offer a control for most of the customer needs. Additional controls and devices are available to meet even the most demanding operating logic.

Condensate High Level Switch


This switch shuts down the unit when the water level in the drain pan reaches an unsafe level. Building code changes in much of the country now require this type of device.

Three-speed Fan Control


All of our basic control schemes utilize a 2- or 3-speed switch to modulate the cooling output, to maximize the percentage of latent heat removal, and to further minimize the sound level when maximum cooling or heating performance is not required.

Service Switches
We offer concealed service switches for use by maintenance and service personnel to shut off the power while working on the unit.

Fusing
We offer incoming power fusing for all units as well as blower motor and control sub-fusing for units that use electric heat. The blower motor and control sub-fusing (single power source wiring) is required when single source power with electric heat is specified.

Low Voltage Control (24 V)


A low voltage control is available with all of our control schemes.

Control Packages

Wall Series 4039

Vertical Wall Series 155

Horizontal Wall Series 155

24 V Programmable and Non-Programmable Digital Series

28

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
STANdArd FEATurES & OPTIONS, Contd.

Control Package Applications


Unit Type Control option Manual Fan System Type Manual1 Heat Only Cool Only Heat/Cool 2-Pipe Valve Cycle* Heat/Cool with Auxiliary Electric Heat Cool with Total Electric Heat 4-Pipe
NoTe:

Changeover Type None None None Manual Automatic Manual Automatic Manual Automatic Manual Automatic

Wall Series 4039

Heat/Cool

Vertical and Horizontal Wall Series155

24 V Programmable and Non-Programmable Digital Series

1. Fan switch only; no thermostat. Thermostat Features All listed controls include fan switching. 24 V, 115 V, 208 V, 240 V, 277 V Remote Wall Mounted Manual Fan Switch Operation Auto Fan Speed Control Continuous 3-Speed Fan Cycling Fan O.A. Damper Signal Remote Temperature Sensor Adjustable Operating Range Touch Pad/Digital Display Local Temperature Set-Back Water Temperature Purge Cycle Pipe Sensor Wall Series 4039 N/A N/A N/A N/A N/A N/A N/A N/A Control Type1 Vertical and Horizontal Wall Series 155 N/A N/A Opt Kit N/A N/A N/A N/A 24 V Digital Series 24 V only Opt

NoTeS: 1. Control packages with valve cycle control are continuous fan operation only.

2. All wall-mount control packages are shipped loose for field installation. (Boxes, tile rings, plaster rings, etc. are not provided.) 3. Aquastats are included in control packages, as required.

Control Options

24 V control packages Unit-mounted fan switches (Special Quote) Single power source wiring (motor/control fusing) Incoming power fusing Service switches

Minimum room temperature thermostats (Special Quote) Low voltage remote shutdown relays (Special Quote) Fan and valve cycle applications (Special Quote) Thermostats available with large letter print for handicap applications (Special Quote) DX coil applications

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

29

Horizontal Series
STANdArd FEATurES & OPTIONS, Contd.

Supply Air Grilles


Unit Size 02 03 04 06 08 10 12 Nominal CFM 200 300 400 600 800 1000 1200 Recommended Grille Size Inches (Millimeters) 16" x 6" (406 x 152) 20" x 6" (508 x 152) 26" x 6" (660 x 152) 30" x 6" (762 x 152) 38" x 6" (965 x 152) 52" x 6" (1320 x 152) 60" x 6" (1524 x 152)

Return Air Filter Grilles


Unit Size 02 03 04 06 08 10 12 Nominal CFM 200 300 400 600 800 1000 1200 Recommended Grille Size Inches (Millimeters) 24" x 10" (610 x 254) 28" x 10" (711 x 254) 32" x 10" (813 x 254) 42" x 10" (1067 x 254) 42" x 10" (1067 x 254) 54" x 10" (1372 x 254) 64" x 10" (1626 x 254)

NoTeS: 1. Refer to Physical Data, pages 13 through 26 for actual

unit supply air opening dimensions. 2. Field-furnished duct transitions may be required.

NoTeS: 1. Refer to Physical Data, pages 13 through 26 for actual

unit return air opening dimensions. 2. Field-furnished duct transitions may be required.

optional Double Deflection, Aluminum-finish Supply Grille (optional special ship separate for models CHY, CPY, CBY, BHY, and BPY. Consult factory for details.)

optional Hinged, Bar-type, Aluminum-finish Return Grille with Throwaway Filter (optional special ship separate for models CHY, CPY, CBY, BHY, and BPY. Consult factory for details.)

optional Double-deflection, Integral Supply Grille Painted to Match Color of Unit

30

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
STANdArd FEATurES & OPTIONS, Contd.

Nominal Filter Sizes


All cabinet model units (except CH and BH) have non-woven synthetic throwaway filters furnished as standard equipment. Cleanable and pleated filters are optional.
Nominal one-Inch Filter Size - Inches (Millimeters) Unit Size 02 03 04 06 08 10 12 CHY (Note 1) 10" x 24" (254 x 610) 10" x 28" (254 x 711) 10" x 32" (254 x 813) 10" x 42" (254 x 1067) 10" x 42" (254 x 1067) 10" x 54" (254 x 1372) 10" x 64" (254 x 1626) CPY 10" x 18" (254 x 457) 10" x 22" (254 x 559) 10" x 28" (254 x 711) 10" x 33" (254 x 838) 10" x 40" (254 x 1016) 10" x 54" (254 x 1372) 10" x 62" (254 x 1575) CBY Bottom Return Stamped 10" x 28" (254 x 711) 10" x 28" (254 x 711) 10" x 33" (254 x 838) 10" x 45" (254 x 1143) 10" x 45" (254 x 1626) 10" x 62" (254 x 1575) 10" x 62" (254 x 1575) CBY Rear Return Stamped 7" x 21" (178 x 533) 7" x 21" (178 x 533) 7" x 27" (178 x 533) 7" x 38" (178 x 965) 7" x 38" (178 x 965) 7" x 52" (178 x 1321) 7" x 52" (178 x 1321) CXB Bottom Return Stamped 10" x 23-1/2" (254 x 597) 10" x 28" (254 x 711) 10" x 32-1/2" (254 x 826) 10" x 37" (254 x 940) 10" x 41" (254 x 1041) 10" x 54-1/2" (254 x 1384) 10" x 63" (254 x 1600) CXB Rear Return Stamped 8" x 23-1/2" (203 x 597) 8" x 28" (203 x 711) 8" x 32-1/2" (203 x 826) 8" x 37" (203 x 940) 8" x 41" (203 x 1041) 8" x 54-1/2" (203 x 1384) 8" x 63" (203 x 1600) CXB Rear Return Ducted 8" x 23-1/2" (203 x 597) 8" x 28" (203 x 711) 8" x 32-1/2" (203 x 826) 8" x 37" (203 x 940) 8" x 41" (203 x 1041) 8" x 54-1/2" (203 x 1384) 8" x 63" (203 x 1600)

Nominal one-Inch Filter Size - Inches (Millimeters) Unit Size 04 06 08 10 BHY (Note 1) 10" x 32" (254 x 813) 10" x 42" (254 x 1067) 10" x 42" (254 x 1067) 10" x 54" (254 x 1372) BPY Bottom Return with Heat 16-3/4" x 28" (425 x 711) 16-3/4" x 33" (425 x 838) 16-3/4" x 40" (425 x 1016) 16-3/4" x 54" (425 x 1372) BPY Bottom Return without Heat 12-3/4" x 28" (324 x 711) 12-3/4" x 33" (324 x 838) 12-3/4" x 40" (324 x 1016) 12-3/4" x 54" (324 x 1372) BPY Rear Return with Heat 12-3/4" x 28" (324 x 711) 12-3/4" x 33" (324 x 838) 12-3/4" x 40" (324 x 1016) 12-3/4" x 54" (324 x 1372) BPY Bottom Return without Heat 12-3/4" x 28" (324 x 711) 12-3/4" x 33" (324 x 838) 12-3/4" x 40" (324 x 1016) 12-3/4" x 54" (324 x 1372)

NoTeS: 1. Filter sizes for the CH and BH models are recommended filter sizes only. No filter is factory provided with these models.

2. Sizes shown are nominal ordering sizes.

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

31

Horizontal Series
PIPING PACKAGES (TyPICAL)

Two-way Motorized Control Valve


In a two-way motorized control valve package, the motor drives the valve open, and a spring returns the valve to a normally closed position. No water flows with the unit off. The standard supply connection from the coil will accept a swaged copper fitting for field brazing. As an option, this connection may be factory furnished with a union. When a swage is necessary, it becomes part of the valve package. The isolation, or ball, valve in the return piping is shipped loose for field installation.
Air Vent

Three-way Motorized Control Valve


In a three-way motorized control valve package, a diverting valve controls water flow to the coil. When the unit is off, water bypasses the coil and flows directly to the system return. A balancing valve may be specified in the bypass line to permit equal flow balancing.
Air Vent Ball Valve

R Swage Coil 3-way Valve

Optional Balance Valve

Ball Valve
(Ships Separate)

S Swage A Aquastat Ball Valve

Coil 2-way Valve S Swage Ball Valve S

NoTeS: 1. Please note that project specifications for system

Two-way Motorized Control Valve with Changeover


In a two-way motorized changeover control valve package, the motor drives the valve open, and a spring returns the valve to a normally closed position. No water flows through the coil with the unit off. The aquastat bypass line allows a small amount of water to flow from the supply to the return piping when the control valve is closed. The strapon aquastat senses whether the flowing water is cold or hot and switches a contact closed to provide automatic summer/winter changeover (ACO) for the system.
Air Vent

pressure, pressure drop limitations and flow rate should be checked prior to selecting specific components or the valve package size. 2. The supply and return piping connections of the factory-provided valve package are either swaged for field brazing (standard) or union fitted (optional) for connection to the coil. 3. Consult IECs Valve Packages and Piping Components manual or your local representative for detailed piping and valve application information. Factoryprovided valve packages are assembled, brazed, wired electrically and dry-fit to the coil connections before shipping. Field brazing to the coil completes the installation. Some applications dictate shipping isolation valves loose.

Swage

Ball Valve

Coil 2-way Valve A S Swage Aquastat

Aquastat Bleed Bypass Line Ball Valve S

32

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
MECHANICAL SPECIFICATIONS GENERAL DESCRIPTION HORIZONTAL FAN COIL UNITS
CHY Horizontal Hideaway CBY Horizontal Telescoping Hideaway CPY Horizontal Hideaway with Plenum CXB Horizontal Cabinet BHY Horizontal Hi-Static Hideaway BPY Horizontal Hi-Static Hideaway with Plenum

B. CHY, BHY Horizontal Hideaway Units: 1. 2. Cabinet shall be made of heavy gauge galvanized steel. The interior surfaces shall be lined with 1/2" thick standard fiberglass (1/2" thick Premium IAQ fiberglass, 1/2" foil face, or 1/4" closed cell) insulation. Units shall be supplied with a ducted collar for supply duct connection. Units shall have a galvanized (or stainless steel) drain pan extending the entire width of the coil (with second drain connection). Galvanized drain pans shall be internally coated with 2-part closed cell foam insulation.

PART 1
1.1 SUMMARY This section includes fan coil units and accessories. 1.2 SYSTEM DESCRIPTION Horizontal Fan Coil Units, 2-pipe, 4-pipe, or 2-pipe with electric heat, concealed or exposed cabinets that are horizontally mounted. 1.3 QUALITY ASSURANCE Coils shall be tested in accordance with AHRI Standard 440-2008. Each coil shall be factory tested for leakage at 300 psig air pressure with coil submerged in water. Insulation and adhesive shall meet NFPA-90A requirements for flame spread and smoke generation. Base or standard units shall be ETL certified. 1.4 DELIVERY, STORAGE AND HANDLING Unit shall be handled and stored in accordance with the manufacturers instructions. 4. 3.

5.

C. CPY, BPY Horizontal Hideaway with Plenum Units: 1. 2. Units shall be constructed of heavy gauge galvanized steel. The interior surfaces shall be lined with 1/2" thick standard fiberglass (1/2" thick Premium IAQ fiberglass, 1/2" foil face, or 1/4" closed cell) insulation. A heavy gauge plenum shall enclose the blower/motor assembly with bottom or rear return. Units shall be supplied with a ducted collar for supply duct connection. Units shall have a galvanized (or stainless steel) drain pan extending the entire width of the coil (with second drain connection). Galvanized drain pans shall be internally coated with a 2-part closed cell foam insulation.

PART 2 PRODUCTS
2.1 MANUFACTURER A. Basis of design shall be fan coils by International Environment Corporation. 2.2 CONFIGURATION A. General: Factory assembled horizontal fan coil units complete with fan, motor, drain pan, and all required wiring, piping and controls.

3.

4. 5.

6.

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

33

Horizontal Series
MECHANICAL SPECIFICATIONS, Contd.
7. Units shall have non-woven synthetic throwaway (permanent or pleated) filters. 3. IAQ fiberglass, 1/2" foil face, or 1/4" closed cell) insulation. Unit shall have an adjustable height, hinged return air ceiling panel with non-woven synthetic throwaway, (permanent, or pleated) filter. Panel shall be painted with an Arctic White powder-coat finish. Units shall have a galvanized (or stainless steel) drain pan extending the entire width of the coil (with second drain connection). Galvanized drain pans shall be externally coated with a 2-part closed cell foam insulation.

4. D. CXB Horizontal Cabinet Units: 1. 2. Units shall be constructed of heavy gauge galvanized steel. The interior surfaces shall be lined with 1/2" thick standard fiberglass (1/2" thick Premium IAQ fiberglass, 1/2" foil face, or 1/4" closed cell) insulation. Cabinet shall be painted with an Arctic White powder-coat finish. The unit shall have a stamped (double deflection, aluminum finish or steel construction factory installed and painted to match cabinet) discharge grille. The unit shall have removable bottom access panel with stamped return air grille, filter rack, and non-woven synthetic throwaway (permanent or pleated) filter or optional ducted rear return cabinet with a solid bottom access panel. Panel shall be fastened with tamper proof quarter-turn fasteners. Units shall have a galvanized (or stainless steel) drain pan extending the entire width of the coil (with second drain connection). Galvanized drain pans shall be internally coated with a 2-part closed cell foam insulation. 5.

6.

3. 4.

2.3 CERTIFICATION A. Safety: Units shall be listed by Electronics Testing Laboratories, Inc. with the ETL listing indicating the units comply with the minimum requirements of the U.S. and Canadian national product safety standard, UL 1995/CSA C22.2 No. 236. B. Capacities: Coil capacities are tested in accordance with AHRI Standard 440-2008. 2.3.1 MATERIALS A. Coils: All coils shall have 1/2" copper tubes, manual (or automatic) air vents, and aluminum fins, 10 fins per inch spacing. Coil fins shall be mechanically bonded to copper tubes. 0.500" O.D. copper tubes must comply with ASTM B-75. Fin thickness shall be 0.0045" and tube thickness shall be 0.016". All coils shall be leak tested with air at 300 psig under water. 1. For installation in a 2-pipe system, unit shall be equipped with: a. 3-row (or 4-row) coil as shown on equipment drawings b. 2 ball valves c. 1 motorized control valve

5.

6. 7.

8.

E. CBY Horizontal Telescoping Hideaway Units: 1. 2. Units shall be constructed of heavy gauge galvanized steel. The interior surfaces shall be lined with 1/2" thick standard fiberglass (1/2" thick Premium

34

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

Horizontal Series
MECHANICAL SPECIFICATIONS, Contd.
2. For installation in a 4-pipe system, unit shall be equipped with: a. 3/1, 3/2 or 4/1 row-split coil, as shown on equipment drawings b. 4 ball valves c. 2 motorized control valves B. Fans: 1. 2. 3. 4. Fans shall be direct-drive, double-width fan wheels with forward-curved blades. Blower wheels shall be statically and dynamically balanced. Scrolls and fan wheels shall be constructed of galvanized steel. Shall be easily removable. 2. A 4-pipe system shall be capable of providing heating and cooling on demand.

G. Electrical Requirements: 1. Standard unit shall operate on 115 V (208 V, 230 V or 277 V), single phase, 60 Hz electrical power, and all exposed wiring shall be in flexible conduit.

H. Option and Accessories: 1. Unit shall be equipped with nichrome wire strip electric heaters for total or auxiliary electric heat as specified on the equipment schedule. a. Heaters shall be protected by an automatic reset safety cutout switch and a fusible link. b. Heater capacity shall be as specified on the equipment schedule. c. Heaters shall be single phase, 120 V (208 V, 240 V or 277 V) volts as specified on the equipment schedule. d. For total electric heat, unit controls shall include a sequenced heating and cooling thermostat in lieu of the heating/cooling thermostat and automatic changeover device. e. For auxiliary electric heat, unit controls shall include an aquastat to verify system mode. f. A junction box and fuse shall be factory furnished and installed to protect the motor and control circuit when electric heaters are installed. 2. 3. 4. 5. Service switch shall be factory installed. Units shall be equipped with 24 V controls. Units shall be equipped with high level condensate switch. A hinged, bar type aluminum return air grille with filter holder shall be furnished for field installation. Discharge air grille with double deflection, aluminum construction shall be furnished for field installation as shown on equipment schedule. Aluminum grilles shall have a natural anodized finish.

C. Fan Speed and Temperature Control: 3 (high, medium, low) speed control, (off, on, auto), (wall or unit) (auto or manual) thermostat. D. Motors: 1. Motors shall be 3-speed, single phase, 60 Hz permanent split capacitor type for 115 V (208 V, 230 V, or 277 V) permanently lubricated, with sleeve bearings. Motors shall be connected with quick connect electrical plugs. Motors shall have thermal overload protection with automatic reset.

2. 3.

E. Controls and Safeties: 1. Controls: Unit shall be furnished with a 3-speed, 4-position fan switch on a wall plate for field installation. 2. Safeties: Unit fan motor shall be equipped with integral motor protection. F. Operating Characteristics: 1. A 2-pipe system shall be capable of providing heating or cooling as determined by the operating mode of the central water supply system. 6.

International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com

35

The USGBC Member logo is a trademark owned by the U.S. Green Building Council and is used by permission. The logo signifies only that IEC is a USGBC member. USGBC does not review, certify, or endorse the products or services offered by its members.

IEC is dedicated to the environment and for its part, IEC has elected to use recycled materials whenever possible for printed sales materials.

IEC Catalog Part #: I100-90002102 CA-020 Revision 3 2010 International Environmental Corporation (IEC) IEC is a subsidiary of LSB Industries, Inc. NYSE symbol LXU; www.lsb-okc.com

P.O. Box 2598 Oklahoma City, OK 73101-2598 p: 405.605.5000 f: 405.605.5001 www.iec-okc.com

You might also like