Professional Documents
Culture Documents
Horizontal Series
International Environmental Corporation (IEC) works continually to improve its products. As a result, the design and specifications of each product may be changed without notice and may not be as described herein. Please contact IEC for information regarding current design and product specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties but are merely IECs opinion or commendation of its products. Manufacturers standard limited warranty applies.
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
TAbLE OF CONTENTS
3 Table of Contents 4 Portfolio 6 Features & Benefits 7 Unit Model Key 8 Ratings & Listings 9 Air Delivery 10 Electric Heating 11 Motor Data 13 Physical Data 27 Standard Features & Options 32 Piping Packages (Typical) 33 Mechanical Specifications
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
POrTFOLIO
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
POrTFOLIO, Contd.
BPY - Horizontal Hi-Static Hideaway with Plenum 400 CFM to 1000 CFM
The Horizontal Hi-Static Hideaway with Plenum (BPY) fan coil unit is designed for installations requiring a return-air plenum with a unit-mounted filter and filter-rack assembly. The BPY plenum is constructed of galvanized steel and lined with glass-fiber insulation. BPY units are designed with interchangeable panels so that the unit may be modified on site to accommodate a rear or bottom return. Standard BPY units are provided with a galvanized finish.
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
FEATurES & bENEFITS
Application Fit
Multiple cabinet choices are available in 7 nominal CFM sizes for application in a variety of room layouts.
o
Optional airflow configuration (front supply, bottom supply, rear return or bottom return) to meet certain design limitations.
Horizontal Cabinet units (CXB) with aesthetically pleasing cabinetry offer capacities that are ideal for air conditioning in dormitories, small apartments, schools and many other applications. Front supply, bottom or rear return are available.
Outside air connections are available to meet ventilation requirements and reduce field labor (CXB/ CBY/CPY/BPY).
Wide variety of factory assembled valve packages to meet desired controls specifications. Optional condensate overflow switch to address latest building codes where required. Wide variety of optional insulation materials are available to address IAQ concerns.
Horizontal Telescoping Hideaway units with painted access panel (CBY) allows smooth fit up to plaster or sheet rock ceilings. Standard units include bottom louvered return air with the filter located in the access panel.
Horizontal Hideaway models (CHY/BHY) units are installed above the ceiling with or without ducted supply air and open soffit return with an optional ceiling-mounted filter-grille.
Ease of Installation
Factory assembled valve packages minimize piping work at the job site (shipped loose for field mounting). Optional unit mounted controls, service switches and fusing minimize the electrical work required on site. Units are tagged at the factory for clear identification on job site. Opposite end connection units may minimize the piping work on renovation jobs.
Horizontal Hideaway models with plenum (CPY/ BPY) units are installed above the ceiling with or without ducted supply air and ducted return air. The return air filter is either mounted on the unit plenum or installed in an optional ceiling filtergrille.
Design Flexibility
Easy to use ratings program to speed up project design. Standard and high capacity hydronic coils and DX coils are available to match the heating and cooling loads of the space. Optional powder-paint finish colors and grille selections will complement most dcors (exposed units). CXB and CBY units ordered with optional rear return are constructed with a solid bottom panel. Customizable cabinetry makes these units ideal for renovation jobs or where special sizes are required to fit oversized valves and control packages.
Ease of Service
All components are accessible by simply removing the access panel. Filters can be replaced without tools or by opening the bottom panels on exposed units. Blower assembly easily removed from the rear of coil for service and cleaning.
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
uNIT MOdEL KEy
Code Items Code 01 C B
UNIT
02 Y
VINTAGE
03 0 4
SIZE
04 A Y Y Y
COILS
04a C B Y Y
ELECTRIC HEAT
05 C 2
06 R 5
07 C P B
CONTROLS
Horizontal Hideaway Horizontal Hideaway with Plenum Horizontal Telescoping Hideaway Horizontal Cabinet Horizontal Hi-Static Hideaway Horizontal Hi-Static Hideaway with Plenum
02 03 04 06 08 10
200 CFM 300 CFM 400 CFM 600 CFM 800 CFM 1000 CFM
12 1200 CFM
Arrangement 5 6 6
CHY, BHY
Two-pipe Cooling and Heating or Four-pipe Cooling A 3 Row B 4 Row D 2 Row R 3 Row, AAV S 4 Row, AAV
6
CPY, BPY
5 Voltage C D E F V U 120 V 208 V 240 V 277 V 220 V (50)* 240 V (50)* kW** AY BY CY DY FY GY 0.50 1.00 1.50 2.00 3.00 4.00 HY JY KY LY NY YY 5.00 6.00 7.00 8.00 10.00 None Stages Y Single Stage Only 5 6
CXB
6
CBY
Y None
System Manual Fan Operation A Standard Wall Mount (Switch Only) Valve Cycle Control G H J K L M N P Q R 2-Pipe Heat Only 2-Pipe Cool Only 2-Pipe Heat and Cool, MCO 2-Pipe Heat and Cool, ACO 2-Pipe Heat and Cool w/ Aux. Elec. Heat, MCO 2-Pipe Heat and Cool w/ Aux. Elec. Heat, ACO 2-Pipe Cool w/ Total Elec. Heat, MCO 2-Pipe Cool w/ Total Elec. Heat, ACO 4-Pipe Heat and Cool, MCO 4-Pipe Heat and Cool, ACO Thermostat 4 A B P N Basic Wall Series Horizontal Wall Series Vertical Wall Series 24 V Programmable Wall Series 24 V Non-Programmable Wall Series
Consult factory for 50Hz applications. Note that kWs depend on voltage and unit size.
*** Standing in front of the unit, hand is determined by looking into the air supply and assigning the hand to match the location of the cooling coil connections.
NOTE: MCO controls (J, L, N, Q) not available with Standard Unit Mount Thermostat
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
rATINGS & LISTINGS
AHRI Certification
IECs Horizontal Series units are certified in compliance with Air-Conditioning, Heating, and Refrigeration Institute (AHRI) industry standard AHRI-440 for room fan coil units. Approved standard ratings are tabulated below.
C-ETL US Listing
IECs Horizontal Series units are listed by ETL. The C-ETL-US listing signifies that IECs fan coil units have been examined by ETL and are in compliance with both the U.S. and Canadian applicable standards.
3061627
HEATING AND COOLING EQUIPMENT
Standard Ratings
Unit Type Unit Cell Nominal Size CFM 02-A 03-A CHY CPY CXB CBY 04-A 06-A 08-A 10-A 12-A 02-B 03-B CHY CPY CXB CBY 04-B 06-B 08-B 10-B 12-B 04-B BHY 06-B 08-B 10-B 200 300 400 600 800 1000 1200 200 300 400 600 800 1000 1200 400 600 800 1000 Cooling Capacity Total MBH 6.0 9.0 12.1 17.3 22.6 27.5 32.8 6.9 9.8 13.8 19.6 25.5 31.0 37.2 16.0 21.8 26.5 37.2 Sensible MBH 4.4 6.3 8.8 13.0 16.2 21.0 25.0 4.3 6.5 9.8 14.3 18.8 22.0 27.7 11.6 16.0 19.6 27.6 Power Input Watts PSC 87 85 165 225 235 305 435 87 85 145 220 235 300 425 170 205 225 355
EWT, 10F water temperature rise, high fan speed, motor voltage 115/1/60, and air flow under dry coil conditions. 2. For all application ratings, use IECs computer selection program, the quick-selection ratings provided in this catalog, or contact your local IEC representative. 3. For additional information, please consult AHRIs website at www.ahrinet.org.
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
AIr dELIvEry
3 Row
CHY
4 Row
NoTeS: 1. Tabled values are standard CFM at sea level, 70F with dry coil.
2. Ratings include factory-installed filter and/or grille, where applicable. 3. Consult factory for 50 Hz applications.
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
ELECTrIC HEATING
03
04 -
Unit Size 06 08 -
10 -
12 -
Note 6 Note 6
-
Note 6
-
Note 6
-
Note 6
-
Construction
The heater coils of high-grade resistance wire are supported by ceramic insulators on plated steel brackets. These heat elements are suspended directly in front of the fan outlet between the blower and the coil. High limit thermal cutouts protect the heater in the event of air failure. There are many special applications and control sequences for electric heat. For special applications, please consult the factory.
Note 6 Note 6
-
Note 6
-
Note 6
-
Note 6 Note 6
2. Heaters over 48 Amps are subdivided and fused. 3. Electric Heating Capacities (BTUH) = Heater kW x 3413. 4. Electric Heater Amperage = (Heater kW x 1000)/Applied Voltage) 5. Consult factory for 50 Hz applications. 6. High and medium speed only.
10
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
MOTOr dATA
High 115 V 60 Hz 1 Phase Low High 208 V 60 Hz 1 Phase Low High 230 V 60 Hz 1 Phase Low High 277 V 60 Hz 1 Phase Low Medium Medium Medium Medium
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
11
Horizontal Series
MOTOr dATA, Contd.
12
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
PHySICAL dATA
7/8"(22) O.D. CONDENSATE DRAIN OPTIONAL 5/8"(16) O.D. TELL-TALE DRAIN CONNECTION, AVAILABLE ON STANDARD AND EXTENDED DRAIN PANS
D'
TOP VIEW
RESILIENT MOUNTING GROMMET W/ 3/8"(10) DIA. HOLES (TYP. OF 4) H 3/4 (19) E MTG. HOLES 3/4 (19) CHILLED/HOT WATER SUPPLY & RETURN CONNECTIONS 1"(25) SUPPLY DUCT COLLAR 7/8 (22) 17-1/2 (445) 1 (25) 8-3/8 (213) AIR VENT
SUPPLY AIR
FRONT VIEW
Unit Model
CHY02 CHY03 CHY04 CHY06 CHY08 CHY10 CHY12
16 (406)
A
31-1/4 (794) 36-1/4 (921) 43-1/4 (1099) 43-1/4 (1099) 57-1/4 (1454) 65-1/4 (1657) 75-1/4 (1911)
B
16 (406) 20 (508) 26 (660) 31 (787) 38 (965) 52 (1321) 60 (1524)
D
13 (330) 14 (356) 15 (381) 10 (254) 17 (432) 11 (279) 13 (330)
e
18-1/4 (464) 22-1/4 (565) 28-1/4 (718) 33-1/4 (845) 40-1/4 (1022) 54-1/4 (1378) 62-1/4 (1581)
Blower
1 1 2 2 2 4 4
Motor
1 1 1 1 1 2 2
Unit Weight*
36 39 49 59 64 95 107
8-3/4 (222) 19-3/4 (502) 8-3/4 (222) 23-3/4 (603) 8-3/4 (222) 29-3/4 (756) 10 (254) 34-3/4 (883) 10 (254) 41-3/4 (1060) 10 (254) 55-3/4 (1416) 10 (254) 63-3/4 (1619)
NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components.
1. 2. 3. 4. 5. 6.
RH shown, LH opposite. Optional drip lip not required with optional extended drain pan. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drip lip recommended. Threaded fittings must be field tightened and leak tested.
Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
13
Horizontal Series
PHySICAL dATA, Contd.
7/8"(22) O.D. CONDENSATE DRAIN OPTIONAL EXTENDED DRAIN PAN (SEE NOTE 2)
D' A'
TOP VIEW
RESILIENT MOUNTING GROMMET W/ 3/8"(10) DIA. HOLES (TYP. OF 4) H 3/4 (19) 3/4 (19) CHILLED/HOT WATER SUPPLY & RETURN CONNECTIONS 21-1/2 (546) 1" SUPPLY DUCT COLLAR 7/8 (22) 1 (25) 12-3/8 (314) AIR VENT
SUPPLY AIR
FRONT VIEW
Unit Model
CHY02 CHY03 CHY04 CHY06 CHY08 CHY10 CHY12
16 (406)
A
31-1/4 (794) 36-1/4 (921) 43-1/4 (1099) 43-1/4 (1099) 57-1/4 (1454) 65-1/4 (1657) 75-1/4 (1911)
B
16 (406) 20 (508) 26 (660) 31 (787) 38 (965) 52 (1321) 60 (1524)
D
13 (330) 14 (356) 15 (381) 10 (254) 17 (432) 11 (279) 13 (330)
e
18-1/4 (464) 22-1/4 (565) 28-1/4 (718) 33-1/4 (845) 40-1/4 (1022) 54-1/4 (1378) 62-1/4 (1581)
F
6-1/4 (159) 6-1/4 (159) 6-1/4 (159) 7-1/2 (191) 7-1/2 (191) 7-1/2 (191) 7-1/2 (191)
Blower
1 1 2 2 2 4 4
Motor
1 1 1 1 1 2 2
8-3/4 (222) 19-3/4 (502) 8-3/4 (222) 23-3/4 (603) 8-3/4 (222) 29-3/4 (756) 10 (254) 34-3/4 (883) 10 (254) 41-3/4 (1060) 10 (254) 55-3/4 (1416) 10 (254) 63-3/4 (1619)
NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components.
1. 2. 3. 4. 5. 6.
RH shown, LH opposite. Optional drip lip not required with optional extended drain pan. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drip lip recommended. Threaded fittings must be field tightened and leak tested.
Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.
14
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
PHySICAL dATA, Contd.
1 (25)
1" (25) FILTER RETURN AIR 1" (25) RETURN DUCT COLLAR FILTER RETAINER CLIP FILTER REMOVAL
3 (76)
TOP VIEW
3/4 (19)
3/4 (19)
1 (25)
10-1/2 (267)
16 (406)
FRONT VIEW
Unit Model
CPY02 CPY03 CPY04 CPY06 CPY08 CPY10 CPY12
Quantity/Unit
A
31-1/4 (794) 36-1/4 (921) 43-1/4 (1099) 43-1/4 (1099) 57-1/4 (1454) 65-1/4 (1657) 75-1/4 (1911)
B
16 (406) 20 (508) 26 (660) 31 (787) 38 (965) 52 (1321) 60 (1524)
C
18-1/4 (464) 22-1/4 (565) 28-1/4 (718) 33-1/4 (845) 40-1/4 (1022) 54-1/4 (1378) 62-1/4 (1581)
D
13 (330) 14 (356) 15 (381) 10 (254) 17 (432) 11 (279) 13 (330)
e
19-3/4 (502) 23-3/4 (603) 29-3/4 (756) 34-3/4 (883) 41-3/4 (1060) 55-3/4 (1416) 63-3/4 (1619)
6-1/4 (159) 8-3/4 (222) 15-3/8 (391) 6-1/4 (159) 8-3/4 (222) 19-3/8 (883) 6-1/4 (159) 8-3/4 (222) 25-3/8 (645) 7-1/2 (190) 10 (254) 30-3/8 (772) 7-1/2 (190) 10 (254) 37-3/8 (949) 7-1/2 (190) 10 (254) 51-3/8 (1305) 7-1/2 (190) 10 (254) 59-3/8 (1508)
NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components.
1. 2. 3. 4. 5. 6. 7.
RH shown, LH opposite. Optional drip lip not required with optional extended drain pan. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drip lip recommended. Threaded fittings must be field tightened and leak tested. Control box size and position may vary (consult factory).
Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
15
Horizontal Series
PHySICAL dATA, Contd.
1" (25) FILTER RETURN AIR 1" (25) RETURN DUCT COLLAR FILTER RETAINER CLIP FILTER REMOVAL
7/8" (22) O.D. CONDENSATION DRAIN STRIP HEATER HIGH LIMIT 1-1/2 (38) 1-1/8 (29) 2-1/4 (57) C FRONT MTG. HOLES B A A'
3 (76)
TOP VIEW
1" (25) SUPPLY 7/8 DUCT (22) COLLAR SUPPLY F AIR
3/4 (19)
3/4 (19) RESILIENT MOUNTING GROMMET W/ 3/8" (10) DIA. HOLES (TYP. OF 4)
3/4 (19)
CHILLED/HOT WATER SUPPLY & RETURN CONNECTIONS OPTIONAL DRIP LIP SHIPPED LOOSE (NOTE 5)
10-1/2 (267)
16 (406)
FRONT VIEW
Unit Model
CPY02 CPY03 CPY04 CPY06 CPY08 CPY10 CPY12
Quantity/Unit
A
31-1/4 (794) 36-1/4 (921) 43-1/4 (1099) 43-1/4 (1099) 57-1/4 (1454) 65-1/4 (1657) 75-1/4 (1911)
B
16 (406) 20 (508) 26 (660) 31 (787) 38 (965) 52 (1321) 60 (1524)
C
18-1/4 (464) 22-1/4 (565) 28-1/4 (718) 33-1/4 (845) 40-1/4 (1022) 54-1/4 (1378) 62-1/4 (1581)
D
13 (330) 14 (356) 15 (381) 13 (330) 17 (432) 11 (279) 13 (330)
e
19-3/4 (502) 23-3/4 (603) 29-3/4 (756) 34-3/4 (883) 41-3/4 (1060) 55-3/4 (1416) 63-3/4 (1619)
6-1/4 (159) 8-3/4 (222) 15-3/8 (391) 6-1/4 (159) 8-3/4 (222) 19-3/8 (883) 6-1/4 (159) 8-3/4 (222) 25-3/8 (645) 7-1/2 (190) 10 (254) 30-3/8 (772) 7-1/2 (190) 10 (254) 37-3/8 (949) 7-1/2 (190) 10 (254) 51-3/8 (1305) 7-1/2 (190) 10 (254) 59-3/8 (1508)
NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components.
1. 2. 3. 4. 5. 6. 7.
RH shown, LH opposite. Optional drip lip not required with optional extended drain pan. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drip lip recommended. Threaded fittings must be field tightened and leak tested. Control box size and position may vary (consult factory).
Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.
16
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
PHySICAL dATA, Contd.
OPTIONAL "L" SHAPE DRIP LIP, SHIPPED LOOSE (NOTE 5) CHILLED/HOT WATER SUPPLY & RETURN CONNECTION RESILIENT MOUNTING GROMMETS WITH 3/8"(10) DIA. HOLE (TYP. OF 4) 7/8"(22) KNOCKOUT 1 (25) 1-1/2 (38) 1 (25) 6-1/8 (156)
26 (660)
20-3/4 (527)
1 (25)
TOP VIEW
6-1/8 (156) 1-1/2 (38) 12(305) 11-1/4 MIN. (286) 14(356) MAX. B
SUPPLY AIR
1"(25) SUPPLY DUCT COLLAR HINGED BOTTOM RETURN AIR PANEL 7/8"(22) O.D. CONDENSATE DRAIN CONNECTION
RETURN AIR
FRONT VIEW
Unit Model
CBY02 CBY03 CBY04 CBY06 CBY08 CBY10 CBY12
A
35 (889) 35 (889) 41 (1041) 53 (1346) 53 (1346) 75 (1905) 75 (1905)
F
6 (152) 6 (152) 6 (152) 7 (178) 7 (178) 7 (178) 7 (178)
Unit Weight*
115 120 135 150 155 227 241
NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components.
1. 2. 3. 4. 5. 6.
RH shown, LH opposite. Internal factory valve packages and drains may not align w/cabinet knockouts. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drip lip required for units with valves. Threaded fittings must be field tightened and leak tested.
Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
17
Horizontal Series
PHySICAL dATA, Contd.
OPTIONAL "L" SHAPE DRIP LIP, SHIPPED LOOSE (NOTE 5) 26 (660) 20-3/4 (527) CHILLED/HOT WATER SUPPLY & RETURN CONNECTION RESILIENT MOUNTING GROMMETS WITH 3/8"(19) DIA. HOLE (TYP. OF 4)
TOP VIEW
6-1/8 (156)
A B C 1-1/2 (38)
1-1/4 (32)
1-1/2 (38)
SUPPLY AIR
1"(25) SUPPLY DUCT COLLAR HINGED BOTTOM RETURN AIR PANEL 7/8"(22) O.D. CONDENSATE DRAIN CONNECTION
RETURN AIR
FRONT VIEW
Unit Model
CBY02 CBY03 CBY04 CBY06 CBY08 CBY10 CBY12
A
35 (889) 35 (889) 41 (1041) 53 (1346) 53 (1346) 75 (1905) 75 (1905)
F
6 (152) 6 (152) 6 (152) 7 (178) 7 (178) 7 (178) 7 (178)
Unit Weight*
117 122 137 152 157 229 243
NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components.
1. 2. 3. 4. 5. 6.
RH shown, LH opposite. Optional drip lip not required with optional extended drain pan. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drip lip required for units with valves. Threaded fittings must be field tightened and leak tested.
Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.
18
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
PHySICAL dATA, Contd.
36 (914)
TOP VIEW
A 1-1/2 (38) 11-1/4 12"(305) (286) MIN. 14"(356) MAX. HINGED BOTTOM RETURN AIR PANEL 6" (152) E 1-1/2 (38)
1-1/2(38) OPTIONAL DUCTED REAR RETURN 7/8"(22) O.D. CONDENSATE DRAIN CONNECTION
FRONT VIEW
SUPPLY AIR
A
35 (889) 35 (889) 41 (1041) 53 (1346) 53 (1346) 75 (1905) 75 (1905)
F
6 (152) 6 (152) 6 (152) 7 (178) 7 (178) 7 (178) 7 (178)
Unit Weight*
115 120 135 150 155 227 241
NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components.
1. 2. 3. 4. 5. 6.
RH shown, LH opposite. Internal factory valve packages and drains may not align w/cabinet knockouts. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drip lip required for units with valves. Threaded fittings must be field tightened and leak tested.
Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
19
Horizontal Series
PHySICAL dATA, Contd.
CBY - Horizontal Telescoping Hideaway with Bottom Supply with Electric Heat
1(25) 1-1/2(38) CONTROL BOX STRIP HEATER HIGH LIMIT ELECTRIC STRIP HEATER ELEMENT OPTIONAL "L" SHAPE DRIP LIP, SHIPPED LOOSE (NOTE 5) 36 (914) CHILLED/ HOT WATER SUPPLY & RETURN CONNECTION
30-3/4 (781)
RESILIENT MOUNTING GROMMETS WITH 3/8"(10) DIA. HOLE (TYP. OF 4) 1(25) 7/8"(22) KNOCKOUT 1-1/2(38) KNOCKOUT (TYPICAL)
1-1/2(38) 1(25) A E
TOP VIEW
1-1/2(38) 11-1/4 (286) 12"(305) MIN. 14"(356) MAX. D 1-1/2 (38)
FRONT VIEW
Unit Model
CBY02 CBY03 CBY04 CBY06 CBY08 CBY10 CBY12 NoTeS: *
Unit Weight*
117 122 137 152 157 229 243
1. 2. 3. 4. 5. 6.
Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. RH shown, LH opposite. Internal factory valve packages and drains may not align w/cabinet knockouts. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drawing is not to scale and is provided for Drip lip required for units with valves. reference only. Dimensions may vary with Threaded fittings must be field tightened and leak tested. options ordered. Consult IeC web site for up to date drawings.
20
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
PHySICAL dATA, Contd.
18 (457)
2 (51) 2 (51)
2 (51)
TOP VIEW
C B
RETURN AIR
FRONT VIEW
Unit Model
CXB02 CXB03 CXB04 CXB06 CXB08 CXB10 CXB12 NoTeS: *
Quantity/Unit F G
11 (279) 11 (279) 11 (279) 12 (305) 12 (305) 12 (305) 12 (305)
B
17-1/8 (435) 21-1/2 (546) 25-7/8 (657) 34-5/8 (879) 39 (991) 52-1/8 (1324) 60-7/8 (1546)
C
10-7/16 (265) 10-1/4 (260) 11-1/16 (281) 9-3/16 (233) 10-1/2 (267) 10-15/16 (262) 10-9/16 (268)
e
34 (864) 38 (965) 44 (1118) 49 (1245) 56 (1422) 70 (1778) 78 (1981)
Blower
1 1 2 2 2 4 4
Motor
1 1 1 1 1 2 2
Unit Weight*
98 118 126 168 176 215 245
5-3/4 (146) 5-3/4 (146) 5-3/4 (146) 6-3/4 (171) 6-3/4 (171) 6-3/4 (171) 6-3/4 (171)
1. 2. 3. 4. 5. 6.
Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. RH shown, LH opposite. Internal factory valve packages and drains may not align w/cabinet knockouts. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drawing is not to scale and is provided for Drip lip required for units with valves. reference only. Dimensions may vary with Threaded fittings must be field tightened and leak tested. options ordered. Consult IeC web site for up to date drawings.
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
21
Horizontal Series
PHySICAL dATA, Contd.
2 (51) 2 (51)
2 (51)
TOP VIEW
1-1/2 (38)
AIR VENT
SUPPLY AIR F
APPROX. 2 REF. (51) RESILIENT MOUNTING GROMMETS WITH 3/8" (10) DIA. HOLE (TYP. OF 4) REMOVABLE HINGED R.A./ACCESS PANEL
RETURN AIR
FRONT VIEW
Unit Model
CXB02 CXB03 CXB04 CXB06 CXB08 CXB10 CXB12 NoTeS: *
B
17-1/8 (435) 21-1/2 (546) 25-7/8 (657) 34-5/8 (879) 39 (991) 52-1/8 (1324) 60-7/8 (1546)
C
10-7/16 (265) 10-1/4 (260) 11-1/16 (281) 9-3/16 (233) 10-1/2 (267) 10-15/16 (262) 10-9/16 (268)
e
34 (864) 38 (965) 44 (1118) 49 (1245) 56 (1422) 70 (1778) 78 (1981)
G
11 (279) 11 (279) 11 (279) 12 (305) 12 (305) 12 (305) 12 (305)
Blower
1 1 2 2 2 4 4
Motor
1 1 1 1 1 2 2
Unit Weight*
100 120 128 170 178 217 247
1. 2. 3. 4. 5. 6.
Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. RH shown, LH opposite. Internal factory valve packages and drains may not align w/cabinet knockouts. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drawing is not to scale and is provided for Drip lip required for units with valves. reference only. Dimensions may vary with Threaded fittings must be field tightened and leak tested. options ordered. Consult IeC web site for up to date drawings.
22
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
PHySICAL dATA, Contd.
1 (25)
OPTIONAL 5/8"(16) O.D. TELL-TALE DRAIN CONNECTION, AVAILABLE ON STANDARD AND EXTENDED DRAIN PANS
E MTG. HOLES B A
TOP VIEW
RESILIENT MOUNTING GROMMET W/ 3/8"(10) DIA. HOLES (TYP. OF 4) 3/4 (19) H E 3/4 (19)
AIR VENT
SUPPLY AIR
11-1/4 (286)
FRONT VIEW
16 (406)
Unit Model
BHY04 BHY06 BHY08 BHY10 NoTeS: *
Quantity/Unit G
8-3/4 (222) 10 (254) 10 (254) 10 (254)
A
43-1/4 (1099) 43-1/4 (1099) 57-1/4 (1454) 65-1/4 (1657)
B
26 (660) 31 (787) 38 (965) 52 (1321)
D
15 (381) 10 (254) 17 (432) 11 (279)
e
28-1/4 (718) 33-1/4 (845) 40-1/4 (1022) 54-1/4 (1378)
F
6-1/4 (159) 7-1/2 (191) 7-1/2 (191) 7-1/2 (191)
H
29-3/4 (756) 34-3/4 (883) 41-3/4 (1060) 55-3/4 (1416)
Blower
2 2 2 4
Motor
1 1 1 2
Unit Weight*
62 73 82 128
1. 2. 3. 4. 5. 6.
Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. RH shown, LH opposite. Optional drip lip not required with optional extended drain pan. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drip lip recommended. Threaded fittings must be field tightened and leak tested. Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
23
Horizontal Series
PHySICAL dATA, Contd.
TOP VIEW
RESILIENT MOUNTING GROMMET W/ 3/8"(10) DIA. HOLES (TYP. OF 4) H 3/4 (19) E 3/4 (19) 1"(25) SUPPLY 1 DUCT (25) COLLAR 7/8 (22) 23-3/4 (603) 12-3/8 (314) AIR VENT
SUPPLY AIR
11-1/4 (286)
FRONT VIEW
Unit Model
BHY04 BHY06 BHY08 BHY10 NoTeS: *
16 (406)
Quantity/Unit G
8-3/4 (222) 10 (254) 10 (254) 10 (254)
A
43-1/4 (1099) 43-1/4 (1099) 57-1/4 (1454) 65-1/4 (1657)
B
26 (660) 31 (787) 38 (965) 52 (1321)
D
15 (381) 10 (254) 17 (432) 11 (279)
e
28-1/4 (718) 33-1/4 (845) 40-1/4 (1022) 54-1/4 (1378)
F
6-1/4 (159) 7-1/2 (191) 7-1/2 (191) 7-1/2 (191)
H
29-3/4 (756) 34-3/4 (883) 41-3/4 (1060) 55-3/4 (1416)
Blower
2 2 2 4
Motor
1 1 1 2
Unit Weight*
64 75 84 130
1. 2. 3. 4. 5. 6.
Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. RH shown, LH opposite. Optional drip lip not required with optional extended drain pan. All dimensions are +/- 1/4" (6). Product specifications are subject to change without notice. Drip lip recommended. Threaded fittings must be field tightened and leak tested. Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.
24
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
PHySICAL dATA, Contd.
4 (102) 18 (457)
TOP VIEW
1"(25) SUPPLY DUCT 7/8 (22) COLLAR CHILLED/HOT WATER SUPPLY & RETURN CONNECTIONS SUPPLY AIR G F OPTIONAL DRIP LIP (NOTE 6) SHIPPED LOOSE A 16 (406)
3/4 (19)
3/4 (19)
12-3/4 (324)
FRONT VIEW
Unit Model A A
43-1/4 (1099) 43-1/4 (1099) 57-1/4 (1454) 65-1/4 (1657)
H
30-1/4 (768) 35-1/4 (895) 42-1/4 (1073) 56-1/4 (1429)
BPY04 31-1/4 (794) BPY06 36-1/4 (921) BPY08 43-1/4 (1099) BPY10 57-1/4 (1454) NoTeS: *
6-1/4 (159) 8-3/4 (223) 7-1/2 (190) 10 (254) 7-1/2 (190) 10 (254) 7-1/2 (190) 10 (254)
1. 2. 3. 4. 5. 6. 7. 8.
Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. RH shown, LH opposite. Optional drip lip not required with optional extended drain pan. All dimensions are +/- 1/4" (6). Plenum hanger clip location may vary depending on unit accessories. Product specifications are subject to change without notice. Drip lip recommended. Control box size and position may vary (consult factory). Threaded fittings must be field tightened and leak tested. Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
25
Horizontal Series
PHySICAL dATA, Contd.
OPTIONAL 5/8"(16) O.D. TELL-TALE DRAIN CONNECTION,AVAILABLE ON STANDARD AND EXTENDED DRAIN PANS 1"(25) FILTER OPTIONAL EXTENDED DRAIN PAN (SEE NOTE 2) D' BOTTOM ACCESS PANEL RETURN AIR 1"(25) RETURN DUCT COLLAR FILTER RETAINER FILTER CLIP REMOVAL
1-1/2 (38)
C MTG. HOLES B A
A' 3 (76)
TOP VIEW
3/4 (19)
1/2 (13)
SUPPLY G F AIR 16 (406) REAR ACCESS PANEL RETURN AIR FILTER REMOVAL
1"(25) FILTER
FRONT VIEW
Unit Model
BPY04 BPY06 BPY08 BPY10
A
43-1/4 (1099) 43-1/4 (1099) 57-1/4 (1454) 65-1/4 (1657)
B
26 (660) 34 (787) 38 (965) 52 (1321)
C
28-1/4 (718) 33-1/4 (845) 40-1/4 (1022) 54-1/4 (1378)
D
15 (381) 10 (254) 17 (432) 11 (279)
e
29-3/4 (756) 34-3/4 (883) 41-3/4 (1060) 55-3/4 (1416)
H
30-1/4 (768) 35-1/4 (895) 42-1/4 (1073) 56-1/4 (1429)
Quantity/Unit
6-1/4 (159) 8-3/4 (223) 7-1/2 (190) 10 (254) 7-1/2 (190) 10 (254) 7-1/2 (190) 10 (254)
NoTeS: *
1. 2. 3. 4. 5. 6. 7. 8.
Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. RH shown, LH opposite. Optional drip lip not required with optional extended drain pan. All dimensions are +/- 1/4" (6). Plenum hanger clip location may vary depending on unit accessories. Product specifications are subject to change without notice. Drip lip recommended. Control box size and position may vary (consult factory). Threaded fittings must be field tightened and leak tested. Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for up to date drawings.
26
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
STANdArd FEATurES & OPTIONS
Factory Installed option
X (Rear) X X X X X X X X X X X X X X X X X X X (CXB X (CXB) X X X X X X
Standard
X X (Bottom) X X X X X X X X X X X X
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
27
Horizontal Series
STANdArd FEATurES & OPTIONS, Contd.
As detailed in the table on page 29, we offer a control for most of the customer needs. Additional controls and devices are available to meet even the most demanding operating logic.
Service Switches
We offer concealed service switches for use by maintenance and service personnel to shut off the power while working on the unit.
Fusing
We offer incoming power fusing for all units as well as blower motor and control sub-fusing for units that use electric heat. The blower motor and control sub-fusing (single power source wiring) is required when single source power with electric heat is specified.
Control Packages
28
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
STANdArd FEATurES & OPTIONS, Contd.
Changeover Type None None None Manual Automatic Manual Automatic Manual Automatic Manual Automatic
Heat/Cool
1. Fan switch only; no thermostat. Thermostat Features All listed controls include fan switching. 24 V, 115 V, 208 V, 240 V, 277 V Remote Wall Mounted Manual Fan Switch Operation Auto Fan Speed Control Continuous 3-Speed Fan Cycling Fan O.A. Damper Signal Remote Temperature Sensor Adjustable Operating Range Touch Pad/Digital Display Local Temperature Set-Back Water Temperature Purge Cycle Pipe Sensor Wall Series 4039 N/A N/A N/A N/A N/A N/A N/A N/A Control Type1 Vertical and Horizontal Wall Series 155 N/A N/A Opt Kit N/A N/A N/A N/A 24 V Digital Series 24 V only Opt
NoTeS: 1. Control packages with valve cycle control are continuous fan operation only.
2. All wall-mount control packages are shipped loose for field installation. (Boxes, tile rings, plaster rings, etc. are not provided.) 3. Aquastats are included in control packages, as required.
Control Options
24 V control packages Unit-mounted fan switches (Special Quote) Single power source wiring (motor/control fusing) Incoming power fusing Service switches
Minimum room temperature thermostats (Special Quote) Low voltage remote shutdown relays (Special Quote) Fan and valve cycle applications (Special Quote) Thermostats available with large letter print for handicap applications (Special Quote) DX coil applications
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
29
Horizontal Series
STANdArd FEATurES & OPTIONS, Contd.
unit supply air opening dimensions. 2. Field-furnished duct transitions may be required.
unit return air opening dimensions. 2. Field-furnished duct transitions may be required.
optional Double Deflection, Aluminum-finish Supply Grille (optional special ship separate for models CHY, CPY, CBY, BHY, and BPY. Consult factory for details.)
optional Hinged, Bar-type, Aluminum-finish Return Grille with Throwaway Filter (optional special ship separate for models CHY, CPY, CBY, BHY, and BPY. Consult factory for details.)
30
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
STANdArd FEATurES & OPTIONS, Contd.
Nominal one-Inch Filter Size - Inches (Millimeters) Unit Size 04 06 08 10 BHY (Note 1) 10" x 32" (254 x 813) 10" x 42" (254 x 1067) 10" x 42" (254 x 1067) 10" x 54" (254 x 1372) BPY Bottom Return with Heat 16-3/4" x 28" (425 x 711) 16-3/4" x 33" (425 x 838) 16-3/4" x 40" (425 x 1016) 16-3/4" x 54" (425 x 1372) BPY Bottom Return without Heat 12-3/4" x 28" (324 x 711) 12-3/4" x 33" (324 x 838) 12-3/4" x 40" (324 x 1016) 12-3/4" x 54" (324 x 1372) BPY Rear Return with Heat 12-3/4" x 28" (324 x 711) 12-3/4" x 33" (324 x 838) 12-3/4" x 40" (324 x 1016) 12-3/4" x 54" (324 x 1372) BPY Bottom Return without Heat 12-3/4" x 28" (324 x 711) 12-3/4" x 33" (324 x 838) 12-3/4" x 40" (324 x 1016) 12-3/4" x 54" (324 x 1372)
NoTeS: 1. Filter sizes for the CH and BH models are recommended filter sizes only. No filter is factory provided with these models.
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
31
Horizontal Series
PIPING PACKAGES (TyPICAL)
Ball Valve
(Ships Separate)
pressure, pressure drop limitations and flow rate should be checked prior to selecting specific components or the valve package size. 2. The supply and return piping connections of the factory-provided valve package are either swaged for field brazing (standard) or union fitted (optional) for connection to the coil. 3. Consult IECs Valve Packages and Piping Components manual or your local representative for detailed piping and valve application information. Factoryprovided valve packages are assembled, brazed, wired electrically and dry-fit to the coil connections before shipping. Field brazing to the coil completes the installation. Some applications dictate shipping isolation valves loose.
Swage
Ball Valve
32
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
MECHANICAL SPECIFICATIONS GENERAL DESCRIPTION HORIZONTAL FAN COIL UNITS
CHY Horizontal Hideaway CBY Horizontal Telescoping Hideaway CPY Horizontal Hideaway with Plenum CXB Horizontal Cabinet BHY Horizontal Hi-Static Hideaway BPY Horizontal Hi-Static Hideaway with Plenum
B. CHY, BHY Horizontal Hideaway Units: 1. 2. Cabinet shall be made of heavy gauge galvanized steel. The interior surfaces shall be lined with 1/2" thick standard fiberglass (1/2" thick Premium IAQ fiberglass, 1/2" foil face, or 1/4" closed cell) insulation. Units shall be supplied with a ducted collar for supply duct connection. Units shall have a galvanized (or stainless steel) drain pan extending the entire width of the coil (with second drain connection). Galvanized drain pans shall be internally coated with 2-part closed cell foam insulation.
PART 1
1.1 SUMMARY This section includes fan coil units and accessories. 1.2 SYSTEM DESCRIPTION Horizontal Fan Coil Units, 2-pipe, 4-pipe, or 2-pipe with electric heat, concealed or exposed cabinets that are horizontally mounted. 1.3 QUALITY ASSURANCE Coils shall be tested in accordance with AHRI Standard 440-2008. Each coil shall be factory tested for leakage at 300 psig air pressure with coil submerged in water. Insulation and adhesive shall meet NFPA-90A requirements for flame spread and smoke generation. Base or standard units shall be ETL certified. 1.4 DELIVERY, STORAGE AND HANDLING Unit shall be handled and stored in accordance with the manufacturers instructions. 4. 3.
5.
C. CPY, BPY Horizontal Hideaway with Plenum Units: 1. 2. Units shall be constructed of heavy gauge galvanized steel. The interior surfaces shall be lined with 1/2" thick standard fiberglass (1/2" thick Premium IAQ fiberglass, 1/2" foil face, or 1/4" closed cell) insulation. A heavy gauge plenum shall enclose the blower/motor assembly with bottom or rear return. Units shall be supplied with a ducted collar for supply duct connection. Units shall have a galvanized (or stainless steel) drain pan extending the entire width of the coil (with second drain connection). Galvanized drain pans shall be internally coated with a 2-part closed cell foam insulation.
PART 2 PRODUCTS
2.1 MANUFACTURER A. Basis of design shall be fan coils by International Environment Corporation. 2.2 CONFIGURATION A. General: Factory assembled horizontal fan coil units complete with fan, motor, drain pan, and all required wiring, piping and controls.
3.
4. 5.
6.
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
33
Horizontal Series
MECHANICAL SPECIFICATIONS, Contd.
7. Units shall have non-woven synthetic throwaway (permanent or pleated) filters. 3. IAQ fiberglass, 1/2" foil face, or 1/4" closed cell) insulation. Unit shall have an adjustable height, hinged return air ceiling panel with non-woven synthetic throwaway, (permanent, or pleated) filter. Panel shall be painted with an Arctic White powder-coat finish. Units shall have a galvanized (or stainless steel) drain pan extending the entire width of the coil (with second drain connection). Galvanized drain pans shall be externally coated with a 2-part closed cell foam insulation.
4. D. CXB Horizontal Cabinet Units: 1. 2. Units shall be constructed of heavy gauge galvanized steel. The interior surfaces shall be lined with 1/2" thick standard fiberglass (1/2" thick Premium IAQ fiberglass, 1/2" foil face, or 1/4" closed cell) insulation. Cabinet shall be painted with an Arctic White powder-coat finish. The unit shall have a stamped (double deflection, aluminum finish or steel construction factory installed and painted to match cabinet) discharge grille. The unit shall have removable bottom access panel with stamped return air grille, filter rack, and non-woven synthetic throwaway (permanent or pleated) filter or optional ducted rear return cabinet with a solid bottom access panel. Panel shall be fastened with tamper proof quarter-turn fasteners. Units shall have a galvanized (or stainless steel) drain pan extending the entire width of the coil (with second drain connection). Galvanized drain pans shall be internally coated with a 2-part closed cell foam insulation. 5.
6.
3. 4.
2.3 CERTIFICATION A. Safety: Units shall be listed by Electronics Testing Laboratories, Inc. with the ETL listing indicating the units comply with the minimum requirements of the U.S. and Canadian national product safety standard, UL 1995/CSA C22.2 No. 236. B. Capacities: Coil capacities are tested in accordance with AHRI Standard 440-2008. 2.3.1 MATERIALS A. Coils: All coils shall have 1/2" copper tubes, manual (or automatic) air vents, and aluminum fins, 10 fins per inch spacing. Coil fins shall be mechanically bonded to copper tubes. 0.500" O.D. copper tubes must comply with ASTM B-75. Fin thickness shall be 0.0045" and tube thickness shall be 0.016". All coils shall be leak tested with air at 300 psig under water. 1. For installation in a 2-pipe system, unit shall be equipped with: a. 3-row (or 4-row) coil as shown on equipment drawings b. 2 ball valves c. 1 motorized control valve
5.
6. 7.
8.
E. CBY Horizontal Telescoping Hideaway Units: 1. 2. Units shall be constructed of heavy gauge galvanized steel. The interior surfaces shall be lined with 1/2" thick standard fiberglass (1/2" thick Premium
34
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
Horizontal Series
MECHANICAL SPECIFICATIONS, Contd.
2. For installation in a 4-pipe system, unit shall be equipped with: a. 3/1, 3/2 or 4/1 row-split coil, as shown on equipment drawings b. 4 ball valves c. 2 motorized control valves B. Fans: 1. 2. 3. 4. Fans shall be direct-drive, double-width fan wheels with forward-curved blades. Blower wheels shall be statically and dynamically balanced. Scrolls and fan wheels shall be constructed of galvanized steel. Shall be easily removable. 2. A 4-pipe system shall be capable of providing heating and cooling on demand.
G. Electrical Requirements: 1. Standard unit shall operate on 115 V (208 V, 230 V or 277 V), single phase, 60 Hz electrical power, and all exposed wiring shall be in flexible conduit.
H. Option and Accessories: 1. Unit shall be equipped with nichrome wire strip electric heaters for total or auxiliary electric heat as specified on the equipment schedule. a. Heaters shall be protected by an automatic reset safety cutout switch and a fusible link. b. Heater capacity shall be as specified on the equipment schedule. c. Heaters shall be single phase, 120 V (208 V, 240 V or 277 V) volts as specified on the equipment schedule. d. For total electric heat, unit controls shall include a sequenced heating and cooling thermostat in lieu of the heating/cooling thermostat and automatic changeover device. e. For auxiliary electric heat, unit controls shall include an aquastat to verify system mode. f. A junction box and fuse shall be factory furnished and installed to protect the motor and control circuit when electric heaters are installed. 2. 3. 4. 5. Service switch shall be factory installed. Units shall be equipped with 24 V controls. Units shall be equipped with high level condensate switch. A hinged, bar type aluminum return air grille with filter holder shall be furnished for field installation. Discharge air grille with double deflection, aluminum construction shall be furnished for field installation as shown on equipment schedule. Aluminum grilles shall have a natural anodized finish.
C. Fan Speed and Temperature Control: 3 (high, medium, low) speed control, (off, on, auto), (wall or unit) (auto or manual) thermostat. D. Motors: 1. Motors shall be 3-speed, single phase, 60 Hz permanent split capacitor type for 115 V (208 V, 230 V, or 277 V) permanently lubricated, with sleeve bearings. Motors shall be connected with quick connect electrical plugs. Motors shall have thermal overload protection with automatic reset.
2. 3.
E. Controls and Safeties: 1. Controls: Unit shall be furnished with a 3-speed, 4-position fan switch on a wall plate for field installation. 2. Safeties: Unit fan motor shall be equipped with integral motor protection. F. Operating Characteristics: 1. A 2-pipe system shall be capable of providing heating or cooling as determined by the operating mode of the central water supply system. 6.
International Environmental Corporation Horizontal Series Fan Coil Technical Catalog www.iec-okc.com
35
The USGBC Member logo is a trademark owned by the U.S. Green Building Council and is used by permission. The logo signifies only that IEC is a USGBC member. USGBC does not review, certify, or endorse the products or services offered by its members.
IEC is dedicated to the environment and for its part, IEC has elected to use recycled materials whenever possible for printed sales materials.
IEC Catalog Part #: I100-90002102 CA-020 Revision 3 2010 International Environmental Corporation (IEC) IEC is a subsidiary of LSB Industries, Inc. NYSE symbol LXU; www.lsb-okc.com