You are on page 1of 5

Alternators:

LSA 52,2 XL80 Ratings

50 Hz

1500 rpm

2000 kVA

6600 V

4 poles

PARTNER_LSA 52.2 XL80 4P 50Hz 6600V_en_1-2011

kVA / kWe - Cos = 0,8


PR* / 40 C 150 K 6300 V - 6600 V 2120 1696

3 phase
PR* / 27 C 163 K 6300 V - 6600 V 2200 1760

Duty / Ambient Temperature Rise Tension (*) kVA kWe (*) Y connection * PR= Peak rating

Continuous duty (BR) / 40 C Class.H/125 K Class.F/105 K 6300 V - 6600 V 6300 V - 6600 V 1824 2000 1600 1459

Reactances (%) - class H / 6600 V - 2000 kVA


unsaturated saturated 0,530 2,050 1,887 1,230 1,132 0,228 0,194 1,230 1,132 0,126 0,107 0,158 0,134 0,142 0,121 0,092 0,063 0,180

Short-circuit ratio Direct axis synchronous reactance Quadrature axis synchronous reactance Direct axis transient reactance Quadrature axis transient reactance Direct axis subtransient reactance Quadrature axis subtransient reactance Negative sequence reactance Zero sequence reactance Stator leakage reactance Rotor leakage reactance

Kcc Xd Xq X'd X'q X''d X''q X2 X0 Xs or Xl Xr

Time constants ( s )
Open circuit direct axis transient time constant Open circuit quadrature axis transient time constant Short-circuit direct axis transient time constant Short circuit quadrature axis transient time constant Open circuit direct axis subtransient time constant Open circuit quadrature axis subtransient time constant Subtransient direct axis time constant Subtransient quadrature axis time constant Armature time constant T'do T'qo T'd T'q T''do T''qo T''d T''q Ta 1,880 NA 0,209 NA 0,036 0,140 0,020 0,018 0,040

Resistance
Armature resistance X/R ratio Zero sequence resistance Negative sequence resistance Ra X/R R0 R2 1,130 9,478 3,067 2,840

Other data - Class H /6600 V - 2000 kVA


no load excitation current full load excitation current full load excitation voltage Air flow Harmonic rate (**) total harmonic content line to line , at no load or with linear and balanced load. io ( A) ic (A) uc (V) M3/s % 1,7 4,7 50 2,5 NA

Efficiencies ( % )(3 phase - Classe H - 6600 V - 2000 kVA)


COS = 0,8 75% 95,9 COS = 1 75% 96,8

25% 92,9

50% 95,4

100% 95,9

110% 95,9

25% 93,4

50% 96,1

100% 97,0

110%

97,1

Electric Power Generation

Electric Power Generation

Alternators:

LSA 52,2 XL80 Ratings

50 Hz

1500 rpm

2000 kVA

6600 V

4 poles

PARTNER_LSA 52.2 XL80 4P 50Hz 6600V_en_1-2011

Efficiencies P.F. kVAP.F. 0,8 Cos = 0,8 1 / / kWe PF 1 PF 0,8

3 phase

98 97

Efficiency - Rendement en %

96 95 94 93 92 91 90 25%

50%

75%

100%

Load - Charge - % of rated electrical kW

Transient voltage variation : 6600 V - 50 Hz Transient voltage dip curve versus load impact
30%

25%

Voltage dip - (% of rated voltage)

20%

15%

10%

5%

PF = 0
0% 0,0 0,4 0,8 1,2 1,6

PF = 0,8
2,0

Inrush - Appel de charge - % of rated kVA

Transient voltage rise curve versus load rejection


20%

15%

Voltage rise - (% of rated voltage)

10%

5%

PF = 0,8

0% 0,00

0,25

0,50

0,75

1,00

1,25

1,50

kVA shedding at P.F. - % of rated kVA

Electric Power Generation

Electric Power Generation

Alternators:

LSA 52,2 XL80

50 Hz

1500 rpm

2000 kVA

6600 V

4 poles

PARTNER_LSA 52.2 XL80 4P 50Hz 6600V_en_1-2011

Ratings 3 phase short-circuit curves at no loadkVA /rated -speed ( = 0,8 and kWe Cos Y connection ) 3 phase

Isc (Per unit - rms)


14 Heat damage curve Symmetrical phase to neutral short circuit 12 Symmetrical two phase short circuit Symmetrical three phase short circuit short circuit at generator terminals 10

0 0,001

0,01

0,1

10

Time (sec)

100

Capability curve ( PQ diagram )


kWe / rated kVA
0,7 p.f. 0,8 p.f. 0,9 p.f. 0,944 p.f. 1 0,9 0,8 0,6 p.f. 0,7 0,6 0,5 0,4 p.f. 0,4 0,3 p.f. 0,3 0,2 p.f. 0,1 p.f. 0,2 0,1 0 -1 -0,8 -0,6 -0,4 -0,2 0 0,2 0,4 0,6 0,8 1 0,3 p.f. 0,2 p.f. 0,1 p.f. 0,4 p.f. 0,6 p.f. 0,9 p.f. 0,875 p.f. 0,8 p.f. 0,7 p.f.

0,5 p.f.

0,5 p.f.

kVAr / rated kVA

Electric Power Generation

Electric Power Generation

PARTNER_LSA 52.2 XL80 4P 50Hz 6600V_en_1-2011

SPECIALLY ADAPTED FOR GENSET APPLICATIONS


The alternator is designed to be suitable for typical generator set applications,such as: backup, base production, cogeneration, marine applications, rental, telecommunications, etc.

COMPLIANT WITH INTERNATIONAL STANDARDS


The alternator conforms to the main international standars and regulations IEC 60034, NEMA MG 1.22, ISO 8523/3, CSA UL 1446, UL 1004B on request, marine regulations, etc. It can be integrated into a CE marked generator The alternator is designed, manufactured and marketed in an ISO 9001 and ISO 14001 environment.

TOP OF THE RANGE ELECTRICAL PERFORMANCE


- Class H insulation. - Standard 6-wire winding, 2/3 pitch for Low Voltage, and 5/6 pitch for Medium & High Voltage - Other voltages are possible with optional adapted windings. - High efficiency and motor starting capacity.

EXCITATION AND REGULATION SYSTEM SUITED TO THE APPLICATION


The alternator can be supplied with 'AREP+PMI' or PGM excitation system, according to the alternator specification. standard excitation system is AREP with R449 A.V.R.

Excitation system
regulator R 449 D 510 AREP+PMI std Option PMG Option Option C.T. mains // R726 mains // Option included

Regulation options
R731 3 phase sensing Option included Option external Pot. Option Option

voltage regulation accuracy 0,5%

PROTECTION SYSTEM SUITED TO THE ENVIRONMENT


The alternator is IP 23 in standard. - Standard winding protection for clean environments with relative humidity 95%, including indoor marine environments. Options : IP43 - IP44 : filters on air inlet and air outlet , water mist separator Winding protections for Harsh environments and relative humidity greater than 95% Space heaters. Thermal protection for winding.(PT100)

REINFORCED MECHANICAL STRUCTURE USING FINITE ELEMENT MODELLING


-Compact and rigid assembly to better withstand genset or engine vibrations. - Steel frame. - Cast iron flanges and shields. -Twin-bearing and single-bearing versions designed to be suitable for most engines on the market. -Half-key balancing. -Regreasable bearings.

ACCESSIBLE TERMINAL BOX PROPORTIONED FOR OPTIONAL EQUIPMENT


- Easy access to the voltage regulator and to the connections. - Possible incorporation of accessories for parralleling, protection and measurement.

COMMON DATA insulation class winding pitch terminals drip proof altitude overspeed

H 2/3 (n 6S) 6 IP 23 1000 m 2250 min-1

excitation system regulation accuracy (*) sustained short-circuit current Total harmonic (**) TGH / THC waveform : NEMA= TIF - (**) Waveform : C.E.I. = FHT - (**)

AREP+PMI ou PMG

0,5 % 300% (3 IN) : 10S < 3,5% < 50 < 2%

(*) steady state duty. (**) total harmonic content line to line , at no load or full rated linear and balanced load.
Products and materials shown in this catalog may, at any time, be modified in order to follow the latest technological developments, improve the design or change conditions of utilization. Their description cannot, in any case, engage LEROY-SOMER liability. The values indicated are typical values.

Electric Power Generation

Electric Power Generation

PARTNER_LSA 52.2 XL80 4P 50Hz 6600V_en_1-2011

Thermal damage curve


Stator current (per rated current) 3

2,5

1,5

1 10 100 Maximum duration (seconds) 1000 10000

Unbalanced load curve


Negative phase sequence current (per rated current) 3

0 1 10 100 1000 10000 Maximum duration of fault (seconds)

Stator Earth Fault Current


Fault Current (A) 75

50

C
25

C : Extensive damage B : Considerable damage A : Acceptable damage

B A

0 0 1 2 3 4 5 6 7 8 9 10 11 12 Maximum duration of fault (seconds)


Electric Power Generation Electric Power Generation