SEPCOS-SCM Presentation
Due to insulation of rails the potential of the track-earth is floating (in time and location) Stray current appears in case of insulation deterioration (dirt, premature ageing and wear insufficient maintenance) Corrosion of metallic structure in soil and close of tracks happens
A healthy systems presents a specific voltage profile called reference or imprint A deficiency of insulation between the rail and the earth will modify this voltage distribution The track potential can be used to ensure the healthy of the system and determine a modification in behavior of the stray current by comparison with the reference curves
26/08/2011 4
Proposed system is in compliance with BMRCL EP1-CC chapter 18.2.6.6 (taking into account Addendum 1) Proposed system fulfill the request from DDC document chapter 9 (Stray current monitoring) The proposed software will include more functionallity than requested - measurement of the current when the SCD in closed - log file of the SCD closing and taking into account in the analyse
26/08/2011
ST AT IO N ST 1 AT IO N ST 2 AT IO N ST 3 AT IO N ST 4 AT IO N ST 5 AT IO N ST 6 AT IO N ST 7 AT IO N ST 8 AT IO N ST 9 AT IO N ST 10 AT IO N ST 11 AT IO N ST 12 AT IO N ST 13 AT IO N ST 14 AT IO N ST 15 AT IO N 16
26/08/2011
30.00
20.00
U [V]
10.00
0.00
-10.00
Time [s]
SEPCOS-SCM Architecture
Scheron Sepcos- SCM collects the voltages between the return line and the structure earth via the measuring system integrated in the overvoltage device (SCD) along the tracks. The transmission of the measured values from the SCD to the central unit is done via a communication network: Ethernet, TCP/IP, MODBUS TCP, IEC61850, IEC60870-5-104 and DNP3 Existing network can be used as from the RTU The central unit archives, analyses and depicts the potential of the tracks via an HMI interface executable
8
SCADA
RTU
26/08/2011
IEC 60870-5-104
RTU 560
SWITCH
IEC 61850
SEPCOS FEEDER SEPCOS FEEDER SEPCOS FEEDER SEPCOS FEEDER
Display
Display
Display
Display
26/08/2011
10
IEC 60870-5-104
RTU 560
SWITCH
IEC 61850
SCD with Track (Rails) to Earth (MET) voltage measurement
26/08/2011
11
26/08/2011
12
Industrial Computer CPU board Intel Atom Fan-less, HD PCI-Raid Systems SATA 2x250 GB 19 display for table or panel mounting Touchscreen display HMI licence software included IEC60870-5-104 protocol installed (server) Raid Technology: - Dual disk data archive - Data Mirroring
26/08/2011
13
SEPCOS-SCM Central Unit (in OCC ctrl room) Main Technical data
No 1 2 3 description Maximum number of measuring points Communication protocol Frequency of acquisition Data Min. 60 for one system IEC60870-5-104 (for this project) 2 sec Parameterization possible by software: from 2 to 60 min for short-term mode from 1 to 7 days for long-term mode 10 most relevant measurements All points for 16 weeks Mean values saved for 10 years 250 GB (with integrated RAID backup technology) English, French, Spanish
5 6
7 8
26/08/2011
14
SEPCOS-SCM Supervision
Supervision of status of Short Circuiting devices at all stations and giving an alarm if the device has operated.
26/08/2011 15
Possibility to depict the max. and min reference threshold Average values Average values of the absolute Time window adjustable for long (days) and short (hours) analysis Adjustment of calculation step 160 min for short time 17 days for long time
26/08/2011
17
Possibility to depict the max. and min reference threshold Average values Average values of the absolute Time window adjustable for long (days) and short (hours) analysis Adjustment of calculation step 160 min for short time 17 days for long time
26/08/2011
18
26/08/2011
19
U [V]
120.00
100.00
80.00
60.00
40.00
20.00
-20.00
-40.00
-60.00
-80.00
The algorithm can differentiate the abnormal change in operating conditions from the rail-to-earth faults because the effects on the line are different.
26/08/2011 20
80.00
60.00
40.00
20.00
-20.00
-40.00
-60.00
-80.00
Insulation fault
The algorithm can differentiate the abnormal change in operating conditions from the rail-to-earth faults because the effects on the line are different.
26/08/2011 21
SEPCOS-SCM Reference
Stray currents measurement by direct current measuring (SCD): - 1998 Taiwan Taipei Blue & Tucheng Line - 2007 Taiwan Taipei Orange & SX Line - 2008 Singapore CCL - 2000 Iran Tehran TURSC Line 1 HMI interfaces (using same software): - since 2005 Switzerland Basel/Bern/Luzern Tramway - 2010 Germany Leipzig Tramway - since 2005 Belgium Train line - 2011 Venezuela Caracas metro L1 - 2008 Venezuela Barquisimeto trolleybus - 2011 Georgia Train line - 2010 Azerbaijan Baku metro Stray currents measurement by rail-to-earth potential measurement: - since 2007 Iran Tehran Line 3,4 & Isphan metro - 2007 China Beijing L1/L2/L10 - 2009 China Chengdu L1, Xian L1 - 2010 Brazil Sao Paulo Train (CPTM)
26/08/2011 22
SEPCOS-SCM
26/08/2011
23
SEPCOS-SCM
Secheron Offer
As a complete DC system provider for BMRCL (including SCD devices) we have necessary expertise in measurement of Stary current monitoring and fully comply the contractual conditions. We are glad to offer 3 years of warantee to give more confidence including visit of our expert every year.
26/08/2011