You are on page 1of 2

0,6/1kV CABLES

16

LKSM-EMC

Armoured power and control cable


with improved EMC screening
0,6/1kV

9/2011

DESIGN:

STANDARDS:
IEC 60092-353, design

1. Conductor
2
-stranded copper conductor 1,5-10mm 2 IEC 60228, class 2
-stranded copper conductor 16-150mm IEC 60228, class 5
2. Insulation
- XLPE plastic
IEC 60092-351
3. Bedding
- filler tape
4. Screen
- copper tape, coverage 100%
5. Armour
- copper wire braid, coverage > 90%
IEC 60092-350
6. Sheath
- polyolefine plastic, SHF1
IEC 60092-359
- standard colour black, other colours on request

Flameretardant
Fireresistant
Halogenfree
Low
smoke
emission

Application: For fixed installation in most areas and on open deck in ships.
Design to meet requirements for improved EMC screening properties.
Main characteristics
Rated voltage

AC 0,6/1kV (1,2kV)
DC 0,9/1,5kV (if voltage to earth does not exceed 0,9kV)

Maximum conductor
temperature

+ 90 C

Flame-retardant

IEC 60332-1-2 -test for single insulated wire and cable


IEC 60332-3-22 -test for bunched wires and cables,
category A

Halogen-free

IEC 60754 series

Smoke emission

IEC 61034 series

Transfer impedance

IEC 61196-1

(typical value 26dB over 1m/m


at 100MHz [20m/m])

For details see general information section


Minimum recommended installation temperature -15 C
Lowest operation temperature -40 C
Core identification:

See technical information section.


Cable with yellow/green protective earth (PE)
conductor on request

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi

17

Part number

2x1,5
2x2,5
2x4
2x6
2x10
2x16
2x25
2x35
3x1,5
3x2,5
3x4
3x6
3x10
3x16
3x25
3x35
3x50
3x70
3x95
3x120
3x150
4x1,5
4x2,5
4x4
4x6
4x10
4x16
4x25
4x35
4x50
4x70
4x95
4x120
4x150
5x1,5
7x1,5
10x1,5
12x1,5
14x1,5
16x1,5
19x1,5
24x1,5
24x2,5

Crosssection of
armour
mm2
3,6
4,1
4,6
5,1
8,5
11,4
12,4
14,7
3,8
4,3
5,0
5,6
8,9
10,9
14,6
15,1
18,3
22,0
22,9
37,9
39,4
4,3
4,7
5,5
8,5
9,9
12,0
14,8
18,2
19,6
22,6
37,9
39,4
43,7
4,7
5,1
9,9
10,0
10,1
10,7
11,4
13,6
15,3

Nominal
outer
diameter
mm

Approximate
weight
kg/km

Current
Rating A
at +45C

10,0
10,5
12,0
13,0
16,0
18,5
23,0
25,5
10,5
11,5
12,5
14,0
16,5
19,5
24,5
27,0
32,0
36,5
42,0
47,0
53,0
11,0
12,5
13,5
15,5
18,5
22,0
27,0
29,5
35,5
40,0
47,5
52,5
59,0
12,1
13,1
16,8
17,2
18,0
21,4
22,6
23,4
26,3

140
170
240
335
525
715
1030
1325
170
210
280
390
620
825
1230
1575
2190
2950
3805
4875
6035
200
255
335
500
750
1010
1495
1955
2700
3655
4915
6070
7580
240
285
432
473
523
780
890
835
1125

20
26
34
44
61
80
105
130
16
21
28
36
50
66
86
107
137
168
199
232
267
16
21
28
36
50
66
86
107
137
168
199
232
267
13
12
11
10
9
12
11
8
11

Min. bending
radius fixed
installation
mm
60
65
70
80
95
110
140
155
60
70
75
85
100
120
145
160
195
220
250
285
320
65
75
80
95
110
130
160
180
215
240
285
315
355
75
80
100
100
110
115
120
140
155

9/2011

27480
27481
27482
27483
27484
27485
27486
27487
26861
26863
26865
26867
26869
26872
26874
26876
26878
26880
26882
26884
26886
26942
26944
26946
26948
26950
26952
26954
26956
26958
26960
26962
26964
26966
27488
27495
27497
27499
25701
27503
27505
27507
27508

Number of
conductors &
cross-section
n x mm2

0,6/1kV CABLES

LKSM-EMC 0,6/1kV