Levine Lectronics and Lectric E-mail: John@L-3.com GE Multilin / Instrument Transformers, Inc.
1
Agenda
Current Transformers Voltage Transformers Required Information for Specifying CTs & VTs Take Home Rules for CTs & VTs Applications where used
Circuit Isolation Reduce voltage and currents to reasonable working levels. Phasor combinations for summing and measuring power
5
CURRENT TRANSFORMERS
TYPES OF C.T. CONSTRUCTION The most common type of C.T. construction is the DOUGHNUT type. It is constructed of an iron toroid, which forms the core of the transformer, and is wound with secondary turns.
Secondary Winding
Primary Conductor
Iron Core
Polarity
Direction of Primary Current Primary Polarity Marks IEEE IEC
H1 P1 X1 S1
Polarity
X1 S1
IEEE IEC
H1 P1
10
11
Accuracy Class - %
0.30
10%
0.30
Rating Factor
CT Metering Accuracy
Actual secondary current
0.6
1.2
Indicating Instruments
Indicating Instruments
* All accuracy classes defined by IEEE C57.13 or C57.13.6 * Accuracy classes include both ratio & phase angle error
16
Expressed in ohms
Standard values = B0.1, B0.2, B0.5, B0.9, B1.8 E0.04, E0.2
All burdens defined by IEEE C57.13 or C57.13.6 for 60 Hz only
17
Metering
CT CLASSIFICATION for Metering A current transformer for metering purposes may typically have an accuracy of 0.3%. The C.T. must maintain this accuracy for normal load currents, provided the rated burden on the C.T. is not exceeded. It is quite acceptable, and in fact desirable, for the C.T. to saturate when fault current flows. The accuracy for a typical metering C.T. is specified as: 0.3 M 0.9
O.3%
METERING
This metering C.T. has an accuracy of 0.3% when the GE Multilin connected burden does not exceed 0.9 OHMS. Transformers, Inc. Instrument
Burden (Ohms)
(B0.1, B0.2, B0.5, B0.9, B1.8) E0.2, E0.04)
(0.15*, 0.15S^)
* Accuracy class is stated at 100% rated current * At 10% rated current, twice the error is allowed (5% for 0.15 class) ^ Accuracy class is stated at 100% to 5% rated current
20
Accuracy Class - %
0.30
10% 0.30
100%
200%
300%
400%
0.60
1.0
2.0
3.0
4.0
21
Rating Factor
27
Format
10 C 400
Accuracy
Letter
Voltage at 20 times CT
T = Determined by test C = Calculated K = Calculated L = Low internal secondary impedance H = High internal secondary impedance
28
CT 1200:5 C or T100
Terminal Volts = (20 times rated) (Total external burden) 100 Volts = (100 amps) (1.0 )
29
CT 1200:5 C or T200
Terminal volts = (20 times rated) (Total external burden) 200 Volts = (100 amps) (2.0 )
30
Relaying
31
1000:5 CT
IB >4.5 amps IE<0.5amps
1000 Amps
5amps
With 10% error, IB is anywhere from 4.5 to 5.5 amps Most Protection CTs also have a Metering CT accuracy so you could use this value for calculating the error at lower currents
33
CT Burden Calculation
How do we calculate this?
Secondary current Burden of Devices () CT Burden of Leads () Total Burden Z T
X1 X2
Primary Current
34
CT Burden Calculation
Z T = RCT + RL + ZB
ZT = Total burden in ohms (vector summation of resistance and inductance components) RCT = CT secondary resistance in ohms @75 deg C (DCR) RL = Resistance of leads in ohms (Total loop distance) ZB = Device impedance in ohms Assumption: 3 phase CTs are Y connected
35
100:5 C.T. Secondary Winding Resistance (DCR) = .062 ohm Resistance of Cable from C.T. to Relay and back = .1 ohms
.062 .1
.02
If we have a fault of 2,000 amps and the C.T. ratio is 100:5 then the C.T. secondary current is 100 amps. Therefore we will produce a voltage of 100 amps x .182 ohms = 18.2 Volts. To prevent CT saturation, select a CT with a knee point above 18.2 Volts.
37
780-102 is a 1000 to 5 CT, Class C100 1000:5 C.T. Secondary Winding Resistance (DCR) = .32 ohm
If we have a fault of 20,000 amps and the C.T. ratio is 1000:5 then the C.T. secondary current is 100 amps. Therefore we will produce a voltage of 100 amps x .428 ohms = 42.8 Volts. To prevent CT saturation, select a CT with a knee point above 42.8 Volts.
What happens if the fault current is 40,000 amps?
38
Current Ratio
Low ratio and high accuracy are not friends!!
Burden
High burden and High Accuracy are not friends!!
39
CT Saturation
What is CT Saturation?
40
41
CT Accuracy
Remanence Flux
Can occur if current interrupted when core is saturated If DC flows in windings during testing Need a voltage above 60% of knee point to reduce the remanence to less than 10% of saturation flux density.
42
Potential Transformers
44
Definitions
Voltage Transformer (VT)
An instrument transformer used to reflect a primary voltage into a secondary voltage through a magnetic medium. Always connected in parallel with primary conductor across a circuit load. Secondary (measuring) voltage is usually 115 or 120 volts nominally. The secondary voltage level is selected for ease of measurement and safety.
45
46
POTENTIAL TRANSFORMERS
VP
2400/120 = 20/1
Vs
Relay
47
These standard burden designations have no significance at frequencies other than 60 Hz.
51
VT Installation Guidelines
Caution:
Rated voltage: Do not operate above 110% Line to ground rated: Do not connect line to line
IEEE VT Groups
VT Group No. of Bushing Connection Method Neutral Grounding Notes
1
2
2
2
open
Y-Y possible open Y-Y possible
Any
Any
Y-Y-Y
Any
4A
Y-Y
Effectively
4B
Y-Y
Y-Broken Corner
5 1 Y-Y
Noneffectively Effectively
VT Typical Connections
60
CT Application:
Dimensions: Max. Outside: CT Window: Current Ratio:
___Metering
___ Inches ___ mm
___Protection
___B0.1 ___B0.2 ___B0.5 ___B0.9 ___B1.8 ______Other ___2.5 ___5.0 ___10 ___15 ___30 ______Other C______(IEEE) ___60HZ ___1.0 ___VA, ___P___(IEC)
Outer Insulation:
Insulation Class:
___Standard
___Polyester tape
___105 0C (Standard)
Other Special Requirements (dimensional constraints, mounting requirements, etc): ______________________________________________________________________________ ______________________________________________________________________________
62
___50HZ
___W ___X ___M ___Y (Enter 0.3, 0.6, 1.2, or leave blank) ___10VA ___25VA ___50VA ___100VA (Enter 0.2, 0.5, 1.0, or leave blank)
___Z
___ZZ ___200VA
63
___120V ___115V ___110V ___120/3 ___115/3 ___110/3 ___Other _________________ ___1.9 for 30s
___Primary
___Primary
___Secondary
___None
(600 720 V)
___Switchgear Style
64
QUESTIONS?
72
73
74
LV Switchboards LV Panelboards
Typical CT Models
5 Series
19RT
8SHT
75
LV Switchboards LV Panelboards
Typical VT Models
76
L.V. MCCs
Typical CT Models
5 Series
19RT
8SHT
77
3P85
L.V. Switchgear
79
L.V. Switchgear
Current Transformers GE 2000 amp frame Model 560 Metering Model 561 Protection
80
L.V. Switchgear
Current Transformers GE 4000 amp frame Model 562 Metering Model 563 Protection
81
L.V. Switchgear
No more room in the front? We can recommend a different model CT for the rear bus area.
82
L.V. Switchgear
Typical 3 Phase VT Installation
3VTL460 3 Phase VT
83
M.V. Switchgear
Typical Line Up
84
M.V. Switchgear
Current Transformers 778 / 779 680 /780 Series Typical IEEE Metering & Protection
85
M.V. Switchgear
M.V. Switchgear
Model 203 CTs mounted in rear bus compartment
87
M.V. Switchgear
Zero Sequence CT Model 593, 594
88
M.V. Switchgear
Typical VT Rollout Drawer
(2) PTG5s in open delta configuration
Installed in enclosure
89
M.V. Switchgear
Typical CPT Rollout Drawer
CPT 5 & 15 kV 5 to 15 kVA
Installed in enclosure
90
MV MCCs
Lets open a door and see whats inside
91
MV MCCs
92
Generators
93
95
Power Transformers
Slip over current transformer for installation over exterior of outdoor bushing
Power Transformers
Metering applications for indoor instrument transformers on outdoor power transformers
98
Questions?