You are on page 1of 4

Technical data sheet

2008

MV Network Management - Easergy range

Flair 21D - 22D - 23D

Self-powered fault passage indicators

Easergy Flair 21D - 22D - 23D is a line of DIN-format, compact-size, efficient, self-powered fault passage indicators.
n At the leading edge of technology, they are used on directly earthed, resistive neutral underground MV networks (detection of earth faults) and on all networks (detection of overcurrent). n Self-powered, they ensure uninterrupted detection and indication of the passage of fault current. n Compact and in DIN format, they fit naturally into MV cubicles.
n Skilfully designed, they offer a digital
PE41007

ammeter function.

Selection table
Reference No. Flair 21D

Fault current indicator without power supply

Description

Flair 21DT

Flair 22D

Dual-power fault current indicator

59916 Self-powered detector 2-digit display External indicator output Ammeter 59919 Self-powered detector with telecontrol interface 2-digit display External indicator output Relay output External reset input 59918 Self-powered and lithium battery-powered detector 4-digit display Transistor output: external indicator SCADA Ammeter / Peak demand Relay output External reset input Optional zero sequence CT 59917 9 Vdc-48 Vdc external-power detector 4-digit display Transistor output: external indicator SCADA Ammeters / Peak demand Relay output External reset input Optional zero sequence CT

Flair 23D

External-power fault current indicator

Detection of phase-to-phase faults and earth faults

Fault detection

Overcurrent detection

n 4 microswitch-selected detection thresholds. n With Flair 22D and Flair 23D, a threshold of 100 A to 800 A may also be selected, by steps of 100 A, using the keypad on the front of the device. n Fault sensing time: 40 ms.

Earth fault sensing up to 5 A

Principle: the detector checks for current variations (di/dt) on the 3 phases. A 70 s delay is applied for validation of the fault by the upstream protection device. n 7 microswitch-selectable detection thresholds from 20 A to 160 A. n With Flair 22D and Flair 23D, a threshold of 5 A to 160 A may also be selected using the keypad on the front of the device. For thresholds below 20 A, a zero sequence CT must be used.

Detection of earth faults

Inrush

n To avoid unsollicited tripping when loads are energized, a 3 s delay is applied when the network is powered up.

Display of settings and faulty phase

Fault indication
Indication
Indication is activated as soon as a fault is validated. n Fault indication by a red LED on the front of the device. n Faulty phase indication (earth fault) on LCD display. n Remote indication by optional external flashing lamp: o for Flair 21D and Flair 21DT, which have no power supply, the external lamp is equipped with a lithium battery. n Activation of a contact for SCADA except for Flair 21D.

Automatic reset

Reset of indication

n Automatic reset upon return of load current. n Manual reset by button on front of device. n Reset by external input except for Flair 21D. n Reset by timer: o Flair 21D and Flair 21DT: 4-hour timer o Flair 22D and Flair 23D: microswitch-adjustable timer o at the end of the delay, the LEDs turns off, the SCADA contact is de-activated, and faulty phase display is maintained until the current returns.

PE41007

Easy-to-read LCD display

Clear, comprehensive display


Display principle
n The load current is shown on the display. n When a fault is detected, the faulty phase is indicated. n Settings can be scrolled by pressing the button on the Flair 21D. Settings and measurements can be scrolled by pressing the buttons on the Flair 22D and Flair 23D.

PE41007

Short-circuit fault thresholds Earth fault thresholds Validation (no current) Reset upon return of current Reset timer Faulty phase Load current MV network frequency Peak demand current Residual current

Display of settings

Flair 21D
b b b b

Flair 21DT
b b b b

Flair 22D
b b b b b

Flair 23D
b b b b b

Faulty phase and measurements

L1-L2-L3 b

L1-L2-L3 b

L1-L2-L3 b 50/60 Hz b

L1-L2-L3 b 50/60 Hz b b

Current sensors

Description

Accessories
phase current for CT for RM6 cubicle split core phase current CT for cables split core zero sequence CT for cables with lithium battery standard

Reference
CTR2200 MF1 CTRH2200 BVP BVE

UV

59925 59963 59926 59922 59988

Flair 21D
b b

Flair 22D
b b b

Flair 23D
b b b

External indicators

b b b

b No power supply b Overcurrent and earth fault b Ammeter b Load curent > 3 A b Earth fault > 20 A
DE56421 DE56422

b No power supply b Overcurrent and earth fault b Ammeter b Load curent > 3 A b Earth fault > 20 A b SCADA interface
59922

Application example

b Overcurrent and earth fault b Special settings b Peak demand b Earth fault > 20 A b SCADA interface
DE56424

b Overcurrent and earth fault b Special settings b Sensitive earth fault b Earth fault > 20 A b SCADA interface
59959

59922

DE56423

59959

+
Vdc Vcc +

SCADA Reset

SCADA Reset

SCADA Reset

59916 Flair 21D

59919 Flair 21DT

59918 Flair 22D

59917 Flair 23D

L1 L2 L3
3 x 59925 or 3 x 59963 3 x 59925 or 3 x 59963

L1 L2 L3
3 x 59925 or 3 x 59963

L1 L2 L3
2 x 59925 + 59927

L1 L2 L3

Assembly
b Compact case: v DIN format 93 mm x 45 mm v secured, extraction-proof mounting v terminal connections v mounting in all types of MV cubicle: RM6, SM6, CAS, others. b Current sensors: v specific for RM6 bushing v split core CT for mounting on MV cables v split core zero sequence CT for residual current measurement.

PE41007

PE41007

Frequency Neutral

Application
Phase-to-phase faults Earth faults Min. current

Technical data
Flair 21D, 21DT
50 Hz and 60 Hz All earthing systems Impedant - direct 3 kV to 36 kV > 3A RM6 - CSA

Flair 22D

Voltage Load Switchgear

50 Hz and 60 Hz All earthing systems Impedant - direct 3 kV to 36 kV RM6 - RMR - SM6 - CAS 200 A, 400 A, 600 A, 800 A 100 A to 800 A (100 A steps) 2 dip-switches + keypad 40 ms 3s Yes di / dt None, 20, 40, 60, 80, 100, 120, 160 A 20, 40, 80, 120, 140, 160 40 ms 70 s None, 20, 40, 60, 80, 100, 120, 160 A 5 A to 160 A (10 A intervals) 40 ms 70 s 3 A current return (70 s) Yes Yes Factory setting = 4 h 2, 4, 8, 16, 24 h Yes Yes Yes Yes Lithium No Red LED 4-digit LCD Yes Yes (1 A resolution) 5% Yes Peak demand, frequency RM6: 2 or 3 phase CTs Others: 2 or 3 split CTs Diameter: 170 mm Yes

Flair 23D

50 Hz and 60 Hz All earthing systems Impedant - direct 3 kV to 36 kV RM6 - RMR - SM6 - CAS 200 A, 400 A, 600 A, 800 A 100 A to 800 A (100 A steps) 2 dip-switches + keypad 40 ms 3s Yes di / dt None, 20, 40, 60, 80, 100, 120, 160 A 20, 40, 80, 120, 140, 160 40 ms 70 s None, 20, 40, 60, 80, 100, 120, 160 A 5 A to 160 A (10 A intervals) 40 ms 70 s 3 A current return (70 s) Yes Yes Factory setting = 4 h 2, 4, 8, 16, 24 h Yes Yes Yes Yes No 12 Vdc to 48 Vdc Red LED 4-digit LCD Yes Yes (1 A resolution) 5% Yes Peak demand, frequency RM6: 2 or 3 phase CTs Others: 2 or 3 split CTs Diameter: 170 mm Yes
ART.75961 Schneider Electric Industries SAS - All rights reserved

Overcurrent fault Accuracy 5%

Fault detection

Earth fault With three phase CTs Accuracy 10%

Switch-set thresholds Keypad-set thresholds Configuration Sensing time Inrush Confirmation Algorithm Switch-set thresholds Keypad-set thresholds Sensing time Validation Switch-set thresholds Keypad-set thresholds Sensing time Validation Automatic Manual on front of device External contact Delayed (keypad setting) LED indicator External contact External indicator Phase indication On measurement CTs

Phase-to-earth fault With zero sequence CT Accuracy 10%

Reset

200 A, 400 A, 600 A, 800 A No 2 dip-switches 40 ms 3s Yes di / dt None, 20, 40, 60, 80, 100, 120, 160 A No 40 ms 70 s None, 20, 40, 60, 80, 100, 120, 160 A No 40 ms 70 s 3 A current return (70 s) Yes Flair 21DT 4h No Yes Flair 21DT Flair 21DT Yes I load > 3A No No Red LED 2-digit LCD Yes Yes (10 A resolution ) 5% Yes (display only) No RM6: 3 phase CTs Others: 3 split CTs No Yes

Signalling

Self-supply Battery External supply

Power supply

Display

Sensors

Fault Display Faulty phase Charging current Accuracy Setting Others Phase CT Zero sequence CT Test

Miscellaneous
Dielectric Electromagnetic Climatic Mechanical

Characteristics

IEC 60 255-5 IEC 61000-4-4 (level 4) IEC 61000-4-12 Operating temperature: 30C + 70C Storage temperature: 40C + 85C IEC 6068-2-6 IEC 60068-2-29

Insulation: 10 kV Impulse wave: 20 kV Relative humidity: 95% at 40C Salt mist: 200 h Vibration 10 to 500 Hz: 2 g Protection: IP 23

Schneider Electric Industries SAS


89, boulevard Franklin Roosevelt F-92505 Rueil-Malmaison Cedex Tl. : +33 (0)1 41 29 85 00 www.schneider-electric.com www.easergy.com

As standard, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper Publishing : Schneider Electric Industries SAS Production : Schneider Electric Industries SAS Printing : Imprimerie du Pont de Claix/JPF - Made in France 08-2008

ENMED304007EN