Professional Documents
Culture Documents
Document ID: 1MRK 514 014-UEN Issued: February 2011 Revision: Product version: 1.1
Copyright
This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used or disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB AB Substation Automation Products SE-721 59 Vsters Sweden Telephone: +46 (0) 21 32 50 00 Facsimile: +46 (0) 21 14 69 18 http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including that any applicable safety or other operational requirements are complied with. In particular, any risks in applications where a system failure and/ or product failure would create a risk for harm to property or persons (including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying the equipment, and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks. This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive. The IED is designed in accordance with the international standards of the IEC 60255 series.
Safety information
Dangerous voltages can occur on the connectors, even though the auxiliary voltage has been disconnected.
Whenever changes are made in the IED, measures should be taken to avoid inadvertent tripping.
The IED contains components which are sensitive to electrostatic discharge. Unnecessary touching of electronic components must therefore be avoided.
Table of contents
Table of contents
Section 1 Introduction.......................................................................3
This manual........................................................................................3 Intended audience..............................................................................3 Product documentation.......................................................................4 Product documentation set............................................................4 Document revision history.............................................................5 Related documents........................................................................5 Symbols and conventions...................................................................7 Safety indication symbols..............................................................7 Manual conventions.......................................................................8
Section 2
Environmental aspects.....................................................9
Sustainable development...................................................................9 Disposing of the IED...........................................................................9
Section 3
Section 4
Mounting.........................................................................13
Required tools..................................................................................13 Checking environmental conditions and mounting space................13 Mounting the IED..............................................................................13 Flush mounting the IED...............................................................13 Rack mounting the IED................................................................15 Rack mounting a single IED...................................................15 Rack mounting two IEDs........................................................18 Wall mounting the IED.................................................................20 Wall mounting with external display module................................21 Mounting the external display module....................................21 Wall mounting the main unit...................................................23 Arranging ventilation....................................................................24
Section 5
Connecting.....................................................................27
Required tools..................................................................................27
Table of contents
Connecting wires..............................................................................27 Connecting screw-compression type wires.................................27 Connecting ring-lug type wires....................................................28 Connecting protective earthing.........................................................28 Connecting analog signals...............................................................30 Connecting current and voltage inputs .......................................31 Connecting IED with a test switch...............................................32 Connecting power supply.................................................................32 Connecting communication..............................................................34 Connecting external display module.................................................35
Section 6
Checking installation......................................................37
Identifying hardware and software version.......................................37 Checking mounting...........................................................................37 Energizing the IED............................................................................37
Section 7
Section 8
Technical data................................................................41
Case and HMI display variants.........................................................41 Front side of the IED....................................................................41 Rear side of the IED....................................................................42 Dimensions.......................................................................................42 Enclosure class................................................................................43
Section 9
Section 10 Glossary.........................................................................51
Section 1 Introduction
Section 1
Introduction
1.1
This manual
The installation manual contains instructions on how to install the IED. The manual provides procedures for mechanical and electrical installation. The chapters are organized in chronological order in which the IED should be installed.
1.2
Intended audience
This manual addresses the personnel responsible for installing the product hardware. The installation personnel must have basic knowledge of handling electronic equipment.
Section 1 Introduction
1.3
1.3.1
Product documentation
Product documentation set
Decommissioning deinstalling & disposal Planning & purchase
Commissioning
Engineering
Engineering manual Installation manual Commissioning manual Operation manual Service manual Application manual Technical manual Communication protocol manual en07000220.vsd
IEC07000220 V1 EN
Figure 1:
The engineering manual contains instructions on how to engineer the IEDs using the different tools in PCM600. The manual provides instructions on how to set up a PCM600 project and insert IEDs to the project structure. The manual also recommends a sequence for engineering of protection and control functions, LHMI functions as well as communication engineering for IEC 60870-5-103, IEC 61850 and DNP3. The installation manual contains instructions on how to install the IED. The manual provides procedures for mechanical and electrical installation. The chapters are organized in chronological order in which the IED should be installed. The commissioning manual contains instructions on how to commission the IED. The manual can also be used by system engineers and maintenance personnel for assistance during the testing phase. The manual provides procedures for checking of external circuitry and energizing the IED, parameter setting and configuration as
Operation
Installing
Maintenance
Section 1 Introduction
well as verifying settings by secondary injection. The manual describes the process of testing an IED in a substation which is not in service. The chapters are organized in chronological order in which the IED should be commissioned. The operation manual contains instructions on how to operate the IED once it has been commissioned. The manual provides instructions for monitoring, controlling and setting the IED. The manual also describes how to identify disturbances and how to view calculated and measured power grid data to determine the cause of a fault. The service manual contains instructions on how to service and maintain the IED. The manual also provides procedures for de-energizing, de-commissioning and disposal of the IED. The application manual contains application descriptions and setting guidelines sorted per function. The manual can be used to find out when and for what purpose a typical protection function can be used. The manual can also be used when calculating settings. The technical manual contains application and functionality descriptions and lists function blocks, logic diagrams, input and output signals, setting parameters and technical data sorted per function. The manual can be used as a technical reference during the engineering phase, installation and commissioning phase, and during normal service. The communication protocol manual describes a communication protocol supported by the IED. The manual concentrates on vendor-specific implementations. The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. The service manual is not available yet.
1.3.2
1.3.3
Related documents
Documents related to REB650 Application manual Technical manual Commissioning manual Table continues on next page Identity number 1MRK 505 262-UEN 1MRK 505 263-UEN 1MRK 505 264-UEN
Section 1 Introduction
Documents related to REB650 Product Guide, configured Type test certificate
Documents related to REL650 Application manual Technical manual Commissioning manual Product Guide, configured Type test certificate
Identity number 1MRK 506 325-UEN 1MRK 506 326-UEN 1MRK 506 327-UEN 1MRK 506 328-BEN 1MRK 506 328-TEN
Documents related to RET650 Application manual Technical manual Commissioning manual Product Guide, configured Type test certificate
Identity number 1MRK 504 124-UEN 1MRK 504 125-UEN 1MRK 504 126-UEN 1MRK 504 127-BEN 1MRK 504 127-TEN
Documents related to REC650 Application manual Technical manual Commissioning manual Product Guide Type test certificate
Identity number 1MRK 511 246-UEN 1MRK 511 247-UEN 1MRK 511 248-UEN 1MRK 511 249-BEN 1MRK 511 249-TEN
Documents related to REG650 Application manual Technical manual Commissioning manual Product Guide Type test certificate Rotor Earth Fault Protection with Injection Unit RXTTE4 and REG670
Identity number 1MRK 502 033-UEN 1MRK 502 034-UEN 1MRK 502 035-UEN 1MRK 502 036-BEN 1MRK 502 036-TEN 1MRG001910
Documents related to REQ650 Application manual Technical manual Commissioning manual Product Guide Type test certificate
Identity number 1MRK 505 266-UEN 1MRK 505 267-UEN 1MRK 505 268-UEN 1MRK 505 269-BEN 1MRK 505 269-TEN
Section 1 Introduction
650 series manuals Communication protocol manual, DNP3 Communication protocol manual, IEC 61850 Communication protocol manual, IEC 60870-5-103 Point list manual, DNP3 Engineering manual Operation manual Installation manual Identity number 1MRK 511 241-UEN 1MRK 511 242-UEN 1MRK 511 243-UEN 1MRK 511 244-UEN 1MRK 511 245-UEN 1MRK 500 093-UEN 1MRK 514 014-UEN
1.4
1.4.1
The warning icon indicates the presence of a hazard which could result in personal injury.
The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
The information icon alerts the reader of important facts and conditions.
The tip icon indicates advice on, for example, how to design your project or how to use a certain function. Although warning hazards are related to personal injury, it is necessary to understand that under certain operational conditions, operation of damaged equipment may result in degraded process performance leading to personal injury or death. Therefore, comply fully with all warning and caution notices.
Conventions used in IED manuals. A particular convention may not be used in this manual. Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also contains definitions of important terms. Push button navigation in the LHMI menu structure is presented by using the push button icons, for example: and . To navigate between the options, use HMI menu paths are presented in bold, for example: Select Main menu/Settings. LHMI messages are shown in Courier font, for example: . To save the changes in non-volatile memory, select Yes and press Parameter names are shown in italics, for example: The function can be enabled and disabled with the Operation setting. The ^ character in front of an input or output signal name in the function block symbol given for a function, indicates that the user can set an own signal name in PCM600. The * character after an input or output signal name in the function block symbol given for a function, indicates that the signal must be connected to another function block in the application configuration to achieve a valid application configuration.
Section 2
Environmental aspects
2.1
Sustainable development
Sustainability has been taken into account from the beginning of the product design including the pro-environmental manufacturing process, long life time, operation reliability and disposing of the IED. The choice of materials and the suppliers have been made according to the EU RoHS directive (2002/95/EC). This directive limits the use of hazardous substances which are the following:
Table 1:
Substance Lead - Pb Mercury - Hg Cadmium - Cd Hexavalent Chromium Cr (VI) Polybrominated biphenyls - PBB Polybrominated diphenyl ethers - PBDE
Operational reliability and long life time have been assured with extensive testing during the design and manufacturing processes. Moreover, long life time is supported by maintenance and repair services as well as by the availability of spare parts. Design and manufacturing have been done under a certified environmental system. The effectiveness of the environmental system is constantly evaluated by an external auditing body. We follow environmental rules and regulations systematically to evaluate their effect on our products and processes.
2.2
electronic waste. These handlers can sort the material by using dedicated sorting processes and dispose of the product according to the local requirements.
Table 2:
IED Unit
Box Manuals
10
Section 3
3.1
3.2
3.2.1
3.2.2
3.2.3
If the IED has damaged during transportation, make a claim against the transport contractor, and notify the local ABB representative.
11
Section 3 Unpacking, inspecting and storing 3.2.4 Returning an IED damaged in transit
If damage has occurred during transport, appropriate actions must be taken against the latest carrier. Please inform the nearest ABB office or representative. Notify ABB immediately if there are any discrepancies in relation to the delivery documents.
3.3
Storing
If the IED is stored before installation, it must be done in the original transport packaging in a dry and dust free place. Observe the environmental requirements stated in the technical manual.
12
Section 4 Mounting
Section 4
Mounting
4.1
Required tools
Use Torx TX10 and TX15 screwdrivers when attaching the mounting kits to the IED.
4.2
4.3
4.3.1
13
Section 4 Mounting
K A H
B
C
IJ
E F
4
GUID-1D54537B-5CA1-4FDB-8957-AE3B1BFF7933 V1 EN
Figure 2:
A B C D E F H I J K 240 mm 227 mm 272 mm 6 mm 220 mm 265.9 mm 300 mm 254 mm
G 21.55 mm
5. 6.
Place a nut and a washer on each threaded studs. Tighten the nuts.
14
Section 4 Mounting
GUID-F360FEBB-FE45-4305-81C8-3E7A7CF117B1 V1 EN
Figure 3:
A B
C 13 mm
Check the allowed minimum bending radius from the optical cable manufacturer.
4.3.2
4.3.2.1
Section 4 Mounting
2
GUID-3ADB2064-698C-4738-8B46-540D0FD325B1 V1 EN
Figure 4:
1 Screws
3. 4. 5. 6.
Attach the left mounting bracket to the left-hand side of the IED using the required screws. Tighten the screws. Mount the IED with the rack mounting panels to the 19" rack. Tighten the screws.
16
Section 4 Mounting
C
B
1
Figure 6:
A B
2
Rack mounted IED
GUID-C8DC00E4-0416-424B-B1DF-432BE0AD40A6 V1 EN
224 mm + 12 mm with ring-lug connector 1 Plastic plugs 25.5 mm 2 Screws 3 Left mounting bracket 4 Right mounting bracket
Check the allowed minimum bending radius from the optical cable manufacturer.
17
Section 4 Mounting
4.3.2.2 Rack mounting two IEDs
1. 2. 3.
Remove the plastic plugs from the side of the case on both of the two IEDs. Locate the pins on the two middle mounting brackets to the holes on the sides of the two IEDs. Mount the upper and lower mounting brackets to the two IEDs using the screws at the required location. Make sure that the lower venting hole on the IEDs line up with the venting hole in the lower mounting bracket.
4
Figure 7:
6
Mounting IEDs
GUID-36783A5D-1F19-45B1-88E7-D1B18912A451 V1 EN
1 Upper mounting bracket 2 Vent holes 3 Right mounting bracket 4 Lower mounting bracket 5 Screws 6 Left mounting bracket 7 Middle mounting brackets
4. 5.
Tighten the screws. Mount the left and right mounting brackets to both sides of the IED assembly using fixing screws.
18
Section 4 Mounting
6. 7. 8.
Tighten the screws. Mount the IEDs with the rack mounting panels to the 19" rack. Tighten the screws.
E
1
D
A B
GUID-77659F5C-692A-4A14-BE37-623C09FCBF0C V1 EN
Figure 8:
A B
Make sure that the lower venting holes in the IED is not obstructed.
Check the allowed minimum bending radius from the optical cable manufacturer.
19
Drill four screw holes according to the dimensional drawing. Mount the mounting brackets using the required screws. Remove the plastic plugs from the side of the IED. Fit the IED securely between the mounting brackets by using the required screws. Tighten the screws.
A B
D E
1
GUID-E8BD96E7-EF70-4287-BA2E-1ADD385AB9B8 V1 EN
Figure 9:
A B C D E F 270 mm 6.8 mm 268.9 mm 190.5 mm 296 mm
252.5 mm 2 Screw
G 13 mm
It is recommended to connect wires and terminal strips before IED is fitted on mounting brackets.
20
Section 4 Mounting
Check the allowed minimum bending radius from the optical cable manufacturer.
4.3.4
4.3.4.1
21
Section 4 Mounting
GUID-15A9D16B-8000-4D89-AD06-1BF601905B21 V1 EN
Figure 10:
A B C D E F H I J 220 mm M3 265.9 mm 250.9 mm 20 mm 114 mm 38 mm 128 mm 33 mm
G 7.5 mm
2. 3. 4. 5. 6.
Thread the four holes for the M3 screws. Draw the LHMI cable through the hole for cable from IED to LHMI. Connect the cable to the LHMI. Mount the external LHMI display using four M3 screws. Tighten the four M3 screws. When the LHMI is installed on the cabinet door, earth the door with a 16.0 mm2 flat copper cable.
22
Section 4 Mounting
The display module is connected to the main unit of the IED using the RJ-45 cable that is included in the delivery of the IED.
Check the allowed minimum bending radius from the optical cable manufacturer.
4.3.4.2
GUID-3451F22D-1B9E-47A1-A407-9D87B83AD837 V1 EN
Figure 11:
4. 5.
Tighten the screws. Connect a cable to the RJ-45 connection on the front panel of the main unit to the corresponding connection on external LHMI display module.
23
Section 4 Mounting
GUID-5C185EAC-13D0-40BD-8511-58CA53EFF7DE V1 EN
Figure 12:
A B C D E F 25.5 mm 220 mm 13 mm 265.9 mm 258.6 mm 265.9 mm
G 224 mm
Check the allowed minimum bending radius from the optical cable manufacturer.
4.3.5
Arranging ventilation
Ventholes are located at the bottom and on the back plate of the IED. Reserve sufficient space round the IED to ensure adequate ventilation. Reserve at least 1U below and above the unit. Reserve for rack mount approximately 10 cm behind the unit, measured from the surface of the cover. Ensure sufficient space for the wiring and the installation of cable ducts.
24
Section 4 Mounting
25
26
Section 5 Connecting
Section 5
Connecting
5.1
Required tools
Only use a screwdriver and insert bits for slotted (Nr.1 / 3.5mm blade) when handling CT/VT terminals of screw-compression type and slotted 4.5 mm blade when handling CT/VT terminals of ring-lug type.
5.2
Connecting wires
All connections are made on the rear of the case. No soldering is needed.
1. 2. 3.
Connect each signal connector terminal with one 0.5...2.5 mm2 wire or with two 0.5...1.0 mm2 wires. Connect each compression type (X101 and X102) terminal for CTs/VTs with one 0.5...6.0 mm2 wire or with two of maximum 2.5 mm2 wires. Connect terminals on the communication module for IRIG-B with one 0.2 1.5 mm2 wire. Use multi-strand wire in door mounting.
5.2.1
2.
27
Ring-lug type insulated terminal can be used for signal connectors X101 and X102. The maximum outside diameter for the M4 ring-lug type terminals is 9 mm.
5.3
1.
Loosen the nut from the protective earth pin to connect a separate earth protection lead.
28
Section 5 Connecting
GUID-C75F6FD4-485D-464D-B7B0-55FD1AA608E9 V1 EN
Figure 13:
The protective earth pin is located below connector X102 on the 6U half 19 case
29
Section 5 Connecting
Each IED must have its own earth lead connected to the earth circuit connector. 2. 3. 4. 5. Connect the earth lead to the earth bar. Thread the copper cable on the protective earth pin. Tighten the nut on the protective earth pin. Support the earth lead so that it cannot break or weaken. Observe the situations for mechanical, chemical or electrochemical reasons.
5.4
GUID-44E54B97-4E48-46E1-8515-ED3087BACC0A V2 EN
Figure 14:
30
Section 5 Connecting
GUID-56FBFBB8-3388-4473-AF87-B725AFEF57BA V2 EN
Figure 15:
5.4.1
GUID-61D346C6-30D8-468A-8641-654864811C53 V1 EN
Figure 16:
1 VT symbol 2 CT symbol
31
Section 5 Connecting
Table 3:
Terminal X101-1, 2 X101-3, 4 X101-5, 6 X101-7, 8 X101-9, 10 X102-1, 2 X102-3, 4 X102-5, 6 X102-7, 8 X102-9, 10
See the connection diagrams for information on the analog input module variant included in a particular configured IED. The primary and secondary rated values of the primary VT's and CT's are set for the analog inputs of the IED.
5.4.2
5.5
32
Section 5 Connecting
GUID-0D1D8DEF-CF06-41FD-9417-103AB94C173D V1 EN
Figure 17:
Connect the terminals on the auxiliary voltage connector correctly. Different power supplies use different terminals.
33
Section 5 Connecting
No damage will occur when the plug is inserted 180 degrees turned.
1 48-125 VDC 1
3
open
Correct
3
open
GUID-C2321B6B-3157-4F0A-AD25-ACE8E71C4462 V2 EN
Figure 18:
5.6
Connecting communication
Before connecting communication, check that the HW module has the correct communication interfaces. The communication module is located on the left side of the IED when viewing the case from the rear. The fiber optical cables are very sensitive to handling. Do not bend too sharply. The minimum curvature radius is 250 mm for the glass fiber cables. If cable straps are used to fix the cables, apply with loose fit. Always hold the connector, never the cable, when connecting or disconnecting optical fibers. Do not twist, pull or bend the fiber. Invisible damage may increase fiber attenuation thus making communication impossible. Strictly follow the instructions from the manufacturer for each type of optical cables/connectors. See the technical manual for product-specific communication interfaces.
34
Section 5 Connecting
5.7
35
36
Section 6
Checking installation
6.1
6.2
Checking mounting
Check that all fixing screws are tight and that all cables are connected.
6.3
If the IED detects a diagnostic error during start-up, the green Ready LED flashes and the internal fault code is displayed on the LCD.
37
38
Section 7
7.1
Product lifecycle
In the product lifecycle, there is going to be a time to upgrade the IED to a next generation unit. At some point of the product lifecycle, the IED will be upgraded to a next generation unit. When selecting the original product, already consider the upgrading and extension possibilities that the specific product offers for its whole lifecycle.
7.2
The Product identifiers submenu contains product related information including product type, serial number, order number, production date and SW version. The Installed HW submenu contains information about the HW modules.
7.3
39
7.4
7.5
40
Section 8
Technical data
8.1
8.1.1
GUID-54166097-76E0-42A6-ADA7-D8580D1B2B1D V1 EN
Figure 19:
41
1 9 10 15 1 13
2 5 6 7 11 13 17 18 3 4 8 10 14 15 16
12
14
16
2 5 6 7 11 12 17
18
1 9 12 1 7 11
4 5 6 7 8 10 11 13 15 17 18 3 4 5 6 8 9 10 12
14
16
13
14
15
16
17
18
1 2 15 17 3 4 3 4 8 9 12 13 18 1 6 7 5 6 7 10 14 16 2
11
10
11
12
13
14
15
16
17
18
2 6 7 11 13 17 18 1
10
12
14
15
16
10
11
12
13
14
15
16
17
18
3 6
7 8 9 10
10
GUID-A87FAB18-230C-4DBC-B13E-81DAE22DEA73 V1 EN
10
11
12
13
14
15
16
17
18
X0
X1
1
X4
2 3 4
X9
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
HMI
LAN1
IRIG-B
Rx
Tx
8.1.2
8.2
Dimensions
Figure 20:
42
Table 4:
Description Width Height Depth Weight box Weight LHMI
8.3
Enclosure class
Table 5:
Description Front side Rear side, connection terminals
Table 6:
Description Front and side
43
44
Section 9
9.1
9.1.1
Mounting kits
Flush mounting kit
Mounting frame Screws Nuts and washers Dimensions for screw holes
GUID-87C934B9-C35C-4424-9516-4BFB61146EE5 V1 EN
Figure 21:
45
Table 7:
Items
Mounting kit
Order number 1KHL400228R0001
9.1.2
GUID-21666A58-8EF4-4C05-9D04-F91FBB224EA4 V1 EN
Figure 22:
Table 8:
Items
9.1.3
46
GUID-934DD622-5D8F-47D5-B8FB-354E7DF513A6 V1 EN
Figure 23:
Table 9:
Items
9.1.4
47
GUID-11F37B1B-595B-4287-8FFB-E2A77EA2DA03 V1 EN
Figure 24:
Table 10:
Items
Wall-mounting kit (cabling towards the mounting wall) for one 6U half 19 housing IED
9.1.5
48
GUID-61DD3FD5-CEA6-4B90-9310-7D64BB93AEE2 V1 EN
Figure 25:
9.2
Cables
Table 11:
Items LHMI cable (1m) LHMI cable (2m) LHMI cable (3m) LHMI cable (4m) LHMI cable (5m)
49
50
Section 10 Glossary
Section 10
Glossary
AC ACT A/D converter ADBS AI ANSI AR ASCT ASD AWG BI BOS BR BS CAN CB CCITT
Alternating current Application configuration tool within PCM600 Analog-to-digital converter Amplitude deadband supervision Analog input American National Standards Institute Autoreclosing Auxiliary summation current transformer Adaptive signal detection American Wire Gauge standard Binary input Binary outputs status External bistable relay British Standards Controller Area Network. ISO standard (ISO 11898) for serial communication Circuit breaker Consultative Committee for International Telegraph and Telephony. A United Nations-sponsored standards body within the International Telecommunications Union. Capacitive Coupled Voltage Transformer Protection Current Transformer class as per IEEE/ ANSI Combined megapulses per second Communication Management tool in PCM600 Close-open cycle Way of transmitting G.703 over a balanced line. Involves two twisted pairs making it possible to transmit information in both directions Standard format according to IEC 60255-24 Way of transmitting G.703 over a balanced line. Involves four twisted pairs, two of which are used for transmitting data in both directions and two for transmitting clock signals
51
COMTRADE Contra-directional
Section 10 Glossary
CPU CR CRC CROB CS CT CVT DAR DARPA DBDL DBLL DC DFC DFT DHCP DIP-switch DI DLLB DNP DR DRAM DRH DSP DTT EHV network EIA EMC EMF EMI EnFP EPA ESD FCB
52
Central processor unit Carrier receive Cyclic redundancy check Control relay output block Carrier send Current transformer Capacitive voltage transformer Delayed autoreclosing Defense Advanced Research Projects Agency (The US developer of the TCP/IP protocol etc.) Dead bus dead line Dead bus live line Direct current Data flow control Discrete Fourier transform Dynamic Host Configuration Protocol Small switch mounted on a printed circuit board Digital input Dead line live bus Distributed Network Protocol as per IEEE/ANSI Std. 1379-2000 Disturbance recorder Dynamic random access memory Disturbance report handler Digital signal processor Direct transfer trip scheme Extra high voltage network Electronic Industries Association Electromagnetic compatibility (Electric Motive Force) Electromagnetic interference End fault protection Enhanced performance architecture Electrostatic discharge Flow control bit; Frame count bit
650 series Installation Manual
Section 10 Glossary
Modular 20 channel telecommunication system for speech, data and protection signals Access multiplexer Compact time-division multiplexer for the transmission of up to seven duplex channels of digital data over optical fibers Electrical and functional description for digital lines used by local telephone companies. Can be transported over balanced and unbalanced lines Communication interface module with carrier of GPS receiver module Graphical display editor within PCM600 General interrogation command Gas-insulated switchgear Generic object-oriented substation event Global positioning system High-level data link control, protocol based on the HDLC standard Plastic fiber connector Human-machine interface High speed autoreclosing High-voltage High-voltage direct current Integrating deadband supervision International Electrical Committee IEC Standard, Instrument transformers Part 6: Requirements for protective current transformers for transient performance Substation automation communication standard Institute of Electrical and Electronics Engineers A network technology standard that provides 100 Mbits/s on twisted-pair or optical fiber cable PCI Mezzanine Card (PMC) standard for local bus modules. References the CMC (IEEE P1386, also known as Common Mezzanine Card) standard for the mechanics and the PCI specifications from the PCI SIG (Special Interest Group) for the electrical EMF (Electromotive force). Intelligent electronic device
GCM GDE GI GIS GOOSE GPS HDLC protocol HFBR connector type HMI HSAR HV HVDC IDBS IEC IEC 60044-6
IED
53
Section 10 Glossary
I-GIS Instance
Intelligent gas-insulated switchgear When several occurrences of the same function are available in the IED, they are referred to as instances of that function. One instance of a function is identical to another of the same kind but has a different number in the IED user interfaces. The word "instance" is sometimes defined as an item of information that is representative of a type. In the same way an instance of a function in the IED is representative of a type of function. 1. Internet protocol. The network layer for the TCP/IP protocol suite widely used on Ethernet networks. IP is a connectionless, best-effort packet-switching protocol. It provides packet routing, fragmentation and reassembly through the data link layer. 2. Ingression protection, according to IEC standard Ingression protection, according to IEC standard, level 20 Ingression protection, according to IEC standard, level 40 Ingression protection, according to IEC standard, level 54 Internal failure signal InterRange Instrumentation Group Time code format B, standard 200 International Telecommunications Union Local area network High-voltage software module Liquid crystal display Local detection device Light-emitting diode Miniature circuit breaker Mezzanine carrier module Multifunction vehicle bus. Standardized serial bus originally developed for use in trains. National Control Centre Open-close-open cycle Overcurrent protection On-load tap changer Over-voltage A term used to describe how the relay behaves during a fault condition. For example, a distance relay is overreaching when the impedance presented to it is smaller than the
650 series Installation Manual
IP
IP 20 IP 40 IP 54 IRF IRIG-B: ITU LAN LIB 520 LCD LDD LED MCB MCM MVB NCC OCO cycle OCP OLTC OV Overreach
54
Section 10 Glossary
apparent impedance to the fault applied to the balance point, that is, the set reach. The relay sees the fault but perhaps it should not have seen it. PCI PCM PCM600 PC-MIP PISA PMC POR POTT Process bus PSM PST PT ratio PUTT RASC RCA RFPP RFPE RISC RMS value RS422 RS485 RTC RTU SA SBO SC SCS SCADA SCT SDU Peripheral component interconnect, a local data bus Pulse code modulation Protection and control IED manager Mezzanine card standard Process interface for sensors & actuators PCI Mezzanine card Permissive overreach Permissive overreach transfer trip Bus or LAN used at the process level, that is, in near proximity to the measured and/or controlled components Power supply module Parameter setting tool within PCM600 Potential transformer or voltage transformer ratio Permissive underreach transfer trip Synchrocheck relay, COMBIFLEX Relay characteristic angle Resistance for phase-to-phase faults Resistance for phase-to-earth faults Reduced instruction set computer Root mean square value A balanced serial interface for the transmission of digital data in point-to-point connections Serial link according to EIA standard RS485 Real-time clock Remote terminal unit Substation Automation Select-before-operate Switch or push button to close Station control system Supervision, control and data acquisition System configuration tool according to standard IEC 61850 Service data unit
55
Section 10 Glossary
Subminiature version A, A threaded connector with constant impedance. Signal matrix tool within PCM600 Station monitoring system Simple network time protocol is used to synchronize computer clocks on local area networks. This reduces the requirement to have accurate hardware clocks in every embedded system in a network. Each embedded node can instead synchronize with a remote clock, providing the required accuracy. Switch for CB ready condition Switch or push button to trip Neutral point of transformer or generator Static VAr compensation Trip coil Trip circuit supervision Transmission control protocol. The most common transport layer protocol used on Ethernet and the Internet. Transmission control protocol over Internet Protocol. The de facto standard Ethernet protocols incorporated into 4.2BSD Unix. TCP/IP was developed by DARPA for Internet working and encompasses both network layer and transport layer protocols. While TCP and IP specify two protocols at specific protocol layers, TCP/IP is often used to refer to the entire US Department of Defense protocol suite based upon these, including Telnet, FTP, UDP and RDP. Threaded Neill-Concelman, a threaded constant impedance version of a BNC connector Current transformer class according to IEC User management tool A term used to describe how the relay behaves during a fault condition. For example, a distance relay is underreaching when the impedance presented to it is greater than the apparent impedance to the fault applied to the balance point, that is, the set reach. The relay does not see the fault but perhaps it should have seen it. See also Overreach. Process interface components that deliver measured voltage and current values Coordinated Universal Time. A coordinated time scale, maintained by the Bureau International des Poids et Mesures (BIPM), which forms the basis of a coordinated
650 series Installation Manual
U/I-PISA UTC
56
Section 10 Glossary
dissemination of standard frequencies and time signals. UTC is derived from International Atomic Time (TAI) by the addition of a whole number of "leap seconds" to synchronize it with Universal Time 1 (UT1), thus allowing for the eccentricity of the Earth's orbit, the rotational axis tilt (23.5 degrees), but still showing the Earth's irregular rotation, on which UT1 is based. The Coordinated Universal Time is expressed using a 24-hour clock, and uses the Gregorian calendar. It is used for aeroplane and ship navigation, where it is also sometimes known by the military name, "Zulu time." "Zulu" in the phonetic alphabet stands for "Z", which stands for longitude zero. UV WEI VT X.21 3IO 3UO Undervoltage Weak end infeed logic Voltage transformer A digital signalling interface primarily used for telecom equipment Three times zero-sequence current. Often referred to as the residual or the earth-fault current Three times the zero sequence voltage. Often referred to as the residual voltage or the neutral point voltage
57
58
59
Contact us
ABB AB Substation Automation Products SE-721 59 Vsters, Sweden Phone +46 (0) 21 32 50 00 Fax +46 (0) 21 14 69 18 www.abb.com/substationautomation