Weekday / weekend room temperature controller


Heating applications

REV17..

Use

Mains-independent, battery-operated room temperature controller featuring user-friendly operation, easy-to-read display and large numbers Self-learning two-position controller with PID response (patented) Operating mode selection: - 7-day (weekday / weekend) automatic mode. with max. 3 heating phases - Continuous comfort mode - Continuous energy saving mode - Frost protection - Exception day (24 hour operation) with max. 3 heating phases A separate temperature setpoint can be entered in automatic mode and for the exception day for each heating phase To control a heating zone

Room temperature control in: Single-family and vacation homes Apartments and offices Individual rooms and professional office facilities Commercially used spaces Control for the following equipment: Magnetic valves of an instantaneous water heater Magnetic valves of an atmospheric gas burner Forced draught gas and oil burners Electrothermal actuators Circulating pumps in heating systems Electric direct heating Fans of electric storage heaters Zone valves (normally open or normally closed)

CE1N2203en 24.04.2008

Building Technologies

Function Type summary Room temperature controller with 7-day (weekday/weekend) time switch REV17 Room temperature controller with 7-day (weekday/weekend) time switch and receiver for time signal from Frankfurt, Germany (DCF77) REV17DC Ordering Please indicate the type number as per the "Type summary" when ordering. Delivery The controller is supplied with batteries. Mechanical design Plastic casing with an easy-to-read display and large numbers, easily accessible operating elements, and removable base. The housing contains the controller's electronics, DIP switches, and the relay with potential-free changeover contact. The easily accessible battery compartment allows for easy exchange of two 1.5 V alkaline batteries, type AA. The base with terminal block provides lots of space to connect the wires. Display and operating elements PID control with self-learning or selectable switching cycle time 2-point control 7-day time switch Remote control Preselected 24-hour operating modes Override function Holiday mode Party mode Frost protection mode Information level to check settings Reset function Sensor calibration Minimum limitation of setpoint Periodic pump run Protection against valve seizure Synchronization to radio time signal from Frankfurt, Germany (REV17DC)

2 / 13 Siemens Building Technologies Room temperature controller REV17.. CE1N2203en 24.04.2008

Display
Change battery Alarm Heating mode Date (day - month - year) Time of day Room temperature (measured) Clear text display line (max. 18 spaces) Weekday (max. 3 spaces)
0 4 8 12 16 20 24

Info

Info

24 hour timeframe Switching pattern with flashing time cursor Weekday block Weekend block

Without language selection

Setpoint for remote control Setpoint for comfort mode Setpoint for absence Room temperature Setpoint for frost protection mode Energy saving mode setpoint C / F Time signal from Frankfurt

Time unit Absence/holiday mode set Absence/holiday mode active Party mode active Temperature unit C or F Heating/pump on Remote control active

Operating mode selector Automatic weekly mode with max. three heating phases per day. Exception day with max. three heating phases. Continuous comfort mode (= continuous comfort temperature). Continuous energy saving mode (= continuous energy saving temperature). Frost protection mode ( = continuous frost protection temperature).

INFO Pressing the Info button once illuminates the display. Illumination automatically turns off after a short period of time. Pressing the Info button again activates the information display: is lit. The unit first displays queued error messages followed by important information (e.g. time switch programs, etc.).

Plus button Increase values, set time, or make a selection.

3 / 13 Siemens Building Technologies Room temperature controller REV17.. CE1N2203en 24.04.2008

Override button / party mode In the time switch program, this button allows you to quickly change from the active temperature level to the next and back. Thus, you can quickly change to energy saving temperature when you leave the apartment for a short period of time, thus saving energy. The display indicates the change. It is valid only until the next switching time. Activate party mode: Press the button for 3 seconds. Party mode is available only in operating modes and . In party mode, the controller controls to a freely selectable temperature for a freely selectable period of time. In party mode, symbol is displayed along with the end of party mode.

Minus button Decrease values, set time, or make a selection

Program selection slider

Time Day Month Year (2 spaces for day, month, and year) Block of weekdays or block of weekend 1, 2, or 3 heating phases Start Heating phase 1 Setpoint Heating phase 1 End Heating phase 1 Start Heating phase 2 Setpoint Heating phase 2 End Heating phase 2 Start Heating phase 3 Setpoint Heating phase 3 End Heating phase 3

Energy saving temperature in the automatic mode and exception day time switch programs Start of absence / holiday Temperature setpoint during absence / holiday End of absence / holiday Temperature setpoint at active remote control RUN Slider position RUN allows for closing the cover

4 / 13 Siemens Building Technologies Room temperature controller REV17.. CE1N2203en 24.04.2008

Operating modes

Operation with time switch program

The controller offers the two time switch programs

and

Enter a start time and end time for each heating phase. Also comfort temperature setpoint can be freely entered for each heating phases. Between the heating phases the controller always switches to the same, freely selectable energy saving temperature setpoint.
C 22 21 20 18
Heatin g ph ase 1 Heating phase 2 Heating phase 3

Example with 3 heating phases

16 06 08 12 14 18 22 h

Continuous operating modes

The controller also offers the three 3 continuous modes energy saving mode and frost protection mode.

comfort mode,

Setpoints

You can freely adjust the setpoints for the weekly and 24-hour operating modes. Setting range for all setpoints without setpoint limitation 335 C. Setting range for all setpoints with setpoint limitation 1635 C.
Factory settings: Heating

Factory setting

, ,

20 C 16 C 8 C

,
Factory settings: Switching times Heating phases 1. 2. 3. P1 07:00 06:00 06:00 P2 23:00 08:00 08:00 P3

12 C

P4 PASS 22:00 13:00

P5 PASS PASS 17:00

P6 PASS PASS 22:00

PASS 17:00 11:00

Weekday / Weekend Time switch

Three different switching patterns are available to simplify entry of switching times. These can be assigned as blocks to the corresponding weekdays 15 and weekend days 67. As a result, you need to adapt the switching times and room temperatures only once for each block. Switching pattern Blocks

5 / 13 Siemens Building Technologies Room temperature controller REV17.. CE1N2203en 24.04.2008

2205Z04

Enter holidays or absences

You can enter the beginning, temperature and end of your holidays. At the beginning of the holidays, the controller switches to the desired holiday temperature and returns to the previously set operating mode at the end of the holidays. In holiday mode, symbol is displayed along with the end of holiday mode. Proceed as follows to enter your settings: Set slider to position 15 (start of absence): Press for your holidays. or to set the start date or to set

Set slider to position 16 (temperature during absence): Press the desired temperature while on holidays. Set slider to position 17 (end of absence): Press for your holidays. Return the slider to position RUN. Symbol RUN symbol. Press Remote control , , , or

to set the end date

is displayed to the left of the

or move the slider to end holiday mode prematurely.

Use a suitable remote control unit to activate the "Remote control" temperature setpoint in the controller. Changeover takes place by making a potential-free contact connected to terminals T1 and T2. A flashing symbol indicates active remote control mode. After the contact opens, the previously set operating mode is reactivated. Operation according to controller setting Temperature setpoint remote control active

T1
2252Z05

T1
, ,
,
, ,
2252Z06

T2

T2

Suitable remote control units are: Telephone modem, manual switch, window contact, presence detector, central unit, etc. Enter temperature for active remote control You can freely select the temperature for active remote control. Activating remote control immediately enables control to the remote control temperature regardless of the currently active operating mode. When you deactivate remote control, the controller returns to the set operating mode. A flashing symbol indicates active remote control mode. Proceed as follows to enter your settings: Set slider to position 18 (temperature for active remote control): Press to set the desired temperature for active remote control. RUN Return the slider to position RUN. or

6 / 13 Siemens Building Technologies Room temperature controller REV17.. CE1N2203en 24.04.2008

Technical features DIP switches

ON /

OFF

7
Periodic pump run and anti-lime function
On

Sensor calibration On A Sensor calibration Off Setpoint limitation 1635 C B Setpoint limitation 335 C C Temperature display F Temperature display C PID self-learning D PID 6 PID12 2-point Factory setting: All DIP switches to OFF
After you change one or several DIP switch positions, you must press the DIP switch reset button to reset the DIP switch. Otherwise, the previous setting remains active!

Periodic pump run and anti-lime function


Off Quartz

F Radio clock

DIP switch reset


2211Z32

ON
1 2 3 4 5 6 7 8 9

A Sensor calibration: DIP switch 1

If the displayed room temperature does not match the measured room temperature, the temperature sensor can be recalibrated. Set DIP switch to ON and press the DIP switch reset button: CAL symbol is displayed. The currently measured temperature flashes. or to recalibrate by max. 5 C. Press Set DIP switch to OFF and press the DIP switch reset button to save the settings.

B Setpoint limitation: DIP switch 2

The minimum setpoint limitation of 16 C prevents undesired heat transfer to neighboring spaces in buildings featuring several heating zones. DIP switch ON: Setpoint limitation 1635 C. DIP switch OFF: Setpoint limitation 335 C (factory setting). Press the DIP switch reset button to save the settings.

C Temperature display in C or F: DIP switch 3

DIP switch ON: Temperature display in F. DIP switch OFF: Temperature display in C (factory setting). Press the DIP switch reset button to save the settings.

7 / 13 Siemens Building Technologies Room temperature controller REV17.. CE1N2203en 24.04.2008

D Control behavior: DIP switches 4 and 5

The REV17 is a two-position controller with PID control. The room temperature is controlled through cyclic switching of an actuating unit. DIP switches 4 ON and 5 ON: PID self-learning Adaptive control for all applications. DIP switches 4 ON and 5 OFF: PID 6 Fast controlled system for applications in locations with large temperature deviations. DIP switches 4 OFF and 5 ON: PID 12 Normal controlled system for applications in locations with normal temperature deviations. DIP switches 4 OFF and 5 OFF: 2-point For complex controlled systems, simple two-position controller with 0.5 C switching difference (factory setting). Press the DIP switch reset button to save the settings.

E Periodic pump run and anti-lime function: DIP switch 6

Only applicable with controlled circulating pump or valve! This function protects the pump or valve during extended OFF periods against possible seizure caused by liming. Periodic pump run is activated every 24 hours at 12 p.m. for three minutes (symbol is displayed during active pump run). DIP switch ON: Pump run On. DIP switch OFF: Pump run On (factory setting). Press the DIP switch reset button to save the settings.

F Radio clock: DIP switch 10

Only applicable to REV..DC (with integrated DCF77 receiver to receive time signal from Frankfurt, Germany)! DIP switch ON: Clock run by controller-internal quartz. DIP switch OFF: Time signal DCF77 from Frankfurt, Germany.

Press the DIP switch reset button to save the settings.

Note on synchronization

Note on reception No reception

During startup, REV..DC synchronizes automatically to the time signal (DCF77) from Frankfurt, Germany. Synchronization takes max. 10 minutes. Synchronization restarts each time you press the button or move the program selection slider from the RUN position during these 10 minutes. Siemens recommends to set the desired settings upon startup, install the REV..DC in the desired location, and not carry out any actions on the REV..DC for the next 10 minutes. In normal operation, the REV..DC synchronizes to the radio clock every day at 3:10 a.m. The time signal from Frankfurt is modulated to a radio signal. The reception of this radio signal depends on the distance to Frankfurt, atmospheric conditions as well as the location where the REV..DC is installed. Siemens cannot guarantee that the REV..DC can receive the time signal from Frankfurt at any time and any place. The radio clock symbol is deactivated and an error message is displayed if the clock was not able to synchronize the time for 7 consecutive days. The controller then runs on the internal quartz.

G DIP switch reset


ON
1 2 3 4 5 6 7 8 9
2211Z32

After you change one or several DIP switch positions, you must press the DIP switch reset button to reset the DIP switch. Otherwise, the previous setting remains active!

8 / 13 Siemens Building Technologies Room temperature controller REV17.. CE1N2203en 24.04.2008

Access to the expert level Set the program selection slider to RUN. Press and simultaneously for 3 seconds, release the buttons, and within 3 seconds press and hold down and simultaneously for 3 seconds, release , and press for another 3 seconds. This releases the engineering settings. is displayed. The display first shows language selection with Code 00. Press the buttons or to navigate the settings. Confirm settings by pressing . Press the operating mode selector to exit the engineering settings. Code list Function block Basic settings Code 00 01 02 10 11 12 30 Clock settings 31 32 Note 1: Name Language Sensor calibration Switching differential 2-point Illumination time Background brightness Contrast Time zone Deviation from time signal in Frankfurt (Central European Time CET) (see Note 1) Start of daylight saving time (see Note 2) End of daylight saving time (see Note 3) Factory setting English off 0.5 C 10 seconds 0 0 0 hours 31. March 31 (03-31) 31. October 31 (1031) Your setting

LCD optimization

Note 2:

Note 3:

This entry has no effect if the radio clock either is inactive or not available. The time signal received from Frankfurt is shifted by the value set in Code 30 (time zone) if the radio clock is active. The time is always changed over at 2 a.m. on the Sunday preceding the set date if there is no radio clock or if it is inactive. The time change is shifted by the value set in Code 30 (time zone) when the radio clock is active. The time is always changed over at 3 a.m. on the Sunday preceding the set date if there is no radio clock or if it is inactive.

Functional check

a) Check the display. If there is no display, check insertion and function of the batteries.
b) Operating mode Continuous comfort mode , read displayed temperature. c) Set the temperature setpoint higher than the displayed room temperature (see operating instructions). d) The relay and, as a result, the actuating device must switch at the latest after one minute. Symbol is displayed. If not displayed: Check actuating device and wiring. It is possible that in heating mode the room temperature is higher than the set temperature setpoint. e) Set the temperature setpoint for operating mode Continuous comfort mode desired value. f) Select the desired operating mode. to the

9 / 13 Siemens Building Technologies Room temperature controller REV17.. CE1N2203en 24.04.2008

Reset User-defined settings: , and simultaneously for 3 seconds: This resets all temperature and time settings of the program selection slider to default values (see also "Factory settings" in the operating instructions). The expert settings remain unchanged. The clock starts at 12 p.m., the date on 01-01-08 (01 - January - 2008). During the reset, all display fields are lit and can be checked accordingly. All user-defined settings plus expert settings:
ON
1 2 3 4 5 6 7 8 9

, and simultaneously for Press the DIP switch reset button 5 seconds: After the reset, all factor settings are reloaded. This applies to the program selection slider as well as to the expert settings. Engineering Mount the room temperature controller in the main living room. Select the mounting place so that the sensor can acquire the air temperature in the room as accurately as possible and without being influenced by solar radiation or other heat or refrigeration sources. Mounting height is approx. 1.5 m above the floor. You can mount the unit on most commercially available recessed conduit boxes or directly on the wall.

Mounting and installation

Begin installation by first attaching and wiring the base. You can mount the base on
most commercially available recessed conduit boxes or directly on the wall. Then insert the controller from top to bottom into the base. For more information, see the installation instructions supplied with the unit. Comply with all local regulations on electrical installation. Wire separately the remote control contact T1 / T2 using a separate, shielded cable. Remove from the batteries the battery transit tab designed to prevent premature activation of the unit: Select desired language by or . Confirm by . You can change the control characteristics using the DIP switch on the rear of the unit. Set any thermostatic radiator valves to their fully open position, if present in the reference room. Recalibrate the temperature sensor (see "Sensor calibration") if the displayed room temperature does not match the room temperature measured.

Commissioning

Notes

This is a software class A controller designed for use at a normal degree of pollution.

10 / 13 Siemens Building Technologies Room temperature controller REV17.. CE1N2203en 24.04.2008

2211Z32

Technical data General unit data Supply Batteries (alkaline AA) Life Backup of clock when changing battery (all other data remain in EEPROM) Switching capacity of relay Voltage Current Protection class Sensing element Measuring range Time constant Setpoint setting ranges All temperature settings Resolution for settings and displays Setpoints Switching times Actual value measurement Actual value display Time display CE conformity Electromagnetic compatibility Low voltage directive C-tick Automatic electrical controls for household and similar use EN 60 730-1 Electromagnetic compatibility Immunity Emissions Operation Climatic conditions Temperature Humidity Storage and transport Climatic conditions Temperature Humidity Mechanical conditions Excl. packaging Housing Base Housing with base EN 61000-6-2 EN 61000-6-3 3K3 as per IEC 60 721-3 5...40 C <85 % r.h. 2K3 as per IEC 60 721-3 -25...70 C <93 % r.h. 2M2 as per IEC 60 721-3 0.29 kg RAL9003 signal white RAL7038 gray 90 x 134.5 x 30 mm DC 3 V 2 x 1,5 V Ca. 2 years Max. 1 min

AC 24250 V 0.16 (2.5) A II as per EN 60 730-1 NTC 10 k 1 % at 25 C 050 C Max. 10 min 335 C 0.2 C 10 min 0.1 C 0.2 C 1 min 2004/108/EEC 2006/95/EC

Standards

N474

Product safety

Environmental conditions

Weight Color Size

11 / 13 Siemens Building Technologies Room temperature controller REV17.. CE1N2203en 24.04.2008

Connection diagrams
2252A02

DC 3 V

L T1 T2 L2 L1

N1

S1
N N

AC 24...250 V

M1 Y1

REV17 / REV17DC L Phase, AC 24 250 V N.O. contact, L1 AC 24 250 V / 6 (2.5) A N.C. contact, L2 AC 24 250 V / 6 (2.5) A Circulating pump M1 REV17 controller N1 Application examples

S1 T1 T2 Y1

Remote control unit (potential-free) Remote control signal Remote control signal Actuating device

N1
T

T T

F1 F2

N1
F2
T

F1
T

Y2

Y2

M1
2252S01

M1
2252S02

Instantaneous water heater

Atmospheric gas burner

N1

N1
T

N1
T

Y1 M1

Y3

Y4

Zone valve

2252S03

Circulating pump with precontrol by manual mixing valve

F1 F2 M1 N1

Thermal reset limit thermostat Manual reset safety limit thermostat Circulating pump REV17.. room temperature controller

Y1 Y2 Y3 Y4

3-port valve with manual adjustment Magnetic valve Three-port valve with actuator Two-port valve with actuator

12 / 13 Siemens Building Technologies Room temperature controller REV17.. CE1N2203en 24.04.2008

2252S04

Dimensions

30

134,5

56

0 6

94

82 56

13 83,5 130

13 / 13 Siemens Building Technologies

2008 Siemens Switzerland Ltd

16,2

Subject to change

Room temperature controller REV17..

CE1N2203en 24.04.2008

2206M03

REV17 User Guide


Slider Positions

SIEMENS BUILDING TECHNOLOGIES

1
Time setting

2
Date Day / Month / Year

3
Weekdays 1-5 Weekend 6-7

4
1, 2 or 3 Comfort phases

5
Start time Comfort phase 1

6
Temperature Comfort phase 1

7
End Comfort phase 1

8
Start time Comfort phase 2

9
Temperature Comfort phase 2

10
End Comfort phase 2

11
Start time Comfort phase 3

12
Temperature Comfort phase 3

13
End Comfort phase 3

14
Saving temp. time program

15
Start Absence

16
Temperature Absence

17
End Absence

18
Temperature remote control

If the selected operating mode does not support the setting, the time display shows PASS. STEP Symbol

Programming Initial Start Up - Enabling Battery Power:

Remove the controller from the mounting base and pull out the black insulating tape tab from the battery compartment: The controller turns on automatically. Re-insert the controller in the mounting base. Language Selection: After startup, a welcome message appears for approx 2 minutes. Press a button to interrupt the message. Language selection starts or until your desired language appears. Press or move the slider to accept with ENGLISH (factory setting). Press your language choice. Hint: if you choose the incorrect language, an Expert Level Reset will need to be performed. This is achieved by: Pressing simultaneously the DIP switch reset button (on the back of the unit under the dip switch cover) and the and for 5 seconds: After this reset, all factory settings will be reloaded. This applies to both the slider settings and the settings made on the expert level. Setting Time:

Move the Slider to position 1 (time setting): Press Setting Date:

or

to set the time.

Slider in position 2 (date: day/month/year): Press Weekday (1-5) and Weekend (6-7) Blocks:

or

to set the date. (Note: the day of the week is automatically chosen)

Slider in position 3 (Monday- Friday weekdays

, Saturday and Sunday weekend or

): You will notice the flashing to toggle between both blocks.

or
Comfort Phases:
6

blocks in the top right hand corner. Press the

Slider in position 4 (there are 3 comfort phases): Press Setting Time in Comfort Phase 1:

or

to set the comfort phases you desire.

Slider in position 5 (start time comfort phase 1): Press

or

to set the start time. or buttons

Hint: you will notice the flashing time cursor on the 24 hour time bar (at the bottom of the screen) corresponding with the entered time, moves as you adjust the time with the
8

Setting Temperature in Comfort Phase 1: Slider in position 6 (temperature comfort phase 1): Press Setting Time to End Comfort Phase 1: or to set the temperature.

Slider in position 7 (end time comfort phase 1): Press , ,

or

to set the end time.

Setting Time and Temperature for Comfort Phase 2 and 3: Slider positions 810 (comfort phase 2) and slider positions 1113 (comfort phase 3): Same procedure as above for comfort phase 1.

10

Setting Energy Saving Temperature from Monday to Sunday: Slider in position 14 (energy saving temperature in time switch programs Automatic and Exception day): Press or to set the temperature. Note: The energy saving temperature is valid Monday through Sunday. It does not depend on operating mode "Continuous
energy saving".
Hint: 12 If you do not want your heating to come on at night (or anytime it is controlling to the setpoint) then set this value low e.g. 3.0 C

11

RUN

Complete Programming

Move the slider to RUN position and close the cover.

REV17 User Guide

Room temperature controller REV17

Slider positions
Page 1 of 2

RUN

Operating Mode Selection


There are five operating modes as described in the table below.
Operating mode symbol descriptions Automatic weekly mode with maximum three heating phases per day. (typical setting during winter) Exception day with maximum three heating phases. Enables you to program Automatic switching sequences different to usual automatic program. Ideal for long weekends. Continuous comfort mode (heater will maintain set point continuously until removed) e.g. heater will be on 24/7 Continuous energy saving mode (Night time set point). Continuous Frost protection mode/OFF Mode (continuous frost protection, can be set between 8 and 3 if room temperature drops below this set value the C C, heater will turn on). To set this use the or buttons and wait until it stops flashing

Select operating mode


Press the operating mode button to scroll down and back up to the top in order to select one of 5 modes.

Operating modes with time program


The controller offers both time programs Automatic Do you feel too warm / too cold ? Press or to set the temperature. The setting is temporary and active only until the next time the controller activates a change. Note: To set your own programs, see: "Enter customized temperatures and switching times". and Exception day

Continuous operating modes


The controller offers continuous operating modes "Continuous comfort mode "Continuous energy saving mode Do you feel too warm / too cold ? Press or to set a continuous temperature. and frost protection mode ,

Enter holidays or absence


You can enter start, temperature and end of your holidays. The controller switches to the set holiday temperature at the start of the holidays and back to the preset operating mode at the end of the holidays. During holiday mode, symbol Proceed as follows: Slider in position 15 (start of absence): Press or to set the starting date of the holidays. or to set the temperature effective during flashes and the end of the holidays is displayed.

Slider in position 16 (temperature during absence): Press the holidays. Slider in position 17 (end of absence): Press or

to set the end date of the holidays. .

RUN

Move the slider back to RUN. Symbol To quit holiday mode prematurely, press

appears to the left of symbol , , ,

or move the slider.

How can I tell if my heater should be running? When the REV Controller requires the heater to be heating you should see the screen. symbol on the right side of the

REV17 User Guide

Room temperature controller REV17

Page 2 of 2

G2203

REV17..
Installation instructions
A D

E B

C F

CE1G2203xx

18.01.2008

1/6

/ 1.1.5
24 h 3 min. on off 12:00 12:00

/ 1.1.1 DIP Switch 1: OFF DIP Switch 1: ON DIP Switch 7: OFF

/ 1.1.6 DIP Switch 7: ON

/ 1.1.3 DIP Switch 3: OFF DIP Switch 3: ON

/ 1.1.7

/ 1.1.4
2211Z16

t PID self-learning
C
2211Z16

t
6 min
2211Z16

PID 6

t
12 min

PID 12
2211Z16

DIP-Switch-Reset

0,5 C

t 2-Point

2/6

18.01.2008

CE1G2203xx

Mounting notes REV17..


1

Placement of unit
The REV17.. should be mounted in the main living room (for wall mounting, refer to Figs. B through E) The REV17.. must be located such that it can acquire the room temperature as accurately as possible, without getting affected by direct solar radiation or other heat or refrigeration sources

Mounting
Refer to Figs. A through E

3
Note:

Checking the wiring


Do not use stranded wires, only solid wires or stranded wires with ferrules!

For electrical connections, refer to Connection diagram.

min. 10 cm

2261Z03

Notes
The local regulations for electrical installations must be complied with If the reference room is equipped with thermostatic radiator valves, they must be set to their fully open position

Commissioning
1

Switching on the REV17..


Remove the black battery transit tab (Fig. F); as soon as the tab is removed, the unit is ready to operate (also refer to operating instructions)

Press one of the buttons to stop the running display. The choice of languages starts with ENGLISH (factory setting). Press or until the language you require appears. or move the slider to confirm the selected language Press (also refer to Fig. G)

Selecting the language


When starting up, the display shows the type of controller at top left and THANK YOU in all available languages on the text line

CE1G2203xx

18.01.2008

3/6

Configuration and function check REV17.


1
1.1

Configuration
DIP switches
ON / OFF 1 2 3 4 5 6 7
Periodic pump run on Periodic pump run off Quartz 1.1.6 Radio clock
When changing one or several DIP switch reset DIP switch positions, a DIP switch reset must be made by pressing the DIP switch reset
ON
1 2 3 4 5 6

See 1.1.5

See 1.1.1

Sensor calibration on Sensor calibration off Setpoint limitation 1635 C Setpoint limitation 335 C Temperature display F Temperature display C PID self-learning PID 6 PID12 2-Point

1.1.2

1.1.3

2211Z32

1.1.7

1.1.4

) button (also refer to Fig. Otherwise, the previous settings will be maintained!

Factory setting: All DIP switches

OFF

1.1.1 Sensor calibration: DIP switch 1


Set the DIP switch to ON and press the DIP switch reset button: The display shows CAL. The room temperature currently acquired blinks. or to make a recalibration of max. 5 C. To save Press the entry, set the DIP switch to OFF and press the DIP switch reset button (also refer to Fig. ).

DIP switch 4 OFF and 5 ON: PID 12 For normal controlled systems, applications at locations with normal temperature variations. DIP switch 4 OFF and 5 OFF: 2-Point For difficult controlled systems, 2-position controller with a switching differential of 0.5 C (factory setting). Save the entry by pressing the DIP switch reset button (also refer to Fig. ).

1.1.2 Setpoint limitation: DIP switch 2


DIP switch ON: DIP switch OFF: Setpoint limitation 1635 C Setpoint limitation 335 C (factory setting) Save the entry by pressing the DIP switch reset button.

1.1.5 Periodic pump run: DIP switch 6


Can only be used when circulating pump or valve is controlled! This function protects the pump or valve against seizing during longer off periods. Periodic pump run is activated for 3 minutes every 24 hours at 12:00 (display showing symbol ). DIP switch ON: Pump run on (also refer to Fig. DIP switch OFF: Pump run off (factory setting) Save the entry by pressing the DIP switch reset button. )

1.1.3 Temperature display in C or F: DIP switch 3


DIP switch ON: DIP switch OFF: Temperature display in F Temperature display in C (factory setting) Save the entry by pressing the DIP switch reset button (also refer to Fig. ).

1.1.6 Radio clock: DIP switch 7


Can only be used with REV..DC (with integrated DCF77 receiver for time signal from Frankfurt)! DIP switch ON: Clock runs on built-in quartz

1.1.4 Control action: DIP switches 4 and 5


DIP switch 4 ON and 5 ON: PID self-learning Adaptive control for all types of application. DIP switch 4 ON and 5 OFF: PID 6 For fast controlled systems, applications at locations with great temperature variations.

DIP switch OFF: Time signal DCF77 from Frankfurt Save the entry by pressing the DIP switch reset button (also refer to Fig. ).

1.1.7 DIP switch reset


When changing one or several DIP switch positions, press the DIP switch reset button to make a DIP switch reset. Otherwise, the previous settings will be maintained! (Also refer to Fig. ).

Accessing the expert level


and and keep for 3 seconds, then release the buttons and, within 3 depressed for another 3 seconds. This enables you to and . Confirm the and for 3 seconds, release on display (also refer to Fig. G).

Move the selector slider to the RUN position and press simultaneously seconds, press simultaneously access the expert level for making the settings on that level. settings by pressing . .

Starting with code 00, the display shows the choice of languages. Navigation on the expert level is made possible with The expert level is quit by pressing the operating mode selection button

4/6

18.01.2008

CE1G2203xx

Code list Function block


Basic settings

Code
00 01 02 10 11 12 30

Name
Language Sensor calibration Switching differential 2-point Illumination time Background brightness Contrast Time zone Deviation from time signal received from Frankfurt (Central European Time CET) (refer to Note 1) Start of summer time (refer to Note 2) End of summer time (refer to Note 3)

Factory setting
English off 0.5C 10 seconds 0 0 0 hours March 31 (31-03) October 31 (31-10)

Your setting

LCD settings

Clock settings 31 32

Note 1: If the radio clock is not active or not present, this setting has no impact. With the radio clock active, the time signal received from Frankfurt is shifted by the value set under code 30 (time zone). Note 2: If the radio clock is not active or not present, the time change always takes place at 02:00 on the Sunday before the set date. With the radio clock active, the time change is shifted by the value set under code 30 (time zone). Note 3: If the radio clock is not active or not present, the time change always takes place at 03:00 on the Sunday before the set date. With the radio clock active, the time change is shifted by the value set under code 30 (time zone).

4 3 Function check
a) Check the display. If there is no display, check the batteries , read the temperature b) Continuously Comfort mode displayed c) Set the temperature setpoint to a level above the displayed room temperature (see operating instructions) d) The relay and thus the actuating device must respond within 1 minute. Symbol appears on the display. If not: Check actuating device and wiring The room temperature is possibly higher than the adjusted temperature setpoint to

Reset

User-defined settings: Press simultaneously , and for 3 seconds: All temperature and time settings of the slider positions are reset to their default values (refer to section Factory settings in the operating instructions). The settings made on the expert level will remain unchanged. The clock starts at 12:00, the date on 01-01-08 (01 - January - 2008). During the reset time, all sectors of the display are illuminated and can thus be checked. All user-defined settings plus those made on the expert level: and Press simultaneously the DIP switch reset button, for 5 seconds: After this reset, all factory settings will be reloaded. This applies to both the slider settings and the settings made on the expert level.

e) Set temperature setpoint of Continuously Comfort mode the required level f) Select the required operating mode

Notes
The controller is classified as a device of software class A and designed for use in environments with normal degree of pollution

CE1G2203xx

18.01.2008

5/6

Dimensions

30

134,5

56

REV17..
94 82 56

13 83,5 130

Connection diagram

2252A02

16,2

en L Lx L1 L2 M1 N T1 T2 N1 S1 Y1 Live, AC 230 V Live, AC 24 ... 250 V N.O. contact, AC 24 ... 250 V / 6 (2,5) A N.C. contact, AC 24 ... 250 V / 6 (2,5) A Circulating pump Neutral conductor Signal <remote operation> Signal <remote operation> Room temperature controller REV17.. Remote operation unit (potentialfree) Actuating device

DC 3 V

L T1 T2 L2 L1

REV17..

N1

S1
N N

AC 24...250 V

M1 Y1

2008 Siemens Switzerland Ltd.

Subject to alteration

6/6