You are on page 1of 10

FM Global Property Loss Prevention Data Sheets

1-3
May 2008 Page 1 of 10

HIGH-RISE BUILDINGS

Table of Contents
Page 1.0 SCOPE ................................................................................................................................................... 2 1.1 Changes .......................................................................................................................................... 2 2.0 LOSS PREVENTION RECOMMENDATIONS ....................................................................................... 2 2.1 Construction and Location ............................................................................................................... 2 2.2 Protection ......................................................................................................................................... 5 2.3 Equipment and Processes .............................................................................................................. 8 2.4 Human Element ............................................................................................................................... 9 3.0 SUPPORT FOR RECOMMENDATIONS ............................................................................................... 9 3.1 Illustrative Losses ............................................................................................................................ 9 3.1.1 Fire Spreads Five Stories via Windows and Openings at the Edge of Floors ..................... 9 4.0 REFERENCES ..................................................................................................................................... 10 4.1 FM Global ....................................................................................................................................... 10 4.2 Other .............................................................................................................................................. 10 APPENDIX A GLOSSARY OF TERMS ..................................................................................................... 10 APPENDIX B DOCUMENT REVISION HISTORY ..................................................................................... 10

List of Figures
Typical exterior window arrangement ............................................................................................... 3 Window heights ................................................................................................................................ 3 Exterior wall glass in metal frame. Firestopping friction fit in space and supported by clip angle. . 4 Firesafing friction fit into space and held in place by clip angle secured to exterior precast concrete panel .................................................................................................................................. 4 Fig. 2C. Firesafing support welded in place .................................................................................................. 5 Fig. 2D. Continuous glass exterior ................................................................................................................. 6 Fig. 3. Leaning high-rise buildings ................................................................................................................. 7 Fig. Fig. Fig. Fig. 1A. 1B. 2A. 2B.

2008 Factory Mutual Insurance Company. All rights reserved. No part of this document may be reproduced, stored in a retrieval system, or transmitted, in whole or in part, in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise, without written permission of Factory Mutual Insurance Company.

1-3
Page 2

High-Rise Buildings
FM Global Property Loss Prevention Data Sheets

1.0 SCOPE This data sheet provides recommendations concerning the unique hazards associated with high-rise buildings. 1.1 Changes May 2008. A reference to Data Sheet 5-23, Emergency and Standby Power Systems, was added. An editorial review was completed. 2.0 LOSS PREVENTION RECOMMENDATIONS 2.1 Construction and Location 2.1.1 Ensure the fire resistance of major structural components is at least equal to: 2 3 2 2 hours hours hours hours for for for for floor slabs and beams columns shafts and chases stairwell and elevator enclosures

Where spalled or missing fire-resistive coatings are encountered in construction, the maximum area of spalling that can be tolerated before repair is needed is only a few square inches. Where high-strength concrete (HSC) is proposed, employ one of the design considerations outlined below should be employed to limit spalling and weakening of the concrete during fire exposure: a) Provide a fire-resistant covering over the outer surface of the column, or b) Provide an additional thickness of HSC, or c) Modify the HSC mix, as verified by fire test. It is the responsibility of the designer to verify the proposed protection thickness or formula variation provides adequate fire resistance as recommended above. 2.1.2 The exterior vertical spread of fire in unsprinklered buildings can be minimized when the distance between any floor and the bottom of the window on the next story above that floor (H) is at least 2.8 times the window height (h) if windows are permanently closed, and at least 3.8 times the window height if windows can be opened. (See Fig. 1a.) Exterior vertical fire spread can be prevented if: H 2.8 h, if windows are closed (permanently); or H 3.8 h, if windows can be opened. When there is more than one window per floor (in the vertical direction), ensure the distance (H) between the top of the floor of expected fire origin and the top of the lower window on the floor above is at least equal to 3.8 times the sum of the window heights on an individual floor to help prevent vertical exterior firespread. (See Fig. 1b.) H 3.8 htot where: htot = height of lower window plus height(s) of upper windows(s) Such protection is considered equivalent to H 2.8 h, when there is only one window. This assumes all windows are closed. When windows can be opened, ensure the following criteria are met: H 4.8 htot If separation is less than that recommended above or if the exterior walls contain combustibles, the potential for exterior vertical firespread via windows exists. htot = h1 + h2 H 3.8 htot (for closed windows) H 4.8 htot (for open windows)

2008 Factory Mutual Insurance Company. All rights reserved.

High-Rise Buildings
FM Global Property Loss Prevention Data Sheets

1-3
Page 3

Fig. 1A. Typical exterior window arrangement

Fig. 1B. Window heights

2.1.3 Protect openings between floors found in shafts, chases and stairwells, or openings in partitions between floor areas, should be protected with FM Approved (see Appendix A for definition) and labeled fire doors. Ensure these are normally closed or are automatic closing fire doors having a fire rating of at least 1-12 hours (unless otherwise noted) and installed in accordance with Data Sheet 1-23, Protection of Openings in Fire Subdivisions. 2.1.4 Have openings in floor slabs used for utilities (poke-throughs) protected with FM Approved floor penetration fire stops with a 2-hour fire resistance rating.

2008 Factory Mutual Insurance Company. All rights reserved.

1-3
Page 4

High-Rise Buildings
FM Global Property Loss Prevention Data Sheets

2.1.5 Ensure panels used for exterior walls are noncombustible. Examples include concrete, masonry, or glass fiber insulated steel sandwich panels. Ensure the panels and frames are tightly secured at each floor (to prevent outward buckling under fire exposure), with the space between the panels and the floor slabs filled with a noncombustible firesafing (fire-stopping) material, such as mineral wool or ceramic fiber, which has passed a fire-resistance test conducted by a recognized testing lab for a minimum of two hours. Because floor dimensions are usually limited in a high-rise building, internal expansion joints between floor sections are rarely provided. If such a situation is encountered, however, provide protection as described above. Do not use glass fiber as firesafing. Ensure the firesafing is securely held in place. Z clips may be used to support (or to pierce) the underside of the firesafing and hold it in place. (See Figures 2a to 2c for appropriate designs.)

Fig. 2A. Exterior wall glass in metal frame. Firestopping friction fit in space and supported by clip angle.

Fig. 2B. Firesafing friction fit into space and held in place by clip angle secured to exterior precast concrete panel

2008 Factory Mutual Insurance Company. All rights reserved.

High-Rise Buildings
FM Global Property Loss Prevention Data Sheets

1-3
Page 5

Fig. 2C. Firesafing support welded in place

Glass exterior cladding also may be used as long as interior cladding, such as steel panels or gypsum board, limit the window height to within the range noted in Recommendation No. 2.1.2 above. When glass exterior cladding is used, spandrel heights must be defined by interior cladding, such as steel panels or gypsum board. The location of the horizontal joint between vertical sections of glass panels also is critical. If a vertical section of glass panel spans from floor to floor with horizontal joint in line with the floor, assume glass will shatter on the fire floor and the floor above, and analyze exterior fire spread potential the same as for openable windows (H 3.8 h). If the horizontal joint between vertical sections of glass panels occurs at the top of the spandrel immediately above the assumed fire floor (see Fig. 2d) and the window sill is steel, assume the glass on the fire floor will shatter, but the next glass panel above will remain intact and seal off the window opening on the floor above the fire if the window ratio is H 2.8 h. Ensure sandwich panel curtain walls using aluminum skins, combustible insulation (such as foam plastic) or no insulation are completely interrupted at each floor with a barrier of equal fire resistance to that of the floor. 2.1.6 Separate atriums and other open areas that extend between multiple floors from adjacent occupied areas with a smoke-tight fire partition having a fire-resistance rating of at least two hours. Protect openings with FM Approved and labeled fire door (normally closed or automatically operated by smoke detection) with a minimum 1-12 hour fire rating. If windows are provided in the fire partition, ensure they have a minimum 1-12 hour fire rating. 2.1.7 Arrange protection against d earthquake in accordance with Data Sheet 1-2, Earthquakes; Data Sheet 1-28, Wind Design; Data Sheet 1-29, Roof Deck Securement and Above-Deck Roof Components; Data Sheet 1-49, Perimeter Flashing; and the Approval Guide, a publication of FM Approvals. 2.1.8 Guidelines relating to vertical firespread in this data sheet do not apply to leaning high-rise buildings. (See Fig. 3.) 2.2 Protection 2.2.1 Provide sprinkler protection for all high-rise buildings as follows: a) Provide automatic sprinkler protection throughout all high-rise buildings. b) Provide all atriums with sprinkler protection at the roof level as well as at each floor, under corridors or balconies facing the atrium. If the ceiling or roof is more than 30 ft (9 m) high, keep the combustible loading at a limited level. 2.2.2 Install sprinklers in accordance with Data Sheet 2-0, Installation Guidelines for Automaic Sprinklers, and Data Sheet 3-26, Fire Protection Water Demand for Nonstorage Sprinklered Properties.

2008 Factory Mutual Insurance Company. All rights reserved.

1-3
Page 6

High-Rise Buildings
FM Global Property Loss Prevention Data Sheets

Fig. 2D. Continuous glass exterior

2.2.3 Provide an adequate water supply for fire protection according to Data Sheet 3-26, Data Sheet 3-7N/13-4N, Centrifugal Fire Pumps (NFPA); and Data Sheet 2-0, Installation Guidelines for Automatic Sprinklers. Ensure pressure does not exceed 175 psi (1206 kPa) (12.1 bar) on sprinkler piping, sprinklers and backflow preventers. 2.2.4 Whenever possible, design water supply and fire protection systems to avoid the need for pressureregulating valves. When unavoidable, install FM Approved pressure-regulating valves in accordance with Data Sheet 3-11, Pressure-Reducing Valves for Fire Protection Service. 2.2.5 Provide standpipes for Class III service with both 2-12 in. (64 mm) and 1-12 in. (38 mm) hose connections in accordance with Data Sheet 4-4N, Standpipe and Hose Systems. Ensure the water supply is able to provide a total demand of 500 gal/min (1890 L/min) plus 250 gal/min (945 L/min) for each additional standpipe at an adequate pressure at the topmost outlet. Contact the fire service to determine needed water pressure, taking into consideration the operating pressure for the particular nozzles used and friction loss through the hose. The sprinkler and hose demand outlined in Recommendation No. 2.2.2 need not be added to these demands, but should be available as recommended. 2.2.6 Install grouped electrical cables according to the National Electrical Code and Data Sheet 5-31, Cables and Bus Bars.

2008 Factory Mutual Insurance Company. All rights reserved.

High-Rise Buildings
FM Global Property Loss Prevention Data Sheets

1-3
Page 7

Fig. 3. Leaning high-rise buildings

2.2.7 Provide a supervised fire alarm system connected to a constantly attended location. Have the alarm system monitor waterflow alarms for each sprinklered floor, all smoke detectors, and heat detectors in unsprinklered areas, and provide electrical supervision for fire pumps, tanks and reservoirs in accordance with Data Sheet 9-1, Supervision of Property, and other applicable data sheets. Due to the large number of sprinkler valves and the impact of a shut valve, also have valve tamper alarms constantly monitored. 2.2.8 Provide portable fire extinguishers in accordance with Data Sheet 4-5, Portable Extinguishers.

2008 Factory Mutual Insurance Company. All rights reserved.

1-3
Page 8

High-Rise Buildings
FM Global Property Loss Prevention Data Sheets

2.2.9 Protect ducts for air conditioning and exhaust systems in accordance with Data Sheet 1-45, Air Conditioning and Ventilating Systems, and Data Sheet 7-78, Industrial Exhaust Systems. 2.2.10 Arrange smoke control for atriums as follows: a) Provide an independent, mechanical smoke exhaust system at the top of the atrium for removal of smoke that rises to this level from the base of the atrium, or from floors opening to it. Design the exhaust system to provide at least six air changes per hour in the atrium. If the volume exceeds 600,000 ft3 (16, 800 m3), design the exhaust system to provide at least four air changes per hour. Other designs made according to NFPA 92B may be acceptable. b) Have the exhaust system activated by smoke detectors installed at the atrium ceiling level, in accordance with Data Sheet 5-48, Automatic Fire Detectors, and the Approval Guide. c) Where practical, design the air-handling systems in areas adjacent to the atrium to pressurize these areas upon smoke detection. 2.2.11 Provide an independent air supply system to pressurize the stairwells as follows: a) Have the air supplied through a single duct running vertically inside the stairwell. b) Provide air injection at alternate floors to ensure air movement, and maintain pressurization. c) Ensure the air-distribution system is continuously self-balancing, eliminating the need for extensive adjustments following installation. d) Arrange the stairwell pressurization system in zones comprising a maximum of 14 stories per zone. Design the system to maintain pressurization with three doors open per zone. e) Protect fans, power supply, and distribution system by enclosing them in construction of at least 2-hour fire resistance. f) If two different zones are located on the same floor, ensure they are separated from each other by fire walls of equal fire resistance to that of the stairwell enclosure. 2.2.12 Elevator protection depends on the size and type of building. The following recommendations can be adapted to meet a particular need. a) Design high-rise buildings so elevator shafts are away from the areas of potential fire danger; i.e., on the perimeter or in an isolated core. b) Configure elevator controls so that activation of a fire alarm in the emergency communication center will send them directly to the first floor or lobby. c) Ensure at least two elevators servicing each floor have the ability to be dedicated for firefighters use and to be operated with special keys. Ensure these elevators are in protected shafts that have a 2-hour fire resistance. 2.2.13 Establish an emergency communication center for the following functions, according to the size of the building and its fire hazards: a) The control point for emergency communication b) The control point for emergency operation of all the building electro-mechanical systems, such as fans, elevators, smoke control, fire protection, etc. c) The center for directing firefighting and rescue operations 2.3 Equipment and Processes 2.3.1 Provide an emergency generator, capable of furnishing power for emergency lighting, communication, emergency elevators, fire pump, and smoke control operation as a minimum. Ensure the fuel supply is adequate for the full demand for a minimum of two hours. (See OS 5-23 for protection of generator fuel supplies.)

2008 Factory Mutual Insurance Company. All rights reserved.

High-Rise Buildings
FM Global Property Loss Prevention Data Sheets

1-3
Page 9

2.4 Human Element 2.4.1 Establish an Emergency Response Team (ERT) trained for emergency action. Place it under the direction of building management. Include a person in charge, someone to call the public fire service, fire pump operator, and sprinkler valve operators, as a minimum. Seek the cooperation of the building owner and tenants, so ample trained personnel will be available at all times to handle emergencies. Have the person in charge coordinate with the public fire service in planning for any emergency. Review these plans annually. Arrange for a person knowledgeable of the building construction and occupancy to be stationed at the building command center to assist and direct the public fire service. 2.4.2 Have the fire alarm and smoke control systems, including alarms and shutdown devices, thoroughly inspected and checked for proper operation by adequately trained personnel at least every six months. In particular, have the following equipment examined: a) Have the system-activating devices, such as fusible links or heat or smoke detectors, checked to ensure hey are not covered with residue, or are otherwise impaired. b) Inspect fire and smoke dampers at least annually to detect damage, obstructions and corrosion. c) Have heat and smoke detector systems inspected and tested. Follow the manufacturers or installers recommendations in maintaining, inspecting, and testing the equipment. d) Arrange the overall system so it can be adequately tested every six months by simulating emergency mode conditions. 2.4.3 Ensure all equipment requiring servicing and testing is readily accessible, and a practical means is provided for adequate cleaning. 2.4.4 Provide sufficient instrumentation for testing and maintaining the fire protection equipment. 2.4.5 Ensure fire pumps, sprinkler systems and standpipe systems are maintained, inspected, and tested in accordance with the applicable FM Global data sheets. All equipment and controls should be clearly identified. 2.4.6 Provide testing and maintenance manuals for other fire protection equipment in accordance with the manufacturers and installers instructions. These should include operating, servicing, testing and troubleshooting information. 2.4.7 Do not store material, particularly combustibles, in the stairwell enclosures. 3.0 SUPPORT FOR RECOMMENDATIONS 3.1 Illustrative Losses 3.1.1 Fire Spreads Five Stories via Windows and Openings at the Edge of Floors This facility was a 62-story office tower located in the business district of a large city. The building had protected steel with floors of concrete over steel form deck. The structural frame was 3-hour fire rated, and the stairwells, elevator enclosures and floor assemblies were 2-hour fire rated. The exterior walls were glass curtain walls in an aluminum frame with a 3 in. (76 mm) space between the floor slab and the curtain wall filled with fiber batt insulation. A sprinkler system was being installed at the time of the fire, but was not in service. A fire started on the 12th floor, which was occupied by computer work stations in an open floor plan (few interior partitions). About 12 hour after the first alarm, witnesses reported that the 12th and 13th floors were heavily involved in the fire. About one hour into the fire, witnesses noted that the exterior windows on the 13th floor were breaking and flames propagating outside to the 14th floor. Later, the fire department reported that fire spread to the 16th floor through the space between the floor slab and the glass curtain wall. Control of the fire took almost four hours and the combined efforts of 64 fire companies, over 380 fire fighters, and four helicopters. The 12th, 13th, and 14th floors were gutted by the fire. Contents on the 15th floor were severely damaged. Contents located at the perimeter of the 16th floor were fire damaged. Fire spread to a small room on the 27th floor via an air handling duct. However, minimal damage occurred. Water damage was reported on all floors below the fire, and smoke damage was reported as high as the 50th floor. Minor damage was reported

2008 Factory Mutual Insurance Company. All rights reserved.

1-3
Page 10

High-Rise Buildings
FM Global Property Loss Prevention Data Sheets

to the protected steel of the structural frame, although it was reported that at least portions of the floor slabs on the 13th, 14th, 15th, and 16th floors had to be replaced. 4.0 REFERENCES 4.1 FM Global Data Sheet 1-2, Earthquakes Data Sheet 1-20, Protection Against Fire Exposure Data Sheet 1-23, Protection in Openings in Fire Subdivisions Data Sheet 1-28, Wind Design Data Sheet 1-29, Roof Deck Securement and Above-Deck Roof Components Data Sheet 1-45, Air Conditioning and Ventilating Systems Data Sheet 1-49, Perimeter Flashing Data Sheet 2-0, Installation Guidelines for Automatic Sprinklers Data Sheet 3-7, Fire Protection Pumps Data Sheet 3-11, Pressure Reducing Valves for Fire Protection Service Data Sheet 3-26, Fire Protection Water Demand for Nonstorage Sprinklered Properties Data Sheet 4-4N, Standpipe and Hose Systems Data Sheet 4-5, Portable Extinguishers Data Sheet 5-31, Cables and Bus Bars Data Sheet 5-48, Automatic Fire Detectors Data Sheet 7-78, Industrial Exhaust Systems Data Sheet 9-1, Supervision of Property Data Sheet 5-23, Emergency and Standby Power Systems Approval Guide, publication of FM Approvals, Building Materials Section 4.2 Other National Fire Protection Association, NFPA 92B, Smoke Control for Atriums and Large Spaces APPENDIX A GLOSSARY OF TERMS FM Approved: references to FM Approved in this data sheet mean the product or service has satisfied the criteria for FM Approval. Refer to the Approval Guide for a complete listing of products and services that are FM Approved. Firesafing: Compressable, fire-resistant insulation installed between the interior side of an exterior wall and the edge of the floor slab, to help prevent vertical firespread. High-rise building: A fire resistive building whose upper floors are above the public fire services ability to fight a fire from the exterior of the building. Spandrel: Exterior wall construction that extends from the top of a window on a lower floor to the bottom of the window on the floor above. Smoke control: A method used to limit the spread of smoke from a fire by exhausting smoke from a fire floor or compartment, and pressurizing adjacent floors or compartments to prevent smoke from entering. APPENDIX B DOCUMENT REVISION HISTORY May 2008. A reference to Data Sheet 5-23, Emergency and Standby Power Systems, was added. An editorial review was completed.

2008 Factory Mutual Insurance Company. All rights reserved.

You might also like