You are on page 1of 6

Alpha Series

1
Alpha Series
400, 600, 1000 and 1500W
AC/DC Modular
Key Market Segments & Applications
Up to 16 outputs
Voltages up to 48V, Current up to 300A
Fast-on output connection
Worldwide approvals & CB report
Medical Approval Option
3 Year Warranty
Features and Benefits
Features Benefits
Low Profile Simpler to install in system
Fast-on output terminal Reduces installation time/errors
Medical Approval available Suitable in medical applications
Instrumentation
Medical
Automation
Security
Network Servers and Routers
Broadcast
ATE
Industrial Computing
Lifesciences/Laboratory
INPUT
InputVoltage
Alpha400 90-264Vac
Alpha600 90-264Vac,160-358Vdc
Alpha1000 85-264Vac,120-360Vdc
Alpha1500 85-264Vac(1000Wbelow150Vacinput)
InputFrequency 47-63Hz(440HzwithreducedPFC-consultfactory)
InrushCurrent <50Aat25Cand264Vac(coldstart)
InputFuse
250VacHBCFastActing(notuseraccessible)
10Afor400W
12Afor600W
20Afor1000Wand1500W
LeakageCurrent 1.1mAmaxat264Vac&63Hz
LowerLeakageOption seeconfiguringguide
PowerFactor 0.99typical
OUTPUT
Voltage/Current Seemoduleoutputtable
TurnonDelay 1.5smax at90Vac(150VacforAlpha1500W)&100%ratedoutputpower
RiseTime <50ms to90%ofvoltage,monotonicriseabove10%
TurnonOvershoot <5%or250mV Loadtypedependant,noovershootwithresistiveload
Efficiency 75% typicalat230Vac&100%ratedpower,configdependent
Holdup 15msmin
at90Vac&100%ratedoutputpower
13msfor1000W,8msfor1500Wandat207Vacfor1500W
Ripple&Noise <2% (or100mVifgreater)Pk-Pk,usingEIAJtestmethod&20MHzbandwidth
VoltageAccuracy <1% ofsetVoltage
RemoteSense Yes Standardonsingleoutputmodules
MinimumLoad No onanyoutput
TemperatureCoefficient <0.02% ofratedvoltageperC
LoadRegulation <0.5%or25mV for0-100%loadchange(withsenseconnected,<2%without)
LineRegulation <0.5% for90-264Vacinputchange(210-264Vacfor1500W)
CrossRegulation <0.2% for100%loadchangeonanyotheroutput
TransientResponseRecovery
<10% ofsetvoltagefor50%loadchange(above25%load)
500s forrecoveryto1%or100mVofsetvoltage(1000sforSmodule)
OverVoltageProtection Standard foralloutputs
OverCurrentProtection Standard foralloutputs
ShortCircuitProtection <150% ofratedcurrent,whenoutputvoltage<1%
OverTemperatureProtection Yes Shutsdownalloutputs.Cycleacoff/ontoreset
Note shutdowntempvariesaccordingtoambient,outputpowerandinputV
Alpha Series
2
ENVIRONMENT
Temperature 0Cto70Coperational,-40to85Cstorage(max12months)
Derating 50Cto70Cderateeachoutputby2.5%perC
LowTemperatureStart-up -20C
Humidity 5-95%RHnoncondensing
Shock 3000shocks,eachof10g (16ms)halfsine
Vibration 10-200Hz@1.5g
Altitude 3,000metresoperational(15,000metresnonoperational)
Pollution Degree2,Materialgroup3
IPRating IP10
IMMUNITY Criteria
ElectrostaticDischarge EN61000-4-2 Level4
Airdischarge 15kV
Contactdischarge 8kV
A
ElectromagneticField EN61000-4-3 Level3 10V/m(testedto12V/m) A
Fast/BurstTransient EN61000-4-4 Level4
Input 4kV
Outputs 2kV,
Testedat5kHzand100kHz
A
SurgeImmunity EN61000-4-5 Level3
LinetoLine (Differential) 1.1kV
LinetoEarth (CommonMode) 2.2kV
A
ConductedRFImmunity EN61000-4-6 Level3 10V(testedto12V) A
PowerFrequencyMagneticField EN61000-4-8 Level4 30AContinuous A
VoltageDips,Variation,Interruptions EN61000-4-11 Class3
A
Bfor5sinterruptions
VoltageFluctuations EN61000-4-14 Class3 For100to240Vnominal A
SAFETY APPROVALS
Date Amendments Date Amendments
EN60950-1 2001 IEC60601-1a 1988 A1,A2
UL60950-1 2003 UL60601-1a 2003
CSA22.2No60950-1 2003 CSA60601-1a 2003
IEC60950-1* 2001 CEMark LVDirective2006/95/EC(EN60950-1)
*CBCertificateandreportavailableonrequest a-OnlyforLL,RLandTLleakagevariants.CA400+CA1000only
EMISSIONS
RadiatedElectricField EN55022
ClassB(asperCISPR.22)
ClassAforAlpha1000/1500
Seeapplicationnotefordetails.
OnlyforStypeleakageversions
ConductedEmissions EN55022
ClassB(asperCISPR.22)
ClassAforAlpha1000/1500
OnlyforStypeleakageversions.
M&LtypesmeetClassA
ConductedHarmonics EN61000-3-2:2001 ComplianttoClassA
Flicker EN61000-3-3:1995+A1:2001 Compliant-d
max
only.
ISOLATION
InputtoOutput Reinforced 4.3kV(dc) OutputtoEarth Operational 500V(dc)
InputtoEarth Basic 2.3kV(dc) OutputtoOutput Operational 500V(dc)
PRODUCT, GENERIC & COLLATERAL STANDARDS
LowVoltagePowerSupply,EMC EN61204-3:2001
ComplianttoHigh
SeverityImmunity
ClassAemissionsforCA1000/CA1500
MedicalElectricalEquipment,EMC EN61601-1-2:2001 Compliant ClassAemissionsforCA1000/CA1500
Immunityforresidential,commercialandlight
industrialenvironments
EN61000-6-1:2001 Compliant
Immunityforindustrialenvironments EN61000-6-2:2001 Compliant
Emissionsforresidential,commercialand
lightindustrialenvironments
EN61000-6-3:2001 Compliant CA1000andCA1500notcompliant
Emissionsforindustrialenvironments EN61000-6-4:2001 Compliant
Alpha Series
3
OUTPUT VOLTAGES (single output modules) (twin output modules)
Module
Adjustment
Range (Volts)
Amps Slots Module
V1 Adjustment
Range (Volts)
Amps
V2 Adjustment
Range (Volts)
Amps Slots
A 4.5 - 5.5 60 2 E 5 - 16 8 5 - 16 8 1
AA 4.5 - 6.5 60 2 EB 4.5 - 5.5 9 4.5 - 5.5 9 1
B 4.5 - 5.5 25 1 EQ 4.5 - 5.5 9 2.7 - 3.9 9 1
BB 4.5 - 6.5 25 1 H 18 - 32 5 18 - 32 5 1
C 5 - 16 16
a
1 P 18 - 29 5 5 - 16 8 1
D 18 - 29 8 1
F 9 - 16 33 2
G 17.5 - 29 25
b
2
a) 12Amaxabove12V
b) 21Amaxabove24.5V
c) Derateoutputcurrentby0.25A/Vabove40V
d) 1Amaxabove29V
J 30 - 48 10
c
2
K 18 - 29 15 2
L 1.8 - 3.2 25 1
M 5 - 16 8 1
N 18 - 32 5
d
1
Q 2.7 - 3.9 25 1
R 2.7 - 3.9 60 2
S 2.5 - 5.7 85 2
T 1.8 - 3.2 60 2
U 10 - 21 16 1
W 4.5 - 5.5 15 1
Z 4.5 - 5.5 25 1
TheextensiverangeofoutputmodulesandoptionsmakeitpossibletoachievemanycombinationsofVoltsandAmps.Toachievetheopti-
mumconfiguration,pleasecontactoursalesoffice.Howeveryoucanalsocreateyourownconfigurationfromthisdatasheetbyusingthe
guidebelow.
Configuring from Datasheet
1 CalculatetotaloutputpowertodetermineAlpha400W,600W,1000Wor1500Wandselectconverter,thenselectrequiredCoolingand
LeakageCurrentfromthefollowingtable:-
2 SelectOutputModulesandOptionsfromtheOutputVoltagestables.
Example-ifyourequire5.2V/18Awithoutputinhibit:-
a)selectBasclosestmatchforvoltageandcurrentandprefixwithvoltage(e.g.5.2B)
b)addsuffixforoption(ifrequired)
_PAforparallel/currentshare(forN+1redundantapplications)
_PPforparallel(increasecurrentfromonePSU)
_INforinhibit
_RPforremoteprogramming
_MF(onlyapplicableon1stmodule)forglobalinhibit,acfailand5V/50mAstandbysupply
c)repeatforotheroutputs
Ensurethatthetotalwidthofallselectedmodulesiswithintheslotsforthechosenconverter.Forexample:-
CA600LL 5A 12/12E 24D whichrepresentsafouroutput600WAlphawithForwardair,240AEarthLeakage,with:-
Output1=5V/60Awithremotesense
Output2=12V/8A
Output3=12V/8A
Output4=24V/8Awithremotesense
3 Contact TDK-Lambda to validate configuration and issue a part number.
Alpha Configuring Guide
Output
Power
400 (5slots)
600 (5slots)
1000 (7slots)
1500 (8slots)
Cooling
empty Forwardair-Standard
QFa Forwardair-Quietfan
RAb Reverseair
Earth Leakage
Current
(at264Vac,63Hz)
empty Standard1.1mA
ML 500A
LL 240A
RL 110A
TL 50A
CA 400 QF LL
Notes:
a) CA400/600only.CA400deratesto300W,CA600deratesto475W
b) Contactsalesofficefordetails
Alpha Series
4
4
5
6
1
2
3



Pin IN option PA option PP option RP option MF option
1 n/c +Sense +Sense +Sense Inhibit(low)
2 ModuleGood ModuleGood n/c -Sense 5Vsupply
3 Inhibit Starpoint n/c Control2 PowerFail
4 n/c -Sense -Sense n/c 0V
5 -Power -Power n/c Control1 Inhibit(high)
6 -Power Starpoint n/c n/c n/c
Alpha 400
Alpha 600
+
-
+
-
+
-
+
-
+
-
+
-
6
5
4
3
2
1
Remote sense
1 slot, 2 output 1 slot, 1 output 2 slot, 1 output
M
F

o
p
t
i
o
n
IN,PA,
PP,RP
Option
Option Connections
Alpha Series
5
Alpha 1000
Alpha 1500
Alpha Series
6
Document number 69698 - Rev 4.3 - Jan 11
L06AL 0|8TR|UT|0N
T0K-LAH0A EHEA www.emea-tdk-|ambda.com
T0K-Lambda France 8A8
ZAC des 0e|ac|es
8P 10ZZ-0orelz-|e-C|ale|
91910 Les u||s
Frarce
Te|: 33 1 0 12 Z1 5
Fax: 33 1 0 12 Z1
lrarce_lr.ld|-|aroda.cor
WWW.lr.ld|-|aroda.cor
lla|y 3a|es 0ll|ce
v|a de| Lavoralor| 128/130
20092 C|r|se||o 8a|saro (Vl)
lla|y
Te|: 39 02 1 29 38 3
Fax: 39 02 1 29 09 00
|rlo.|la||a_|l.ld|-|aroda.cor
WWW.|l.ld|-|aroda.cor
T0K-Lambda Cermany Cmbh
Kar|-8o|d-3lrasse 10
ZZ855 Ac|err
0errary
Te|: 19 Z811 0
Fax: 19 Z811 5000
|rlo.gerrary_de.ld|-|aroda.cor
WWW.de.ld|-|aroda.cor
Auslr|a 3a|es 0ll|ce
Aredslrasse 22
2511 Leooersdorl
Auslr|a
Te|: 13 225 55 81
Fax: 13 225 15 12
|rlo.gerrary_de.ld|-|aroda.cor
WWW.de.ld|-|aroda.cor
T0K-Lambda UK Ltd.
K|rgs|ey Averue
l|lracoroe
0evor EX31 8E3
ur|led K|rgdor
Te|: 11 (0) 12 Z1 85
Fax: 11 (0) 12 Z1 8 18 91
poWerso|ul|ors_u|.ld|-|aroda.cor
WWW.u|.ld|-|aroda.cor
Nem|c Lambda Ltd.
K|ooulz
0|val las||os|a 18800
lsrae|
Te|: 9 Z23 902 1333
Fax: 9 Z23 902 1ZZZ
|rlo_rer|c.co.||
WWW.rer|c.co.||
Russ|a
Tec|r|ca| 3upporl:
3l Pelersourg
Te|: Z (812) 58013
3a|es:
VoscoW
Te|: Z (199) Z55ZZ32
|rlo_ld|-|aroda.ru
WWW.ld|-|aroda.ru

You might also like