S900 Remote Terminal Unit

T&D
Energy Automation & Information

S900 Remote Terminal Unit

Introduction
The S900 is made up of components designed to implement systems tailored for Supervisory Control and Data Acquisition (SCADA).The S900 is constructed to the highest standards of performance, safety, and reliability to meet the requirements of the ELECTRICAL Power industry.

Main Features
Power :The S900 contains one 32bit 32-MHz microprocessor per processing unit. Modular Construction :The S900 incorporates a wide range of hardware modules : Industrial I/O modules Communications modules CPU modules Enclosures Peripheral devices Test and maintenance equipment. Capacity :The S900 has been specially designed for medium and large-capacity systems (up to 5000 I/Os). Distributed I/O :Inputs/outputs may be centralized or geographically distributed in a site.Processing units are interconnected through a FIP fieldbus (1Mb/s). Communication :The S900 uses standard communication protocols for : Communication with Master Station Communication with Intelligent Electronic Devices (IEDs).

Figure 1:The S900 Remote Terminal Unit

Flexibility :The S900 architecture aims to minimize the variety of hardware modules installed.Also module features are customized through software to reduce maintenance and the need for spare parts. Immunity :The S900 is designed to meet the international requirements relating to electrical strength in disturbed environments (including IEC, IEEE, and ANSI standards). Open architecture :The S900 architecture is based on a VMEbus that allows high levels of integration for additional hardware modules.

Environment
The S900 is integrated into a system that may include the following components : Conventional devices to be supervised and controlled ; Intelligent Electronic Devices (IEDs) to be supervised and controlled ; One, two or three master stations ; One or two printers ; One alphanumeric terminal (VDU + keyboard) ; One synchronization clock (Radio or Satellite).

Master Station 1

Master Station 1 Printer 1 Printer 2 S900 extended rack

Master Station 3 or local Station

S900 main rack

FIP Bus

Alphanumeric control
OPN A9311

IEDs

I/Os

I/Os

OPN A9311

OPN A9311

OPN A9311

IEDs

External clock

Figure 2: Environment Overview

User interface
Database running ORACLE. Programmable logic controller including the five defined IEC 61131-3 languages (ISaGRAF).

Scan cycle :1s minimum Offset and gain control Capacity : 480 Digital measurements (DRM) : BCD (16 bits), Binary (16 bits), Gray (16 bits), 1 among N (16 or 32 bits) Scan cycle :100ms minimum Capacity : 51 Countings (RCT) : Maximum count input frequency : 25Hz One or two inputs per remote counting Filtering Capacity : 144 Controls (RC) : Single, dual Transient from 100ms to 15s, continuous. Immediate operation, Remote Select Before Operate (RSBO), Local Select Before Operate (LSBO) Capacity : 1024 Analog setpoints (ASP) : Current 0-5mA, 0-10mA, 0-20mA, 5mA, 10mA, 20mA, 4-20mA Capacity : 60
3

Functions
The S900 RTU can handle both digital and analog inputs/outputs. Data capture and output are accomplished by I/O modules or via Intelligent Electronic Devices (IEDs).The entities and related functions controlled by the S900 RTU include : I/O Capacity Signalings (RS) : Single, dual Normal, reverse, transient Scan cycle :1ms to 10ms Filtering for complementary fault or fleeting Capacity : 4300 Analog measurements (ARM) : Current 4-20mA, 0-10mA, 10mA, 5mA, 1mA (with external resistors) Voltage 5V, 2.5V, 1.25V

Digital setpoints (DSP) : BCD (16 bits), Binary (16 bits), Gray (16 bits), 1 among N (16 or 32 bits). Direct execution or by steps (20 steps with a duration from 1s to 30s) Capacity : 51 Tap changer positions (TP) : BCD (3 decades), 1 among N coded, Decimal coded with tap Capacity : 51 Multiple master station communications The S900 can communicate with three master stations using separate communication protocols and separate databases for each of them.One master station is able to access S900 through two channels (dual channel connections). The S900 supports multiple protocols : IEC 60870-5-101. HNZ 66S15. HNZ-ELENAS. Many custom protocols.

Connection to IEDs The S900 can acquire data (I/O points) from IEDs.This is accomplished by polling each IED, through serial ports with a maximum speed of 19200 baud.Up to 32 serial ports can be managed for all the different communications (Master station, IEDs).Up to 256 IEDs can be connected to the S900 (primary and secondary racks). The S900 supports multiple protocols : Standard Modbus using RTU mode Extended Modbus for acquisition of time-tagged events IEC 60870-5-101 IEC 60870-5-103 (VDEW) K-bus Courier.
100

Field BUS FIP

To SAU900 board To SAU900 board

KITZ
G E C A L S T H O M T&D G E C A L S T H O M T&D

Kbus link to MiCOM relay


OPN A9311 OPN A9311 OPN A9311 OPN A9311 OPN A9311

Modbus link to Protections or PLC

Modbus link to Protections or PLC

Figure 3: Connection to IEDs

Automatic Functions Performing automatic controls based on ISaGRAF soft-logic package can be implemented on each CPU boards to define : Interlock functions Supervision functions Autoreclose, etc. Local Data logging The S900 supports : An alphanumeric terminal VDT900 (screen + keyboard) One or two printers The VDT900 provides the ability to :Monitor the real-time state of all digital and analog data ; Send operator commands ; Display the archive file ; Modify the date and time. The printer provides the ability to : Print status changes ; Print the result of the operator request Archiving Recording of 2000 events in a FIFO queue. Recording of system fault conditions in a special buffer containing up to 200 faults. Local or remote interface.

Full alarm Level Full Alarm Full S S Empty Alarm Empty 0 Start Alarm General S Program with Relay Logic (FDB) Program with Logic box (FDB)

1 1

Empty Empty Alarm

2 2

Full Full alarm

Program in Grafcet (SFC)

Figure 4: Automatic Functions

Local alarms Three loops can be used in the S900 for alarms. A RS, RM or internal status change can initiate a local alarm.The alarm contact closing time is user-selectable. Internal and external data can be grouped using a logical OR gate on one alarm loop.

Synchronization The S900 can be synchronized by an external clock or by the master station. The main CPU synchronizes the other racks through a FIPbus with an accuracy of 25s. The S900 can synchronize the IEDs with an accuracy less than 2ms. The internal clock accuracy is 10-5 s.
4

Tools and Peripherals


GBD900 GBD900 is a Database Generator implemented in a compatible PC running in a relational environment (ORACLE). The GDB900 configurator includes : Hardware configuration Operating parameters and limits Specific customers labels The databases for secondary racks are directly imported from the primary rack through the FIP fieldbus.
Figure 5: GBD900

SIM900 SIM900 is a master station simulator designed around a compatible PC laptop terminal.It permits the testing of the communication between the master station and the S900.
Figure 6: SIM900

SIM930 SIM930 is a test case used to simulate digital and analog inputs/outputs.
Figure 7: SIM930

Automatic call of stand-by staff Remote consultation

Wall mimic panel

Energy management : - curves of provisional load - not delivered energy - generators positioning - statistics - management of meters Remote PROCETTs

Mo

dbu

Transmissions to other computers

SCADA-PROCETT 5000W

RTU-S900

RTU-S900

Compatibility with PROCETT 5000W


The S900 can be used with the supervisory Control and Monitoring PROCETT 5000W. PROCETT 5000W is a centralized Supervisory Control and Data Acquisition (SCADA) system for local or remote site industrial facilities.Its high real-time performance make it ideally suited to handle events occurring in electric power networks and plants. Standards and Performance Pentium-based microcomputer. Windows multitasking operating system, and WRTEX real-time kernel. C++ object library. HNZ, Modbus and IEC 870-5-101communication protocols. Ethernet networking. Smart couplers.
6

Figure 8: PROCETT 5000W

Ease of operation Sophisticated, mouse-driven. Multiple windows, multiple screen (one or two). Cascaded, tiled and overlapping windows. Intuitive pull-down menus and icons. Dialog boxes and lists. Zoom in/out. Object-oriented graphics. Scalability PROCETTs :open and modular design lets you scale-up easily in terms of : Hardware architecture and functionality Associated peripheral devices Remote Terminal Units (RTUs) Communication capabilities.

Capacity PROCETT 5000W can handle up to: 10000 remote signals. Remote signals status inputs captured as single or dual, transient or continuous contacts 2000 remote controls. Remote controls outputs returned as single or dual, momentary or continuous contacts 2000 remote measurements. Remote measurements with analog or digital values 500 remote counts. Pulse inputs 500 setpoints. Setpoints with digital or analog output values.

Sample configurations
PROCETT 5000W

Direct link (figure 9) IEDs : Up to 255 IEDs. S900 : 1 main rack + Up to 31 secondary racks. Capacity : Up to 5000 I/0s FIP Bus : 1km maximum without transmitter
OPN A9311 OPN A9311

IEDs

Distance or local link


OPN A9311 OPN A9311 OPN A9311

FIP BUS
OPN A9311

Figure 9: Direct link between S900 and PROCETT 5000W

Concentrator S900 (figure 10) IEDs : Up to 255 IEDs per sub-RTU. S900 : One S900 in concentrator Up to nine S900 in sub-RTU connected to the concentrator Up to 32 racks per sub-RTU Capacity : Up to 5000 I/0s FIP Bus : 1km maximum per sub-RTU S900 without transmitter
FIP BUS
OPN A9311 OPN A9311 OPN A9311

PROCETT 5000W

S900 Concentrator

Distance or local link

IEDs

OPN A9311

OPN A9311

OPN A9311

Figure 10:With a S900 in concentrator

Concentrator ITE29 (figure 11) ITE29 : Up to 8 RTU S900 connected to the concentrator board IEDs : Up to 255 IEDs per RTU S900 S900 : Up to 32 racks per RTU Capacity : Up to 15000 I/0s FIP Bus 1km maximum per RTU S900 without transmitter
OPN A9311 OPN A9311

PROCETT 5000W

ITE29 Distance or local link ITE29

IEDs
OPN A9311

OPN A9311

FIP BUS

Figure 11:With a concentrator ITE29 7

Clock Master station(s)

Local operator station (PROCETT 5000W) Printer

External modem

Primary rack CPU + FIP Interface VME BUS I/O

Internal Modem

Serial Async Unit

Serial Async Unit Power supply

I/O

Serial Async Unit

I/O

FIP BUS

IEDs

OPN A9311

OPN A9311

OPN A9311

OPN A9311

First secondary rack I/O CPU + FIP Interface VME BUS Serial Async Unit I/O I/O I/O Power supply

OPN A9311

OPN A9311

OPN A9311

IEDs

Second secondary rack I/O CPU + FIP Interface VME BUS Serial Async Unit I/O I/O I/O Power supply

31 secondary racks maximum

OPN A9311

OPN A9311

OPN A9311

IEDs

The architecture of the S900 is based on a FIP bus used to connect the different rack units. Each rack incorporates a power supply, a CPU, I/O and communication modules on a VMEbus. The primary rack handles the communication, process controls, peripheral devices, inputs/outputs and general automatic functions. The secondary racks manage the inputs/outputs and local automatic functions.

Figure 12: General architecture

S900 Hardware Components

CPU 930-Main CPU Module 32-bit 68020 microprocessorbased. Clock frequency :32 MHz. Memory :8MB static RAM with lithium battery backup.256 KB EPROM. Static RAM with write-protect facility for each memory bank; Real-time clock. Lithium battery backed-up clock/calendar. VMEbus interface (24 address lines-16 data lines).

Two V24/V28 asynchronous lines (operating at 50 to 38400 baud) available on front-panel,= 9-pin CANNON connectors. Watchdog timer with automatic restart capability + Alarm loop. One Watchdog + power failure lamp. Six signal loops (including Watchdog). Eight front-panel status lamps. Two ON/OFF inputs. Interface for daughterboard FBS 910 over FIP network. Interface for rack-to-rack timing : 2100V peak isolation.

Power consumption : 5V supply : 1A ; +12V supply : 0.1A ; -12V supply : 0.1A. Module width : one slot in the VMEbus rack. MTBF : 36 years.

SAU 900-Serial Asynchronous Unit

FBS 910-Field Instrumentation Protocol Bus Subunit VLSI FULLFIP chip.

DAU 900-Digital Acquisition Unit (48Vdc), DAU 901 (24Vdc), DAU 902 (110/125Vdc), DAU 903 (220Vdc) DAU904 (60Vdc)

FIPLD1 medium driver (twisted pair). Private static RAM (256 KB). Line matching transformer (150W). Four isolated V.24/V.28 serial asynchronous links. VMEbus interface. Program baud rate ranging from 50 to 19200 baud per channel. Isolation between interface circuit and ground : 1.4kV peak at 50Hz. Isolation between interface circuit and logic : 2.8kV peak at 50Hz Electrical safety complies to IEC 950 Signals handled : TD, RD, RTS, CTS, DCD, DSR and DTR Four front-panel 9-pin CANNON connectors Power source : +5V supply :1.2A Module width : one slot in the VMEbus rack MTBF : 22.3 years Line isolation : 2.1kV peak at 50Hz. Line speed : 1Mbit/s. Front-panel 9-pin connector. Power source : +5V supply :200mA. Module width : 0 (plugged into CPU 900). MTBF : 83.3 years. 48 opto-isolated digital inputs. Dielectric isolation : 2.8kV peak at 50Hz. Input voltage current 24 Vdc (DAU901) 10 mA 48 Vdc (DAU900) 5 mA 110 Vdc (DAU902) 3 mA 125 Vdc (DAU902) 3 mA 220 Vdc (DAU903) 2 mA. One common point for eight inputs. Loop resistance : less than 100W Max. EMI protection : meets the requirements as described in IEC 255-4, IEEE 472 and ANSI C37-90 standards. Power source :+5V supply : 50mA. VMEbus rack. MTBF : 81.2 years.

10

DOU 900-Digital Output Unit

DOU 910-Digital Output Unit DOU 911-Digital Output Unit 32 digital relay outputs with execution relay. 48Vdc or 125Vdc control commands. Closing wetted to 48Vdc through 390W resistor or 125Vdc with short-circuit current limited to 2A. Open set to + reference voltage. Dielectric isolation : 2.8kV peak at 50Hz. EMI protection : meets the requirements as described in IEC 255-4, IEEE 472 and ANSI C37-90 standards. Watchdog timer. Output control chain selfmonitored. Output voltage monitored. Relays de-energized on fault condition. Output : 60Vdc through 390W or 60V : 0.5A or 125V :0.2A. Power sources :+5V supply : 30mA ; +12V supply : 20mA ; plus +5V supply : 40mA per closed contact. VMEbus interface. Module width :One slot in the VMEbus rack. MTBF :91 years.

DOU 920-Digital Output Unit 12 digital outputs with double normally open relays. For DO 0 to 7, one common point for 4 relays. For DO 8 to 11, one common point for 2 relays. The output is potential free. Dielectric isolation: 2.8kV peak at 50Hz. EMI protection: meets the requirements as described in IEC 255-4, IEEE 472 and ANSI C37-90 standards. Watchdog timer. Output control chain selfmonitored. +5V supply monitored. Auto control time monitored. Relays de-energised on fault condition. Breaking/closing capacity: Maximal voltage: 250VDC or VAC. Continuous current: 5A Surge current: 30A during 500 ms Closing power: 1000VA under L/R = 40 ms Open current: 0.2A under 220VDC and L/R=40ms; 4A under 230VAC and cos=0.4 Power sources: +5V supply: 30mA; +12V supply: 20mA; plus +5V supply: 40mA per closed contact. VME bus interface. Module width: One slot in the VME bus rack. MTBF: 91 years

32 digital relay outputs. One common point for two outputs. Dielectric isolation : 2.8kV peak at 50Hz. EMI protection : meets the requirements as described in IEC 255-4, IEEE 472 and ANSI C3790 standards. Watchdog timer. Output control chain selfmonitored. +5V supply monitored. Supervision of the self-monitoring function. Relays de-energized on fault condition. Breaking capacity : 2A-250V250VA/600W. Power sources : +5V supply : 50mA ; +12V supply : 20mA ; plus +5V supply : 40mA per closed contact. VMEbus interface. Module width :One slot in the VMEbus rack. MTBF :123.6 years.

11

ACU 900-Analog to digital Converter Unit

AAU 900-Analog Acquisition Unit

AOU 900-Analog Output Unit

12-bit A/D Converter (11 bits + sign). Conversion method : Successive approximation. Conversion rate : 120 samples/second. Common-mode rejection ratio : 99dB at 50Hz. Accuracy including AAU : better than 0.1% (voltage), 0.2% (current) at 25C (full scale). Temperature coefficient : 30ppm/C. Power sources : +5V supply : 26mA ; +12V supply : 30mA ; -12V supply : 30mA. VME interface. Module width :one slot in the VMEbus rack. MTBF : 196.3 years.

24 multiplexed analog inputs. Input ranges : 5/10/20mA ; 4-20mA ; 1.25/2.5/5V. Series-mode rejection ratio : 36dB at 50Hz. Isolation voltage : 2.8kV peak at 50Hz in common mode. Input impedance : 5mA-1000W ; 10mA-500W ; 20mA-250W. EMI protection : meets the requirements as described in IEC 255-4, IEEE 472 and ANSI C37-90 standards. Power sources : +5V supply : 30mA ; +12V supply : 60mA ; -12V supply : 60mA. VMEbus interface. Module width :one slot in the VMEbus rack. MTBF : 77.3 years.

Six analog outputs. Output ranges : 5/10/20mA. Resolution : 11 bit + sign. Accuracy : better than 0.2% at 25C (full scale). Isolation voltage : 2.8kV peak at 50Hz in common mode. Output impedance : greater than 1MW. Load impedance : 5mA-6000W ; 10mA-3000W ; 20mA-1500W. EMI protection : meets the requirements as described in IEC 255-4, IEEE 472 and ANSI C37-90 standards. Power sources : +5V supply : 160mA ; +12V supply : 1A ; +12V supply : 0A from external power supply. VMEbus interface. MTBF : 76.4 years.

12

PCU 900-Power Converter Unit (48Vdc), PCU 910 (24Vdc), PCU 920 (110/125Vdc), PCU 930 (220/250Vdc)

RACK 900-VME rack with I/O connected via rear-panel connector

SIM 930-I/0 Simulator

Control panel used to simulate inputs/outputs. Double size Eurocard VME rack. Width : 19 inches. Height : 6U. Depth : 300mm. 21 slots available (20.32 pitch). VMEbus (P1) on PCB Address bus (24 bits) Data bus (16 bits) Control signals +5V and 12V. I/O connected via rear-mounted removable 64-pin DIN connector. MTBF : 103.8 years. Simulates 48 digital inputs using switches. Displays 32 digital outputs. Simulates 24 analog inputs. Selects 1 among 24 inputs. Incorporates two trimpots. Returns one analog output on terminal Selects 1 among 6 outputs. Two terminals for connection to a voltmeter. Simulates counting. Incorporates 1 trimpot to adjust pulse speed. Powered by an external 24, 48, or 125Vdc source. Supplied with cables.

Input voltages: 48Vdc : 20% (PCU 900) 24Vdc : 20% (PCU 910) 110Vdc : 20% (PCU 920) 125Vdc : 20% (PCU 920) 220Vdc : 20% (PCU 930) 250Vdc : 20%, +10% (PCU 930). Output voltage supplied : +5V and 12V for the VMEbus. Floating power supply (primary and secondary). Switched and fused protected. One PCU per rack. Module width : two slots in the VMEbus rack. MTBF : 23 years.

We can provide standard or special enclosures. Please contact us.

13

SIM 900-Master Station Simulator

VDT 900-Alphanumeric Video Display Terminal RS 232 interface. Display format :80 columns by 25 lines. Power supply :230Vac or 110Vac.

PROCETT 5000W-Local Operator Station

Used for testing and commissioning a typical configuration PC-based with the following minimum requirements : VGA colour display, keyboard, 12MB RAM, 51/4 or 31/2 disk drive Hard disk > 30MB, mouse, printer One parallel port and one serial port Interfaces with the S900 RTU via one or two serial channels on communication module Supplied with cable for connection to S900 Software license SIL900 GBD 900-Database Generator Generate S900 and SIM 900 database PC-based with the following minimum requirements : VGA color display, 12MB RAM, 420MB hard disk Printer Software license DBL 900 Software license Windows 95 AUT 900-Logic Diagram Generator Generation of S900 programmable logic PC based with the following minimum requirements : VGA color display, 12 MB RAM, 420 MB hard disk CD-ROM drive, 31/2, 1.44 MB floppy Software license ISaGRAF
14

PRT 900-Printer RS 232 interface Print speed :300 cps Print format :132 columns Power supply :230 Vac or 110 Vac

PC-based on Pentium CPU with the following minimum requirements : 48MB of RAM, 1 GB of highspeed, hard disk drive storage 31/2, 1.44 MB floppy drive, CD-ROM drive Color graphic monitors (super VGA), keyboard and mouse Printer(s) Software License PROCETT 5000W Software license Windows 95

Operating conditions Power supply Environmental : Influence of temperature cold, temperature = 0C dry, heat, temperature = 60C Damp heat, steady state temperature = 40C, relative humidity = 95%, duration = 4 days Rapid variation temperature variation speed = 20C/h, limits of temperature : 0C to 60C Salt mist duration = 4 days Mechanical conditions : Sine wave vibration frequency range :10-500Hz, amplitude :10/57Hz = 0.035mm acceleration : 57 to 500Hz = 0.5g, duration = 10 cycles Electrical safety : Insulation resistance voltage = 500V, duration = 1minute, resistance > 100MW Dielectric withstand voltage : 2kV (50Hz) for I/O voltage : 1.5kV (50Hz) for FIP link voltage : 1kV (50Hz) for asynchronous links Impulse voltage withstand impulse waveform : 1.2s/50s voltage : 5kV (CM) for digital input/output voltage : 2kV (CM) for analog input/output voltage : 3kV (CM) for power supply and FIP Protection indexIP 21 DC Power distributing immunity Short interruptions : 20ms Electromagnetic Compatibility Oscillatory waves : 2.5kV (CM), 1kV (DM) Fast transient disturbance : 2kV (CM), 5.0kHz, 1 minute Electrostatic discharge : 6kV point contact discharge 8kV discharge in air Susceptibility :26 to 1000MHz, 10V/m Magnetic Compatibility : Susceptibility : 50/60Hz, 30A/m IEC 870-2-1 IEC 255-22.1 IEC 1000-4-4 IEC 255-5 IEC 68-2-1 IEC 68-2-2 IEC 68-2-3 IEC 68-2-14 IEC 68-2-11 24Vdc, 48Vdc, 110Vdc, 125Vdc, 220Vdc 250Vdc 20% 20%, +10%

IEC 68-2-6

IEC 255-5

IEC 255-5

IEC 1000-4-2 IEC 1000-4-3 IEC 1000-4-8

DESIGN, MANUFACTURING, MARKETING, SALES AND CURATIVE MAINTENANCE OF SUPERVISORY CONTROL AND DATA ACQUISITION (SCADA) SYSTEMS OF ALSTOM T&D EAI

ISO9001
15

CE Marking

Transmission & Distribution Energy Automation & Information, Le Sextant, 3 avenue Andr Malraux, 92300 Levallois-Perret. France Tel: +33 (0) 1 41 49 20 00 Fax: +33 (0) 1 41 49 24 85 energy-automation.information@tde.alstom.com www.tde.alstom.com Contact Centre on line 24 hours a day : +44 (0) 1785 25 00 70
ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM. Other names mentioned, registered or not, are the property of their respective companies. Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.

Publication: S900/EN BR/Ea

2002 ALSTOM - 060201 Clment Imprimeurs