Technical Comparison

INPUT Nominal Input Voltage Input Frequency Input Connections Input voltage range for main operations Maximum Input Current Input Breaker Capacity Maximum Short Circuit Withstand (Icw) Input Total Harmonic Distortion Type of Input Protection Required OUTPUT Output Power Capacity Max Configurable Power Nominal Output Voltage Output Voltage Note Efficiency at Full Load Output Voltage Distortion Output Frequency (sync to mains) Crest Factor Waveform Type Output Connections Output Voltage Tolerance Output Voltage THD Overload Operation Efficiency at Half Load

Required Output Current Protection Neutral Output Current Bypass Battries & Run Time Battery Type Included Battery Modules Available Battery Slots Typical recharge time Nominal Battery Voltage End of Discharge Battery Voltage

Page 1

Sheet1
DC Over current Protection Maximum Available Short Circuit Current Efficiency in Battery Operation End of Discharge Maximum Battery Current

Overload Operation Hot Swappable Communications & Management

Interface Port(s) Available SmartSlot Interface Quantity Control panel Audible Alarm Emergency Power Off (EPO) Physical Maximum Height Maximum Width Maximum Depth Rack Height Environmental Operating Environment Operating Relative Humidity Protection Class Audible noise at 1 meter from surface Conformance

Regulatory Approvals

Page 2

Sheet1

APC Symmetra PX (32 KW Scalable to 160 KW) 400V 3PH 40 - 70 Hz Hard Wire 5-wire (3PH + N + G) 340 - 477V 59A 100.0 A 30.0 kA Less than 5% for full load gL fuse 32 kW / 32 kVA 160 kW / 160 kVA 230V,400V 3PH Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage 95.00% Less than 2% 50/60 Hz +/- 3 Hz user adjustable +/- 0.1 Unlimited Sine wave (1) Hard Wire 5-wire (3PH + N + G) +/-1% static and +/- 5% at 100% load step < 2% for 0 to 100% linear load and < 5% for full n 10 minutes @ 125% and 60 seconds @ 150% 95.00%

250A 80A Built-in Static Bypass VRLA 3 6 3.50 hour(s) +/-192 V (split battery referenced to neutral) +/-154 V

Page 3

Sheet1
756A 2 kA 94.00% 110

10 minutes @ 125% and 60 seconds @ 150% Yes

SmartSlot 2 Multi-function LCD status and control console Alarm when on battery : distinctive low battery alarm : configurable delays Yes

1991.00 mm 1200.00 mm 1070.00 mm 42U 0 - 40 C 0 - 95% NEMA 1 61.00 dBA

EN 50091-1,EN/IEC 62040-3,EN/IEC 62040-1-1,FCC Part 15 Class A,VFI-SS-111

Page 4

Sheet1

Emerson APM (30 KW Scalable to 150 KW) 380 / 400 / 415, 3PH 40 - 70 Hz 4 Wires 305V 477V, 208V 304V (With Linear Aerating up to 70% Load) 60A Not installed (to be installed by client) Not available <1 (linear load), <4 (non-linear load3) Not installed (recommended to install by client) 30 kW / 30 kVA 150 kW / 150 kVA 380 / 400 / 415, 3PH 380 / 400 / 415, 3PH >96% at 50% - 70% Load, >95% at 25% Load <1% for steady state, and <5% for transient state 50/60 Hz +/- 3 Hz user adjustable, +/- 0.02% Data Not available Sine wave 3PH, 4 wires Steady State 1% (balanced load), 5% transient voltage response <1% for Linear Load & <4% for Non-Linear Load 10 minutes @ 125% and 60 seconds @ 150% , 20msecond @ >150% 95.50% Thermomagnetic circuit-breaker, rated up to 125% of nominal output current.(installed by client) 1.7 x In Built-in Static Bypass VRLA 2 5 Not available ? ?

Remarks

Emerson Lags

Emerson Lags

Emerson Lags

Emerson Leads Emerson Leads

Emerson Lags

Emerson Leads

Emerson Leads

Page 5

Sheet1
? ? ? ? <105% load, 60min 105%~125% load, 10min, 125%~150% load, 1min, >150% load, 200ms Yes The RS232 port provides serial data.Liebert APM

UPS has facility of internally fitted SNMP and Modbus card options.
Avocents Infrastructure Management Solutions Internally fitted SNMP and Modbus card options. UPS alarm, for example, AC input failure

UPS fault, for example, fuse or hardware fault


Yes

2000 600 1100 No info available 0 - 40 C 0 - 95% IP-20 55 62 dBA

Emerson Leads

IEC60950-1; IEC 62040-1-1/A; En50091-2 Class-A EN50091-2/IEC62040-2/AS 62040-2 (C3) EN50091-3/IEC62040-3/AS 62040-3 (VFI SS 111)

Page 6