You are on page 1of 32

Symmetra LX

Technical Training

Agenda
Technical Training Mechanical Design System Architecture Theory of Operation System User Interface Information Sources Questions and Answers

The target audience of this presentation is expected to have completed Symmetra LX Family Overview and Symmetra LX Configuration trainings.
2003 APC corporation.

Systems
Tower 230V

8kVA N+1 (5.6kW)

16kVA N+1 4-batts (11.2kW)

16kVA N+1 13-batts (11.2kW)


Ships with (2) Power Modules, (9) Battery Modules installed, rest ship on pallet Up to (13 Battery Modules) 100A hard-wire input 230V L-N-G 400V L-L-L-N-G No receptacles

Ships (1) Power Modules, (1) Ships (2) Power Modules, (2) Battery Battery Modules installed, rest ship Modules installed, rest ship on pallet on pallet Up to (4) Battery Modules Up to (2) Battery Modules 100A hard-wire input 50A hard-wire input 230V L-N-G 230V L-N-G 400V L-L-L-N-G 400V L-L-L-N-G No receptacles
Symmetra LX 2003 APC corporation.

No receptacles

Systems
Rack-mount 230/480V

8kVA N+1 13U (6.4kW)


Ships as empty frame w/ modules on pallet 50A hard-wire input 230V L-N-G 400V L-L-L-N-G (6) IEC320C19; (8)IEC320C13
Symmetra LX 2003 APC corporation.

16kVA N+1 19U (12.8kW)


Ships as empty frame w/ modules on pallet 100A hard-wire input 230V L-N-G 400V L-L-L-N-G (10) IEC320C19; (8)IEC320C13

Extended Run Frames

Stackable 9-battery tower XR frame


18 battery modules in same space as 12 today. Available Q4. Today use current black Symmetra XR12 12-battery frame.
Symmetra LX 2003 APC corporation.

Stackable 3 and 9-battery rack-mount XR frames


Available Q4. Today use current black SYRMXR4I 4-battery frame.

Battery cabinet extension cables


Enables connection from LX tower to current Symmetra XR12 SYAOPT3- 208V 4-foot SYAOPT3I- 230V 4-foot SYOPT3- 208V 15-foot SYOPT3I- 230V 15-foot

Mechanical design
120/208 and 230 VAC

Footprint: 19.0 x 29.1 inches 482.5 mm x 738.5 mm


XR9 frame 8kVA frame XR3 frame

16kVA XR frame

16kVA frame

TWR RM
2003 APC corporation.

N/A 5U

23.7 inches 602.0 mm

23.7 inches 602.0 mm

34.2 inches 869.0 mm

57.0 inches 1446.5 mm

13U

13U

19U

N/A

Mechanical design
All systems

Rack mount
2003 APC corporation.

Tower

Mechanical design
UPS Network Management Card with Environmental Monitoring
Provides remote user interface, Manage via Web Browser, SNMP, and Telnet. Includes PowerChute Network Shutdown.

Extended Run Connector Allows hot-install of up to seven Extended Run Frames for quick, easy response to changing runtime needs Removable Input/Output Wiring Tray (LX only)
Allows easy hard-wiring at install and fast maintenance.

Extended Run Communication Card


Allows Intelligence Modules to monitor the health of external batteries

Field-replaceable Power Distribution Panels


Enable quick in-field modification of output receptacles to fit changing needs. Tower models ship with no receptacles, rack-mount models ship with receptacles appropriate for different voltage needs.
Symmetra 2003 APC corporation.

1:1 & 3:1 option in single product (230V LX only)


Same product can be wired for either 3 or 1-phase input. (Rack/Tower 9 and 19 slot frames)

230V

200/208V

Mechanical design
All systems

Rack mount
2003 APC corporation.

Tower

Mechanical design
Frame Electronic Module Field-replaceable, Not Hot-swappable Intelligence Modules Hot-swappable
only one at a time!

All systems

Battery Modules Hot-swappable PowerView Display Hot-swappable Flash upgradeable

Single Front Door Field-replaceable

Power Modules Hot-swappable

Symmetra LX 2003 APC corporation.

Theory of operation
All systems

Power sharing and redundancy N+1


2003 APC corporation.

Mechanical design
All systems

Frame Electronic Module

Intelligence Module

Power Module

Battery Module

2003 APC corporation.

Mechanical design
All systems

Network Management Card

I/O wiring tray

Symmetra LX communications card EPO and Enable Switch External battery connector
2003 APC corporation.

PDU

System architecture
230 VAC

2003 APC corporation.

Symmetra LX Theory of Operation


Power Module Diagram
155 -276 VAC Input

Rectifier & PFC

+/- DC Bus

Inverter Output Section

240 VAC 120/208V or 120/240V 60hz Output


220/230/240V 50hz

A/C out (typical)

Battery Charger

120 VDC Battery

2003 APC corporation.

Theory of operation
230 VAC

Symmetra LX Power Module DC Bus +/-400VDC

AC-1

PFC (Power Factor Correction)

INVERTER

AC-OUT

+BATT AC Battery Charger

MID MID

Double conversion on-line UPS

2003 APC corporation.

Theory of operation
230 VAC

Symmetra LX Power Module DC Bus PFC +/-400VDC (Power Factor Correction)

AC-1

INVERTER

AC-OUT

+BATT AC Battery Charger

MID MID

Utility power

2003 APC corporation.

Theory of operation
230 VAC

Symmetra LX Power Module DC Bus +/-400VDC

AC-1

PFC (Power Factor Correction)

INVERTER

AC-OUT

+BATT AC Battery Charger

MID MID

Battery power

2003 APC corporation.

Theory of operation: Power module


All systems
100/200 and 120/208 VAC models Phase to Phase Per Phase 200 208 240 100 120 SYPM4KP 3740 3890 4000 1870 2244 2800 3200 3200 1400 1600 18.7 18.7 16.7 18.7 18.7 0.75 0.82 0.80 0.75 0.71 0.90 0.90 0.98 0.90 0.90 230 VAC models Phase to Neutral 220 230 240 SYPM4KI 4000 4000 4000 2800 2800 2800 18.2 17.4 16.7 0.70 0.70 0.70 0.98/0.90

Part number: Max Output Power (kVA) Max Output Power (Watts) Max Output Current (from Inverters) Output Power Factor (Watt/VA) Input Power Factor (Watt/VA)

2003 APC corporation.

Theory of operation: Overload


Less than 105%: indefinitely More than 105%: 4 seconds. Then Overload fault is indicated.
All systems

2003 APC corporation.

Theory of operation: Battery Module:


All systems SYBT5 SYBT5FR for 120/208 and 230VAC models for 100/200 VAC model

120VDC: 10 X 12VDC 7.2AH Maximum 7 extended run (XR) frames 4 Power Modules charge 4 Battery Modules in appx. 3 hours. Each Power Module contains a 300W charger.

XR3 frame

XR9 frame
2003 APC corporation.

Theory of operation: Intelligence module


All systems

Module Fault This IM in Control

Normal Bypass UPS_ON operation

Cold Boot Switch

LEDs

Diagnostics serial port


2003 APC corporation.

System user interface


All systems

Input circuit breaker

Maintenance bypass switch

PowerView display
2003 APC corporation.

System user interface


All systems SmartSlot Cards

Network interface card (standard)

ENABLE switch

Simple signalling interface


2003 APC corporation.

InfraStruXure Management InfraStruXure Management Design Benefits Design Benefits Network Management Card Screen Shot Network Management Card Screen Shot

Browser Accessible Browser Accessible Saves installing software on the Saves installing software on the network management console. network management console.

Main Status Screen: Main Status Screen: Overview of key Overview of key functions; UPS and card functions; UPS and card

Left-hand bar Left-hand bar Quick link other Quick link other functions functions
2003 APC corporation.

System user interface


All systems XR battery module System enable switch EPO switch connector (dry contact or external 24VDC) External PowerView display (up to 15 feet / 5 meters away)

2003 APC corporation.

User Interface Design Benefits


Navigation Display
High visibility and backlit Menu, status, mode change and set point adjustment

Escape
Easy to return to previous menu item

Security
Password protected

Help Status Lights


Indicates current system status, alarms, warnings independent of LCD display

Consistent User Interface


Same user interface across all APC UPS, cooling, and environmental monitoring products

Detailed instruction on operation

Enter
Select current menu item, confirm change

2003 APC corporation.

Accessories
208/120V SYAPD1 - (1) L14-30R, (2) L5-20R SYPD3 - (1) L6-30R, (2) L6-20R SYPD7 - (3) L6-20R SYPD11 - (2) L6-30R 230V SYPD4 - (2) IEC320C19, (8) IEC320C13 SYPD8 - (4) IEC320C19 SYPD9 - (1) 32A hard-wire connection
Symmetra LX 2003 APC corporation.

Replacement internal back-plates

Retaining Screws

SYPD10 - (1) IEC309, (2) IEC320C19

Accessories
1Phase Service Bypass Panels Wall-mount or rack-mount Online, test, and bypass modes Different options for SYLX World-wide
SBP16KP- All hardwire connections

208/120V
SBP16KRMP4U- (6) L14-30R SBP16KRMP4U-HW (1) L14-30R, (3) L5-20R, (1) HW 100A

230V
SBP16KRMI4U- (3) HW 32A

Symmetra LX 2003 APC corporation.

Accessories
Power Distribution Units (PDU)

Expansion PDU
Used to enable extra Rack PDU L14-30P input plug w/ 28 ft cord Output receptacles: 120V
AP7580- (4) L5-20R AP7582- (12) 5-20R AP7583- (4) L5-30R

208V
AP7581- (4) L6-20R AP7584- (4) L6-30R

230V (require SYPD9)


AP7585- (4) IEC320C19 16A AP7586- (4) IEC309 32A
Symmetra LX 2003 APC corporation.

Rack PDU: Basic, Metered, Switched


Vertical & Tool less Mount
Zero U mounting

Load Indicator LED


Identifies overload and warning conditions

Input Selector
Press to invert display Press to monitor the next phase

Snap into a NetShelter VX rear channel

Current Monitor
Displays current draw for the phase indicated

Single input
One branch whip connection Multi-branch input provides 5.7kW of AC power

Reset Button
Resets Rack PDU without affecting outlet state

Serial Port
Provides local access to the control console

Network Connection
Access, configure, and manage via Web, SNMP, Telnet, or InfraStruXure Manager

Multiple Outlets
Connect multiple pieces of equipment Provides 120V/208V on one strip

2003 APC corporation.

Questions

Symmetra LX 2003 APC corporation.