ELECTRICAL DEPARTMENT
Page 2
2. PRIMARY TRANSMISSION: Primary transmission is carried out at 132KV, 220 KV or 400KV.600 KV systems are also developed and 700KV to 1000KV is under design stage. Single circuit or double circuit over head transmission line is used. This line is run to different remote areas. One or more lines are used depending upon the need. A receiving station is used at the end of the transmission line.66KV voltage is stepped down to 66KV.
3. SECONDARY TRANSMISSION: Required numbers of 66kv secondary transmission lines are run in different areas. The secondary transmission is done either the over head lines or by the underground cables. Distribution substation is kept the end of the secondary Transmission line.66kv voltage is stepped down to 11kv in the distribution substation.
4. PRIMARY DISTRIBUTION OR HT DISTRIBUTION: In distribution substation the 66KV voltage is stepped down to 11KV.HT consumers are supplied power through 11KV feeder. This is called the primary Distribution .Other 11KV feeders are run to different area. Distribution Transformer is kept at the end of each 11KV feeder.
5. SECONDARY DISTRIBUTION OR LT DISTRIBUTION: Distribution transformer step down the 11KV voltage to 415V.From here the consumer are supplied power with the help of three Phase wire and one neutral wire. House hold consumer are given power through one phase and one neutral wire, while the consumer like flour mills, pump for agriculture etc.are given power through three phase wire and one neutral wire.
Page 3
1. Step up transformer: This transformer is kept in the switch yard of the generating station. This Transformer step up the generated voltage to the voltage of Transmission
2. Line supports: Steel tower are used to support the conductor of the transmission line.
3. Line insulators: Suspension and strain type porcelain insulator are used to insulate the conductor from the ground.
4. Conductor: Copper conductors were used for the transmission line but ACSR conductors are now widely used in place of copper conductor due to the increased price of copper.
5. Step down transformer: Step down transformer is provided at the end of the transmission line which steps down the primary transmission voltage.
Page 4
7. Regulators: Voltage regulators are provided for the voltage regulation of line and for the improvement of the power factor of the line, the synchronous condensers are provided at the end of the transmission line.
Page 5
Cross arms fitted to the poles or steel towers. And live wires are tied to the insulator. Line supports are made of wood, R.C.C. or steel. Here we shall obtain information about construction of different types of line supports and their relative advantages and disadvantages.
I)
When the length of an overhead transmission line is up to 50km and the line voltage is comparatively low (<20kv), it is usually considered as a short
Page 6
Transmission line. Due to smaller length and lower voltage, the capacitance effects are small and hence can be neglected.therefor, while studying performance of a short transmission line, only resistance and inductance of the line are taken into account.
II)
When the length of an overhead transmission line is about 50-150km and the line voltage is modernly high (>20kv<100kv), it is considered as a medium transmission line. Due to sufficient length and voltage of the line, the capacitance effects are taken into accont.for purposes of calculation, the distributed capacitance of the line is divided and lumped in the form of condensers shunted across the line at one or more points.
III)
When the length of an overhead transmission line is more than 150 km and line is very high (>100kv), it is considered as along transmission line. For the treatment of such a line, the lines constant are considered uniformly distributed over the whole length of the line and rigorous methods are employed for solution.
An overhead line may be used to transmit or distribute electrical power. The successful operation line depends to a great extent upon the mechanical design of the line. While construct an overhead line, it should be ensured that mechanical strength of the line is such so as to provide against the most probable weather condition. In general, the main components of an overhead line are
Page 7
OVERHEAD TRANSMISSON SYSTEM (1).conductor: Conductor which carry electric power from the sending end
station to the receiving end station.
(2). Supports:
Supports which may be poles or towers and keep the conductor from at a suitable level above the ground.
(3).insulator:
Insulator which are attached to supports and insulate the conductors from the ground.
Fig: c: insulator
4).cross arms:
Cross arms which provide support to the insulators.
Page 8
1: Wooden poles:
These are made of seasoned wood (Sal or chir) and are suitable for lines of moderate X-sectional are and of relatively shorter spans, say up to 50 meters. Such supports are cheap, easily available, provide insulating properties and, therefore, are widely used for distribution purposes in rural areas as an economical proposition. The wooden poles generally tend to rot below the ground level, causing foundation failure. In order to prevent this, the portion of the pole below the ground level is impregnated with preservative compounds like creosote oil. Double pole structure of the a or h type are often used to obtain higher transverse strength than could be economically provided by means of single poles.
Page 9
2: Steel poles:
The steel poles are often used as a substitute for wooden poles. They possess greater mechanical strength, longer life and permit longer spans to be used. Such poles are generally used for distribution purposes in the cities. This type of supports need to be galvanized or painted in order to prolong its life. Steel poles are two types (1): rail pole and (2): tubular pole.
Page 10
In tubular poles hollow round steel pipes are used. It is in three to four steps over the length. It is broad at the lower portion and narrow at the above. And steel poles can be used for the street lighting by bending the upper portion.
3: Rcc pole:
The reinforced concrete poles have become very popular as line supports in recent years. They have greater mechanical strength, longer life and permit longer spans than steel poles. Moreover, they give good outlook; require little maintaince and have good insulating properties.fig show R.C.C poles for single and double circuit. The holes in the poles facilities the climbing of poles and at the same time reduce the weight of line supports. The main difficulty with the use of these poles is the high cost of transport owing to their heavy weight. Therefore such poles are often manufactured at the site in order to avoid heavy cost of transportation.
Page 11
4: Steel tower:
In practice, wooden, steel and reinforced concrete poles are used for distribute purposes at low voltage, say up to 11kv.however, for long distance transmission at higher voltage, steel tower are invariably employed. Steel tower have greater mechanical strength are invariably employed. Steel tower have greater mechanical strength, longer life, can withstand most severe climatic condition and permit the use of longer spans. The risk of interrupted service due to broken or punctured insulation is considerably reduced owing to longer spans. Tower footings are usually grounded by driving rods into the earth. This minimizes the lightning troubles as each tower acts as a lightning conductor.
Page 12
Types of insulator:
The successful operation of an overhead line depends to a considerable extent upon the proper selection of insulator. There are several types of insulator but the most commonly used are pin type, suspension type strain insulator and shackle insulator.
Pin type insulators are used for transmission and distribution of electric power at the voltage up to 33kv the pin type insulator become too bulky and hence uneconomical. In case of puncture, the discharge occurs from conductor to pin through the body of the insulator. When such breakdown is involved, tice, sufficient thickness of porcelain is provided in the insulator to avoid puncture by the line voltage. The ratio of puncture strength to flash over voltage is known as safety factor. It is
Page 13
The cost of pin type insulator increases rapidly as the working voltage is increased.therefor, this type of insulator is not economical beyond 33kv.for high voltage (>33kv), it is usual practice to use suspension type insulator shown in fig. They consist of porcelain discs connected in series by metal links in the form of a string. The conductor is suspended at the bottom end of this string while the other end of the string is secured to the cross arm of the tower. Each unit or discs is designed for low voltage, say 11kv.the number of discs in series would obviously depend upon the working voltage. For instances, if the working voltage is 66kv, then six discs in series will be provided on the string.
Page 14
3: strain insulator:
When there is a dead end of the line or there is corner or sharp curve, the line is subjected to greater tension. In order to relive the line of excessive, strain insulator are used. For low voltage lines (<11kv), shackle insulator are used as strain insulator. However for high voltage transmission lines, strain insulator consists of an assembly of suspension insulator as shown in fig. The discs of insulator are used in the vertical plane. When the tension in lines is exceedingly high, as at long river spans, two or more strings are used in parallel.
Page 15
In early days, the shackle insulators were used as strain insulator. But now days they are frequently used for low voltage distribution lines. Such insulator can be used either in horizontal position or in a vertical position, they can be directly fixed to the pole with a bolt or to the cross arm.fig show a shackle insulator fixed to the pole. The conductor in the groove is fixed with a soft binding wire.
Corona:
When an alternating potential difference is applied across two conductors whose spacing is large as compared to their diameters, there is no apparent change in the condition of atmosphere air surrounding the wires if the applied voltage is low. However, when the applied voltage exceeds a certain value, called critical disruptive voltage the conductor are surrounded by a faint violet glow called corona.
Page 16
Theory of corona formation some ionization is always present in air due to cosmic rays, ultraviolet radiation and radioactivity. Therefore, under normal condition, the air around the conductor contains some ionized particles and neutral molecules. When p.d is applied between the conductor potential gradient is setup in the air which will have maximum value at the conductor surfaces. Under the
Page 17
Skin effect:
When a conductor is carrying steady direct current (d.c.),this current is uniformly distributed over the whole x-section of the conductor .however an alternating current flowing through the conductor does not distribute uniformly rather it has the tendency to concentrate near the surface of the conductor as shown in fig. This is known as skin effect. The tendency of alternating current to concentrate near the surface of a conductor is known as skin effect.
Page 18
The skin effect depends upon the following factor: (i) (ii) nature of material Diameter of wire: - increase with the diameter of wire.
Page 19
It may be noted that skin effect is negligible when the supply frequency is low (<50Hz) and conductor diameter is small (<1cm).
2. Maintenance.
3. Possibility of fault.
4. Safety.
Less (adv.) Inductance is less due to the closed conductor, so the voltage drop is less due to the inductive reactance (adv.) No disturbance is caused (adv.)
Page 20
Fault location is easy and repairing is also easy.(adv.) Overall cost is less even 9. Capital cost. through the cost of supports is more (adv.) 10.Working voltage. Overhead lines are used up to and more than 400 kv(adv.) More. Changes are easy 11.Flexibility (adv.)
CONCLUSION:
Our discussion answers the most important questions about the behavior of transmission lines. We show that it is the attenuation of higher frequencies that causes the rounding of voltage transitions as they propagate along a transmission line. Higher frequencies travel faster than lower frequencies, so dispersion cannot be the cause of the rounding. Very low frequencies travel several times slower than high frequencies, and the result is that the low-frequency content of a voltage transition might arrive several microseconds later than the initial sharp edge. This late-arrival explains the settling of transitions that we observe at the far end of long transmission lines.
REFERANCES:
Www.wikipedia.org/wiki/Electric_power_transmission Www.intel.com/education/.../class06_transmission_line_basics www.amanogawa.com/transmission.html
http://indolinkenglish.wordpress.com http://www.velco.com/Environment/Documents/Transmission%20Line