You are on page 1of 4

Prime Rating

These ratings are applicable for supplying continuous electrical power


(at variable load) in lieu of commercially purchased power. There is no
limitation to the annual hours of operation and this model can supply 10%
overload power for 1 hour in 12 hours.
Standby Rating
These ratings are applicable for supplying continuous electrical power (at
variable load) in the event of a utility power failure. No overload is
permitted on these ratings. The alternator on this model is peak
continuous rated (as defined in ISO 8528-3).
Standard Reference Conditions
Note: Standard reference conditions 25C (77F) Air Inlet Temp, 100m
(328 ft) A.S.L. 30% relative humidity.
Fuel consumption data at full load with diesel fuel with specific gravity of
0.85 and conforming to BS2869: 1998, Class A2.
FG Wilson has manufacturing facilities in the following locations:
Northern Ireland Brazil China India USA
With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.
To contact your local Sales Office please visit the FG Wilson website at www.FGWilson.com
Output Ratings Ratings and Performance Data
Leroy Somer
Generating Set Model Prime* Standby* Engine Make & Model:
Alternator manufactured for
FG Wilson by:
Alternator Model:
Control Panel:
Circuit Breaker Type:
Engine Speed: RPM
Base Frame:
Frequency: 50 Hz 60 Hz
Fuel Tank Capacity:
litres (US gal)
Dimensions and Weights
Length (L)
mm (in)
Width (W)
mm (in)
Height (H)
mm (in)
Dry
kg (lb)
Wet
kg (lb)
Dry = With Lube Oil Wet = With Lube Oil and Coolant
Ratings in accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-1/22.
Generating set pictured may include optional accessories.
www.FGWilson.com
/ /
/ /
Fuel Consumption: l/hr (US gal/hr)
(100% Load)
- Prime
PowerWizard 1
Ratings at power factor.
Image for illustration purposes only.
- Standby
Available Options
FG Wilson offer a range of optional features to tailor our generating
sets to meet your power needs. Options include:
Upgrade to CE Certification
A wide range of Sound Attenuated Enclosures
A variety of generating set control and synchronising panels
Additional alarms and shutdowns
A selection of exhaust silencer noise levels
For further information on all of the standard and optional features
accompanying this product please contact your local Dealer or visit:
www.FGWilson.com
Perkins 2806A-E18TAG3
LL7024J
-
480V, 60 Hz
- - - -
675.0 kVA 540.0 kW 750.0 kVA 600.0 kW
P675P5/P750E5
Heavy Duty Fabricated Steel
3 Pole ACB/MCCB
1800 -
1000 (264.2)
138.4 (36.6) -
155.6 (41.1) -
4111 (161.9) 1536 (60.5) 2246 (88.4) 4905 (10814) 4975 (10968)
0.8
Exhaust System
Silencer Type:
Silencer Model & Quantity:
Pressure Drop Across Silencer
System: kPa (in Hg)
Silencer Noise Reduction Level: dB
Maximum Allowable Back Pressure:
kPa (in Hg)
Exhaust Gas Flow: m/min (cfm)
Exhaust Gas Temperature: C (F)
60 Hz 50 Hz
- Prime
- Standby
- Prime
- Standby
Lubrication System
Oil Filter Type:
Total Oil Capacity: l (US gal)
Oil Pan: l (US gal)
Oil Type:
Oil Cooling Method:
Cooling System
Cooling System Capacity: l (US gal)
Water Pump Type:
Heat Rejected to Water & Lube Oil:
kW (Btu/min)
Heat Radiation to Room: Heat radiated from engine and alternator
kW (Btu/min)
Radiator Fan Load: kW (hp)
Radiator Cooling Airflow: m/min (cfm)
External Restriction to
Cooling Airflow: Pa (in H
2
O)
Cooling system designed to operate in ambient conditions up to 50C (122F).
Contact your local FG Wilson Dealer for power ratings at specific site conditions.
60 Hz 50 Hz
- Prime
- Standby
- Prime
- Standby
Engine Technical Data Air Systems
No. of Cylinders / Alignment:
Cycle:
Bore / Stroke: mm (in)
Induction:
Engine Speed: rpm
Performance
Gross Engine Power: kW (hp)
BMEP: kPa (psi)
Fuel System
Fuel Filter Type:
Recommended Fuel:
Fuel Consumption: l/hr (US gal/hr)
Prime
50 Hz
60 Hz
110% 100% 75% 50%
Load Load Load Load
60 Hz
50 Hz
Standby Load Load Load Load
50% 75% 100% 110%
(Based on diesel fuel with a specific gravity of 0.84 and conforming to BS2869,
Class A2)
Air Filter Type:
Combustion Air Flow: m/min (cfm)
Max. Combustion Air Intate
Restriction: kPa (in H
2
O)
60 Hz 50 Hz
Cooling Method:
Governing Type:
Governing Class:
Compression Ratio:
Displacement: l (cu. in)
Moment of Inertia: kg m (lb/in)
Engine Electrical System:
Weight: kg (lb)
60 Hz 50 Hz
- Standby
- Prime
- Standby
- Prime
- Standby
- Prime
- Dry
- Wet
- Voltage / Ground
- Battery Charger Amps
513 (955) -
542 (1008) -
130.0 (4591) -
143.0 (5050) -
6.8 (2.0) -
10 -
0.47 (0.139) -
SD200 (1)
Industrial
Water
53.5 (14.1)
55.5 (14.7)
Eco, Full Flow
API CH4 / CI4
61.0 (16.1) -
Centrifugal
163.9 (9321)
170.9 (9719)
-
-
41.6 (2366) -
45.6 (2593) -
14.0 (18.8) -
804.0 (28393) -
125 (0.5) -
- 1800
Class A2 Diesel
Eco Replaceable Element
6 / In Line
4 Stroke
145.0 (5.7)/183.0 (7.2)
Turbocharged Air To Air
Charge Cooled
Water
ISO 8528 G2
Electronic
14.5:1
18.1 (1104.5)
7.44 (25424)
24/Negative
70
2050 (4519)
2158 (4758)
- 2270.0 (329.3)
2494.0 (361.7) -
617.5 (828.0)
678.2 (909.0)
-
-
72.6 (19.2) 103.3 (27.3) 138.4 (36.6) 155.3 (41.0)
- - - -
79.2 (20.9)
-
114.7 (30.3)
-
155.6 (41.1)
-
Replaceable Element
44.3 (1564) -
47.6 (1681) -
6.3 (25.3) -
Alternator Physical Data
Manufactured for FG Wilson by:
Model:
No. of Bearings:
Insulation Class:
Winding Pitch Code:
Wires:
Ingress Protection Rating:
Excitation System:
AVR Model:
Overspeed: rpm
Voltage Reguation: (Steady state)
Wave Form NEMA = TIF:
Wave Form IEC = THF:
Total Harmonic content LL/LN:
Radio Interference:
Radiant Heat: kW (Btu/min)
- 50 Hz
- 60 Hz
Voltage Technical Data 50 Hz
Voltage Prime: Standby:
kVA kW kVA kW
Alternator
Performance Data:
Data Item
Motor Starting
Capability* kVA
Short Circuit
Capacity** %
Reactances: Per Unit
Xd
X'd
X"d
Reactances shown are applicable to prime ratings.
*Based on 30% voltage dip at 0.6 power factor.
**With optional permanent magnet generator or AREP excitation.
Leroy Somer
Suppression is in line with European
Standard EN61000-6
Voltage Technical Data 60 Hz
Voltage Prime: Standby:
kVA kW kVA kW
60 Hz 50 Hz
Alternator Operating Data
300 300 300
3.380 4.530 2.840
0.170 0.220 0.140
0.132 0.178 0.111
1694 1283 1993
R450M
AREP
IP23
12
2/3 - 6
H
1
LL7024J
480/277V 600.0 750.0 540.0 675.0
220/127V 600.0 750.0 540.0 675.0
380/220V 600.0 750.0 540.0 675.0
600.0 750.0 540.0 675.0 440/254V
42.6 (2423)
-
4.0%
2.0%
50
+/- 0.5
2250
480/277V 380/220V
220/127V
440/254V
FG Wilson has manufacturing facilities in the following locations:
Northorn rolond rozll Chlno ndlo USA
Wlth hoodguortors ln Northorn rolond, FC Wllson oorotos throuqh o Clobol Doolor Notworl.
To contoct your locol Solos Offlco looso vlslt tho FC Wllson wobslto ot www.FCWllson.com
n llno wlth our ollcy of contlnuous roduct dovolomont, wo rosorvo tho rlqht to chonqo soclflcotlon wlthout notlco
Dealer contact details:
Documentation
A full sot of oorotlon ond molntononco monuols ond clrcult wlrlnq dloqroms.
Generating Set Standards
Tho ogulmont moots tho followlnq stondords. S5000, SO 8528, SO 304, LC 0034, NLMA MC-1.22.
FC Wllson ls o fully occrodltod SO 001 comony.
Warranty
All rlmo ogulmont corrlos o ono yoor monufocturor's worronty. Stondby ogulmont, llmltod to 500 runnlnq hours or yoor, hos o two yoor monufocturor's
worronty. For dotolls on worronty covor looso contoct your locol Doolor, or vlslt our wobslto. FCWllson.com.