(7) EVN PTC2 DaNang HaTinh - Testing

GE Energy

Factory Test Plan


Verifies
Responses to CT secondary currents Control Wiring Software Control Relay and Switch operations Scaling HMI Display Control Cabinet Input/Output

(7) EVN PTC2 DaNang HaTinh - Testing

GE Energy

Field Test Plan


Subset of Factory Test Plan Also Includes check of:
CT ratio, wiring, and fiber optics by means of Primary Current Injection PLC Inputs and Outputs Bypass Breaker Signal and Scaling to RTU

(7) EVN PTC2 DaNang HaTinh - Testing

GE Energy

Field Test Order


Power up Initialization Software Verification Ground Protection Hardware Platform Hardware

(7) EVN PTC2 DaNang HaTinh - Testing

GE Energy

Maintenance Testing
PLC Software Ground Control (Platform Simulator)
Bypass Breaker Outputs to Customer Equipment

Platform Equipment

(7) EVN PTC2 DaNang HaTinh - Testing

GE Energy

PLC Software Verification


Working copy stored in Flash Memory Backup copy stored on Proficy ME PC and on disks PC backup and Flash Memory copies are identical if LOGIC EQUAL is displayed with the Proficy ME programmer software.

(7) EVN PTC2 DaNang HaTinh - Testing

GE Energy

PLC Software Error Correction


Verify that Proficy ME PC copy is identical to other backups
if so, the Flash Memory is corrupted
load PLC from Proficy ME PC burn new copy to Flash Memory

if not, load a good copy of the software to the Proficy ME PC to get a LOGIC EQUAL

(7) EVN PTC2 DaNang HaTinh - Testing

GE Energy

Platform Simulator
Generates Fiber Optic Signals Can be used to completely test the ground based protection and control equipment Simulated platform currents are controlled via PC software

(7) EVN PTC2 DaNang HaTinh - Testing

GE Energy

Wave entry location, will toggle between Default and Transient, depending on selection.

Feedback zone platform data feedback from GFOI

Input the IP address of the PLC in the location and press enter

Platform Simulator Execution Screen


(7) EVN PTC2 DaNang HaTinh - Testing
9

GE Energy

Simplified Platform Simulator


PC Enter Values of Platform Currents Values Downloaded to GFOI via PLC CPU PLC
GFOI

Control Actions

Verify numerical results on the Proficy ME screens

Proficy ME Computer

Observe PLC Control Actions on the HMI Display Verify numerical values with the Proficy ME computer
(7) EVN PTC2 DaNang HaTinh - Testing
10

GE Energy

Platform Equipment
Test Platform Control
inject primary or secondary currents verify PLC reading (after ground control has been tested)

(7) EVN PTC2 DaNang HaTinh - Testing

11

GE Energy

2001

Successful 500 kV Staged Fault Testing of GE Protection System

(7) EVN PTC2 DaNang HaTinh - Testing

12

GE Energy

Primary Current Injection


Use High Current Power Supply Verify CT ratios and wiring Verify sense of capacitor and capacitor unbalance CTs Read Values on HMI Testing Screen

(7) EVN PTC2 DaNang HaTinh - Testing

13

GE Energy

Primary Injection Test


(7) EVN PTC2 DaNang HaTinh - Testing
14

GE Energy

Questions
Testing Frequency? Emergency Procedures? Hardware Failures? Where to get help? ??