You are on page 1of 6

Fan Coils

Large Capacity Fan Coil Units600 to 3000 cfm


Five direct drive hideaway or cabinet ceiling unit sizes from 600 to 2000 cfm Five belt drive hideaway or cabinet ceiling unit sizes from 800 to 3000 cfm 3-row to 6-row primary coil; 1-row or 2-row secondary heating coil Heavy-gauge, galvanized steel construction for longer life UL listing For more detail, refer to Catalog 735. For the most current information, refer to www.mcquay.com.

Vertically-mounted copper tube, aluminum fin coil

Heavy-gauge galvanized steel construction with 1" neoprene coated glass fiber insulation

Full-size mounting slots in heavy-gauge hangers Large diameter fan wheels and housings

Fan Coils

Discharge duct collar

Multi-speed PSC motor

Full width insulated drain pan, available in galvanized or stainless steel with overflow drain connection

7/8" O.D. copper drain connection

3/4" O.D. copper overflow drain connection (optional, standard with stainless steel pan)

Available options
Stainless steel drain pan with overflow drain connection Deluxe valve package low or highvoltage 1 or 2-row hot water coils (preheat position) Condensate overflow detection kits Disconnect

Direct drive hideaway unit

Direct drive cabinet ceiling unit

170

2010 McQuay Products Catalog

Fan Coils
Large Capacity Fan Coil Units, Direct DrivePerformance Data
Standard Coil Water Cooling Capacity Ratings1
High capacity and heating capacity detail is available in Catalog 720.

Unit types SCD, SHD SCD, SHD SCD, SHD SCD, SHD SCD, SHD

Size S06 S08 S12 S16 S20

Cooling capacity2 Total Btuh Sensible Btuh 17,600 14,500 26,000 19,700 37,000 26,800 53,000 40,000 61,000 48,000

Water flow (gpm) 3.5 5.2 7.4 10.6 12.2

Water flow p.d. (ft. w.c.) 5.7 3.5 8.1 3.2 3.2

1. Cooling capacities based on 80F DB/67F WB entering air, 45F entering water, 10F water temperature rise in SHD unit with plenum operating at high fan speed with no external static pressure. 2. For cooling coil capacity ratings at conditions other than those listed, consult your McQuay representative.

Large Capacity Fan Coil Units, Belt DrivePerformance Data


Unit types Size S08 S12 Cabinet and hideaway S16 S20 S30 Airflow (cfm) 800 900 1200 1300 1600 1800 2000 2200 3000 3200 Cooling capacity2 Total Btuh Sensible Btuh 24,000 17,700 25,615 19,241 37,265 27,027 38,898 28,581 48,121 35,472 51,121 38,482 57,596 45,014 60,565 48,102 91,633 66,864 94,813 69,923 Water flow (gpm) 4.8 5.1 7.5 7.8 9.7 10.3 11.5 12.1 18.3 19.0 Water flow p.d.(ft. w.c.) 3.1 3.4 8.2 8.8 2.7 3.0 2.9 3.1 2.9 3.1

1. Cooling capacities based on 80F DB/67F WB entering air, 45F entering water, 10F water temperature rise. 2. For cooling coil capacity ratings at conditions other than those listed, consult your McQuay representative.

Belt drive hideaway unit

Belt drive cabinet ceiling unit

2010 McQuay Products Catalog

171

Fan Coils

Standard Coil Water Cooling Capacity Ratings1

Fan Coils
Large Capacity Fan Coil Units, Direct Drive UnitsDimensional DataSCD Model
Right-hand unit shown. (Hand of unit determined by cooling unit connection when facing discharge.)

Fan Coils

SCD model S06 S08 S12 S16 S20

A 24 26 33 44 46

B 17 5/8 17 5/8 17 5/8 17 5/8 21 1/8

C D 37 20 46 20 46 24 46 36 50 41 3/4

E 4 6 8 6 6

F 19 21 28 39 41

G 44 1/4 53 1/4 53 1/4 53 1/4 57 1/4

H 18 1/2 18 1/2 23 1/2 38 1/2 38 1/2

Unit dimensions (in)1 J K M N 14 5/8 2 4 7/16 2 11/16 14 5/8 3 4 7/16 4 7/16 14 5/8 4 1/2 4 7/16 4 7/16 14 5/8 4 4 7/16 4 7/16 18 5/8 2 1/8 5 1/16 4 1/8

P 9 9/16 12 1/16 12 1/16 8 3/16 9 7/16

R 11 3/8 13 7/8 13 7/8 13 3/4 16 1/4

S 14 1/4 16 3/4 16 3/4 16 3/4 19 1/4

T 1 9/16 1 9/16 1 9/16 2 1/4 2 1/4

U 1 9/16 3 3/4 3 3/4 2 1/4 2 1/4

V W 1 9/16 1 3 3/4 1 3 3/4 1 2 1/4 1 4 3/16 1 1/4

1. All dimensions approximate. Certified drawings available upon request.

172

2010 McQuay Products Catalog

Fan Coils
Large Capacity Fan Coil Units, Direct Drive UnitsDimensional DataSHD Model
Right-hand unit shown. (Hand of unit determined by cooling unit connection when facing discharge.)

SHD model S06 S08 S12 S16 S20

A 22 24 31 39 41

B 14 16 1/2 16 1/2 16 1/2 19

D 14 16 23 31 33

Unit dimensions (in)1 E R 10 7/8 16 3/8 13 3/8 18 3/8 13 3/8 25 3/8 13 3/8 33 3/8 15 5/8 35 3/8

S 29 5/8 29 5/8 29 5/8 29 5/8 32 1/8

U 15 3/4 15 3/4 15 3/4 15 3/4 18 1/4

V 15 3/8 15 3/8 15 3/8 15 3/8 17 3/8

1. All dimensions approximate. Certified drawings available upon request.

2010 McQuay Products Catalog

173

Fan Coils

Fan Coils
Large Capacity Fan Coil Units, Belt Drive UnitsDimensional DataHZ Model
Right-hand unit shown. (Hand of unit determined by cooling unit connection when facing discharge.)

Fan Coils

HZ model S08 S12 S16 S20 S30

No. of fans 1 1 2 2 2

A 24 31 39 41 60

C 28 1/2 28 1/2 28 1/2 28 1/2 30

D 16 1/4 23 31 33 1/4 49

E 13 3/8 13 3/8 13 3/8 15 3/8 15 3/8

Unit dimensions (in)1 F J 24 21 31 28 39 36 41 38 57 54

N 16 1/2 16 1/2 16 1/2 18 3/4 18 3/4

P 15 3/4 15 3/4 15 3/4 18 1/4 18 1/4

Q 3 3 3 3 6

R 18 1/2 25 1/2 33 1/2 35 1/2 51 1/2

1. All dimensions approximate. Certified drawings available upon request.

174

2010 McQuay Products Catalog

Fan Coils
Large Capacity Fan Coil Units, Belt Drive UnitsDimensional DataCZ Model
Right-hand unit shown. (Hand of unit determined by cooling unit connection when facing discharge.)

CZ model S08 S12 S16 S20 S30

No. of fans 1 1 2 2 2

A 24 31 39 41 60

C 28 1/2 28 1/2 28 1/2 28 1/2 30

D 16 1/4 23 31 33 1/4 49

E 13 3/8 13 3/8 13 3/8 15 3/8 15 3/8

Unit dimensions (in)1 F J 24 21 31 28 39 36 41 38 57 54

N 16 1/2 16 1/2 16 1/2 18 3/4 18 3/4

P 15 3/4 15 3/4 15 3/4 18 1/4 18 1/4

Q 3 3 3 3 6

R 18 1/2 25 1/2 33 1/2 35 1/2 51 1/2

1. All dimensions approximate. Certified drawings available upon request.

2010 McQuay Products Catalog

175

Fan Coils

You might also like