You are on page 1of 2

Flooded Tubular Technology For Long Float & Cycle life Applications

Website: www.hazebattery.com E mail : sales@hazebattery.com

Manufactured to the highest international standards, the range is ideal for reliable use in all extreme cycling applications.

Operation
Nominal Voltage - 2V Float Charge - 2.23 - 2.30 vpc at 20 - 25oC Frequent Use Applications - Superior cycle life at all depths of discharge Design Life - 15 Years @ 25oC Connection - Cables, bus bar connectors and terminal covers available on request. Operating Temperature - -20 to 50oC

Construction
VRLA - Flooded, periodic topping-up required Positive plate - Tubular, Pb Sb alloy for long float and cycle life Negative Plate - Flat pasted with frame Separator - Microporous Polymer Formation - Superior proprietry in-case-formation Electrolyte - Very high purity Sulfuric acid Flame Arrester - Standard Terminal - Female insert as standard, proven, reliable, long life sealing method Case - High impact resistant SAN, flame retardant to UL94-V0 on request. Cover ABS. Venting valve - EPDM rubber, excellent acid resistance for long life Specification - Built to comply with IEC 896-2, DIN 43534, BS 6290 Pt4, Eurobat. Transport - Approved as non-hazardous cargo for ground, sea and air transportation in accordance with US DOT Regulation 49 and ICAO & IATA Packing Instruction 806.

Sealed Lead Acid 2 Volt Tubular Flooded Monobloc

HAZE Flooded Tubular Range utilizes proven materials & construction technology tailored for the specific demands of Industries Worldwide with long float & cycle Life applications. Performance is greatly enhanced by the inclusion of special materials, techniques and processes developed through extensive R&D and exhaustive testing.

Battery Model OPzS 200 OPzS 250 OPzS 300 OPzS 350 OPzS 420 OPzS 490 OPzS 600 OPzS 770 OPzS 800 OPzS 1000

LI

LI

Nominal Voltage 2 2 2 2 2 2 2 2 2 2

QUA

QUA

C1 1.67 VPC
131 165 197 229 274 318 388 496 515 646

C3 1.75 VPC
159 201 240 278 332 386 471 603 626 784

C5 1.77 VPC
172 218 259 301 360 418 510 653 678 849

C10 1.80 VPC


194 244 291 338 404 470 573 733 761 954

C100 1.85 VPC


230 291 347 403 481 559 682 873 906 1135

TY

A SSURED
FI
RM
005

ISO 14001 SS G

TY

A SSURED

ISO 9001 SS G

FI
RM

QUALITY MANAGEMENT

UKAS

The Quality & Management system governing the manufacture of this product is ISO 9001:2000 and ISO 14001:2004 certified.

Battery Model OPzS 200 OPzS 250 OPzS 300 OPzS 350 OPzS 420 OPzS 490 OPzS 600 OPzS 770 OPzS 800 OPzS 1000

Dimensions (mm) Length Width Height 105 126 147 126 147 168 147 215 215 215 208 208 208 208 208 208 208 254 193 235 360 360 360 475 475 475 650 475 650 650

Total Height 395 395 395 510 510 510 685 510 685 685

Approx. Weight Kg 17.5 20.5 26 28.5 33 39 46 59 62.5 75.5

Dimensions (Inch) Length Width Height 4.13 4.96 5.79 4.96 5.79 6.61 5.79 8.46 8.46 8.46 8.19 8.19 8.19 8.19 8.19 8.19 8.19 10.00 7.60 9.25 14.17 14.17 14.17 18.70 18.70 18.70 25.59 18.70 25.59 25.59

Total Height 15.55 15.55 15.55 20.08 20.08 20.08 26.97 20.08 26.97 26.97

Approx. Weight lbs 38.6 45.3 57.5 63.0 72.9 86.2 101.7 130.4 138.1 166.9

Terminal Terminal Internal Resistance 18 Nm Pairs mOhms Torque 1 1 1 1 1 1 1 1 2 2 0.95 0.77 0.69 0.60 0.52 0.43 0.39 0.34 0.30 0.22 M8 M8 M8 M8 M8 M8 M8 M8 M8 M8

Charging The maximum applied charging current should be 20% of C20. In cyclic applications the maximum applied charging voltage should be 2.4 vpc. For: - Daily discharge less than 0.4 x C100. Use 2.30 - 2.35 at 20 Degrees C - Daily discharge more than 0.4 x C100. Use 2.35 - 2.40 at 20 Degrees C o Charging Voltage is adjusted 5 mV/ C

9000 8000

Cycle Life Vs DOD

7000 6000 5000 4000 3000 2000 1000 0 0%


R

No. of Cycles

EMC
Germany

tested

90%

80%

70%

60%

50%

40%

30%

20%

10%

UL Recognised Component MH28512


110507

% DOD