Professional Documents
Culture Documents
BOARD INSULATION 15080* PROCESS EQUIPMENT INSULATION 40 42 23** MINERAL BOARD INSULATION 07 21 13**
Fire Performance:
ASTM E 136 CAN4 S114 ASTM E 84(UL 723) CAN/ULC S102 Behaviour of Materials at 750C (1382F) Test for Non-Combustibility Surface Burning Characteristics Surface Burning Characteristics Non-Combustible Non-Combustible Flame Spread = 0 Smoke Developed = 0 Flame Spread = 0 Smoke Developed = 0 In Compliance with ASTM C612 @ 1200F(650C) <1% @ 1200F (650C)
Dimensional Stability:
ASTM C 356 Linear Shrinkage
Moisture Resistance:
ASTM C 1104 Moisture Sorption 0.03%
Thermal Resistance:
ASTM C 518 (C 177) R-value/inch @ 75F RSI value/25.4 mm @ 24C Corrosiveness to Steel Stainless Steel Stress Corrosion Specification as per Test Methods C871 and C692: U.S. Nuclear Regulatory Commision, Reg. Guide #1.36: U.S. Military Specifications MIL-I-24244 (all versions including B and C) 4.2 hr.ft.F/Btu*** 0.74 mK/W Pass Conforms
Corrosive Resistance:
ASTM C 665 ASTM C 795 ****
Acoustical Performance
ASTM C 423 CO-EFFICIENTS AT FREQUENCIES Thickness 1.5 2.0 3.0 125 Hz 0.15 0.26 0.62 250 Hz 0.47 0.68 1.03 500 Hz 0.98 1.14 1.20 1000 Hz 1.06 1.13 1.10 2000 Hz 1.02 1.06 1.08 4000 Hz 1.02 1.07 1.10 NRC 0.90 1.00 1.10
*MASTER FORMAT 1995 EDITION **MASTER FORMAT 2004 EDITION *** at the time of manufacturing
Thermal Conductivity:
0.12 0.10
Thermal Conductivity (W/mC) Therm al Conductivity (Btu.in/hr.ft2F)
0.90 0.80 0.70 0.60 0.50 0.40 0.30 0.20 0 100 200 300 400 500 600 700
M e a n Te m p e ratu re (F)
0.08 0.06 0.04 0.02 0 50 100 150 200 250 300 350 400
M e an Te m p e ratu re (C)
Compressive Strength:
ASTM C 165 at 10%: at 25%: 63 psf (3 kPa) 146 psf (7kPa)
Density:
ASTM C 612-93 - Nominal ASTM C 612-00 - Actual
64 kg/m3 56 kg/m3
Dimensions:
24 (width) x 48 (length) 610 mm (width) x 1219 mm (length)
Thickness:
Product thickness is available in 1.5 through 4 in 1/2 increments, as well as 5 and 6 offerings. For additional sizes, please contact our customer service representatives.
Facing:
This product can be faced with reinforced foil. Please note that the facing will influence the products service temperature range.
**** Provisions for lot testing may be required, consult manufacturer. Note: As ROXUL Inc. has no control over installation design and workmanship, accessory materials or application conditions, ROXUL Inc. does not warranty the performance or results of any installation containing ROXUL Incs. products. ROXUL Incs. overall liability and the remedies available are limited by the general terms and conditions of sale. This warranty is in lieu of all other warranties and conditions expressed or implied, including the warranties of merchantability and fitness for a particular purpose.