LSC BUS DUCT

LS Cable Bus Duct System

LSC Bus Duct SYSTEM

1. INTRODUCTION
1.1 GENERAL SPECIFICATIONS 1.3 CATALOGING

1.2 OUTSTANDING FEATURE OF LSC BUS DUCT

2. HIGH POWER DISTRIBUTION (600A~6000A)


2.1 GENERAL SPECIFICATIONS 2.1.1 I-SERIES BUS DUCT 2.1.2 8-SERIES BUS DUCT 2.1.3 F-SERIES BUS DUCT 2.1.4 Y-SERIES BUS DUCT 2.2 GROUNDING & IP DEGREE 2.2.1 GROUNDING 2.2.2 IP DEGREE 2.3 PART DIMENSIONS 2.3.1 SECTIONAL DIMENSIONS 2.3.2 FLANGED END DIMENSIONS 2.3.3 PHYSICAL DATA FOR FITTINGS 2.4 BRANCH METHOD 2.5 TECHNICAL DATA 2.6 MAINTENANCE

3. MEDIUM POWER DISTRIBUTION (100A~400A)


3.1 M-SERIES (MINI BUS DUCT) 3.2 B-SERIES (BABY BUS DUCT)

45

4. AIR INSULATED BUS DUCT


4.1 A-SERIES (LOW VOLTAGE) 4.2 H-SERIES (HIGH VOLTAGE)

51

1. INTRODUCTION
1.1 1.2 1.3 GENERAL SPECIFICATIONS OUTSTANDING FEATURE OF LSC BUS DUCT CATALOGING

BUS DUCT which has non-corrosive conductor covered by non-flammable


insulator inside of steel housing for protection is an electrical distribution system made rapid progress and growth recently as the most optimized option with flexibility and lower losses for massive power delivery in high rise commercial building and industrial plant.

1.1 General Specifications


BUS DUCT, A Power Distribution System of High Stability & Easy Maintenance
When electrical power became widely used in industry, a need was created for a rational energy carrying and distribution system to supply the machineries with electricity. Basically, LSC Bus Duct has been designed, manufactured, and provided in the following conditions. Suitable to Mass-Current
LSC Bus Duct system which can carry massive power upto 6000A with lower losses is used as distribution system for main line according to needs of high-rise building and factory plant through the features of flexibility, safety, reliability, economical efficiency and improved demerits of cable epochally. LSC Bus Duct system is simplified so that load may be freely diverged, extending, moving, replacing and maintenance of the load easily. Meanwhile, this has a fine view harmonized with modern architectural sense.

Bus Bar
Copper bus bar has conductivity of 99% or more, or Aluminum bus bar has conductivity of 61% or more. Plating between contact sections of conductors are; Cu conductor : Tin-Plated Al conductor : Silver-Plated This plating improves the contact resistance and prevents electrical corrosion.

Temperature Rise Property


Temperature rise shall be within 55C in the joint part of conductor and 40C or less in the external surface of duct, under an ambient temperature of 40C or less.

Service Conditions
Ambient temperature : -15C~40C Relative Humidity : 95% or below Installation Attitude : Maximum 1000M above sea level

Insulation
Multi-Layer polyester films of class B(130C) shall be applied into thickness 0.5mm on conductor. BMC forms which is polyester reinforced by glass fiber shall be applied as a spacer between conductors of joint part or conductor and duct.

Standards
KSC 8450: Bus ways JISC 8364: BUS DUCT IEC 60439-1&2: Bus ways BSEN 60439: Bus ways

FR-Insulation
Multi-Layer of Fire Resistant Insulator(1200C) shall be applied on conductor.

1.2 Outstanding Feature of LSC Bus Duct


Benefits of LSC Bus Duct over wire and conduit
LSC Bus Duct System can improve installation area and cost with the compact size in a big jump. Labor Savings
LSC Bus Duct installation is faster when compared to other method of low voltage power distribution. While material costs may be slightly higher, the labors required to install LSC Bus Duct is often much lower. This results in an overall reduction in total installation cost.

Lower Voltage Drop


Because of its extremely low reactance, LSC Bus Duct voltage drop is low. This efficient design allow power to be delivered in an installation with the highest efficiency possible. This makes LSC Bus Duct ideal for efficient power distribution in commercial or industrial facilities.

Easy to Install
LSC Bus Duct incorporates the one joint bolt type. For connection work, bolt fastening forces were unified into the torque of 1200kg.cm.

Compact Size
LSC Bus Duct requires less space than wire and conduit.

1. Set the center line and level together

2. Fit together till the duct joiners touch the stoppers.

3. Tighten the MF nut by special ratchet wrench till the neck part of nut is broken and locked.

4. Attach the joint cover with M6 bolt & nut.

5. Completion of joint.

Better Transmission Efficiency. Future Expansion Flexibility. High Short-Circuit Ratings. Harmonized View.

SAFETY POINT: Nut (1) shall be neither taken off, nor dropped. when neck (2) is broken, twisting force remains.

1.3 Cataloging
LSC BUS DUCT CODING
Table 6
VOLTAGE SHAPE CURRENTS FIRE RANGE STRUCTURE RANGE RESISTANCE BRANCH LIMITS GROUNDING LSC BUS DUCT TYPE IG TYPE I P Grade (41.54.65) IG41 IG54 IG65 IP41 IP54 IP65 IH41 IH54 IH65 IF41 IF54 IF65 8G41 8G54 8G65 8P41 8P54 8P65 8H41 8H54 8H65 8F41 8F54 8F65 FG41 FG54 FG65 FP41 FP54 FP65 FH41 FH54 FH65 FF41 FF54 FF65 YG41 YG54 YG65 YP41 YP54 YP65 YH41 YH54 YH65 YF41 YF54 YF65 MP41 MP54 MP65 BP41 BP54 BP65 LP41 LP54 LP65 AP41 A-SERIES PE EARTH Low Voltage AP54 AP65 HP41 OVER 600V H-SERIES PE EARTH High Voltage HP54 HP65

GENERAL I-SERIES PE EARTH TO 400A WITHOUT POWER SHUTDOWN

IP TYPE

HALF EARTH

IH TYPE

FULL EARTH GENERAL TYPE GENERAL COMPACT TYPE 8-SERIES TO 800A WITHOUT POWER SHUTDOWN PE EARTH

IF TYPE

8G TYPE

8P TYPE

HALF EARTH

8H TYPE

BELOW 600V 600A~6000A

FULL EARTH

8F TYPE

GENERAL F-SERIES PE EARTH TO 400A WITHOUT POWER SHUTDOWN FIRE RESISTANCE TYPE Y-SERIES PE EARTH TO 800A WITHOUT POWER SHUTDOWN

FG TYPE

FP TYPE

LSC BUS DUCT SYSTEM

HALF EARTH

FH TYPE

FULL EARTH

FF TYPE

GENERAL

YG TYPE

YP TYPE

HALF EARTH

YH TYPE

FULL EARTH

YF TYPE

200A~400A

M-SERIES

Mini

100A~200A AIR INSULATED BELOW 100A TYPE GENERAL TYPE

B-SERIES

PE EARTH

Baby

L-SERIES

Lighting

600A~4000A

EACH TYPE OF BUS DUCT CAN BE SUPPLIED as IP DEGREE IP41~IP66

BUS DUCT SYSTEM


Building
3F
EN DC LO SE R

SPRING VERTICAL HANGER


D EN

D GE AN FL L ICA RT W BO EL

2F

VE

EXPANSION JOINT

RIG ID V HA NG ERT ICA ER L

L TA ON RIZ HO E TE

SE WI AT R FL NGE HA

D GE AN FL D N E

PLUG IN HOLE

1F
PLUG IN UNIT
RE DU CE R
AL NT IZO OR -SET H F OF

RIGID VERTICAL HANGER

ME D HA IUM NG ER

HO R EL IZON BO TA W L

BASE CHANNEL

VE TE E

RT

D GE AN OX FL DB EN

FEED IN BOX
W GE ED GER N HA ISE

ICA

TR END FLANGED END BOX Transformer

B1
T SW CH

Y RA ET BL CA GE AR

BUS DUCT SYSTEM


Factory

FL EN ANDE DB D OX L ICA RT VE BOW EL


r oo Ind

Insulated Bus Duct

or tdo Ou

HO RI EL ZON BO T W AL

Insulated Bus Duct

PLUG IN MINI BUS DUCT

3.3KV 3P 3W 1200A(Cu-Fe) High Voltage Bus Duct


AL NT IZO T OR -SE H F OF

E WIS GE R ED ANGE H

Feed in Box

TR END FLANGED Transformer


R H.V GEA H ITC SW

FL

AN

D GE

EN

Cable

R L.V GEA H ITC SW

PLUG IN HOLE

PLUG IN MINI BUS DUCT PLUG IN BABY BUS DUCT

END CLOSER

PLUG IN BOX

2. HIGH POWER DISTRIBUTION (600A~6000A)


2.1 GENERAL SPECIFICATIONS 2.1.1 I-SERIES BUS DUCT 2.1.2 8-SERIES BUS DUCT 2.1.3 F-SERIES 2.1.4 Y-SERIES 2.2 GROUNDING & IP DEGREE 2.2.1 GROUNDING 2.2.2 IP DEGREE 2.3 PART DIMENSIONS 2.3.1 SECTIONAL DIMENSIONS 2.3.2 FLANGED END DIMENSIONS 2.3.3 PHYSICAL DATA FOR FITTINGS 2.4 BRANCH METHOD 2.5 TECHNICAL DATA 2.6 MAINTENANCE

2.1 General Specifications


2.1.1 I-Series Bus Duct
I-Series (Insulated Bus Duct) is a totally enclosed non-ventilated and sandwitch type bus duct system for 110, 220, 380, 440 and 600V power distribution. This is designed for indoor and drip-proof use and available from 600 to 6000A. The load branch of this I-Series are by plug-in unit upto 400A and by Tap-off unit over 400A. There are one bar, two bars and three bars per phase according to Ampacity.
Fastening Bolt & Washer Reinforcement Band for Reducing Hysteresis & Eddy Current Loss and Reinforcing Short Circuit Capacity Steel Duct Coated with Paint

Four Layer Polyester Film of Class B(130C)

Copper or Aluminum

R.Head Bolt High Tension Joint Bolt Disk Spring(C) Stopper(D) Joint Cover

Cross Head Driver

Bolt & Washer

Insulation Spacer(B) Contact Surface(A)

Housing Connection

Joint Cover Square Nut

(A) Contact Surface Silver-Plated for Aluminum Tin-Plated for Copper. (B) Insulation Spacer Polyester Resin BMC. (C) Disk Spring (Belleville Washer) Absorbs the Expansion & Contraction of Joint Parts. (D) Stopper Regulates the Length of Conductor Lapping. (E) Captive Hardware Anti-Rotation Fitting for Fastening High Tension Joint Bolt.

I- Series Bus Duct have Four Types according to Grounding Conductor.


OPTION TYPE Grounding Option IP Grade Option OPTION 1 Code : IG TYPE Code : IG41 TYPE Code : IG54 TYPE Code : IG65 TYPE Description Integral housing system OPTION 2 Code : IP TYPE Code : IP41 TYPE Code : IP54 TYPE Code : IP65 TYPE Integral housing & External Earth bus bar system OPTION 3 Code : IH TYPE Code : IH41 TYPE Code : IH54 TYPE Code : IH65 TYPE Integral Half Earth bus bar system OPTION 4 Code : IF TYPE Code : IF41 TYPE Code : IF54 TYPE Code : IF65 TYPE

Table 10

Integral Full Earth bus bar system

10 11

2.1.2 8-Series
8-Series(Plug-in 800A Bus Duct) has same all characteristics as I-Series. However 8-Series is specially designed for larger branch plug-in Amperes. The maximum branch of this 8-series is by plug-in upto 800A and by Tap off over 800A. So, this type is very useful for factory.
8-Series have double branch capacity. Max Plug in Ampere is 800A
Plu g-in Mo ld

Mo ld C ove r

RST

Ca ble

D-PLUG IN TYPE Fig. 11.1

I-Series have single branch capacity. Max Plug in Ampere is 400A


Plu g-in Co ver

RST

Ca ble

S-PLUG IN TYPE Fig. 11.2

8-Series Bus Duct have Four Types according to Grounding Conductor.


OPTION TYPE Grounding Option IP Grade Option OPTION 1 Code : 8G TYPE Code : 8G41 TYPE Code : 8G54 TYPE Code : 8G65 TYPE Description Integral housing system OPTION 2 Code : 8P TYPE Code : 8P41 TYPE Code : 8P54 TYPE Code : 8P65 TYPE Integral housing & External Earth bus bar system OPTION 3 Code : 8H TYPE Code : 8H41 TYPE Code : 8H54 TYPE Code : 8H65 TYPE Integral Half Earth bus bar system OPTION 4 Code : 8F TYPE

RSTN

RSTN

Table 11

Code : 8F41 TYPE Code : 8F54 TYPE Code : 8F65 TYPE Integral Full Earth bus bar system

2.1.3 F-Series Bus Duct


F-Series(Fire Resistant Bus Duct) complies with IEC 60331 (Fire Resistant, 750C/ 180min). This LSC FR Bus Duct provides a integrity & reliability when fire occurred. Fire Resistant Insulator (heat resistance 1200C) shall be applied on conductor. All mechanical & electrical characteristics are same as I-Series.

Steel Duct with Coating

Fire Resistant Insulator (Heat Resistance 1200C) Copper or Aluminum

Insulation Spacer Silver Plated Joint

F-Series Bus Duct have Four Types according to Grouding Conductor.


OPTION TYPE Grounding Option IP Grade Option OPTION 1 Code : FG TYPE Code : FG41 TYPE Code : FG54 TYPE Code : FG65 TYPE Description Integral housing system OPTION 2 Code : FP TYPE Code : FP41 TYPE Code : FP54 TYPE Code : FP65 TYPE Integral housing & External Earth bus bar system OPTION 3 Code : FH TYPE Code : FH41 TYPE Code : FH54 TYPE Code : FH65 TYPE Integral Half Earth bus bar system OPTION 4 Code : FF TYPE

Table 12

Code : FF41 TYPE Code : FF54 TYPE Code : FF65 TYPE Integral Full Earth bus bar system

12 13

2.1.4 Y-Series Bus Duct


Y-Series(Plug-in 800A & FR Bus Duct) have combined functions of the F-Series and 8-Series. This Y-Series Bus Duct are fire resistant and have plug-in 800A hole.

Y-Series Bus Duct have Four Types according to Grounding Conductor.


OPTION TYPE Grounding Option IP Grade Option OPTION 1 Code : YG TYPE Code : YG41 TYPE Code : YG54 TYPE Code : YG65 TYPE Description Integral housing system OPTION 2 Code : YP TYPE Code : YP41 TYPE Code : YP54 TYPE Code : YP65 TYPE Integral housing & External Earth bus bar system OPTION 3 Code : YH TYPE Code : YH41 TYPE Code : YH54 TYPE Code : YH65 TYPE Integral Half Earth bus bar system OPTION 4 Code : YF TYPE

Table 13

Code : YF41 TYPE Code : YF54 TYPE Code : YF65 TYPE Integral Full Earth bus bar system

We construct the Digital Infrastructure in every corner of the world.

2.2 GRONUDING & IP DEGREE


2.2.1 GROUNDING
G-Type, P-Type-Integral housing & External PE Bus
G-type is built with an Integral housing grounding system and provide an integral housing continuous current capacity ground path. P-type is built with an Integral housing grounding and external Earth bus system and provide an integral housing and external continuous current capacity ground path. P-TYPE
W W

G-TYPE

P.E BUS(CU) 3t x 25w

A Fig. 14.2

Fig. 14.1

H-Type, F-Type-Internal Bus Bar


H-type is built with an internal bus bar system and provide an integral 50% continuous current capacity ground path. H-TYPE
W W

F-type is built with an internal bus bar system and provide an integral 100% continuous current capacity ground path. F-TYPE
W W

Half Earth 50%E

Full Earth 100%E

H
A B H

A
C B A PEN 1/2PE =A=B=C

A N C B A PE 1/2PE =A =B=C= N C B A PEN PE =A =B=C

N C B A PE PE =A =B=C =N

Fig. 14.3
For dimensions and weights information, Please contact us.

Fig. 14.4

14 15

2.2.2 IP DEGREE
LSC Bus Duct provides optimum performance in the most demanding applications. Through superior design and applied materials technology, it assures uptime and reliability, even in severe-duty weather environments.

Protection Degree IP41 /IP42


With a degree of protection IP41/IP42, this Bus Duct System is ideal for in-door uses.
W H B A

Fig. 15.1

Protection Degree IP54 /IP55


W(IP54)

Fig. 15.2

Protection Degree IP65 /IP66


W+ 100

W+ 86

36

Fig. 15.3

Construction options
IEC Degree of Protection IP41/IP42 IP54/IP55 IP65/IP66 For dimensions and weights information, Please contact us. Available Bus Duct Feeder, Plug-in, Riser Feeder, Plug-in, Riser Feeder Construction Type Indoor Spray-proof/Splash-proof Outdoor

36

H+86

With a degree of protection IP65/IP66, this Bus Duct System is ideal for outdoor uses and wherever exist corrosive atmospheres. Stainless steel housing is optional.

27

Feeder, plug-in and tap-off Bus Duct are available with either drip-proof or splash-proof construction. Generally for feeders, additional duct structure will be treated over one for indoor as below figures. So, weight will be added that much. Material used is steel plate on principle. but is adaptable according to users request.

H H+27

W(IP54)

H +100 H W+50 H+50

Table 15

2.3 PART DIMENSIONS


2.3.1 SECTIONAL DIMENSIONS
2.3.1.1 G-Type : Integral Housing Applying

I-Series & F-Series Dimensions. With Aluminum Conductors


Rating in Amps 600 800 1,000 1,200 1,500 1,600 2,000 2,500 3,000 3,500 4,000 4,500 5,000 6,000 A 6 6 6 10 10 10 10 10 10 10 10 10 10 10 Dimensions(mm) W B 3W 4W 55 100 125 75 100 125 100 100 125 100 110 140 125 110 140 150 110 140 175 110 140 230 110 140 150x2 110 140 175x2 110 140 200x2 110 140 230x2 110 140 175x3 110 140 200x3 110 140 Weight (kg/m) H 115 135 160 160 185 210 235 290 385 435 485 545 635 710 3W 11 13 15 19 22 25 28 35 46 52 58 73 83 93 4W 13 15 18 23 27 31 34 43 56 64 72 88 100 112

Table 16.1
Flg. a.d a.d a.d a.d a.d a.d a.d a.d b.e b.e b.e b.e c.f c.f

With Copper Conductors


Rating in Amps 600 800 1,000 1,200 1,500 1,600 2,000 2,500 3,000 3,500 4,000 4,500 5,000 6,000 A 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Dimensions(mm) W B 3W 4W 55 100 125 55 100 125 75 100 125 100 100 125 125 100 125 150 100 125 175 100 125 125x2 100 125 150x2 100 125 175x2 100 125 200x2 100 125 150x3 100 125 175x3 100 125 200x3 100 125 Weight (kg/m) H 115 115 135 160 185 210 235 335 385 435 485 560 635 710 3W 18 18 21 27 32 37 42 58 70 80 93 109 125 141

Table 16.2
Flg. a.d a.d a.d a.d a.d a.d a.d b.e b.e b.e b.e c.f c.f c.f

Fig. 16

4W 22 22 27 33 40 47 53 73 88 101 119 136 157 178

Dimensions : Millimeters

NOTE: Feeder standard lengths is 3000mm Min. 500mm

8-Series & Y-Series Dimensions.


W-Dimensions PHASE Width 3W 180 4W 230

Table 16.3

NOTE: Conductor size are same. Additional duct & Plug-in BMC structure will be treated over one for G-type. so weight will be added that much. For more information contact us.

16 17

2.3.1.2 P-Type : External PE Bus Applying

I-Series & F-Series Dimensions. With Aluminum Conductors


Rating in Amps 600 800 1,000 1,200 1,500 1,600 2,000 2,500 3,000 3,500 4,000 4,500 5,000 6,000 A 6 6 6 10 10 10 10 10 10 10 10 10 10 10 Dimensions(mm) W B 3W 4W 55 110 140 75 110 140 100 110 140 100 125 170 125 125 170 150 125 170 175 125 170 230 125 170 150x2 125 170 175x2 125 170 200x2 125 170 230x2 125 170 175x3 125 170 200x3 125 170 Weight (kg/m) H 115 135 160 160 185 210 235 290 385 435 485 545 635 710 3W 14 17 18 22 25 28 31 38 49 55 61 76 86 96 4W 16 18 21 26 30 34 37 46 59 67 75 91 103 115

Table 17.1
Flg. a.d a.d a.d a.d a.d a.d a.d a.d b.e b.e b.e b.e c.f c.f

With Copper Conductors


Rating in Amps 600 800 1,000 1,200 1,500 1,600 2,000 2,500 3,000 3,500 4,000 4,500 5,000 6,000 A 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Dimensions(mm) W B 3W 4W 55 110 140 55 110 140 75 110 140 100 110 140 125 110 140 150 110 140 175 110 140 125x2 110 140 150x2 110 140 175x2 110 140 200x2 110 140 150x3 110 140 175x3 110 140 200x3 110 140 Weight (kg/m) H 115 115 135 160 185 210 235 335 385 435 485 560 635 710 3W 21 21 24 30 35 40 45 61 73 83 96 112 128 144

Table 17.2
Flg. a.d a.d a.d a.d a.d a.d a.d b.e b.e b.e b.e c.f c.f c.f

Fig. 17

4W 25 25 30 36 43 50 56 76 91 104 122 139 160 181

Dimensions : Millimeters

NOTE: Feeder standard lengths is 3000mm Min. 500mm

8-Series & Y-Series Dimensions.


W-Dimensions PHASE Width 3W 180 4W 230

Table 17.3

NOTE: Conductor size are same. Additional duct & Plug-in BMC structure will be treated over one for G-type. so weight will be added that much. For more information contact us.

2.3.1.3 H-Type : Integral Half Earth (50%)

I-Series & F-Series Dimensions. With Aluminum Conductors


Rating in Amps 600 800 1,000 1,200 1,500 1,600 2,000 2,500 3,000 3,500 4,000 4,500 5,000 6,000 A 6 6 6 10 10 10 10 10 10 10 10 10 10 10 Dimensions(mm) W B 5W 55 140 75 140 100 140 100 170 125 170 150 170 175 170 230 170 150x2 170 175x2 170 200x2 170 230x2 170 175x3 170 200x3 170 Weight (kg/m) H 115 135 160 160 185 210 235 290 385 435 485 545 635 710 5W 16 17 21 26 31 35 38 47 61 69 78 88 106 119

Table 18.1
Flg. a. a. a. a. a. a. a. a. b. b. b. b. c. c.

W H

With Copper Conductors


Rating in Amps 600 800 1,000 1,200 1,500 1,600 2,000 2,500 3,000 3,500 4,000 4,500 5,000 6,000 A 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Dimensions(mm) W B 5W 55 140 55 140 75 140 100 140 125 140 150 140 175 140 125x2 140 150x2 140 175x2 140 200x2 140 150x3 140 175x3 140 200x3 140 Weight (kg/m) H 115 115 135 160 185 210 235 335 385 435 485 560 635 710 5W 26 26 31 38 45 53 59 81 97 111 130 147 170 192
B

Table 18.2
Flg. a. a. a. a. a. a. a. b. b. b. b. c. c. c.

Fig-a

Fig-b

Fig-c

Fig. 18

Dimensions : Millimeters

NOTE: Feeder standard lengths is 3000mm Min. 500mm

8-Series & Y-Series Dimensions.


W-Dimensions PHASE Width 5W 230

Table 18.3

NOTE: Conductor size are same. Additional duct & Plug-in BMC structure will be treated over one for G-type. so weight will be added that much. For more information contact us.

18 19

2.3.1.4 F-Type : Integral Full Earth (100%)

I-Series & F-Series Dimensions. With Aluminum Conductors


Rating in Amps 600 800 1,000 1,200 1,500 1,600 2,000 2,500 3,000 3,500 4,000 4,500 5,000 6,000 A 6 6 6 10 10 10 10 10 10 10 10 10 10 10 Dimensions(mm) W B 5W 55 180 75 180 100 180 100 180 125 180 150 180 175 180 230 180 150x2 180 175x2 180 200x2 180 230x2 180 175x3 180 200x3 180 Weight (kg/m) H 115 135 160 160 185 210 235 290 385 435 485 545 635 710 5W 17 19 23 29 34 39 42 53 68 77 86 98 118 132

Table 19.1
Flg. a. a. a. a. a. a. a. a. b. b. b. b. c. c.

With Copper Conductors


Rating in Amps 600 800 1,000 1,200 1,500 1,600 2,000 2,500 3,000 3,500 4,000 4,500 5,000 6,000 A 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Dimensions(mm) W B 5W 55 180 55 180 75 180 100 180 125 180 150 180 175 180 125x2 180 150x2 180 175x2 180 200x2 180 150x3 180 175x3 180 200x3 180
B

Table 19.2
Weight (kg/m) H 115 115 135 160 185 210 235 335 385 435 485 560 635 710 5W 28 28 35 42 50 59 66 90 108 123 144 164 189 214 Flg. a. a. a. a. a. a. a. b. b. b. b. c. c. c.

Fig-a

Fig-b

Fig-c

Fig. 19

Dimensions : Millimeters

NOTE: Feeder standard lengths is 3000mm Min. 500mm

8-Series And Y-Series Dimensions.


W-Dimensions PHASE Width 5W 230

Table 19.3

NOTE: Conductor size are same. Additional duct & Plug-in BMC structure will be treated over one for G-type. so weight will be added that much. For more information contact us.

2.3.2 FLANGED END DIMENSIONS


Flanged End
Flanged end is a part connected to transformer or panel. Elbow-type is also available.

Flange W 3.2t W

Flange W 3.2t

Flange 3.2t

200

200

105

105

Fig. 20.1 FLANGED END


H H

200

200

25

25

25

Fig. 20.2

Fig. 20.3

Fig. 20.4

BUS BAR HOLE PATTERN (1 STACK, 2 STACKS, 3 STACKS ARE SAME, ALL HOLES ARE RECTANGULAR)

40 80

40 80

40 80

40 80

200 22 20 22 14

105

20

20

20

20

20

20

11

11 A

11

A A

A A

14

A A A

Fig. 20.5
BAR WIDTH 55mm

Fig. 20.6
BAR WIDTH 75~100mm

Fig. 20.7
BAR WIDTH 125~150mm

Fig. 20.8
BAR WIDTH 175~200mm

Fig. 20.9
BAR WIDTH 230~280mm

Table 20.1
Rating in Amps(A) 600 800 1,000 1,200 1,500 1,600 2,000 2,500 3,000 3,500 4,000 4,500 5,000 6,000 t 6 6 6 10 10 10 10 10 10 10 10 10 10 10 Dimensions(mm) tI W A 3 or 6 55 3 or 6 75 40 3 or 6 100 50 5 or 10 100 50 5 or 10 125 40 5 or 10 150 50 5 or 10 175 60 5 or 10 230 60 5 or 10 150x2 50 5 or 10 175x2 60 5 or 10 200x2 70 5 or 10 230x2 60 5 or 10 175x3 60 5 or 10 200x3 70 B 100 100 100 100 100 100 100 100 130 130 130 130 130 130 Flg. 20.22 0 .5 20.22 0 .6 20.22 0 .6 20.22 0 .6 20.22 0 .7 20.22 0 .7 20.22 0 .8 20.22 0 .9 20.32 0 .9 20.32 0 .7 20.32 0 .8 20.32 0 .9 20.42 0 .8 20.42 0 .8 Rating in Amps(A) 600 800 1,000 1,200 1,500 1,600 2,000 2,500 3,000 3,500 4,000 4,500 5,000 6,000 t 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Dimensions(mm) tI W A 3 or 6 55 3 or 6 55 3 or 6 75 40 3 or 6 100 50 3 or 6 125 40 3 or 6 150 50 3 or 6 175 60 3 or 6 125x2 40 3 or 6 150x2 50 3 or 6 175x2 60 3 or 6 200x2 70 3 or 6 150x3 50 3 or 6 175x3 60 3 or 6 200x3 70 B 100 100 100 100 100 100 100 130 130 130 130 130 130 130

20

40 80

200

Table 20.2
Flg. 20.22 0 .5 20.22 0 .5 20.22 0 .6 20.22 0 .6 20.22 0 .7 20.22 0 .7 20.22 0 .8 20.32 0 .7 20.32 0 .7 20.32 0 .8 20.32 0 .8 20.42 0 .7 20.42 0 .8 20.42 0 .8

ALUMINUM

20 21

COPPER

Flanged End Box


Flanged end box is a part connected to transformer or panel. Elbow-type is also available.

Min Min .:3 00 L

.:3

Min 00 L

.:3

00 L

D D D C C C

Fig. 21.1

Fig. 21.2

Fig. 21.3

Fig. 21.4

* Elastic Band is Optionanl for GEN.BOX Elastic Band

105 200

L=270

105 200 C

70

Fig-17.3 GEN.BOX

Fig. 21.5

Fig. 21.6

Fig. 21.7

Fig. 21.8

Rating in Amps(A) 600~1200 1500~2000 2500 3000 3500~4000 4500 5000 6000 600~1200 1500~2000 2500 3000 3500~4000 4500 5000 6000

No. OF STACKS 1 1 1 2 2 2 3 3 1 1 2 2 2 3 3 3

A 310 385 440 535 635 695 785 860 310 385 485 535 635 710 785 860

B 260 335 390 243x2 293x2 323x2 245x3 270x3 260 335 218x2 243x2 293x2 220x3 245x3 270x3

3 W (mm) C 450 450 450 510 510 510 510 510 450 450 510 510 510 510 510 510

D 200x2 200x2 200x2 230x2 230x2 230x2 230x2 230x2 200x2 200x2 230x2 230x2 230x2 230x2 230x2 230x2

L 270 270 270 270 270 270 270 270 270 270 270 270 270 270 270 270

A 310 385 440 535 635 695 785 860 310 385 485 535 635 710 785 860

Dimensions(mm) 4 W (mm) B C D 260 550 250x2 335 550 250x2 390 550 250x2 243x2 640 295x2 293x2 640 295x2 323x2 640 295x2 245x3 640 295x2 270x3 640 295x2 260 550 250x2 335 550 250x2 218x2 640 295x2 243x2 640 295x2 293x2 640 295x2 220x3 640 295x2 245x3 640 295x2 270x3 640 295x2

L 270 270 270 270 270 270 270 270 270 270 270 270 270 270 270 270

A 310 385 440 535 635 695 785 860 310 385 485 535 635 710 785 860

B 260 335 390 243x2 293x2 323x2 245x3 270x3 260 335 218x2 243x2 293x2 220x3 245x3 270x3

5 W (mm) C D 650 300x2 650 300x2 650 300x2 770 360x2 770 360x2 770 360x2 770 360x2 770 360x2 650 300x2 650 300x2 770 360x2 770 360x2 770 360x2 770 360x2 770 360x2 770 360x2

70

Table 21

COPPER

ALUMINUM

Note: refer to page 20 for flanged end and busbar hole pattern

L=270

Flexible conductor

20 40 70 80

L=270

200

L 270 270 270 270 270 270 270 270 270 270 270 270 270 270 270 270

Cutout and drilling pattern for flanged end

OPENING CUTOUT C C C C C C

Fig. 22.1

Fig. 22.2

Fig. 22.3

Table 22
Rating in Amps (A) 600 800 1000 1200 1500 1600 2000 2500 3000 3500 4000 4500 5000 6000 600 800 1000 1200 1500 1600 2000 2500 3000 3500 4000 4500 5000 6000 Dimensions(mm) A 3-W 240 240 240 240 240 240 240 240 300 300 300 300 300 300 240 240 240 240 240 240 240 240 300 300 300 300 300 300 4-W 340 340 340 340 340 340 340 340 430 430 430 430 430 430 340 340 340 340 340 340 340 430 430 430 430 430 430 430 B 115 135 160 160 185 210 235 290 385 435 485 545 635 710 115 115 135 160 185 210 235 335 385 435 485 560 635 710 3-W 135 135 135 135 135 135 135 135 165 165 165 165 165 165 135 135 135 135 135 135 135 165 165 165 165 165 165 165 C 4-W 185 185 185 185 185 185 185 185 230 230 230 230 230 230 185 185 185 185 185 185 185 230 230 230 230 230 230 230 5-W 235 235 235 235 235 235 235 235 295 295 295 295 295 295 235 235 235 235 235 235 235 295 295 295 295 295 295 295 D 145 165 190 190 215 240 265 320 208 233 258 288 222 247 145 145 165 190 215 240 265 183 208 238 258 197 222 247 Fig. 22.1 22.1 22.1 22.1 22.1 22.1 22.1 22.1 22.2 22.2 22.2 22.2 22.3 22.3 22.1 22.1 22.1 22.1 22.1 22.1 22.1 22.2 22.2 22.2 22.2 22.3 22.3 22.3

22 23

COPPER

ALUMINUM

2.3.3 Physical Data for Fittings


Fittings
LSC Bus Duct has complete ranges which fit to all the lay-out conditions. The other special parts than 90 angle are also available. Designation methods related to turning are specified in Fig.x on the basis of source side and load side. Off set and combination elbow will be applied only when standard elbow is not applied.
Forward

Upward Source Side

Downward Rearward

Load Side

Fig. 23.1

Elbow-Fittings
Upward

Dimensions : mm
AMP. Rating(A)
Forward

Table 23.1 Hor. Elbow X Y 500 500 500 500 500 500 1000 1000 1000 1000 1000 1000 300 300 300 300 300 300 Ver. Elbow X Y 500 500 600 600 700 700 2000 2000 2000 2000 2000 2000 400 400 500 500 600 600

Standard

Downward

Max.
Horizontal. Elbows(Edgewise)

Fig. 23.2
Vertical. Elbows(Flatwise)

Min.
Rearward

600~2500 3000~4000 4500~6000 600~2500 3000~4000 4500~6000 600~2500 3000~4000 4500~6000

Fig. 23.3

* Angel Elbows are available 75~179 turning.

Tee-Fittings
Dimensions : mm
AMP. Rating(A) 600~2500 3000~4000 4500(AL) 4500~6000 600~2500 3000~4000 4500(AL) 4500~6000 600~2500 3000~4000 4500(AL) 4500~6000 Hor. Tee X Y Z 500 500 500 600 600 600 600 600 600 1000 1000 1000 1000 1000 1000 1000 1000 1000 500 500 300 600 600 300 600 600 300 Table 23.2 Ver. Tee X Y Z 500 500 500 600 600 600 700 700 700 700 700 700 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 400 400 400 500 500 500 600 600 600 600 600 600

Standard

Horizontal. Tee(Edgewise)

Fig. 23.4

Max.

Vertical. Tee(Flatwise)

Min.

Fig. 23.5

Offset
Fittings Dimensions : mm
AMP. Rating(A)
Foreward Downward

Table 24.1 Hor. Offset Ver. Offset X Y Z X Y Z 500 500 500 500 500 500 500 500 500 600 600 600 500 500 500 700 700 700 1000 500 1000 1000 1000 1000 1000 500 1000 1000 1000 1000 1000 500 1000 1000 1000 1000 300 250 300 400 500 400 300 250 300 400 500 400 300 250 300 600 500 600

Standard

Max.

Horizontal. Offset

Vertical. Offset

Fig. 24.1

Fig. 24.2

Min.

600~2500 3000~4000 4500~6000 600~2500 3000~4000 4500~6000 600~2500 3000~4000 4500~6000

Combination Elbow
Fittings *Note: All the direction is available. 1. For-wardUp-ward 2. For-wardDown-ward 3. Rear-wardUp-ward 4. Rear-wardDown-ward 5. Down-wardRear-ward 6. Down-wardFor-ward 7. Up-wardRear-ward 8. Up-wardFor-ward Refer Elbow fittings for Dimensions.

Upward

Rearward

Combination Elbow (For-ward+Up-ward)

Combination Elbow (Down-ward+Rear-ward)

Fig. 24.3

Fig. 24.4

Reducer
This Fitting is used to economical engineering system. Another ratings are produced per costomers request. Dimensions : mm
AMP. Rating(A) Primary 1000 1500 2000 2500 3000 4000 Secondary 600~800 800~1200 1200~1600 1500~2000 2000~2500 3000~2500 X Standard : 1000 Min : 700 Max : 2000 Table 24.2 AMP. Rating(A)

Fig. 24.5

Expansion
This Fitting is designed to absorb 25mm longitudinal expansion. In straight run it is recommended to install this section every 40 meters. Dimensions : mm
POLE 3 4 AMP. Rating(A) 600~2000 2500~6000 600~2000 2500~6000 Table 24.3 AMP. Rating(A) X Y 280 300 1500 340 370

Fig. 24.6

24 25

Feed-in box
Feed-in box is a part used for connection to cable by diverging at the end of Bus Duct.

Min Min Min .:3 .:3 00

.:3

00

00 L L

B B B

A A A

Fig. 25.1

Fig. 25.2

Fig. 25.3

Table 25
AMPERE RATINGS (A) 600 800 1000~1200 1500 1600 2000 2500 3000 3500 4000 4500 5000 6000 600~800 1000 1200 1500 1600 2000 2500~3000 3500 4000 4500 5000 6000 No. OF STACKS 1 1 1 1 1 1 1 2 2 2 2 3 3 1 1 1 1 1 1 2 2 2 3 3 3 3 W(mm) B 200 220 250 300 320 350 400 500 550 600 650 700 800 200 220 250 300 320 350 500 550 600 650 700 800 Dimensions(mm) 4 W(mm) B 200 220 250 300 320 350 400 500 550 600 650 700 800 200 220 250 300 320 350 500 550 600 650 700 800 5 W(mm) B 200 220 250 300 320 350 400 500 550 600 650 700 800 200 220 250 300 320 350 500 550 600 650 700 800

A 350 350 350 350 350 350 350 450 450 450 450 500 500 350 350 350 350 350 350 450 450 450 500 500 500

L 400 400 400 400 400 400 400 450 450 450 500 500 500 400 400 400 400 400 400 450 450 450 500 500 500

A 450 450 450 450 450 450 450 550 550 550 600 600 600 450 450 450 450 450 450 550 550 550 600 600 600

L 400 400 400 400 400 400 400 450 450 450 500 500 500 400 400 400 400 400 400 450 450 450 500 500 500

A 500 500 500 500 500 500 500 600 600 600 650 650 650 500 500 500 500 500 500 600 600 600 650 650 650

L 400 400 400 400 400 400 400 450 450 450 500 500 500 400 400 400 400 400 400 450 450 450 500 500 500

COPPER

ALUMINUM

Center Feed-in Box


Center Feed-in box is a part used for connection to cable by diverging at the middle of Bus Duct.

Min .

:30

0
Min

.:3

00

Min

.:3

00 L

B
B

Fig. 26.1

Fig. 26.2

Fig. 26.3

Table 26
AMPERE RATINGS (A) 600 800 1000~1200 1500 1600 2000 2500 3000 3500 4000 4500 5000 6000 600~800 1000 1200 1500 1600 2000 2500~3000 3500 4000 4500 5000 6000 No. OF STACKS 1 1 1 1 1 1 1 2 2 2 2 3 3 1 1 1 1 1 1 2 2 2 2 3 3 3 W(mm) B 200 220 250 300 320 350 400 500 550 600 650 700 800 200 220 250 300 320 350 500 550 600 650 700 800 Dimensions(mm) 4 W(mm) B L 200 400 220 400 250 400 300 400 320 400 350 400 400 400 500 450 550 450 600 450 650 500 700 500 800 500 200 400 220 400 250 400 300 400 320 400 350 400 500 450 550 450 600 450 650 500 700 500 800 500 5 W(mm) B 200 220 250 300 320 350 400 500 550 600 650 700 800 200 220 250 300 320 350 500 550 600 650 700 800

A 350 350 350 350 350 350 350 450 450 450 450 500 500 350 350 350 350 350 350 450 450 450 500 500 500

L 400 400 400 400 400 400 400 450 450 450 500 500 500 400 400 400 400 400 400 450 450 450 500 500 500

A 450 450 450 450 450 450 450 550 550 550 600 600 600 450 450 450 450 450 450 550 550 550 600 600 600

A 500 500 500 500 500 500 600 600 600 600 650 650 650 500 500 500 500 500 500 600 600 600 650 650 650

L 400 400 400 400 400 400 400 450 450 450 500 500 500 400 400 400 400 400 400 450 450 450 500 500 500

26 27

COPPER

ALUMINUM

End closer
End closer is a part used for finishing BUS DUCT line, and the connection is unnecessary. To extend the line, simply remove this part and install it in addition.

205

Fig. 27.1

Switchboard / Switch-gear stub.

FRONT OR REAR

FRONT OR REAR

FRONT OR REAR

FRONT OR REAR

Fig. 27.2

Fig. 27.3

Table 27
MIN. STUB DIMENSIONS(mm) AMPERE RATINGS (A) 600~2000 2500~3500 4000~4500 5000~6000 FIG. 17.1 SINGLE RUN X Y 300 300 350 350 400 400 500 500 X 300 350 400 500 DOUBLE RUN Y 300 350 400 500 Z 400 500 550 550 SINGLE RUN X Y 250 330 300 350 350 400 400 500 FIG. 17.2 X 250 300 350 400 DOUBLE RUN Y 300 350 400 500 Z 400 500 550 550

Wall Flange & BASE CHANNEL


Flange is a part used for prevention of empty space in wall, ceiling, and floor opening. The dimensions of wall opening(cutouts) shall be larger an much as 50mm than external dimensions of BUS DUCT.
300 100 W+100 W+10 100 W+200 W+100

Wall Flange Size


H+215

25

Wall Flange Size


H+100 H+120 H+320
H+160 88.5HOLES

H+15

100

Wall Open Size CUTOUT

Wall Open Size CUTOUT

25

25

FOR INDOOR

FOR OUTDOOR

Fig. 28.1

Fig. 28.2

200MM

Wall

418HOLE
UP Flange Size (=Base channel size)

W+200 130

Floor Open Size


W

200MM

85

W+200

86TAPS
100

Fig. 28.3 BASE CHANNEL * BASE CHANNEL IN CASE FRONT-TYPE(2 Rods)

Floor Openings
1. Front type The F-dimension of Floor opening(cutouts) shall be larger on much as 30mm than external dimensions of BUS DUCT in case Front type of hanger. The Sdimension of Floor opening(cutouts) shall be min W+60
H + 60 S W + 70 35 30 W 35

H+60 H+120 H+160

CUTOUT

2. Side type The S-dimensions of Floor opening(cutouts) shall be larger on much as 35mm than external dimensions of BUS DUCT in case side type of hanger. The Fdimension of Floor opening(cutouts) shall be min H+60

Floor Open Size CUTOUT Fig. 28.4

28 29

30

H+15

W46

H+200

Minimum clearances for heat dissipation


Minimum clearances between bus duct and wall, ceiling or beam are shown in Fig. 29.1.

Wall, ceiling 250mm BEAM 50mm

Wall, ceiling 200mm 500mm

wall

wall

Joint point

200mm

200mm

Fig. 29.1

Minimum distances of bus duct


Minimum distances between parallel-installed bus duct in serveral cases are shown below figures.
HORIZONTAL MOUNTING P1
Joint point
P1

VERTICAL MOUNTING P2
EDGEWSE FORMATION

P3
Joint point
P3

P4

Joint point
P2

P4

200

FLATWISE FORMATION

Joint point

Joint point

100

100

200

100

200

Bus Duct

Vertical hanger

Fig. 29.2

Table 29
3-W AND 3-W P1 P2 P3 P4 110 150 190 270 3-W AND 4-W 135 175 215 275 4-W AND 4-W 130 180 230 270
40 20

Plug-in or Tap-off box or Expansion

Plug-in or Tap-off box or Expansion

Fig. 29.3

Vertical Mounting Hanger


Spring hanger is provided to support bus duct from each floor. The quantity of springs(rods) provided is depend on Bus Duct weight. When th height between stories exceeds 45m, a middle support is required. Openings for attachment are in line on the floor flange, and able to adjust simply. The rigid hanger is the same as the spring hanger, but hasnt any spring, it is used at both ends and middle of line.

Initial Adjusting Nut (Remove after installation)


110 160 W 35 60 H 60 35

290

100x50x5t

160

Water Bank (Out of Supply)


100

16 16 85

30

A type

B type

Fig. 30.1 Spring Vertical Hanger-Front Type

Bracket 35 H H 65 W 65 35

70 16 16 30 P

30

A type

B type

Fig. 30.2 Rigid Vertical Hanger-Side Type

Application of A or B Type
(Average floor height : 3.5~4.5M)
Aluminum Conductor Copper Conductor Aluminum Conductor Copper Conductor 3W 600A 3W 1,600A 4W 600A 4W 1,200A 3W 600A 3W 1,000A 4W 600 4W 800A 3W 2,000A 3W 3,000A 4W 1,500A 4W 2,500A 3W 1,200A 3W 2,500A 4W 1,000 4W 2,500A

Dimensions P for Side type (B type)


Table 30.1
Rating in Amps A Type (1 Rod) 1,000 1,200 1,500 1,600 B Type (2 Rods) 2,000 2,500 3,000 P(mm) 85 85 85 85 110 140 160

100

200

Table 30.2

Notes: 1. Dimension P is common both to Aluminum and copper conductors. 2. Dimension X is adjusted at factory. 3. See pp16~19 for H&W Dimensions. 4. C Type(3 Rod) can be supplied for high amps or high floor

30 31

Horizontal Mounting Hanger


Support one for every I5 meter in principle. Designed for 12mm diameter drop rods.
12

Hanger Rod (Out of supply) Hanger Clamp


20 15 H

Hanger Clamp

12

Hanger Red

20 W 10

Hanger
45 M10 300 350 40 P L 40

45

Hanger

Hanger

Hanger Clamp

Fig. 31.1 Edgewise hanger 1 Row Table 31


Rating in Amps (A) 600~1,200 1,500~2,500 3,000~3,500 4,000~4,500 5,000~6,500 Dimensions (mm) L 350 500 650 750 850 P 300 450 600 700 800

Fig. 31.2 Flatwise hanger 1 Row

Wall

Floor Open

Fig. 31.3 Medium hanger 1 Row


* Install when the height between stories exceeds 4.5m. * Install when the story has a expansion.

* Multi Mounting Hanging Example.


W W 25 A Min.70 H B Min.100 H B Min. 100 H A Min.70 25

300 600 650

B+ H P1 = 2H+2A+2B L1 = P1+50

B+ H

Fig. 31.4 Edgewise hanger 2 Rows

Fig. 31.5 Flatwise hanger 3 Rows

W 25 A Min. 70 H B Min.100 H A Min. 70 25

300 900 950

300

B+H P1 = 2H+2A+2B L1 = P1+50

Fig. 31.6 Edgewise hanger 3 Rows

Fig. 31.7 Flatwise hanger 2 Rows

2.4 BRANCH METHOD


BRANCH METHOD
The lengths of plug-in, tap-off and feeder and the positions of plug-in hole and tap-off will be provided in order to be convenient for maintenance of user. All the standard lengths of plug-in, tap-off, and feeder are 3000mm. And those of plug-in and tap-off on 1000mm to 1500mm in 500mm increments. For plug-in feeder, the rated current diverged is up to 400A(S-Plug in type) or 800A(D-Plug in type) per phase, and for tap-off feeder it is upto 1200A. Plug-in Feeder standards.

*PS1 = 2 HOLES

*PS3 = 6 HOLES

*PS2 = 4 HOLES

NOTE: 1. PS-Feeder has plug-in hole both side. 2. The position can be changed for maintenance or convenience 3. Max. 6 Holes per 3000mm

Fig. 32.1

Tap-off Feeder standards.

Bre

ake

rB

ox

80

Std Min.: 300 .: 1 0(m 00 m) 0(m m)

Std Min.: 300 .: 1 0(m 00 m) 0(m m) 14 00

Ta

po

ff B

ox

Ta

pO

80

ff

Ta

pO

ff

Ta

pO

ff

Fig. 32.2
NOTE: 1. 2 tap-off per 3000mm are recommended. 2. Max branch Ampere is 1200A

32 33

PLUG-IN BOX & TAP OFF BOX


One of the characteristic of bus duct system is easy to install and maintenance of current branch, even when the load is extended and shifted. If there are spare holes or tap-offs on the bus duct line runs the branch units can be attached on the bus duct at any location that the load is added. CT, TD and auxiliary devices can be included in branch units or breaker, that can perceive the status of the system. In case of plug-in unit, it is very easy to install, clip type brush is inserted into busbar. In adoption the right type of branch units, Load type and number that current is branched (include extension of installations) Rating of and short-circuit current Adapted electrical system Installation environments Bus duct type must be considered carefully.

Plug-in Cover

Plug-in Hole Contact Surface

Plug-in Unit

Here is a guide of selection right type of LSC Plug-in Units


Determine the rating, location and quantity of branch units and calculate the short circuit currents. Electric power devices are very different according to the system that is used (building, IDC, factory...), so the type, rating is must be designed carefully and short circut currents is calculated which is ultimate anticipate short circuit available at source. LSC BUS DUCT system is suitable for various electric system and shows outstanding feature.

Determine circuit breaker type(mccb. fuse..)


LSC branch unit can adopt various type of mccb, so its no differents what type of circuit breaker is used within branch of LSC BUS DUCT.

MCCB
MCCB, in which a circuit breaker and trip device are assembled in a mold case, can manually open and close the electric circuit. MCCB can automatically cut off elecctric power in case of overload and short cicuit. MCCB has a variety of rated current frame from small to large capacities(30AF~1200AF). MCCB has four(4) type of breaking capacities economical type(ABE), standard type(ABS), high interrupting type(ABH) and current limiting type(ABL). this feater allows easy application of design with an appropriate breaking capacity. Applied standards KSC-8321, IEC-60947.

Table 34
MCCB RATINGS MODEL FRAME (AF) 50 100 225 400 600 800 1000 1200 50 100 225 400 50 100 225 400 600 800 1000 1200 POLES 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 TRIP RANGE (AT) 5, 10, 15, 20, 30, 40, 50 15, 20, 30, 40, 50, 60, 75, 100 100, 125, 150, 175, 200,225 250, 300, 350, 400 500, 600 700, 800 1000 1200 15, 20, 30, 40, 50 15, 20, 30, 40, 50, 60, 75, 100 125, 150, 175, 200, 225 250, 300, 350, 400 15, 20, 30, 40, 50 125, 150, 175, 200, 225 250, 300, 350, 400 250, 300, 350, 400 500, 600 700, 800 1000 1200 INTERUPTING RATINGS RMS SYMMETRICAL (KA) 220V 380V 460V 600V 25 14 10 5 50 25 25 10 50 25 25 10 50 42 35 22 100 65 50 25 100 65 50 25 100 65 65 45 100 65 65 45 50 25 25 10 65 35 35 18 65 35 35 18 85 65 50 25 100 65 65 35 125 65 65 35 125 100 85 30 125 100 85 30 125 100 85 30 125 100 85 30 125 85 85 65 125 85 85 65

ABS

ABH

ABL

Note: Other brands of MCCB are on request.

34 35

FUSE
FUSE, in which a circuit breaker is assembled by fuse link, holder carrier and base, can manually or electrically open and close the electric circuit. Fuse has outstanding features in breaking capacity, discrimination and stability compare to MCCB. FDS, fuse type switch built in plug in or tap off bow in various type, capacities and manufactuter. Applied standards IEC 269.

Determine additional attachments etc.


CT, TD, concent and auxiliary devices can be included in branch unit or breaker, that can perceive the electric status to the system. The user must conform the exact type of branch unit.

Determine operation method: external door type.


The door of branch unit can be made various type according to customers demand. Here is type of branch units door shape.

Hinge type

Hinge type

External operation

External operation

Fig. 35.1 Interlock

Fig. 35.2 External handle

Hinge type

Hinge type

Internal operation

External operation

Fig. 35.3 Push button

Fig. 35.4 External lever

Separation type

Separation type

Internal operation

External operation External outlet

Fig. 35.5 Bolt fastening

Fig. 35.6 External outlet

Branch unit must match with the bus dcut and rating
There are many type of bus dcut in LSC, so the bus dcut unit is determined by not only breaking device but also the bus dcut type that is inserted.
Table 36
CURRENTS FIRE BUS DUCT RANGE RESIST ANCE
Terminal Block Plug-in Unit

BRANCH AMP 30~400A

BRANCH TYPE S PLUG IN TYPE TAP OFF TYPE D PLUG IN TYPE

I-SERIES GENERAL TYPE 8-SERIES HIGH POWER 600A~ DISTRIBUTION 6000A BRANCH TYPE F-SERIES FIRE RESISTANCE TYPE 600~1200A 30~800A Y-SERIES 600~1200A 30~800A

Insulation Cover Plug-in Contactor

Gasket Insulation Supporter

1000~1200A TAP OFF TYPE 30~400A S PLUG IN TYPE TAP OFF TYPE D PLUG IN TYPE

Fig. 36.1 S-PLUG IN TYPE

1000~1200A TAP OFF TYPE

Flexible joint Terminal Block Plug-in Unit Coble Insulation Cover Plug-in Contactor Gasket Insulation Supporter Tap off Plug-in Unit

Fig. 36.2 D-PLUG IN TYPE

Fig. 36.3 TAP OFF TYPE

When the type of bus duct and branch unit is not matched, the branch unit is not inserted in bus duct so besides the type of breaking device, below Bus Duct type must be checked. Bus duct type: ____________ (ex: I-series, F-series......)

Bus duct pole, capacity and conductor material: _____W _____A (CU, AL) Grouding type: (GE, PE, HE, FE) IP Grade: (IP41, IP54, IP65)

36 37

Branch unit size


Branch unit can be made various size and also cable can be pulled out any direction(rear, side, top) the below are LSC standards.

Fig. 37.1 S-PLUG IN TYPE

Fig. 37.2 D-PLUG IN TYPE

Note: The box size will be changed according to the side or top pulling direction. Table-37 show below pulling box size.

Fig. 37.3 TAP OFF TYPE

Table 37
MODEL ABS ABH, ABL ABS ABH, ABL ABS ABH, ABL ABS ABH, ABL ABS ABH, ABL ABS ABH, ABL ABS ABH, ABL ABS ABH, ABL ABS ABH, ABL FRAME 50, 60 100 200 400 50, 60 100 200 400 600 800 600 800 1000 1200 L 370 400 750 400 500 750 800 800 1000 W 3W 220 220 240 280 280 340 340 340 340 4W 220 220 280 280 280 400 400 400 400 H 200 200 200 200 200 200 200 230 230 I, F-SERIES SAME SIZE I, FSERIES REMARK

8, YSERIES

Flexible conductor
Flexible conductor is made of braided copper wire, and the connection section is silver-plated for excellent contacting property. This is mainly used for expansion joint of BUS DUCT or the connection of BUS DUCT with transformer or panel.

Fig. 38.1

Fig. 38.2

Fig. 38.3

Table 38
AMPS 600 800 800 1000 1000 1200 1500 1600 2000 2500 2500 3000 3000 3500 4000 4500 5000 6000 A (mm) FOR AL, BUS BAR FOR CU, BUS BAR 55 55 55 75 100 75 100 100 125 125 150 150 175 175 230 2x125 2x140 2x150 2x175 2x175 2x200 2x200 3x150 3x175 3x175 3x200 3x200 B (mm) 40 40 50 40 50 40 50 60 60 40 50 50 60 70 50 60 70 Fig 37.1 37.1 37.2 37.2 37.2 37.2 37.3 37.3 37.3 37.3 37.3 37.3 37.3 37.3 37.3 37.3 37.3 37.3

38 39

2.5 TECHNICAL DATA


Impedance
The values of impedance of aluminum and copper conductors for 3-phase alternating current are as follows.

Table 39.1 (unit : 105/M)


RATED LOAD AMPS(A) 600 800 1000 1200 1500 1600 2000 2500 3000 3500 4000 4500 5000 6000 BAR SIZES (mm) (1) 6x55 (1) 6x75 (1) 6x100 (1) 10x100 (1) 10x125 (1) 10x150 (1) 10x175 (1) 10x230 (2) 10x150 (2) 10x175 (2) 10x200 (2) 10x230 (3) 10x175 (3) 10x200 350Hz Rac 11.32 8.37 6.37 3.96 3.26 2.78 2.43 1.93 1.39 1.22 1.09 0.96 0.81 0.73 X 2.95 2.02 1.59 2.05 1.70 1.45 1.27 0.99 0.75 0.65 0.58 0.51 0.45 0.39 Z 11.61 8.61 6.57 4.46 3.68 3.14 2.74 2.17 1.58 1.38 1.23 1.09 0.93 0.83 Rac 11.36 8.45 6.43 4.05 3.34 2.85 2.50 1.98 1.43 1.25 1.12 0.99 0.83 0.75 360Hz X 3.10 2.43 1.91 2.45 2.04 1.74 1.52 1.18 0.90 0.79 0.69 0.61 0.54 0.48 Z 11.78 8.79 6.71 4.73 3.91 3.34 2.93 2.30 1.69 1.48 1.32 1.16 0.99 0.89 Rdc 11.13 8.17 6.12 3.67 2.94 2.45 2.10 1.60 1.22 1.05 0.92 0.80 0.70 0.62

ALUMINUM

Table 39.2 (unit : 105/M)


RATED LOAD AMPS(A) 600 800 1000 1200 1500 1600 2000 2500 3000 3500 4000 4500 5000 6000 BAR SIZES (mm) (1) 6x55 (1) 6x55 (1) 6x75 (1) 6x100 (1) 6x125 (1) 6x150 (1) 6x175 (2) 6x125 (2) 6x150 (2) 6x175 (2) 6x200 (2) 6x230 (3) 6x175 (3) 6x200 350Hz Rac 7.10 7.10 5.29 4.06 3.34 2.85 2.49 1.83 1.42 1.25 1.11 0.95 0.83 0.74 X 2.59 2.59 2.02 1.59 1.31 1.11 0.96 0.68 0.57 0.49 0.43 0.39 0.34 0.30 Z 7.56 7.56 5.56 4.36 3.59 3.06 2.67 1.95 1.53 1.34 1.19 1.03 0.90 0.80 Rac 7.17 7.17 5.35 4.15 3.42 2.92 2.56 1.89 1.46 1.28 1.14 0.97 0.85 0.76 360Hz X 3.10 3.10 2.43 1.91 1.57 1.33 1.16 0.82 0.68 0.59 0.52 0.47 0.40 0.33 Z 7.81 7.81 5.88 4.57 3.76 3.21 2.81 2.06 1.61 1.41 1.25 1.08 0.94 0.83 Rdc 6.87 6.87 5.04 3.78 3.02 2.52 2.16 1.51 1.26 1.08 0.94 0.84 0.72 0.63

Temperature of conductor is at 95C

COPPER

Voltage drop
For 3-phase alternating current, the values of voltage drop per 100 meter are as follows.

Table 40.1 (unit : volt/100m)


VOLTAGE DROP-350Hz RATED LOAD AMPS(A) 600 800 1000 1200 1500 1600 2000 2500 3000 3500 4000 4500 5000 6000 BAR SIZES (mm) 1.00 (1) 6x55 (1) 6x75 (1) 6x100 (1) 10x100 (1) 10x125 (1) 10x150 (1) 10x175 (1) 10x230 (2) 10x150 (2) 10x175 (2) 10x200 (2) 10x230 (3) 10x175 (3) 10x200 11.76 11.60 11.03 8.24 8.46 7.71 8.43 8.34 7.22 7.38 7.52 7.51 7.02 7.59 .95 12.01 11.90 11.34 9.15 9.41 8.57 9.38 9.26 8.08 8.24 8.39 8.37 7.89 8.47 POWER FACTOR .90 11.76 11.76 11.12 9.26 9.54 8.69 9.50 9.37 8.20 8.37 8.51 8.48 8.02 8.59 .85 11.41 11.34 10.82 9.24 9.52 8.67 9.47 9.34 8.20 8.36 8.50 8.46 8.02 8.58 .80 11.02 10.97 10.47 9.14 9.42 8.58 9.37 9.24 8.12 8.28 8.42 8.38 7.96 8.50 .75 10.60 10.56 10.09 8.99 9.26 8.44 9.22 9.08 8 8.15 8.29 8.24 7.85 8.37 1.00 11.80 11.70 11.13 8.42 8.67 7.91 8.66 8.59 7.41 7.58 7.73 7.73 7.22 7.79 .95 12.22 12.17 11.61 9.59 9.89 9.02 9.87 9.76 8.51 8.68 8.85 8.83 8.32 8.96 VOLTAGE DROP-360Hz POWER FACTOR .90 12.03 12.00 11.46 9.80 10.11 9.22 10.08 9.97 8.72 8.89 9.05 9.03 8.53 9.19 .85 11.73 11.72 11.20 9.84 10.16 9.26 10.13 10.00 8.73 8.95 9.10 9.07 8.60 9.25 .80 11.38 11.38 10.89 9.79 10.12 9.22 10.08 9.95 8.75 8.91 9.07 9.03 8.58 9.23 .75 10.99 11.00 10.53 9.69 10.01 9.12 9.97 9.83 8.66 8.83 8.98 8.93 8.51 9.15

ALUMINUM

Table 40.2 (unit : volt/100m)


VOLTAGE DROP-350Hz RATED LOAD AMPS(A) 600 800 1000 1200 1500 1600 2000 2500 3000 3500 4000 4500 5000 6000 BAR SIZES (mm) 1.00 (1) 6x55 (1) 6x55 (1) 6x75 (1) 6x100 (1) 6x125 (1) 6x150 (1) 6x175 (2) 6x125 (2) 6x150 (2) 6x175 (2) 6x200 (3) 6x150 (3) 6x175 (3) 6x200 6.88 9.84 9.17 8.44 8.67 7.89 8.62 7.94 7.39 7.55 7.69 7.39 7.19 7.69 .95 7.37 10.47 9.80 9.05 9.30 8.45 9.23 8.47 7.95 8.10 8.24 7.97 7.74 8.28 POWER FACTOR .90 7.36 10.42 9.78 9.04 9.28 8.44 9.22 8.44 7.94 8.09 8.23 7.98 7.74 8.28 .85 7.26 10.25 9.64 8.92 9.16 8.32 9.09 8.31 7.84 7.99 8.12 7.89 7.64 8.18 .80 7.11 10.02 9.43 8.47 8.97 8.15 8.90 8.13 7.69 7.83 7.95 7.74 7.50 8.02 .75 6.93 9.75 9.19 8.52 8.75 7.95 8.67 7.92 7.50 7.64 7.75 7.56 7.32 7.83 1.00 6.94 9.93 9.27 8.63 8.87 8.08 8.85 8.18 7.58 7.75 7.90 7.58 7.38 7.90 .95 7.60 10.78 10.12 9.43 9.70 8.83 9.66 8.88 8.31 8.48 8.63 8.34 8.10 8.57 VOLTAGE DROP-360Hz POWER FACTOR .90 7.65 10.81 10.18 9.49 9.76 8.89 9.71 8.91 8.31 8.54 8.68 8.41 8.16 8.60 .85 7.60 10.71 10.09 9.42 9.69 8.82 9.63 8.82 9.31 8.47 8.62 8.36 8.11 8.52 .80 7.49 10.52 9.94 9.28 9.55 8.68 9.48 8.67 8.20 8.35 8.49 8.25 8.00 8.38 .75 7.34 10.29 9.73 9.09 9.35 8.51 9.29 8.48 8.04 8.18 8.31 8.10 7.85 8.19

Temperature of conductor is at 95C

40 41

COPPER

Short-circuit characteristics
The short-circuit characteristics shown below are based on KS C 8450 and JIS C 8364. When required, can be designed and supplied a bus duct having a larger capacity, for example, a reinforced type shown below.

Short-current(KA) Symmetrical.m.s

Reinforced type

Standard type

KS/ JIS Standard

Rated Current of BUS DUCT (A) x 100 Fig. 41

Table 41
RATED CURRENT(A) 600 800 1000 1200 1500 1600 2000 2500 3000 3500 4000 4500 5000 6000 KS: Korean standard, JIS: Japanese standard KS/JIS SPEC(KA) 22 22 22 42 42 60 60 60 60 60 60 90 90 90 MAKERS STANDARD(KA) 40 40 50 50 50 60 60 75 75 100 125 125 175 175 REINFORCED TYPE(KA) 75 75 100 100 100 100 100 125 150 200 200 200 200 200

Temperature rise characteristics


If bus duct is energized by the rated current in ambient temperature of 40C or less, the connection section of conductor will be 55C or less, and outside the duct will be 40C or less.

Joint point

Fig. 42.1

The following graph is a result of temperature-rise test for Al-Fe 4W 3000A.

Time(hr)

Fig. 42.2 Table 42


SPOT 1 Description busbar joint 2 busbar joint 3 busbar joint 4 busbar joint 5 housing 6 housing 7 housing 8 housing 9 room temperature

42 43

2.6 MAINTENANCE
Regular maintenance is required to maintain the best performance for the expected span of life through prevention of any unexpected accidents in BUS DUCT line. CHECKING PERIOD
After energizing, check once between a half year and a year. At this time, especially, verify that jointing bolt tightened, and if loosened, tighten it normally. After that, perform regular checking once per year.
Table 43
SECTION Connection section Diverging section Machinery combining section ITEM 1. Isnt bolt loosened? 2. Isnt there any trace of overheating? 3. Isnt there any trace of water penetrated? 4. Arent there discoloration, deformation, damage, or brokenless of bolt, nut, disc spring, insulating spacer? 5. Is the grounding wire connected? 1. Arent there deformation, bending, and damage, etc. of BUS DUCT? 2. Isnt there any problem in support section of paralled and vertical part? 3. Arent there any danger such as water, moisture, high temperature, corrosive gas, serious vibration, dust, etc.? 4. Is the insulation resistance nomal? 5. Isnt there dis-painted or corroded part? ACTION TO TAKE 1. Tighten it into specified torque. 2. Contact with the maker and take proper actions. 3. Clean up it and take action so that water may not fall in. 4. Contact with the maker and take proper actions. 5. Immediately connect it.

The whole line

1. Contact with the maker to take action. 2. Repair it in order to operate normally. 3. Remove dangerous factors. 4. Contact with the maker to take close examination and action. 5. Perform repair, pinting, and cleaning.

UP JOINT COVER STOPPER JOINT COVER CROSS MEAD DRINER BOLT & WASHER RHEAD BOLT M6x15L CONTACT SURTACE INS SPACER SERAL NO.

CAPTIVE HARDWARE HIGH TENSON JOINT BOLT BELLEVLLE WASHER HOUSNG CONNECTION

JONT COVER SOUARE NUT

DOWN JOINT COVER

Fig. 43.1 JOINT ASSY In door (Protection degree : IP41)

Fig. 43.2 JOINT ASSY In door (Protection degree : IP54)

FIN AL CO VE R SE T M6 BOLT x25 L (2 +4 EA ) JO INT IND COV OO ER R

WA TE RP RO OF CO VE R

WA TE RP RO OF DU CT

JO OU INT 01 TD OO COV ER R

BU SD UC T

BU SD UC T

M6

SO P (2 + MUT 4E A)

LB RA CK ET MU T HE M10 . W.5 X N SU . S M1 .W 0 UT S JO INT O B M6 UTDO 2 CO VE NU OR R T

SW WS

M6 x25 LH EX BO LT

Fig. 43.3 JOINT ASSY OUTDOOR (Protection degree : IP65)

Please confirm the following information in the case of order or a technologic inquiry
Purpose Quotation ( Confirming ( ) ) Application System design ( ) ) Producing instruction ( Completion data ( Project details Project Name Contractor/Buyer Consignee/Distributor Installation company Drawing Materials Installation Powering BUS DUCT SPECIFICATION AND SCOPE Type Conductor Plating method Grounding method Duct quality Color Wiring Flange type Supplying scope Insulation ( Cu ( ), Fire resistance ( ) Voltage ), Tin coating ( x ), PI 800 ( ), Mini ( V ) ) SGP( IP41( ), SUS ( ), IP54( ) ), SPC ( ), IP65 ( ) ) ), Baby ( Ampere ), Bare conductor ( ) Amp Delivery details )

), Al (

Silver plate ( Standard ( SPCC ( 5Y7/1 ( 3P3W ( Standard ( Flexible (

), Silver coating ( ), PE ( /Size : ), SUS (

), Inter5W (50%, 100%), Others ( ), AL ( ) ), ( )P( ) IP material IP grade

), SGP(

), CU (

), 7.5BG6/1.5 ( ), 3P4W (

), Others (

), 1P3W (

), 1P2W ( ), End (

)W, Refer to the drawing ( )

), Non standard (

), Box (

), Generator Zebra Box ( ), Vertical parts accessories (

), Connection bus bar (

), Hanger (

), Others (

INSTALLATION SPECIFICATION AND SCOPE Installation method Vertical part hanger Installation site Line constitution Box in/out direction Edgewise ( Front ( Indoor ( ), Flatwise ( ), Mixed ( ), Riser ( ) ), Fire barrier (Economic type, Quality type) mm ) Y( ), N ( )

), Side (

), Medium ( ), Mixed (

), Support (

), Outdoor (

), Installation level ( BOB=FL + ), PNL+Riser ( ), Cable Box ( )

PNL(M/T) + PNL( Up ( ), Down (

), Oil TR+PNL( ), Up/Dwon (

Valance measurement mm)

), Installation level (FL+

PLUG IN UNIT SPECIFICATION AND SCOPE Plug in unit type Magnetic number Switch ampere ABS ( 3P ( ), ABH ( ), 4P ( ), ABL ( ), 2P ( ) ), 42KA ( ), ABE ( ), FDS ( ), MCCB ( Standard ( ) ), Bolting ( ) ), Handle ( ), Lever ( )

Door operation ), 85KA (

Voltage (

V), 22KA (

), 100KA (

), Others (

PRE QUALIFIED DOCUMENT FOR SYSTEM DESIGN 1. Bus duct basic lay out drawing 2. TR and Panel specification 3. Bus duct installation part construction drawing 4. Utility :Y( :Y( :Y( :Y( ), N ( ), N ( ), N ( ), N ( ) ) ) )

44 45

3. MEDIUM POWER DISTRIBUTION (100A~400A)


3.1 3.2 M-SERIES (MINI BUS DUCT) B-SERIES (BABY BUS DUCT)

3.1 M-Series (MINI Bus Duct)


THE LSC MINI BUS DUCT IS A PRACTICAL PRODUCT DESIGNED TO MEET TODAYS NEEDS.
R&D Programs at factories and research centers are designed to respond to the flow of production activities and ever changing requirements. Likewise, a power distribution system for a variety of facility and equipment should be readily and economically adaptable to changes in their locations. The LSC Mini Bus Duct is a wiring system quickly adaptable to such changes. It is both convenient and practical.

1. Connections can be made in any location with the convenient 10 plug-in receptacles 3-meter length. 2. Easily adapts to accommodate a change in machine layout as there are numerous, regularly spaced receptacles. The relocation and addition of new wiring is simple to do as the Bus Duct is constructed in unit from. 3. Electric safety and reliability are high as a copper ground bar run alongside the full length of the Bus Duct. 4. The Bus Duct is small and lightweight for easy installation.

Conductors : High conductivity copper bars. Contact Surfaces : Tin-plated to maintain low contact resistance. Bus Bar Supports : Insulation spacer of polyester resin FRP with high dielectric and mechanical strength. Duct (=Housing=Enclosure) : Steel with copper ground bar. Colors : Epoxy powder painting upon customer request. Ratings : 600V below, 300A~400A.

46 47

FEEDER AND CROSS-SECTION


PLUG-IN HOLES

3000mm

Ampere Ratings(A) 300 400

Conductor Size (mm) 3x35 3x60

Ground bar (mm) 3x15 3x20

WxH (mm) 164x75 164x100

Resistance (/m) 2.19xE4 1.28xE 4

Resistance (/m) 1.28xE4 0.96xE4

Appr.weight (kg/m) 27 37

Housing (Steel)

Conductor (Cu)

Insulator (BMC)

P.E (Cu)

Fig. 47.1

STANDARD CONSTRUCTION

Feed-in Box

Center Feed-in

Plug-in Box

TEE

End closure

Hanger

Elbow Fig. 47.2

3.2 B-Series (BABY Bus Duct)


LSC BABY BUS DUCT IS THE ANSWER FOR MANY DIVERSIFIED APPLICATIONS

1. Connections is possible at location, having 10 plug receptacles within a length of 3 meters. 2. Power supply can be connected at any point as the plug-in method is used for the cable feed-in box. 3. Adaptable to any change in lay-out and can be routed any place-ceiling, wall, trench, etc. 4. Can be installed easily and quickly at low cost because of its socket-type connections. 5. Electric safety and reliability are high as a copper ground bar runs alongside the full length of the Bus Duct. 6. Easily connection or disconnection with wiring and power leakage disconnectors and an output receptacle.
3 4W 3 3W

TOP

INTERNAL NEUTRAL 1 2 3 INTERNAL GROND BUS

1 2 3

1 2 3

Fig. 48.1 INTERNAL GROUND BUS EQUAL TO 66% PHASE CAPACITY

Fig. 48.2 POLARIZING PLUG OUTLET

FEEDER AND CROSS-SECTION


3000

W(140)

H(55)

59

GROUND BAR

BUS BAR

P.1 HOLE

INSULATOR

Fig. 48.3

Ampare Ratings(A) 100

Conductor Size(mm) 3x15

Ground bar(mm) 3x10

W x H(mm) 140x55

Lenght(m) 1~3

Approx.weigts(kg/m) 6~7

48 49

STANDARD CONSTRUCTION

15

Feed-in Box / Center Feed-in

Elbow

TEE

50

End closure

Hanger Fig. 49.1

Plug-in Box

BABY BUS DUCT LAYOUT


US DU CT HO RIZ ON TA L

PL -IN BO X

UG

-IN

BA

B BY

EL BO W

PL F LE EE D

UG

PL

UG

-IN

BO

EN T OR E PP SU TYP L AL W

DC

U OS

RE

B CA

ER NG G H A ;OM O CE

Fig. 49.2

Please confirm the following information in the case of order or a technologic inquiry
M-Series
1. Applicable standard : 2. Rated voltage : 100~600V 3. Rated current : 300~400A 4. Wiring system : ( ) Phase, ( )Wire 5. Current Rating of plug-in box : 6. Conductor material : Copper 7. Place of installation : Indoor, Outdoor, Indoor+Outdoor 8. Color : 7.5BG 6/1.5 5Y7/1 N7.5 etc 9. Drawing of basic layout 10. Single line diagram 11. Something Important

B-Series
1. Applicable standard : 2. Rated voltage : 100~600V 3. Rated current : 100A~200A 4. Wiring system : ( ) Phase, ( )Wire 5. Current Rating of plug-in box : 6. Conductor material : Copper 7. Place of installation : Indoor, Outdoor, Indoor+Outdoor 8. Color : 7.5BG 6/1.5 5Y7/1 N7.5 etc 9. Drawing of basic layout 10. Single line diagram 11. Something Important

MEMO

50 51

4. AIR INSULATED BUS DUCT


4.1 4.2 A-SERIES (LOW VOLTAGE) H-SERIES (HIGH VOLTAGE)

4.1 A-Series (Low Voltage)


A-Series (Air Insulated Bus Duct)
Bus Duct System rated 600A~4000A. There is One bar, Two bar and Three bar per phase according to capacity.

3 WIRE Fig. 52.1

4 WIRE

Fig. 52.2

A-Series Bus Duct Type Table.


AC Ampere Rating 600 800 1000 1200 1500 1600 2000 2500 3000 3500 4000 3 - W PE W Width (mm) 400 400 400 400 400 400 400 500 500 700 700 H Height (mm) 250 260 275 350 350 350 400 350 375 400 400 App. Weight (mm) 51 57 58 64 69 74 90 109 123 138 178 W Width (mm) 400 400 400 400 400 400 400 500 500 700 700 4 - W PE H Height (mm) 250 260 275 350 350 350 400 350 375 400 400

Table 52
App. Weight (mm) 55 58 61 69 76 83 103 127 145 164 218

52 53

COPPER

4.2 H-Series (High Voltage)


LSC HIGH VOLTAGE BUS DUCT GIVE JOY AND SATISFACTION TO CUSTOMERS!
THE ELECTRICAL WORLD OF THE FUTURE High Voltage, Large Capacity!
Need of large capacity in small area Wanted safety and harmony with circumstances Need of large short circuit capacity Savings in installation cost Wanted high quality and well-known product So LSC, the best bus duct maker, should give joy and satisfaction to customers!

LSC High Voltage BUS DUCT


Systems take in a wide range of possibilities, up to 35KV and 4000A This is metal-enclosed non-segregated phase bus systems. Bus bars are supported by epoxy insulator with high dielectric and mechanical strength. Epoxy coating over copper bars provides high dielectric strenght, excellent chemical resistance, durable mechanical characteristics and high thermal emissivity. Enclosure is also made of galvanized steel together with non-magnetic stainless steel to minimize the electric losses.

Conductors : High conductivity copper bars coated


with epoxy.

Contact Surfaces : Silver-plated to maintain low


contact resistance. Bus Bar Supports : Epoxy insulator Enclosure(Duct) : Ventilated steel together with non-magnetic stainless steel (Indoor). Non-ventilated(Outdoor) Colors : Epoxy powder painting with purchasers choice. Ratings : 3.3KV thru 35KV, 600A thru 4000A.

MINIMUM CONSTRUCTION MEASUREMENTS

Feeder

Vertical Elbow

Horizontal Elbow

Horizontal Tee

Horizontal Offset

Vertical Offset

TR. End Box Fig. 54.1

PNL. Flanged End

Wall Flange

STRUCTURAL SUPPORTS
HV. BUS DUCT HV. BUS DUCT Hanger Clamp Hanger Bar C-CHANEL HV. BUS DUCT

W + 200

Hanger support (Indoor)


HV. BUS DUCT

Wall support (Indoor)

Single type support (Outdoor) Fig. 54.2

400

Twin type support (Outdoor)

HV BUS DUCT LAYOUT

SW

BD

R EA HG TTC SW SW BD

Fig. 54.3

54 55

400

Please confirm the following information in the case of order or a technologic inquiry
H-Series
1. Applicable standard : 2. Rated voltage : 3.3KV 6.6KV 7.2KV 11.5KV 13.8KV 15KV 22.9KV 24KV 35KV 3. Rated current : 400A~4000A 4. Wiring system : ( ) Phase, ( )Wire 5. Short-Circuit Capacity : 1.6KV 4KV 8KV 12.5KV 16KV 20KV 25KV 31.5KV 40KV 50KV etc 6. Conductor material : Copper 7. Place of installation : Indoor, Outdoor, Indoor+Outdoor 8. Color : 7.5BG 6/1.5 5Y7/1 N7.5 etc 9. Drawing of basic layout 10. Single line diagram 11. Something Important

A-Series
1. Applicable standard : 2. Rated voltage : 100~600V 3. Rated current : 600~4000A 4. Wiring system : ( ) Phase, ( )Wire 5. Conductor material : Copper 6. Place of installation : Indoor, Outdoor, Indoor+Outdoor 7. Color : 7.5BG 6/1.5 5Y7/1 N7.5 etc 8. Drawing of basic layout 9. Single line diagram 10. Something Important

MEMO