You are on page 1of 25

AS/NZS 3019:2007

Accessed by TAFESA on 18 Sep 2009

AS/NZS 3019:2007

Australian/New Zealand Standard


Electrical installationsPeriodic verification

AS/NZS 3019:2007 This Joint Australian/New Zealand Standard was prepared by Joint Technical Committee EL-001, Wiring Rules. It was approved on behalf of the Council of Standards Australia on 26 October 2007 and on behalf of the Council of Standards New Zealand on 23 October 2007. This Standard was published on 5 November 2007.

The following are represented on Committee EL-001: Association of Consulting Engineers Australia Australian Building Codes Board Australian Electrical and Electronic Manufacturers Association Canterbury Manufacturers Association New Zealand Communications, Electrical and Plumbing Union Consumers' Federation of Australia Electrical Contractors Association of New Zealand Electrical Regulatory Authorities Council Electrical Safety Organisation (New Zealand) Electrical and Communications Association (Queensland) ElectroComms and Energy Utilities Industries Skills Council Energy Networks Association Engineers Australia Institute of Electrical Inspectors Ministry of Economic Development (New Zealand) National Electrical and Communications Association New Zealand Council of Elders New Zealand Electrical Institute Telstra Corporation Limited

Keeping Standards up-to-date


Standards are living documents which reflect progress in science, technology and systems. To maintain their currency, all Standards are periodically reviewed, and new editions are published. Between editions, amendments may be issued. Standards may also be withdrawn. It is important that readers assure themselves they are using a current Standard, which should include any amendments which may have been published since the Standard was purchased. Detailed information about joint Australian/New Zealand Standards can be found by visiting the Standards Web Shop at www.standards.com.au or Standards New Zealand web site at www.standards.co.nz and looking up the relevant Standard in the on-line catalogue. Alternatively, both organizations publish an annual printed Catalogue with full details of all current Standards. For more frequent listings or notification of revisions, amendments and withdrawals, Standards Australia and Standards New Zealand offer a number of update options. For information about these services, users should contact their respective national Standards organization. We also welcome suggestions for improvement in our Standards, and especially encourage readers to notify us immediately of any apparent inaccuracies or ambiguities. Please address your comments to the Chief Executive of either Standards Australia or Standards New Zealand at the address shown on the back cover.

Accessed by TAFESA on 18 Sep 2009

This Standard was issued in draft form for comment as DR 06932.

AS/NZS 3019:2007

Australian/New Zealand Standard


Electrical installationsPeriodic verification

Originated in New Zealand as NZS 3019(Int):2002. Second edition NZS 3019:2004. Third edition AS/NZS 3019:2007.

Accessed by TAFESA on 18 Sep 2009

COPYRIGHT Standards Australia/Standards New Zealand All rights are reserved. No part of this work may be reproduced or copied in any form or by any means, electronic or mechanical, including photocopying, without the written permission of the publisher. Jointly published by Standards Australia, GPO Box 476, Sydney, NSW 2001 and Standards New Zealand, Private Bag 2439, Wellington 6020 ISBN 0 7337 8423 2

Accessed by TAFESA on 18 Sep 2009

AS/NZS 3019:2007

PREFACE
This Standard was prepared by the Joint Standards Australia/Standards New Zealand Committee EL001 Wiring Rules. The Standard aims to provide persons who carry out periodic verification, by inspection and/or testing, with the means to determine, as far as reasonably practicable, whether the installation and all its constituent equipment is in a safe condition for continued use, and that the electrical installation complies with safety requirements for the prevention of fire and the protection of persons and livestock from electric shock. AS/NZS 3019 may be applied through legislative requirements, made in each State and Territory of Australia and in New Zealand, concerned with the safety of electrical installations, that require certain electrical installations to be inspected and tested from time to time. Additionally, verification of an electrical installation may be requested by the owner/occupier or another organization. This Standard differs from the previous New Zealand-only edition, NZS 3019:2004, in that three levels of verification are specified: by basic visual inspection, by visual inspection and limited testing, and by visual inspection and full testing, rather than the verification of specific types of installations. Verification of caravans and pleasure craft previously covered will be contained in the new editions of AS/NZS 3001 and AS/NZS 3004 Part 2 respectively, which are expected to be published in 2008.

Accessed by TAFESA on 18 Sep 2009

AS/NZS 3019:2007

CONTENTS SECTION 1 Scope and general 1.1 Scope .................................................................................................................................... 5 1.2 Types of verification covered ................................................................................................ 5 1.3 Referenced documents ......................................................................................................... 6 1.4 Definitions.............................................................................................................................. 6 1.5 Interpretation ......................................................................................................................... .6 SECTION 2 General requirements 2.1 Reporting of electrically unsafe installations ......................................................................... 2.2 Previous records ................................................................................................................... 2.3 Verification requirements ...................................................................................................... 2.4 Danger to persons or livestock.............................................................................................. 2.5 Adequacy of overcurrent protective devices ......................................................................... 2.6 Instruments............................................................................................................................ 2.7 Qualification........................................................................................................................... 2.8 Frequency of periodic verification ......................................................................................... 2.9 Reporting of periodic verification...........................................................................................

7 7 7 7 7 7 7 7 8

SECTION 3 Verification by basic visual inspection 3.1 General.................................................................................................................................. 9 3.2 Inspection requirements........................................................................................................ 9 SECTION 4 Verification by visual inspection and limited testing 4.1 Verification requirements .................................................................................................... 4.2 General................................................................................................................................ 4.3 Switchboards....................................................................................................................... 4.4 Main earthing conductor...................................................................................................... 4.5 Fixed wired appliances........................................................................................................ 4.6 Overhead lines .................................................................................................................... 4.7 Testing requirements .......................................................................................................... SECTION 5 Verification by visual inspection and full testing 5.1 Requirements ...................................................................................................................... 5.2 Polarity ................................................................................................................................ 5.3 Polarisation.......................................................................................................................... 5.4 Insulation resistance ........................................................................................................... 5.5 Earth fault loop impedance ................................................................................................. 5.6 Protective device fault rating ............................................................................................... 5.7 RCD verification .................................................................................................................. 5.8 Integrity of switchboard connections ................................................................................... 5.9 Testing of final subcircuits supplied from an electrically separated supply ........................ APPENDIX A

10 10 10 11 11 11 12

14 14 14 14 14 14 14 15 15

Periodic verification report forms (Informative) ................................................. 16

Accessed by TAFESA on 18 Sep 2009

COPYRIGHT

AS/NZS 3019:2007

STANDARDS AUSTRALIA/STANDARDS NEW ZEALAND Australian/New Zealand Standard Electrical installations Periodic verification

SECTION 1 SCOPE AND GENERAL


1.1 Scope This Standard sets out the requirements for periodic verification of existing electrical installations which are connected to a low voltage a.c. supply system (exceeding 50 V a.c. but not exceeding 1000 V a.c.). Verification, by inspection and/or testing is intended, as far as reasonably practicable, to determine whether the installation and all its constituent equipment is in a safe condition for continued use.
NOTE Inspection and testing to this Standard should provide evidence that the installation complies with the relevant requirements at the time of construction of the installation.

This Standard does not apply to the periodic verification of the following electrical installations: (a) Installations designed and constructed to the AS/NZS 3000 provisions relating to specific design and installation. Refer to the verification specification prepared for the installation as required by AS/NZS 3000; Installations of the following types: (i) (ii) (iii) (iv) (v) (vi) Relocatable installations and their site installations. Refer to AS/NZS 3001 Marinas and pleasure craft installations. Refer to AS/NZS 3004 Hazardous areas. Refer to AS/NZS 2381.1 and AS/NZS 61241 series Electro-medical areas. Refer to AS/NZS 3003, and in New Zealand only, the provisions of NZS 3003.1 Shows and carnivals installations. Refer to AS/NZS 3002 Construction and demolition sites. Refer to AS/NZS 3012

(b)

In New Zealand it does not apply to: (c) Electrical installations and equipment which operate at non standard voltages and frequencies. Refer NZS 6114; Mobile electro-medical relocatable installations. Refer NZS 6115; and Areas of electrical installations where electrical animal stunning or meat conditioning occurs. Refer to NZS 6116.

(d) (e)
Accessed by TAFESA on 18 Sep 2009

NOTE Periodic testing of appliances is covered by AS/NZS 3760.

1.2 Types of verification covered This Standard provides for verification by: (a) (b) (c) Basic visual inspection; Visual inspection and limited testing; and Visual inspection and full testing.

COPYRIGHT

AS/NZS 3019:2007

NOTE A valid verification certificate issued by Energy Safe Victoria (ESV) under the Home Safety Inspection scheme is deemed to comply with the requirements of this Standard for the periodic inspection, testing and verification of a domestic electrical installation in the State of Victoria.

1.3 Referenced documents Reference is made in this document to the following: AS 61010 Part 1:2005 AS/NZS 2381 Part 1:2005 3000:2007 3001:2001 3002:2002 3003:2003 3004:2002 3012:2003 3017:2007 3760:2003 61241 NZS 3003 Part 1:2003 6114:2006 6115:2006 6116:2006 IEC 61557

Safety requirements for electrical equipment for measurement, control, and laboratory use General requirements

Electrical equipment for explosive atmospheres Selection, installation and maintenance General requirements Electrical installations (known as the Australian/New Zealand Wiring Rules) Electrical installations Relocatable installations (including caravans and tents) and their site installations Electrical installations Shows and carnivals Electrical installations Patient areas of hospitals, medical and dental practices and dialyzing locations Electrical installations Marinas and pleasure craft at low voltage Electrical installations Construction and demolition sites Electrical installations Testing and inspection guidelines In-service safety inspection and testing of electrical equipment Electrical apparatus for use in the presence of combustible dust (All Parts)

Electrical installations Patient areas of hospitals and medical and dental practices Testing requirements Electrical installations Requirements for the safe supply of electricity to installations and equipment operating at non-standard voltages and frequencies Electrical installations Mobile electro-medical connectable installations Safe application of electricity in the meat processing industry

Electrical safety in low voltage distribution systems up to 1000 V a.c. and 1500 V d.c. Equipment for testing, measuring or monitoring of protective measures (All Parts).

1.4 Definitions For the purposes of this Standard the definitions of AS/NZS 3000 and the following apply: Verification The inspection, checking, testing and certification of an existing electrical installation or part of an existing electrical installation. 1.5 Interpretation In this Standard the word shall refers to practices that are mandatory for compliance with this Standard, while the word should refers to practices which are advised or recommended.
Accessed by TAFESA on 18 Sep 2009

The term Informative has been used in this Standard to define the application of the Appendix to which it applies. An Informative appendix is only for information and guidance.

COPYRIGHT

AS/NZS 3019:2007

SECTION 2 GENERAL REQUIREMENTS


2.1 Reporting of electrically unsafe installations Legislation requires specific action (disconnection, isolation, making safe, etc.) or reporting of any defect which constitutes an electrical hazard to persons, livestock or property. 2.2 Previous records Wherever possible, the records and recommendations of previous periodic verifications shall be taken into account. 2.3 Verification requirements Periodic inspection comprising a detailed examination of the installation shall be carried out without dismantling, or with partial dismantling, as necessary, supplemented by appropriate tests from AS/NZS 3000 or AS/NZS 3017, including documentation, to: (a) Confirm that the installation is not damaged or has not deteriorated so as to impair electrical safety; and To identify installation defects and departures from the requirements of this Standard that may give rise to danger.

(b)

These requirements are intended to ensure: (c) (d) The protection of persons and livestock against electric shock and burns; The protection against damage to property by fire and heat arising from an installation defect.

NOTE Existing installations will have been designed and installed to conform to legislative requirements applicable at the time of their design and erection and may have been subsequently repaired using methods that were acceptable when the installation was originally installed. This does not necessarily mean that they are unsafe provided that the installation and repair methods satisfy the fundamental safety principles of AS/NZS 3000, Part 1.

2.4 Danger to persons or livestock Precautions shall be taken to ensure that the process of periodic verification will not cause danger to persons or livestock and will not cause damage to property and equipment even if the circuit is defective. 2.5 Adequacy of overcurrent protective devices When verifying the adequacy of overcurrent protective devices, the interrupting capacity shall be verified by measurement of the fault loop impedance (and hence the fault level) at the point of connection of the protective device.
NOTE Where supply is not available the disconnection times can be verified by measurement of the earth fault loop resistance. The prospective fault level should be sought from the electricity distributor.

2.6 Instruments Measuring instruments should comply either with AS 61010 and IEC 61557 or provide the same or better levels of performance and safety. All measuring instruments shall be:
Accessed by TAFESA on 18 Sep 2009

(a) (b) (c)

Checked for damage and correct operation prior to testing; Used in accordance with their design operating criteria; and Calibrated at appropriate intervals.

2.7 Qualification The verification shall be made by a competent person.

COPYRIGHT

AS/NZS 3019:2007

2.8

Frequency of periodic verification

2.8.1 The frequency of periodic verification of an installation shall be based on the type of installation and equipment, its use and operation, the frequency and quality of maintenance and the external influences to which it is subjected.
NOTE (1) The maximum intervals between periodic verifications may be set by legislation. (2) The interval may be, for instance, some years (e.g. 4 years), with the exception of the following cases where a higher risk may exist and shorter periods may be required: (i) (ii) (iii) (iv) Working places or locations where risks of electric shock, fire or explosion exist due to degradation Working places or locations where both high and low voltage installations exist Communal facilities Safety installations (e.g. emergency luminaires).

For domestic dwellings, longer periods (e.g. 10 years) may be appropriate. When occupancy of a domestic dwelling has changed, a verification of the electrical installation is strongly recommended. (3) The periodic verification report should recommend to the installation owner the recommended interval to the next periodic verification.

2.8.2 In the case of an installation under an effective management system for preventive maintenance in normal use, periodic verification may be replaced by an adequate regime of continuous monitoring and maintenance of the installation and all its constituent equipment by skilled persons. Appropriate records shall be kept. 2.9 Reporting of periodic verification Upon completion of the periodic verification of an existing installation, a certificate shall be provided. Such documentation shall include details of those parts of the installation and limitations of the verification covered by the certificate, together with a record of the inspection, including any deficiencies, and the results of testing. The report may contain recommendations for repairs and improvements, such as upgrading the installation to comply with the current Wiring Rules requirements, as may be appropriate. The certificate shall be given by the person responsible for carrying out the verification, or a person authorized to act on their behalf, to the person ordering the verification. The records of test results should record the results of the appropriate testing detailed in sections 4 and 5. Certificates shall be compiled and signed or otherwise authenticated by a competent person or persons.
NOTE (1) Typical forms are given in Appendix A. (2) National Building Codes may have additional periodic inspection and maintenance requirements for emergency lighting, fire detection and/or protection systems.

Accessed by TAFESA on 18 Sep 2009

COPYRIGHT

AS/NZS 3019:2007

SECTION 3 VERIFICATION BY BASIC VISUAL INSPECTION


3.1 General This section details requirements for basic visual inspection of an electrical installation to confirm that the installation remains in good repair and does not exhibit indications of misuse or damage. This inspection does not include any electrical testing.
NOTE A visual inspection may be required to be performed and reported in a specific manner by legislation.

3.2 Inspection requirements Inspection of electrical equipment and conductors, including consumers mains shall include checks ensuring that: (a) Cables show no undue evidence of insulation or sheath deterioration and have appropriate mechanical protection for the environment in which they are installed; The exposed portions of the earth electrode show no evidence of corrosion, damage or poor connection of the main earthing conductor; Metallic water pipe has not been replaced with plastic piping when the piping is used as the earth electrode; Socket-outlets exhibit no mechanical damage and there is no evidence of overheating; Lamp holders exhibit no evidence of mechanical damage or evidence of undue overheating or arcing; Switchboard and electrical equipment have no conductor insulation deterioration; RCDs, MCBs, fuses and switches show no evidence of mechanical damage; Semi-enclosed rewireable fuses, where fitted, have not deteriorated due to arcing and have no exposed live parts when the fuse carrier is fitted into the fuse base; Switchboard equipment is correctly labelled; Covers of fixed-wired appliances are not broken or missing giving access to live parts or basic insulation;
NOTE Connections to electrical equipment must be enclosed and require the use of a tool to gain access.

(b)

(c)

(d) (e)

(f) (g) (h)

(i) (j)

(k)

Electrical fittings in damp areas have the correct International Protection (IP) rating and are appropriate for the zone. Overhead lines and their entry points into buildings have no evidence of insulation deterioration, rusting of anchorages or deterioration of line-connection boxes; and Safety distance clearances have not been compromised by the introduction of, or modification to, any structures, or by raising of the ground-level under overhead lines. Refer to AS/NZS 3000 for details of aerial conductor clearances.

(l)

(m)

Accessed by TAFESA on 18 Sep 2009

NOTE (1) If the visual inspection reveals evidence of defective connections, overloading or arcing etc., testing in accordance with sections 4 or 5 may be necessary to confirm electrical safety. (2) The use of double adaptors, extension cords and electrical portable outlet devices (EPODs) should be discouraged.

COPYRIGHT

AS/NZS 3019:2007

10

SECTION 4 VERIFICATION BY VISUAL INSPECTION AND LIMITED TESTING


4.1 Verification requirements This section details requirements for the visual inspection and limited testing of an electrical installation to verify that the installation remains in good repair and does not show signs of misuse or damage. This verification is intended to avoid the need for disconnection of supply to the installation and therefore does not include insulation resistance testing.
NOTE An inspection and test may be required to be performed and reported in a specific manner by legislation.

Inspection of electrical equipment shall include those items specified in section 3 together with the additional requirements of this section. 4.2 General Inspection of electrical equipment and conductors, including consumers mains, shall include checks ensuring that: (a) Access to live parts and/or to basic insulation is not possible without the use of a tool, (mains entry box, lampholder and lamp access are exempt from this requirement);
NOTE Connections to electrical equipment must be enclosed and require the use of a tool to gain access.

(b)

Electrical equipment and fixed-wired appliances forming part of the electrical installation are not damaged; Conductors of cables are correctly identified and are connected to the correct terminals of fittings; Conductors are securely held in terminals of fittings and are not subject to tension at the terminations; There is adequate insulation and distance between live conductors and between live conductors and earth; Electrical equipment is adequately supported; Electrical equipment is designed for the environment in which it is located or is suitably enclosed; Lamps do not exceed the rating of the fittings in which they are installed; Fittings are undamaged and serviceable. If fittings show evidence of overheating, the condition of the wiring shall be checked; and Exposed metal liable to become alive is connected to earth.

(c)

(d)

(e)

(f) (g)

(h) (i)

(j)

Accessed by TAFESA on 18 Sep 2009

4.3 Switchboards Inspection of switchboards shall include checks that: (a) The current rating and breaking capacity of protective devices are appropriate for the circuits they protect; Semi-enclosed rewireable fuses, where fitted, have not deteriorated due to arcing and have no exposed live parts when the fuse carrier is fitted into the fuse base; Switches and protective devices are clearly labelled showing the circuit type they control or protect;

(b)

(c)

COPYRIGHT

11

AS/NZS 3019:2007

(d)

Live conductors are insulated or provided with a barrier requiring the use of a tool to gain access; Neutral bars are supported on insulated fittings; Where there are separate earth and neutral bars, earthing conductors are connected to the earth bar and neutral conductors are connected to the neutral bar; The main earthing conductor from the earth electrode is correctly connected at the main switchboard; There is a MEN connection between neutral and earth at the main switchboard; The switchboard is constructed and installed in such a manner that, in the event of fire, the spread of fire will be kept to a minimum; and Residual current devices (RCDs) installed for personal protection have a residual operating current of 30 mA or less.

(e) (f)

(g)

(h) (i)

(j)

4.4 Main earthing conductor Inspection of the main earthing conductor shall include checks ensuring that: (a) (b) The main earthing conductor is the correct size; The main earthing conductor is connected to the earth electrode by a suitable corrosionresistant connection;
NOTE In installations constructed prior to 1976, metallic water pipe may have been used as the earth electrode. Recent work practice in the water supply industry has been to replace metallic pipes with nonconductive pipes. It is recommended that an earth electrode be installed in such installations.

(c) (d) (e)

The main earthing conductor terminations are accessible; Connections are mechanically sound and fixed by a secure system; Connections are protected against mechanical damage, corrosion, and any vibration likely to occur; Connections do not impose any appreciable mechanical strain on the component fittings of the connection; The main earthing conductor is correctly connected at the main switchboard; and Required labelling of the main earth connection is correct.

(f)

(g) (h)

4.5 Fixed wired appliances Inspection of fixed-wired appliances shall include checks ensuring that: (a)
Accessed by TAFESA on 18 Sep 2009

They are correctly positioned and are suitable for the environment in which they are located; Connections of conductors to electrical equipment are correct. When this connection is via flexible cord the cord shall be anchored at both the electrical appliance and the supply fitting; Electrical appliances are correctly mounted and protected against mechanical damage; and Covers are in place preventing access to live parts or basic insulation.

(b)

(c) (d)

4.6 Overhead lines Inspection of overhead lines shall include checks that: (a) The lines and their entry points into buildings have no evidence of insulation deterioration, rusting of anchorages or deterioration of line-connection boxes; and
COPYRIGHT

AS/NZS 3019:2007

12

(b)

Safety distance clearances have not been compromised by the introduction of, or modification to, any structures, or by the raising of the ground level under the lines. Refer to AS/NZS 3000 for details of clearances required.

4.7 Testing requirements The verification of electrical work shall include: (a) (b) (c) Earth continuity testing; Equipotential bonding testing; and Polarity and correct connections testing;

and should include: (d) (e) Leakage current testing; and RCD testing providing interruption of the supply can be tolerated.

NOTE AS/NZS 3017 sets out some of the common test methods required to test low voltage electrical installations.

4.7.1 Earth continuity tests Earth continuity tests shall be carried out to determine, as far as is practical, that: (a) The main earthing conductor between the main switchboard and the earth electrode is continuous and the resistance of the main earthing conductor does not exceed 0.5 ; The connection between any point on the installation required to be earthed and the switchboard earth bar or terminal is continuous; The resistance of protective earthing conductors does not exceed the maximum permitted; and
NOTE AS/NZS 3017 provides values of maximum resistance for various conductor sizes and protective devices.

(b)

(c)

(d)

Fixed wired appliances requiring earthing (Class I) are connected to earth.

4.7.2 Equipotential bonding tests Equipotential bonding tests shall be carried out to ensure that: (a) The connection between any point on the installation required to be equipotentially bonded and the switchboard earth bar is continuous; and The resistance of each equipotential bonding conductor does not exceed 0.5 .

(b)

4.7.3 Polarity and correct connections


Accessed by TAFESA on 18 Sep 2009

Polarity testing shall be performed to the extent that is reasonably practical, with any significant omission being reported. Testing is intended to confirm the following: (a) Every single-pole switch or protective device of the electrical installation operates in the active conductor of the circuit in which it is connected; and Every RCD operates in the active conductor of the circuit(s) to which it is connected, and in the neutral conductor where specified in AS/NZS 3000.

(b)

4.7.4 Leakage current testing Insulation resistance testing requires that the supply be disconnected. Therefore, for limited testing only, such testing is not specified.
COPYRIGHT

13

AS/NZS 3019:2007

However, due to the risks associated with insulation failure, it is recommended that a leakage current test be conducted using a leakage current clamp meter. The test is conducted by simultaneously measuring the current in the active and neutral conductors of the circuit under test. If the leakage current is greater than 10 mA with appliances connected, further testing may be required. 4.7.5 RCD testing The correct operation of RCDs shall be tested by operation of the integral testing device. In New Zealand RCDs for personal protection shall be verified as being type A.

Accessed by TAFESA on 18 Sep 2009

COPYRIGHT

AS/NZS 3019:2007

14

SECTION 5 VERIFICATION BY VISUAL INSPECTION AND FULL TESTING


5.1 Requirements This section details requirements for visual inspection and full testing of an electrical installation to confirm that the installation remains in good repair and does not exhibit indications of misuse or damage. This inspection and testing involves the need for disconnection of supply to all or parts of the installation.
NOTE An inspection and test may be required to be performed and reported in a specific manner by legislation.

Inspection and testing of electrical equipment shall include those items specified in sections 3 and 4 together with the additional requirements of this section. Where a requirement in this section is similar to one in section 4, the requirement of this section applies. 5.2 Polarity Polarity testing shall be carried out to ensure: (a) In a multi-phase circuit a switch, or circuit breaker when used as an isolator, operates simultaneously in all active conductors of the circuit in which it is connected; Neutral conductors of circuits are connected to the neutral bar of the switchboard from which the circuit is supplied; and The consumers main neutral is connected to the neutral bar of the main switchboard.

(b)

(c)

5.3 Polarisation Polarisation testing shall be carried out to ensure: (a) Single phase socket-outlets that accommodate flat-pin plugs are connected so that, when viewed from the front of the socket-outlet, earth, active and neutral are connected in a clockwise order and the earth is connected to the slot on the radial line; and Where multi-phase socket-outlets of the same type form part of an electrical installation the phase sequence of the socket-outlets shall be the same.

(b)

5.4 Insulation resistance An insulation resistance test shall be carried out with test instruments to ensure, so far as practicable, that there is adequate insulation between live parts and earth. 5.5 Earth fault loop impedance The earth fault loop impedance of final subcircuits shall be measured in accordance with the requirements of AS/NZS 3000 or AS/NZS 3017. The method used for testing the earth fault loop shall: (a) (b)
Accessed by TAFESA on 18 Sep 2009

Show the loop impedance in ohms; Give a direct indication of the maximum prospective short circuit current on protective devices; or Give an indication of whether the protective device of a given fault current rating will operate satisfactorily under fault conditions.

(c)

5.6 Protective device fault rating Verify by measurement that the fault level at the point of connection of protective devices does not exceed the fault current interrupting capacity of those protective devices. 5.7 RCD verification The correct operation of RCDs shall be verified by the use of special test equipment.

COPYRIGHT

15

AS/NZS 3019:2007

Tests shall be performed on each final subcircuit protected by an RCD to verify that the RCD operates to disconnect the designated circuit.
NOTE A suitable test could be performed using a test plug with a resistor between the active and earth pins.

5.8

Integrity of switchboard connections

With normal operating loads being supplied for at least 30 minutes, the temperature of switchboard components shall be measured and compared to the ambient temperature to ensure that there is no excessive rise in temperature. Exception: This requirement need not apply to single domestic installations.
NOTE This test should be carried out with a thermal imaging device; however, use of an infrared thermometer is acceptable. For each switchboard, both the ambient temperature and the maximum temperature measured should be recorded and any items whose temperature is significantly above the ambient noted.

5.9 Testing of final subcircuits supplied from an electrically separated supply Final subcircuits supplied from an electrically separated supply shall be tested in accordance with AS/NZS 3000.

Accessed by TAFESA on 18 Sep 2009

COPYRIGHT

AS/NZS 3019:2007

16

Appendix A Periodic Verification Report Forms


(Informative) 1 This verification report form should only be used for reporting on the condition of an existing installation. This verification report form consists of two forms, 3019 Form 1, which contains the certification of the periodic verification, and 3019 Form 2, which details results obtained during inspection and testing. It is intended that these forms be used as follows: (a) (b) Domestic installations, 3019 Form 1 only; Commercial installations, 3019 Forms 1 and 2. When more than one switchboard is installed in the installation a 3019 Form 2 should be prepared for each switchboard.

NOTE The above does not preclude the use of a 3019 Form 2 for a domestic installation for the recording of test results if desired by the person carrying out the testing. The total number of forms used for the inspection report should be indicated on the 3019 Form 1 and a page number allocated to each additional 3019 Form 2 used.

The intended purpose of the verification report should be identified, together with the recipients and inspectors details in the appropriate boxes. The maximum prospective short-circuit current recorded on the 3019 Form 1 should be that at the main switchboard. The prospective short-circuit current of the incoming supply to the switchboard should be recorded on the 3019 Form 2 together with the final subcircuit test results recorded for that switchboard. The Limitations of inspection box on the 3019 Form 1 should fully identify the elements of the installation that are not covered by the report, this aspect having been agreed with the client and other applicable parties (if any), before the periodic inspection and testing is carried out. The recommendation(s) for items requiring attention, if any, should be graded into items which require urgent attention and those which do not in the terms of overall electrical safety of the installation. Where the periodic inspection and testing has resulted in a satisfactory overall assessment, the recommended time interval to the next periodic inspection and testing should be given. If the inspection and testing reveal that parts of the installation require urgent attention, it would be appropriate to state an earlier re-inspection date having due regard to the degree of urgency and extent of the necessary remedial work. If the space available on the form for information or recommendations is insufficient, additional pages should be provided as necessary, and be included in the total page count. Legislation requires specific action (disconnection, isolation, making safe etc.) or reporting of any defect which constitutes an electrical hazard to persons, livestock or property. Other serious defects requiring urgent attention should be so annotated in the report.

Accessed by TAFESA on 18 Sep 2009

COPYRIGHT

17

AS/NZS 3019:2007

GUIDANCE FOR RECIPIENTS (to be attached to the report) This periodic verification report is intended for reporting on the condition of an existing electrical installation. If you were the person ordering this report, but not the owner of the installation, you should pass this report or a copy of it immediately to the owner. This report should be retained in a safe place. It is recommended that this report or a copy of it be placed in or near to the main switchboard of the electrical installation for the information of any person inspecting or undertaking work on the electrical installation in the future. If you later vacate the property, the copy in the main switchboard will provide the new owner with details of the condition of the electrical installation at the time the report was issued. The Limitations of inspection box should fully identify any limitations on the inspections and tests. The person carrying out the testing should confirm these aspects with you before the inspection is carried out. The report will usually contain a list of recommended actions necessary to bring the installation up to an electrically safe condition as detailed in the current electrical Wiring Rules. Legislation requires specific action (disconnection, isolation, making safe, etc) or reporting of any defect which constitutes an electrical hazard to persons, livestock or property. For items classified as requiring URGENT attention, the safety of those using the installation may be at risk, and arrangements should be made for a competent person to undertake the necessary remedial work without delay. For safety reasons, the electrical installation will need to be re-inspected at appropriate intervals by a competent person. The maximum time interval recommended before the next inspection is stated in the report. The report is only valid if the total number of pages stated on page 1 is present.

Accessed by TAFESA on 18 Sep 2009

COPYRIGHT

AS/NZS 3019:2007

18

AS/NZS 3019 Form 1 Installation details: Client: Address of installation:

Certificate of Periodic Verification

This certificate covers the following: (tick one and complete as required) Basic visual inspection in accordance with AS/NZS 3019:2007. Visual inspection and limited testing in accordance with AS/NZS 3019:2007.

Visual inspection and full testing in accordance with AS/NZS 3019:2007.

Estimated age of installation: years Evidence of alterations or additions since last inspection: Yes/No/Not apparent If yes, estimate when carried out years ago Date of last inspection: / / Records available: Yes/No (complete and delete as required) Limitations of inspection: (Detail any limitations of the periodic inspection)

Observations: (Detail items requiring attention) Items requiring URGENT attention:

Other items requiring attention:

Overall electrical tests: Insulation resistance:

M ;

Main switchboard fault level:

kVA

Certification Having carried out a verification of the above installation in accordance with the requirements of AS/NZS 3019:2007 I hereby certify that, subject to the type of verification and limitations as detailed above, the installation satisfies the requirements of AS/NZS 3019:2007 for the issue of this Certificate. Name of person who carried out the verification: Registration type and number: Signature: Date: / /20

Accessed by TAFESA on 18 Sep 2009

This report consists of

pages.

Recommended period for next periodic verification is years, provided that any observations detailed above requiring URGENT attention' are repaired without delay. This report is a valuable document on the safety status of the electrical installation and should be retained for future reference. Placing in or near the main electrical switchboard is recommended. For safety reasons, the electrical installation should be re-inspected at the recommended period by a competent person and this copy given to the person carrying out the next verification.

COPYRIGHT

Accessed by TAFESA on 18 Sep 2009

19

AS/NZS 3019:2007

AS/NZS 3019 Form 2 Switchboard / distribution board No. Address / location

SCHEDULE OF TEST RESULTS Incoming current W Page of Test date / /20 Test equipment type & serial no. Insulation Continuity Earth fault loop RCD tester

R Testers name: Signature: Registration number: Prospective short-circuit current at switchboard input: kA All live wiring and terminals screened from touch without use of tool: Yes /No Description of work carried out:

Final Subcircuit Phase and No.

Protective device Type Fault rating

Conductor Type mm
2

Polarity

Earth continuity

RCD push button test

RCD Current trip test

Insulation resistance to earth

Insulation resistance between conductors

Insulation test voltage

Remarks

Items requiring further action

COPYRIGHT

Accessed by TAFESA on 18 Sep 2009

Standards Australia Standards Australia is an independent company, limited by guarantee, which prepares and publishes most of the voluntary technical and commercial standards used in Australia. These standards are developed through an open process of consultation and consensus, in which all interested parties are invited to participate. Through a Memorandum of Understanding with the Commonwealth government, Standards Australia is recognized as Australias peak national standards body.

Standards New Zealand The first national Standards organization was created in New Zealand in 1932. The Standards Council of New Zealand is the national authority responsible for the production of Standards. Standards New Zealand is the trading arm of the Standards Council established under the Standards Act 1988.

Australian/New Zealand Standards Under a Memorandum of Understanding between Standards Australia and Standards New Zealand, Australian/New Zealand Standards are prepared by committees of experts from industry, governments, consumers and other sectors. The requirements or recommendations contained in published Standards are a consensus of the views of representative interests and also take account of comments received from other sources. They reflect the latest scientific and industry experience. Australian/New Zealand Standards are kept under continuous review after publication and are updated regularly to take account of changing technology.

International Involvement Standards Australia and Standards New Zealand are responsible for ensuring that the Australian and New Zealand viewpoints are considered in the formulation of international Standards and that the latest international experience is incorporated in national and Joint Standards. This role is vital in assisting local industry to compete in international markets. Both organizations are the national
Accessed by TAFESA on 18 Sep 2009

members of ISO (the International Organization for Standardization) and IEC (the International Electrotechnical Commission).

Visit our web sites

www.standards.org.au www.standards.com.au

www.standards.co.nz

Accessed by TAFESA on 18 Sep 2009

GPO Box 476 Sydney NSW 2001 Administration Phone (02) 9237 6000 Fax (02) 9237 6010 Email mail@standards.org.au Customer Service Phone 1300 65 46 46 Fax 1300 65 49 49 Email sales@standards.com.au Internet www.standards.org.au

Level 10 Radio New Zealand House 155 The Terrace Wellington 6001 (Private Bag 2439 Wellington 6020) Phone (04) 498 5990 Fax (04) 498 5994 Customer Services (04) 498 5991 Information Service (04) 498 5992 Email snz@standards.co.nz Internet www.standards.co.nz

ISBN 0 7337 8423 2

Printed in Australia

This page has been left intentionally blank.

Accessed by TAFESA on 18 Sep 2009

You might also like