LCA/LGA/LHA 088 and 100 MODELS LCA PACKAGED COOLING & ELECTRIC HEAT LCA/LGA - 7.5 & 8.5 Ton (26.4 & 29.9 kW) LGA PACKAGED COOLING & GAS HEAT LHA - 7.5 Ton LHA PACKAGED HEAT PUMP
(26.4 kW)
Bulletin #490079 October 1998
*Net Cooling Capacity - 76 000 to 84 000 Btuh (22.3 to 24.6 kW) (19 200 to 21 200 kcal) Gas Input Heating Capacity - 73 000 to 160 000 Btuh (21.4 to 46.8 kW) (18 400 to 40 300 kcal) *Heat Pump Heating Capacity - 77 000 Btuh (22.6 kW) (19 400 kcal) Optional Electric Heat - 5 to 35 kW (4300 to 30 100 kcal)
Table of Contents
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page Required Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page Factory Installed Only Options . . . . . . . . . . . . . . . . . Page Field and/or Factory Installed Accessories . . . . . . . Page Field Installed Only Options . . . . . . . . . . . . . . . . . . . . Page Temperature Control Systems . . . . . . . . . . . . . . . . . . Page Temperature Control Selection Flowcharts . . . . . . . Page Model Number Identification . . . . . . . . . . . . . . . . . . . Page High Altitude Derate LGA Models . . . . . . . . . . . . Page Specifications - LCA/LGA . . . . . . . . . . . . . . . . . . . . . . Page Specifications - LHA . . . . . . . . . . . . . . . . . . . . . . . . . . Page Weight Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2-3 3 4 4 5 6 7 7 7 8 9 10 10 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page Optional Electric Heat Accessories . . . . . . . . . . . . . . Page Electric Heat Data - LCA088 . . . . . . . . . . . . . . . . . . . Page Electric Heat Data - LCA100/LHA088 . . . . . . . . . . . Page Cooling Ratings - LCA/LGA Models . . . . . . . . . . . . . Page Cooling & Heating Ratings - LHA Models . . . . . . . . Page Blower Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . Page Dimensions - LCA Models . . . . . . . . . . . . . . . . . . . . . Page Dimensions - LGA Models . . . . . . . . . . . . . . . . . . . . . Page Dimensions - LHA Model . . . . . . . . . . . . . . . . . . . . . . Page Dimensions - Accessories . . . . . . . . . . . . . . . . . . . . Page Installation Clearances . . . . . . . . . . . . . . . . . . . . . . . . Page 11 11 12 12 13-14 14 15-16 17 18 19 20 21-22 22
NOTE Due to Lennox ongoing committment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incuring liability.
Item
Air Flow Choice Bottom (down-flow) or *horizontal (side) supply and return air Bottom Power Entry For electrical and gas lines Cabinet Heavy gauge galvanized steel, fully insulated, powdered enamel paint finish, large removeable access panels, electrical inlets in cabinet base and electric heat end panel (LCA/LHA only), easy access control area with factory installed controls, low voltage terminal strip, unit lifting holes in base rail Cabinet Access Panels (Hinged) 1 compressor/controls access panel, 1 heating area access panel, 1 blower access panel and 1 air filter/economizer access panel hinged with tool-less access handles, gaskets on all edges for tight seal, blower access panel has steel panel inner liner with insulation sandwiched in-between and air filter/economizer access panel is insulated with fiberglass insulation. Coil Construction Copper tube construction, ripple-edged enhanced aluminum fins, flared shoulder tubing connections, silver soldered construction, factory tested, evaporator coil face split with separate circuits, indoor coil drain connection extends outside of unit cabinet Compressor Crankcase Heater(s) - Two on LCA/LGA models and one on LHA models Filters Disposable 2 inch (51 mm) pleated commercial grade Filter Access Hinged filter door with tool-less access handles Integrated Modular Control (IMC) Solid-state board contains all controls and control relays to operate unit Built-in Functions Include: - Blower On/Off Delay - Built-in Control Parameter Defaults, ensure proper unit operation when power is restored after power failure - Service Relay Output - Defrost Control - Dirty Filter Switch Input - Economizer Control, four modes of operation (outdoor enthalpy, differential enthalpy, temperature and global) - Electric Heat Staging, regulates electric heat during building warm-up - ETM Compatible, various modules (see factory or field installed accessories) - Extensive Unit Diagnostics, (80 diagnostic codes) - Permanent Diagnostic Code Storage - Field Changeable Control Parameters, (65 different parameters) - Gas Valve Delay Between First and Second Stage - Indoor Air Quality Input, monitors CO2 levels, adjusts economizer dampers as needed (four modes of operation), requires optional field installed Indoor Air Quality (CO2) Sensor - Low Ambient Controls Allows unit cooling operation down to 0 F (-17.8 C) - Minimum Run Time - Night Setback Mode, adjusts setpoint, closes outdoor air dampers and operates blower on demand, may be customized for special requirements - Smoke Alarm Mode, (four modes of operation) - Strike Three Low Pressure Control, protects system from low suction pressure while eliminating nuisance faults - Thermostat Bounce Delay - Three Digit Display, (Displays: outdoor temperature, supply air temperature, return air temperature, economizer damper position, Indoor Air Quality, control parameters - Two Stage Thermostat Compatible - Warm-up Mode, (four modes of operation)
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
ISO 9002 Quality Standard - Developed in accordance with International Standards Organization (ISO) quality standards Outdoor Coil Fan PVC coated fan guard furnished Outdoor Coil Fan Motor Overload protected, permanently lubricated, equipped with ball bearings, shaft up, wire basket mount Ratings Rated test conditions are those included in Air Conditioning and Refrigeration Institute (ARI) Standard 210/240-95 while operating at rated voltage and air volumes. Sound rating number rated at test conditions included in Air Conditioning and Refrigeration Institute (ARI) Standard 270-96. Supply Air Blower Belt drive, forward curved blades, blower wheel statically and dynamically balanced, ball bearings, adjustable pulley (allows speed change), blower assembly slides out of unit for servicing Supply Air Motor (Standard Efficiency) Overload protected, equipped with ball bearings Transformer 70VA transformer with built-in circuit breaker *Requires Optional Horizontal Conversion Kit. L Series 088-100 / Page 2
Standard
Standard
Standard
Item
Outdoor Coil Construction Formed type Refrigeration System Consists of: compressors, condenser coils and direct drive fans, evaporator coil and belt drive blowers, expansion valves, high capacity driers, high pressure switches, low pressure switches, full refrigerant charge, crankcase heaters, freezestats (prevent coil freeze-up during low ambient operation or loss of air), low ambient switches, independent refrigerant circuits (allows staging)
Standard
Standard
Item
Compressors Reciprocating type, resiliently mounted on rubber grommets Compressors Copeland Compliant Scroll
Fan and Limit Controls Factory installed, 90 second fan on time delay, dual limit controls (primary and secondary) with fixed temperature setting Heat Exchanger Tubular construction, aluminized steel, life cycle tested Outdoor Coil Construction Formed type Heating System Aluminized steel inshot burners, direct spark ignition, electronic flame sensor, redundant automatic dual gas valve with manual shut-off, induced draft blower, flame rollout switch Refrigeration System Consists of: compressors, condenser coil and direct drive fans, evaporator coil and belt drive blowers, expansion valves, high capacity driers, high pressure switches, low pressure switches, full refrigerant charge, crankcase heaters, freezestats (prevent coil freeze-up during low ambient operation or loss of air) independent refrigerant circuits (allows staging)
Standard
Standard
Item
LHA088S Standard
Defrost Control Furnished on Integrated Modular Control, defrost control provides a defrost cycle, if needed, every 30 or 60 or 90 minutes (adjustable) of compressor on time at outdoor coil temperature below 32 F (0 C). Pressure switch mounted on outdoor coil vapor line terminates defrost cycle.
E E
Standard
Outdoor Coil Construction Formed type Refrigeration System Consists of: compressor, outdoor coil and direct drive fan, indoor coil and belt drive blower, check and expansion valves (indoor and outdoor), high capacity drier, high pressure switch, low pressure switch, reversing valve, defrost control, full refrigerant charge, crankcase heater, freezestat (prevent coil freeze-up during low ambient operation or loss of air), and accumulator.
Standard
Standard
Item
LHA088
Condensate Traps PVC or copper condensate trap factory installed in unit Corrosion Protection Phenolic epoxy coating, applied to condenser coils (with painted base section) and evaporator coils (with painted evaporator base section and painted blower housings), factory applied to either section or both sections Stainless Steel Heat Exchanger (LGA Models) Service Valves Fully serviceable brass valves installed in discharge and liquid lines
N/A NA LHA088
Item
Electric Heat Factory or field installed, helix wound nichrome elements, time delay for element staging, individual element limit controls, wiring harness, may be two-stage controlled, requires Fuse Block and Terminal Block (LHA/LCA Models) Electric Heat Fuse Block Required with Electric Heat. Mounting screws furnished (LCA/LHA Models) Electric Heat LTB2 Terminal Block Required with electric heat Control Systems See pages 6-7 for complete listing Economizer Opposing gear driven recirculated air and outdoor air dampers, plug-in connections to unit, nylon bearings, neoprene seals, 24 volt fully modulating spring return motor, adjustable minimum damper position, damper assembly slides in unit, outdoor air hood must be ordered separately (see below), optional down-flow gravity exhaust dampers available (see below), choice of economizer controls (see below) - Net Weight Economizer Control Choice Sensible Control Furnished on IMC board in unit, uses outdoor air sensor furnished with unit to measure outdoor air temperature and control damper position (Furnished) Global Control Furnished on IMC board in unit, used with Direct Digital Control (DDC) systems, uses global air sensor to control damper position, determines when to use outdoor air for cooling or set damper at minimum position (Furnished) Outdoor Enthalpy Control Adjustable enthalpy sensor, senses outdoor air enthalpy for economizer control, 0 to 100% outdoor air Differential Enthalpy Control Two solid-state enthalpy sensors allow selection between outdoor air and return air (whichever has lowest enthalpy) Down-Flow Gravity Exhaust Dampers Aluminum blade dampers prevent blow back and outdoor air infiltration during off cycle, bird screen furnished - Net Weight Hood for Down-Flow Gravity Exhaust Dampers Automatic fully modulatOutdoor Air Damper Section Linked mechanical dampers, 0 to 25% (fixed) ing spring return damper mooutdoor air adjustable, installs in unit for down-flow applications, outdoor air tor with plug in connection hood must be ordered separately (see below) - Net Weight Manual Outdoor Air Hood Required with LAREMD08/10 Economizer, LAOAD10/15 and LAOADM08/10 Outdoor Air Damper Sections, two cleanable aluminum mesh fresh air filters furnished - Net Weight Model Number - Net Weight Diameter - in. (mm) Power Exhaust Fan Installs in unit for down-flow applications only with econNumber of Blades ressure omizer o tion, provides exhaust air pressure relief, interlocked to run when re option, rovides return air dampers are closed and supply air blower is operating, fan runs when Total air volume - cfm (m3/s) dam ers o en rotected, outdoor air dampers are 50% open (adjustable), motor is overload protected, requires optional down-flow gravity exhaust dampers (see above) Motor Horsepower (W) Total Watts Input Smoke Detector Photoelectric type, installed in supply air section or return air section or both sections
See Electric Heat Data Tables Page 13 See Optional Electric Heat Accessories O tional Table (LCA/LHA Models), Page 10 See pages 6-7
LAGED08/10 - 8 lbs. (4 kg) 24L15 LAOADM08/10 - 28 lbs. (13 kg) LAOAD10/15 - 26 lbs. (12 kg) LAOAH08/10 - 11 lbs. (5 kg) LAPEF08/10 - 28 lbs. (13 kg) 20 (508) - 5 3500 (1.65) @ 0 in. .wg. (0 Pa) 1/3 (249) 230 70K87 - Supply 70K86 - Return
LHA088 ----
Diffusers Aluminum grilles, large center grille, insulated diffuser box with flanges, hanging rings furnished, interior transition (even air flow), internally g , g g g , ( ), y l d( t i l ti ) d t to T-bar ili id l t ili sealed (prevents recirculation), adapts t T b ceiling grids or plaster ceilings - Net Weight
Transitions (Supply and Return) Used with diffusers, installs in roof mounting frame, galvanized steel construction, flanges furnished for duct connection, fully insulated - Net Weight
Horizontal Conversion Kit Two piece duct cover in kit blocks off unit down-flow supply air opening, horizontal return air opening panel (on unit) is moved to block off down-flow return air opening for horizontal applications.
17L25
oHorizontal Gravity Exhaust Dampers Aluminum blade dampers prevent blow back and outdoor air infiltration during off cycle, field installed in return air duct, bird screen and hood furnished - Net Weight Indoor Air Quality (CO2) Sensor Monitors CO2 levels, reports to Integrated Modular Control (IMC) board which adjusts economizer dampers as needed
93J69
47N18
14 inch (356 mm) height Roof Mounting Frame Nailer strip furnished, mates to unit, U.S. National Roofing Contractors Approved, shipped knocked down - Net Weight 24 inch (610 mm) height
Hail Guards Constructed of heavy gauge steel, painted to match cabinet, helps protect outdoor coils from hail damage. Not used with Coil Guards
24L54
Coil Guards Galvanized steel wire guards to protect outdoor coil. Not used with Hail Guards.
24L55
86K84
32K22
28K56
oField installs in return air duct. Two dampers furnished per order no.
48K87
81G59
NO START
NOVAR ETM-2050 KIT 2 Heat / 2 Cool Includes: Control Module, Blower Proving
Switch, Return Air Sensor, Discharge Air Sensor and Wiring Harness
(/(&7520(&+$1,&$/ 7+(50267$7
(Field Furnished)
(97H53)
(30K48)
STOP
NO
NO
(13F16)
START ELECTRO MECHANICAL THERMOSTAT NIGHT THERMOSTAT 1 Heat NON SWITCHING SUBBASE
(13F06)
2 Heat - 2 Cool SWITCHING SUBBASE
(13F12) (13F17)
(13F16)
(30K49)
(30K48)
STOP
NO
NO
NO
(58C92)
START T7300 THERMOSTAT SWITCHING SUBBASE ROOM TEMPERATURE SENSOR W/OVERRIDE BLOWER PROVE SWITCH DIRTY FILTER SWITCH
(81G59)
(81G60)
2 Heat - 2 Cool
(86G67)
RETURN AIR TEMPERATURE SENSOR
(30K49)
(30K48)
STOP
(27C40)
1M
Voltage M= 380/420v-3 phase-50hz
Unit Type G = Cooling w/ Gas Heat C = Cooling Only (w/ opt. Electric Heat) H = Heat Pump Major Design Sequence A = First Generation
Minor Revision Number Heat Type NOTE This space is intentionally left blank, it will be filled in on unit nameplate depending on type of heat ordered.
Cooling Capacity Tons (kW) 088 = 7.5 (26.4) 100 = 8.5 (29.9)
Units may be installed at altitudes up to 2000 feet (610 m) above sea level without any modification. At altitudes above 2000 feet (610 m), units must be derated to match gas manifold pressures shown in table below. NOTE This is the only permissible derate for these units. Altitude - ft. (m) 2001 - 3000 (610 - 915) 3001 - 4000 (915 - 1220) 4001 - 5000 (1220 - 1525) 5001 - 6000 (1525 - 1830) 6001 - 7000 (1830 - 2135) 7001 - 8000 (2135 - 2440) Gas Manifold Pressure - in. w.g. (kPa) 3.6 (0.90) 3.5 (0.87) 3.4 (0.85) 3.3 (0.82) 3.2 (0.80) 3.1 (0.77) L Series 088-100 / Page 7
LCA/LGA088 High 84 900 (24.9) (21 400) 80 500 (23.6) (20 300) 79 000 (23.1) (19 900) 76 000 (22.3) (19 200) 8.85 2.6 8.90 9.5 7.73 2.9 9.80 10.1 86 8 lbs. 0 oz. (3.63 kg) 8 lbs. 0 oz. (3.63 kg) Standard 73 000 (21.4) (18 400) 58 000 (17.0) (14 600) 110 000 (32.2) (27 700) 88 000 (25.8) (22 200) 8 lbs. 8 oz. (3.86 kg) 8 lbs. 8 oz. (3.86 kg) High 106 000 (31.0) (26 700) 85 000 (24.9) (21 400) 160 000 (46.8) (40 300) 128 000 (37.5) (32 300) 80.0%/82.0% 3/4 7 (1.7) 11 (2.7) (1) 12 x 12 (305 x 305) 2 (1.5)
LCA/LGA100 Standard 90 400 (26.5) (22 800) 84 000 (24.6) (21 200) 9.54 2.6 8.80 8.9
8 lbs. 8 oz. (3.86 kg) 8 lbs. 8 oz. (3.86 kg) Standard 73 000 (21.4) (18 400) 58 000 (17.0) (14 600) 110 000 (32.2) (27 700) 88 000 (25.8) (22 200) High 106 000 (31.0) (26 700) 85 000 (24.9) (21 400 160 000 (46.8) (40 300) 128 000 (37.5) (32 300)
Heat Input Type Input (low) Btuh (kW) (kcal) Two Stage Heating Capacity Output (low) Btuh (kW) (kcal) (Natural or LPG/Propane Input (High) Btuh (kW) (kcal) Gas (at Sea Level) Output (High) Btuh (kW) (kcal) Thermal Efficiency - Natural Gas/LPG/Propane Gas Supply Connections npt in. - Natural or LPG/Propane Recommended Gas Supply Pressure wc. in. (kPa) LPG/Propane Blower wheel nominal diameter x width in. (mm) 2 hp (1 5 kW) (1.5 Motor & Drives Di Nominal motor output hp (kW) Voltage & phase (Drive kit #) Rev/Min range Nominal motor horsepower (kW) Voltage & phase (Drive kit #) Rev/Min range Net face area sq. ft. (m2) Tube diameter in. (mm) & Number of rows Evaporator Coil Fins per inch (m) Drain connection number & size in. (mm) fpt Expansion device type Net face area sq. ft. (m2) Condenser Coil Tube diameter in. (mm) & Number of rows Fins per inch (m) Diameter in. (mm) & Number of blades Total air volume cfm (m3/s) Condenser Fans Motor horsepower (W) Motor Rev/Min Total Motor watts Filters (furnished) Type of filter Number and size in. (mm) Natural
380/420v-50hz-3 phase with neutral (1) 704-942, (3) 846-1083, (5) 1050-1300 3 (2.2) 380/420v-50hz-3 phase with neutral (1) 704-942, (3) 846-1083, (6) 1065-1315 9.72 (0.90) 3/8 (9.5) 3 14 (551) (1) - 1 (25.4) Balanced Port Thermostatic Expansion Valve, removeable power head 23.78 (2.21) 3/8 (9.5) 2 20 (787) (1) 24 (610) - 3 4415 (2.08) 1/2 (373) 895 420 Disposable Commercial Grade Pleated (4) 18 x 20 x 2 (457 x 508 x 51) 380/420v-50hz-3 phase with neutral
o q w
Electrical characteristics
Integrated Part Load Value rated at 80 F (27 C) outdoor air temperature.
Rated test conditions are those included in Air Conditioning and Refrigeration Institute (ARI) Standard 360-86 while operating at rated voltage and air volumes.
Sound rating number rated at test conditions included in Air Conditioning and Refrigeration Institute (ARI) Standard 270-96.
F (27 C) db/67 F (19 C) wb entering evaporator air; minimum external duct static pressure.
NOTE Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
oEnergy Efficiency Ratio (Btuh/Watt) oTotal Heating Capacity Btuh (kW) (kcal)
Total Unit Power Input (kW) Coefficient of Performance - Output/Input
Tube diameter in. (mm) & Number of rows Indoor Coil Fins per inch (m) Drain connection Number & size in. (mm) fpt Expansion device type Net face area sq. ft. (m2) Tube diameter in. (mm) & Number of rows Outdoor Coil Fins per inch (m) Expansion device type Diameter in. (mm) & Number of blades Total Air volume cfm (m3/s) Outdoor Fans Motor horsepower (W) Motor rev/min Total Motor watts Filters (furnished) Type of filter Number and size in. (mm)
Electrical characteristics
Cooling Ratings 95 F (35 C) outdoor air temperature and 80 F (27 C) db/67 F (19 C) wb entering indoor coil air.
Rated test conditions are those included in Air Conditioning and Refrigeration Institute (ARI) Standard 340-86 while operating at rated voltage and air volumes.
High T emperature Heating Ratings 47 F (8 C) db/43 F (6 C) wb outdoor air temperature and 70 F (21 C) entering indoor coil air.
Low T emperature Heating Ratings 17 F (-8 C) db/15 F (-9 C) wb outdoor air temperature and 70 F (21 C) entering indoor coil air.
Sound rating number rated at test conditions included in Air Conditioning and Refrigeration Institute (ARI) Standard 270-96.
E E E E
E E E E
E E
E E
NOTE Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
Weight kg
Shipping Weights (Add Factory Installed Options Weights To Base Unit Weights For Total Shipping Weight) LCA088S LCA088H LCA100S LHA088S LCA/LHA Models Only LGA088S LGA088H LGA100S LGA Models Only Base unit Base unit Base unit Base unit Electric Heat (add to Base unit) Base unit with low fire heat exchanger Base unit with low fire heat exchanger Base unit with low fire heat exchanger High Fire Heat Exchanger (add to Base unit) Economizer (add to Base unit) All Models Outdoor Air Damper (add to Base unit) Power Exhaust (add to Base unit) LTL Packaging (less than truck load) (add to Base unit) 1140 1140 1180 1055 1200 1200 1240 30 66 40 28 95 501 501 535 478 544 544 562 14 30 18 13 43
FIELD WIRING
NOVAR ETM-2050 CONTROL SYSTEM
FIELD FURNISHED GLOBAL CONTROLLER OPTIONAL DISCONNECT SWITCH
A Three wire power (See Electrical Data Table) B RS-485 shielded pair twisted wire C Four wire low voltage D Two wire low voltage
Field wiring not furnished
NOTE All wiring must conform to local electrical codes.
OPTIONAL INDOOR AIR QUALITY CO2 SENSOR
A
SINGLE PACKAGE UNIT
C
OPTIONAL ROOM SENSOR
A Three wire power (See Electrical Data Table) B Six wire low voltage (Electro-Mechanical) Seven wire low voltage (Electronic)
C B A
SINGLE PACKAGE UNIT
Nine wire low voltage (Honeywell T7300) Ten wire low voltage (Honeywell T7300 with Service LED) C Two wire low voltage (Electro-Mechanical Only) D Four wire low voltage (All Systems) E Two wire power
Field wiring not furnished
D
OPTIONAL INDOOR AIR QUALITY CO2 SENSOR OPTIONAL TIME CLOCK
Refer to to local electrical codes to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167F (75). Service Factor = 1.15
Refer to to local electrical codes to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167F (75). Service Factor = 1.15
LTB2 ELECTRIC HEAT TERMINAL BLOCK LTB2-175 (30K75) 175 amps (Required For Units Without Disconnect/Circuit Breaker But With Single Point Power Source)
LTB2 Terminal Block (3 phase) 30K75 30K75 30K75 30K75 NOTE Terminal Block is factory installed in units with factory installed electric heat without disconnect/circuit breaker but with single point power source.
Electric Heat Number Volts Model Number (see footnote) Net Weight of Elements Input
1 1 1 1 1 1 *2 *2 *2 *2 *2 *2 *2 *2 *2 380 400 420 380 400 420 380 400 420 380 400 420 380 400 420
kcal
4040 4480 4935 8090 8970 9880 12 100 13 400 14 800 16 200 17 900 19 800 24 300 26 900 26 600
Btuh
16 000 17 800 19 600 32 100 35 600 39 200 48 100 53 200 58 700 64 200 71 100 78 400 96 300 106 700 117 600
Total Unit & Electric Heat (With Power Exhaust) Minimum Circuit Ampacity (A) 2 hp (1.5 kW) 3 hp (2.2 kW)
22 (S) / 21 (H) ( ) ( )
24 (S) / 22 (H) ( ) ( )
26 (S) / 26 (H) ( ) ( )
28 (S) / 28 (H) ( ) ( )
35 (S) / 35 (H) ( )
38 (S) / 38 (H) ( )
45 (S) / 45 (H) 5 5 ( )
47 (S) / 47 (H) ( )
65 (S) / 65 (H) ( ) ( )
67 (S) / 67 (H) ( ) ( )
LCA100 SIZE
EHA100-7.5 EHA100-7 5 5 31 lbs (14 kg) lbs.
1 1 1 1 1 1 *2 *2 *2 *2 *2 *2 *2 *2 *2
380 400 420 380 400 420 380 400 420 380 400 420 380 400 420
4.7 5.2 5.7 9.4 10.4 11.5 14.1 15.6 17.2 18.8 20.8 23.0 28.2 31.2 34.4
4040 4480 4935 8090 8970 9880 12 100 13 400 14 800 16 200 17 900 19 800 24 300 26 900 26 600
16 000 17 800 19 600 32 100 35 600 39 200 48 100 53 200 58 700 64 200 71 100 78 400 96 300 106 700 117 600 65 (S) 6 67 (S) 45 (S) 5 47 (S) 35 (S) 38 (S) 26 (S) ( ) 28 (S) ( ) 21 (S) ( ) 23 (S) ( )
LHA088 SIZE
EHA100-7.5 EHA100-7 5 5 31 lbs (14 kg) lbs.
1 1 1 1 1 1 *2 *2 *2 *2 *2 *2 *2 *2 *2
380 400 420 380 400 420 380 400 420 380 400 420 380 400 420
4.7 5.2 5.7 9.4 10.4 11.5 14.1 15.6 17.2 18.8 20.8 23.0 28.2 31.2 34.4
4040 4480 4935 8090 8970 9880 12 100 13 400 14 800 16 200 17 900 19 800 24 300 26 900 26 600
16 000 17 800 19 600 32 100 35 600 39 200 48 100 53 200 58 700 64 200 71 100 78 400 96 300 106 700 117 600 83 (S) 86 (S) 6 64 (S) 66 (S) 5 54 (S) 56 (S) 44 (S) ( ) 46 (S) ( ) 35 (S) ( ) 36 (S) ( )
NOTE - (H) indicates high efficiency units. (S) indicates standard efficiency units.
*May be used with two stage control. NOTE -- Fuse block must be ordered extra. Factory installed heaters will have the fuse block factory installed. Fuse block must be installed in unit wit h field installed heaters. Also requires LTB2 Terminal Block.
m3/s 17-C (63-F) 19-C (67-F) 22-C (71-F) 1.13 1.41 1.70 1.13 1.41 1.70 1.13 1.41 1.70
cfm 2400 3000 3600 2400 3000 3600 2400 3000 3600
m3/s 17-C (63-F) 19-C (67-F) 22-C (71-F) 1.13 1.41 1.70 1.13 1.41 1.70 1.13 1.41 1.70
cfm 2400 3000 3600 2400 3000 3600 2400 3000 3600
m3/s 17-C (63-F) 19-C (67-F) 22-C (71-F) 1.13 1.41 1.70 1.13 1.41 1.70 1.13 1.41 1.70
cfm 2400 3000 3600 2400 3000 3600 2400 3000 3600
m3/s 17-C (63-F) 19-C (67-F) 22-C (71-F) 1.13 1.41 1.70 1.13 1.41 1.70 1.13 1.41 1.70
cfm 2400 3000 3600 2400 3000 3600 2400 3000 3600
m3/s 17-C (63-F) 19-C (67-F) 22-C (71-F) 1.28 1.60 1.92 1.28 1.60 1.92 1.28 1.60 1.92
cfm 2720 3400 4080 2720 3400 4080 2720 3400 4080
m3/s 17-C (63-F) 19-C (67-F) 22-C (71-F) 1.28 1.60 1.92 1.28 1.60 1.92 1.28 1.60 1.92
cfm 2720 3400 4080 2720 3400 4080 2720 3400 4080
m3/s 17-C (63-F) 19-C (67-F) 22-C (71-F) 1.13 1.41 1.70 1.13 1.41 1.70 1.13 1.41 1.70
cfm 2400 3000 3600 2400 3000 3600 2400 3000 3600
BLOWER DATA - BASE UNIT BLOWER TABLE INCLUDES RESISTANCE FOR LCA088 BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD: 1 - Wet indoor coil air resistance of selected unit. 2 - Any factory installed options air resistance (heat section, economizer, etc.) 3 - Any field installed accessories air resistance (duct resistance, diffuser, etc.) Then determine from blower table blower motor output and drive required. See Page 16 for wet coil and option/accessory air resistance data and blower motors and drives. MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT LCA/LHA models require 3000 cfm (1.41 m3/s) minimum air with electric heat in horizontal applications LCA/LHA models require 2600 cfm (1.23 m3/s) minimum air with electric heat in downflow applications
625
725
0.55 820 (0.41) 0.65 850 (0.48) 0.80 880 (0.60) 0.95 915 (0.71) 1.15 955 (0.86) 1.35 990 (1.01)
0.70 905 (0.52) 0.80 930 (0.60) 0.95 960 (0.71) 1.10 990 (0.82)
1350 2.50 1.10 1065 1.30 1140 1.55 1215 1.85 1285 2.20 (1.87) (0.82) (0.97) (1.16) (1.38) (1.64)
670
760
1355 2.60 1.00 1010 1.20 1085 1.45 1155 1.70 1225 1.95 1290 2.25 (1.94) (0.75) (0.90) (1.08) (1.27) (1.45) (1.68) 1365 2.70 1.15 1030 1.35 1105 1.60 1170 1.80 1240 2.10 1305 2.40 (2.01) (0.86) (1.01) (1.19) (1.34) (1.57) (1.79) 1320 2.55 1380 2.85 1.30 1060 1.50 1125 1.75 1195 2.00 1255 2.25 (1.90) (2.13) (0.97) (1.12) (1.31) (1.49) (1.68)
715
800
760
840
805
880
1335 2.70 1395 3.05 1.30 1020 1.50 1090 1.70 1215 2.20 1280 2.45 1155 1.95 (2.01) (2.28) (0.97) (1.12) (1.27) (1.64) (1.83) (1.45) 1360 2.95 1415 3.25 1.50 1055 1.70 1120 1.95 1185 2.15 1245 2.40 1300 2.65 (2.20) (2.42) (1.12) (1.27) (1.45) (1.60) (1.79) (1.98)
855
925
900
1330 2.95 1385 3.25 1435 3.50 1.60 1030 1.75 1095 2.00 1155 2.20 1215 2.45 1270 2.65 (2.20) (2.42) (2.61) (1.19) (1.31) (1.49) (1.64) (1.83) (1.98)
950
1355 3.25 1410 3.50 1460 3.80 1.70 1010 1.85 1075 2.05 1130 2.25 1190 2.50 1245 2.70 1300 2.95 (2.42) (2.61) (2.83) (1.27) (1.38) (1.53) (1.68) (1.87) (2.01) (2.20) 1335 3.30 1385 3.55 1440 3.85 1490 4.15 1.95 1055 2.15 1115 2.35 1170 2.55 1225 2.80 1280 3.05 (2.46) (2.65) (2.87) (3.10) (1.45) (1.60) (1.75) (1.90) (2.09) (2.28)
995
1320 3.40 1370 3.65 1420 3.95 1470 4.25 1515 4.50 1045 2.30 1100 2.45 1160 2.70 1210 2.90 1265 3.15 (2.54) (2.72) (2.95) (3.17) (3.36) (1.72) (1.83) (2.01) (2.16) (2.35) 1305 3.55 1355 3.80 1405 4.05 1450 4.30 1500 4.60 1545 4.90 1095 2.65 1150 2.85 1200 3.05 1255 3.30 (2.65) (2.83) (3.02) (3.21) (3.43) (3.66) (1.98) (2.13) (2.28) (2.46)
28 - 34 9 - 10 31 - 38 9 - 12
*Throw is the horizontal or vertical distance an airstream travels on leaving the outlet or diffuser before the maximum velocity is reduced to 50 ft. (15 m) per minute. Four sides open.
Additive Electric Heaters (LCA/LHA Models) The certified total heating capacity output shall be Btuh with kW input at volts power supply. Electric heaters shall be available for factory or field installation. Heating elements shall be nichrome bare wire exposed directly to the air stream. Time delays shall bring the elements on and off in sequence with a time delay between each element. Limit controls shall provide overload and short circuit protection. Unit Fuse Block (LCA/LHA Models) Shall be required for units with single point power supply and electric heat. Terminal Block (LCA/LHA Models) Shall be required for units without disconnect switch but with single point power supply and electric heat. Roof Mounting Frame Furnish and install a steel roof mounting frame for bottom discharge and return air duct connection. It shall mate to the bottom perimeter of the equipment. When flashed into the roof it shall make a unit mounting curb and provide weatherproof duct connection and entry into the conditioned area. Height of frame shall be inches (mm). Flashing shall be the responsibility of the roofing contractor. Economizer Section Furnish and install economizer complete with recirculated air dampers, outside air dampers and controls. Low leakage dampers shall ride in nylon bearings. The economizer section shall provide for the introduction of outdoor air for minimum ventilation and free cooling. Integrated economizer control shall allow compressors to cycle for additional cooling, as needed. Damper actuator shall be opposing gear driven, 24 volt, fully modulating design. Plug-in control board (on unit IMC board) shall consist of adjustable minimum positioner, enthalpy setpoint and DIP switches for setting type of control logic used. Economizer control options shall consist of sensible temperature, global, outdoor enthalpy and differential enthalpy (outdoor and return air). Optional outdoor air hood (required) with filters shall be galvanized steel with a powdered enamel paint finish electrostatically bonded to the metal. Economizer shall be available for factory or field installation. Gravity Exhaust Dampers Pressure operated dampers shall be available for factory or field installation. Extruded aluminum dampers shall prevent blow-back and outdoor air infiltration during off cycle. Power Exhaust Fan Shall be available for all models with economizer (down-flow applications only). Direct drive propeller type fan shall exhaust air through optional gravity exhaust damper (required). Motor shall be overload protected. Fan shall be factory or field installed between economizer and gravity exhaust dampers. Horizontal Conversion Kit Shall be available for all models to provide duct covers to block off unit down-flow supply air opening, horizontal return air opening panel (on unit) is moved to block off down-flow return air opening for horizontal applications. Horizontal Gravity Exhaust Dampers Pressure operated dampers shall be available for field installation in the return air duct. Extruded aluminum dampers shall prevent blow-back and outdoor air infiltration during off cycle. Outdoor Air Damper Section Optional outdoor dampers shall be available to provide outdoor air requirements of up to 25%. Models shall be available for manual or automatic operation. Dampers shall be opposing gear driven design. Motorized damper section shall install internal to the unit. Optional outdoor air hood (required) with filters shall be galvanized steel with a powdered enamel paint finish electrostatically bonded to the metal. Dampers shall be available for factory or field installation. Ceiling Diffusers Furnish and install a (flush or stepdown) optional combination ceiling supply and return air diffuser. It shall be capable of not less than ft. (m) radius of effective throw. Supply and return transitions shall be available, for field installation in the roof mounting frame, to provide duct connection to the diffuser. Control Systems Shall provide a selection of control systems to automatically operate the mechanical equipment through the heating or cooling and ventilating cycles as required. Coil Guards Furnish and install galvanized steel coil guards. Hail Guards Furnish and install heavy gauge, painted steel hail guards. Dirty Filter Switch Furnish and install pressure switch that indicates dirty filter, relays information to Integrated Modular Control. Blower Proving Switch Furnish and factory install air pressure switch to monitor blower operation. High Efficiency Blower Motor Furnish and factory install high efficiency blower motor. Indoor Air Quality Sensor Furnish and field install sensor to monitor CO2 levels, relays information to Integrated Module Control which adjusts economizer dampers proportionately to the pollutant level. Service Valves (LCA/LGA) Furnish and factory install fully serviceable brass service valves in discharge and liquid lines. Shall allow refrigerant pump down to high side of system for servicing of low side. Smoke Detectors Furnish and factory install photoelectric type smoke detector in either or both return air section and supply air section. Corrosion Protection Furnish and factory apply phenolic epoxy coating to either or both of the following: Outdoor coils with painted outdoor base section. Indoor coil with painted indoor base section and painted blower housings.
OPTIONAL ACCESSORIES
LCA088 & 100 UNITS SHOWN WITH OPTIONAL ECONOMIZER DAMPERS, POWER EXHAUST FANS, CONVENIENCE OUTLET, UNIT DISCONNECT
CORNER WEIGHTS lbs. (kg)
Model Number lbs. AA kg lbs. BB kg lbs. CC kg lbs. DD kg
LCA088 Base Unit LCA088 Max. Unit LCA100 Base Unit LCA100 Max. Unit
LCA088 Base Unit LCA088 Max. Unit LCA100 Base Unit LCA100 Max. Unit
43-1/2 42-1/2 43 42
21-1/2 22 21 21-1/2
Base Unit The standard unit with NO OPTIONS. Max. Unit The standard unit with ALL OPTIONS Installed. (Economizer, Power Exhaust Fans, High Input Heating and Controls)
Base Unit The standard unit with NO OPTIONS. Max. Unit The standard unit with ALL OPTIONS Installed. (Economizer, Power Exhaust Fans, High Input Heating and Controls)
AA
4 (102) 28 (711)
5-7/8 (149)
4 (102) 28 (711)
BB
BOTTOM SUPPLY AIR OPENING
15 (381)
15 (381)
EE
BOTTOM RETURN AIR OPENING BOTTOM POWER ENTRY 5 x 8 inches (127 x 203 mm) CENTER OF GRAVITY
EVAPORATOR COIL
BLOWER
FF CC
DD
COMPRESSORS BLOWER MOTOR CONDENSER COIL INTAKE AIR CONDENSER COILS 26-1/2 (673)
4 (102)
TOP VIEW
CONDENSER COIL EXHAUST AIR 99-1/4 (2521) OPTIONAL DISCONNECT (Field Provided) CONTROL BOX BLOWER CONDENSER COIL FAN CONDENSER COIL INTAKE AIR
BLOWER
15 (381) 1/2 (13) ELECTRICAL OPTIONAL FORKLIFT SLOTS INLETS ELECTRICAL HEAT (Front and Back) LIFTING HOLES (Factory or Field Installed) (For Rigging Front and Back)
28 (711)
15 (381)
28 (711)
6-5/8 (168)
5-1/4 (133)
5 (127)
FRONT VIEW
BACK VIEW
13-3/4 (349)
FILTERS
OPTIONAL OUTDOOR AIR HOOD (Factory or Field Installed) Furnished with Economizer or Outdoor Air Damper *OPTIONAL GRAVITY 44-13/16 EXHAUST HOOD (1138) (Field Installed) 41-9/16 (1056)
13-3/4 (349)
FILTERS
FILTER OUTDOOR AIR OPTIONAL OUTDOOR AIR HOOD (Factory or Field Installed) OPTIONAL OUTDOOR AIR DAMPERS (Manual or Automatic) (Factory or Field Installed)
*OPTIONAL GRAVITY EXHAUST DAMPERS (Factory or Field Installed) OPTIONAL POWER EXHAUST EXHAUST FANS AIR (Factory or Field Installed) Down-flow Applications Only
CONDENSATE DRAIN
3-1/4 (83)
5 (127)
16-7/8 (429)
(Economizer)
*NOTE - Field Installed in Return Air Duct for Horizontal Applications.
LGA088 & 100 UNITS SHOWN WITH OPTIONAL ECONOMIZER DAMPERS, POWER EXHAUST FANS, CONVENIENCE OUTLET, UNIT DISCONNECT
CORNER WEIGHTS lbs. (kg)
Model Number lbs. AA kg lbs. BB kg lbs. CC kg lbs. DD kg
LGA088 Base Unit LGA088 Max. Unit LGA100 Base Unit LGA100 Max. Unit
LGA088 Base Unit LGA088 Max. Unit LGA100 Base Unit LGA100 Max. Unit
43-1/2 42-1/2 43 42
21-1/2 22 21 21-1/2
Base Unit The standard unit with NO OPTIONS. Max. Unit The standard unit with ALL OPTIONS Installed. (Economizer, Power Exhaust Fans, High Input Heating and Controls)
Base Unit The standard unit with NO OPTIONS. Max. Unit The standard unit with ALL OPTIONS Installed. (Economizer, Power Exhaust Fans, High Input Heating and Controls)
5-7/8 (149)
AA
4 (102) 28 (711)
4 (102) 28 (711)
BB
BOTTOM SUPPLY AIR OPENING
15 (381)
15 (381)
EE
BOTTOM RETURN AIR OPENING BOTTOM POWER ENTRY 5 x 8 inches (127 x 203 mm) CENTER OF GRAVITY
EVAPORATOR COIL
BLOWER
FF CC
DD
COMPRESSORS BLOWER MOTOR CONDENSER CONDENSER COIL COILS INTAKE AIR 26-1/2 (673)
4 (102)
TOP VIEW
CONDENSER COIL EXHAUST AIR 99-1/4 (2521) OPTIONAL DISCONNECT (Field Provided) CONTROL BOX BLOWER CONDENSER COIL FAN CONDENSER COIL INTAKE AIR
BLOWER
28 (711)
15 (381)
28 (711)
6-5/8 (168)
GAS INLET
FRONT VIEW
5-1/4 (133)
5 (127)
BACK VIEW
13-3/4 (349) 47-3/4 (1213) EVAPORATOR COIL CONTROL BOX
13-3/4 (349)
OPTIONAL OUTDOOR AIR HOOD (Factory or Field Installed) Furnished with Economizer or Outdoor Air Damper
FILTERS
FILTER OUTDOOR AIR OPTIONAL OUTDOOR AIR HOOD (Factory or Field Installed) OPTIONAL OUTDOOR AIR DAMPERS (Manual or Automatic) (Factory or Field Installed)
FILTER *OPTIONAL GRAVITY OUTDOOR EXHAUST HOOD AIR (Field Installed) 44-13/16 (1138) *OPTIONAL GRAVITY EXHAUST DAMPERS 41-9/16 (Factory or Field Installed) (1056) OPTIONAL POWER EXHAUST EXHAUST FANS AIR (Factory or Field Installed) Down-flow Applications Only 3-1/4 (83) OPTIONAL END ELECTRICAL INLET
CONDENSATE DRAIN
5 16-7/8 (127) (429) OPTIONAL ECONOMIZER DAMPERS (Factory or Field Installed) LEFT SIDE
(Economizer)
*NOTE - Field Installed in Return Air Duct for Horizontal Applications.
LHA088 UNIT SHOWN WITH OPTIONAL ECONOMIZER DAMPERS, POWER EXHAUST FANS, CONVENIENCE OUTLET, UNIT DISCONNECT
CORNER WEIGHTS lbs. (kg)
Model Number lbs. AA kg lbs. BB kg lbs. CC kg lbs. DD kg
264 306
120 139
214 240
97 109
222 248
101 112
280 322
127 146
43-1/2 42-1/2
1105 1080
21-1/2 22
546 559
Base Unit The standard unit with NO OPTIONS. Max. Unit The standard unit with ALL OPTIONS Installed. (Economizer, Power Exhaust Fans, High Input Heating and Controls)
Base Unit The standard unit with NO OPTIONS. Max. Unit The standard unit with ALL OPTIONS Installed. (Economizer, Power Exhaust Fans, High Input Heating and Controls)
AA
6 (152)
4 (102) 28 (711)
4 (102) 28 (711)
BB
BOTTOM SUPPLY AIR OPENING
15 (381)
15 (381)
INDOOR COIL
BLOWER
EE
BOTTOM RETURN AIR OPENING BOTTOM POWER ENTRY 5 x 8 inches (127 x 203 mm) CENTER OF GRAVITY
FF CC
DD
COMPRESSOR ACCUMULATOR BLOWER MOTOR OUTDOOR COIL INTAKE AIR OUTDOOR COILS 26-1/2 (673)
4 (102)
TOP VIEW
OUTDOOR COIL EXHAUST AIR 99-1/4 (2521) OPTIONAL DISCONNECT (Field Provided) CONTROL BOX BLOWER OUTDOOR COIL FAN OUTDOOR COIL INTAKE AIR
BLOWER
28 (711)
15 (381)
28 (711)
6-5/8 (168)
COMPRESSOR
(/(&75,&$/ ,1/(76
ACCUMULATOR
5-1/4 (133)
5 (127)
FRONT VIEW
13-3/4 (349) 47-3/4 (1213) INDOOR COIL
BACK VIEW
FILTERS
OPTIONAL OUTDOOR AIR HOOD (Factory or Field Installed) Furnished with Economizer or Outdoor Air Damper *OPTIONAL GRAVITY EXHAUST HOOD (Field Installed)
13-3/4 (349)
FILTERS
FILTER OUTDOOR AIR OPTIONAL OUTDOOR AIR HOOD (Factory or Field Installed) OPTIONAL OUTDOOR AIR DAMPERS (Manual or Automatic) (Factory or Field Installed)
CONTROL BOX
*OPTIONAL GRAVITY EXHAUST DAMPERS (Factory or Field Installed) OPTIONAL POWER EXHAUST EXHAUST FANS AIR (Factory or Field Installed) Down-flow Applications Only
3-1/4 (83)
16-7/8 (429) OPTIONAL ECONOMIZER DAMPERS CONDENSATE (Factory or Field Installed) LEFT SIDE DRAIN Return Air Section *NOTE - Field Installed in Return Air Duct for Horizontal Applications.
5 (127)
1-13/16 (46)
Opening
40-1/4 (1022)
Frame
TOP VIEW
14 (356) LARMF08/10-14 24 (610) LARMF08/10-24 NOTE - Roof deck may be omitted within confines of frame. 96-1/4 (2445)
SIDE VIEW
3-7/8 (98)
TOP VIEW
SIDE VIEW
20,000 (137,900)
8-1/8 (206)
29-5/8 (752)
47-5/8 (1210)
29-5/8 (752)
47-5/8 (1210)
LAGEDH08/10 HORIZONTAL GRAVITY EXHAUST DAMPERS (Field Installed in Return Air Duct)
31-5/8 (803) *29-1/2 (749) 6-1/2 (165)
FRONT VIEW
*NOTE - Opening size required in return air duct.
SIDE VIEW
36 (914)
OPTIONAL OUTDOOR AIR HOOD
36 (914)
BLOWER
36 (914)
36 (914)
NOTE - Top Clearance Unobstructed. NOTE - Entire perimeter of unit base require support when elevated above mounting surface. Minimum Clearance To Combustible Materials