Sheet 15 001
15.0-1
Contents
Unitized Power Centers General Description and Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15.0-2 Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15.0-2 Advantages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15.0-2 Third-Party Listing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15.0-3 Seismic Qualication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15.0-3 Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15.0-4 LayoutDimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15.0-5 Specications See Eatons Product Specication Guide, available on CD or on the Web. CSI Format: . . . . . . . . . . . . . . . . . . . . . . . . . . 1995 2010 Section 16313 Section 26 11 16.13
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
21
CA08104001E
General Description
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Ratings
Three-phase kVA: 112.51000 Primary voltages: 2.4 kV Class with 20 kV BIL, 60 Hz 5 kV Class with 30 kV BIL, 60 Hz 15 kV Class with 60 kV BIL, 60 Hz MV power system grounding solid or low resistance grounded (100A) only. UPC product is not to be used on high-resistance or ungrounded MV power systems Transformer windings: Primary connectionsthree-wire delta only Copper or aluminum Type AA, ventilated dry-type NEMA Class 220C insulation 80, 115, 150C rise. When transformer must meet requirements of Federal 10CFR-431K, the 750 and 1000 kVA units are only available in 150C rise Type FA (forced air) available, increases kVA ratings by 33% Primary taps at 95%, 97.5%, 100%, 102.5%, 105% of rated primary voltage Secondary voltages: 208Y/120V, four-wire 240V, three-wire 480Y/277V, four-wire 480V, three-wire 575/380V, four-wire
Advantages
Moving into place is facilitated by the rugged channel base construction and lifting eyes included with each assembly All standard unitized power centers are especially designed to minimum dimensions consistent with safety and reliability Standard unitized power centers are front-only accessible, making against-the-wall installations possibleminimum of 6.00 inches (152.4 mm) from wall for seismic applications, 2.00 inches (50.8 mm) for non-seismic Future load growth is easily accommodated by the addition of unitized power centers to the system without affecting the units serving the original load areas Losses in the medium voltage portion of the distribution system are lower, resulting in a continuous operating savings Secondary output voltage may be adjusted at each unitized power center to compensate for unusual load conditions without affecting the voltage setting of other apparatus in the system Trouble is more quickly isolated with individual units located at or near their served loads Primary power is purchased from the utility at the lower primary power rates, resulting in operational cost savings throughout the life of the equipment Overall installed cost is lower because of the cost benets of medium voltage distribution cable as compared to low voltage cable or busway IQ Energy Sentinel devices can be provided on each feeder circuit to interface with an Eaton PowerNet system to monitor and display electrical energy (kWH). See Tab 3 for more information The IQ family of electronic meters can be provided to monitor the parameters unique to each type of device. With a PONI accessory, each of these devices can be connected to an Eaton PowerNet power monitoring system. See Tab 2 for more information
CA08104001E
15.0-3
Technical Data
Table 15.0-1. Primary Disconnect Switch RatingsType MVS Load Interrupter
Rated Maximum Voltage kV rms Impulse Withstand Voltage kV peak Continuous and Load Break Current Ampere 600 600 600 600 Short-Time Short-Circuit Withstand Current (2 second) kA, rms sym 25 38 25 38 Non-Fused Switch Fault Close and Momentary Rating (10 cycles) kA, rms Asym 40 61 40 61 Fused Switch Fault Close Rating kA, rms Asym
i ii 1
101 101 101 101
Seismic Qualication
4.76 4.76 15 15
60 60 95 95
2 3
Refer to Tab 1 for information on seismic qualication for this and other Eaton products.
Table 15.0-2. Primary Fuse Ampere Rating Current Limiting Eaton Type HCL, 63,000A Symmetrical Interrupting Rating
kVA Primary Fuse Ampere Rating at, kV 2.4 112.5 150 225 300 500 750 1000 45 50 75 100 200 4.16 4.8 25 35 45 60 100 150 200 18 25 40 50 80 120 175 7.2 15 18 25 35 60 85 125 12.0 13.2 13.8 7 10 15 20 40 60 75 7 10 15 20 30 45 60 7 10 15 18 30 45 60
4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Single primary, LV distribution in front of the transformer. Single primary. Separate LV switchboard close coupled to transformer.
CA08104001E
Technical Data
Table 15.0-5. Ventilated Dry-Type Transformer Standard Ratings
kVA Impedance kV Primary LIWV % Class Volts (BIL) Primary Taps Wye Self-Cooled Secondary Secondary Full Volts Load Amperes 208V 112.5 150 225 300 500 750 1000 112.5 150 225 300 500 750 1000 4.5 4.5 4.5 4.5 4.5 5.5 5.5 4.5 4.5 4.5 4.5 4.5 5.5 5.5 5 2400, 4160 or 4800 20 kV, 30 kV, or 30 kV 22-1/2% 208Y/120 or 480Y/277 312 416 625 833 1389 2082 2776 312 416 625 833 1389 2082 2776 480V 135 180 271 361 601 902 1203 135 180 271 361 601 902 1203 150 200 300 400 667 1000 1333 150 200 300 400 667 1000 1333 Fan Cooled (Optional) kVA Secondary Full Load Amperes 208V 416 555 833 1110 1200 2776 3000 416 555 833 1110 1200 2776 3000 480V 180 241 361 481 802 1203 1604 180 241 361 481 802 1203 1604 Transformer Maximum Short-Circuit Amperes rms Symmetrical 208V 11566 11896 14194 15840 24136 36205 48274 6245 8327 12491 15140 24136 36205 48274 480V 5012 5155 6151 6561 10459 15689 20918 2706 3608 5413 6561 10459 15689 20918
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
15
30 kV, 60 kV, 60 kV or 60 kV
22-1/2%
208Y/120 or 480Y/277
Refer to Table 15.0-6 for available temperature rise, fan and secondary voltage options. Short circuit currents assume unlimited utility source, and do not include motor contributions. Maximum load/output is limited to 1200A due to chassis limitation. Maximum load/output is limited to 3000A (cross bus limitation).
Note: All units are three-phase, 60 Hz, 150C rise, 220C insulation system.
CA08104001E
15.0-5
LayoutDimensions
i ii 1 2
MV switch will be fused or nonfused. UL listing available with fused switch only MV fuse class: current limiting, Eaton Type HCL only Primary surge protection shown is optional. Surge arresters, snubber pack or both can be provided Use separate LV switchboard if: LV distribution chassis required is >1200A LV chassis-mounted devices will consume more than 36X of available chassis space Bottom or top entry incoming high voltage cable size and quantity is limited to 250 kcmil, two per phase Vent screens, lters, door gaskets or space heaters are not available in this product FA rating (33% increase in kVA) is optional Available transformer options see Table 15.0-6
Transformer Section 60-Inch Wide With LV Distribution in Front Trans. kVA 500 500 750 Temp. Rise C 80, 115 150 150 Optional Fan Yes Yes Yes Secondary Voltage 480V, 600V All 480V, 600V
Transformer Section 60-Inch Wide With Separate LV Distribution Trans. kVA 500 750 1000 Temp. Rise C 80, 115 150 150 Optional Fan Yes Yes Yes Secondary Voltage All All All
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Available secondary voltages: 208/120V wye (four-wire), 240V delta (three-wire), 480/277V wye (four-wire), 480V delta (three-wire) and 575/380V wye (four-wire). 33% increased kVA capacity with fans. At 208 or 240V secondary, maximum load (output) is limited to 1200A due to chassis limitation. 33% increased kVA capacity with fans, except for 1000 kVA transformer using 208V secondary, maximum load/output is limited to 3000A (cross bus limitation).
CA08104001E
LayoutDimensions
i ii 1
Available Congurations
HV Left Top or Bottom Entry HV Right Top or Bottom Entry
Fan (optional)
Fan (optional) Vent To LV Distribution Chassis 100.00 (2540.0) 85.00 (2159.0) 80.00 (2032.0) 2/ph Max.
2 3 4 5 6 7 8 9 10
37.82 (960.6) Primary Switch 36.00 (914.4) 2/ph Max.
Power Transformer
11 12
36.64 (930.7)
Primary Switch
Foot Print
13 14 15 16 17 18 19 20 21
Note: These UPCs are shipped fully assembled, except 5.00-inch (127.0 mm) top vent or 20.00-inch (508.0 mm) fan and vent assembly, which are shipped separately.
CA08104001E
15.0-7
LayoutDimensions
i ii
Fan (optional) Vent 2/ph Max. 85.00 (2159.0) 100.00 (2540.0) 90.00 To LV Distribution (2286.0) Close-Coupled Switchboard To LV Distribution Close-Coupled Switchboard
1 2 3 4 5
80.00 (2032.0)
Power Transformer 36.00 (914.4) 48.00 or 60.00 (1219.2) (1524.0) 36.00 or 45.00 (914.4) (1143.0)
Power Transformer
6 7
8
37.82 (960.6) Primary Switch Power Transformer 36.64 (930.7) LV Switchboard 36.00 (914.4) LV Switchboard Power Transformer Primary Switch
9 10
11 12 13 14 15 16 17 18 19 20 21
Note: In addition to shipping splits shown, 5.00-inch (127.0 mm) top vent or 20.00-inch (508.0 mm) fan and vent assembly are also shipped separately.
CA08104001E
LayoutDimensions
i ii 1 2 3 4 5 6 7 8 9 10 11
37.82 (960.6) 36.00 (914.4)
Fan (optional) Vent To LV Distribution Chassis 2/ph Max. 2/ph Max. 100.00 (2540.0) 85.00 (2159.0) 80.00 (2032.0)
Power Transformer 36.00 (914.4) 48.00 or 60.00 (1219.2) (1524.0) = Shipping Split One Line/Front Elevation
Power Transformer
Primary Switch
Primary Switch
36.64 (930.7)
Primary Switch
Primary Switch
Foot Print
Foot Print
12 13 14 15 16 17 18 19 20 21
Note: In addition to shipping splits shown, 5.00-inch (127.0 mm) top vent or 20.00-inch (508.0 mm) fan and vent assembly are also shipped separately.
CA08104001E
15.0-9
LayoutDimensions
i ii
Fan (optional) Vent 2/ph Max. 2/ph Max. 100.00 (2540.0) To LV Distribution 90.00 Close-Coupled (2286.0) Switchboard To LV Distribution Close-Coupled Switchboard
1 2 3 4
Power Transformer 36.00 (914.4) 36.00 (914.4) 48.00 or 60.00 (1219.2) (1524.0) 36.00 or 45.00 (914.4) (1143.0) = Shipping Split One Line/Front Elevation
Power Transformer
5 6
7
37.82 (960.6) Primary Switch Primary Switch Power Transformer LV Switchboard 36.64 (930.7) 36.00 (914.4) LV Switchboard Power Transformer Primary Switch Primary Switch
8 9
Note: In addition to shipping splits shown, 5.00-inch (127.0 mm) top vent or 20.00-inch (508.0 mm) fan and vent assembly are also shipped separately.
10 11 12 13 14 15 16 17 18 19 20 21
CA08104001E
LayoutDimensions
i ii
Molded Case Circuit BreakerLayout See Table 15.0-2 for Ampere Ratings
2-Pole ED, EDH, 2-Pole ED, EDH, EDC, EHD, EDC, EHD, FD, FDB, FD, FDB, FDC, HFD 3-Pole 3-Pole ED, EDH, FD, FDB, FD, FDB, FDC, HFD, JD, JDB, JD, JDB, HJD, JDC HJD, JDC 2- or DK, KD, KDB, HKD, KDC 3-Pole 2- or LD, LDB, HLD, LDC, MDL LG 3-Pole HMDL, ND, HND, NDC
2X
1 2 3 4 5 6
Transformer Ventilating Opening Space for Main and Feeder 36X Molded Case Circuit Breakers 3X
4X 6X
Figure 15.0-5. Distribution Panel Layout Mounted in Front of Transformer up to 1200A Panel-Mounted Main and Feeder Devices
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
100% rated main and feeder electronic trip breakers are available rated 4001200A. 90C wire rated at 75C ampacity must be used. May be used as a main device.
Note: For main devices or main bus 1200A and below. Feeder devices mounted in front of transformer. Note: For auxiliary switchboard section layoutadjacent to transformer, refer to Figure 15.0-7 for switchboard section information. Note: Neutral conductor is always gutter mounted.
CA08104001E
15.0-11
LayoutDimensions
i
3
ii
Primary Switch Power Transformer
LV Distribution Chassis
Primary Switch
Power Transformer
LV Switchboard
1 2 3
Front 4
Front
Figure 15.0-6. Base Plan ViewHV Left, LV Distribution in Front of the Transformer
Minimum recommended clearance on each side and rear = 2.00 inches (51.0 mm) for non-seismic applications, 6.00 inches (152.4 mm) for seismic applications. Local jurisdictions may require more. Minimum recommended clearance in the front = 36.00 inches (863.6 mm). Local jurisdictions may require more.
Figure 15.0-7. Base Plan ViewHV Left, LV Switchboard Close-coupled to Transformer on the Right
Minimum recommended clearance on each side and rear = 2.00 inches (51.0 mm) for non-seismic applications, 6.00 inches (152.4 mm) for seismic applications. Local jurisdictions may require more. Minimum recommended clearance in the front = 36.00 inches (863.6 mm). Local jurisdictions may require more.
4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Note: Finished foundation surface shall be level within 0.06 inches (1.5 mm) in 36.00 inches (914.4 mm) left-to-right, front-to-back and diagonally, as measured by a laser level. Refer to actual order drawings for power cable conduit entrance locations.
Note: Finished foundation surface shall be level within 0.06 inches (1.5 mm) in 36.00 inches (914.4 mm) left-to-right, front-to-back and diagonally, as measured by a laser level. Refer to actual order drawings for power cable conduit entrance locations.
CA08104001E
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
CA08104001E