Voltage Voltage per cell No of Cells Minimum Cell Voltage Design Margin Aging factor Temprature correction factor Overload Factor Battery Type Back-Up time 24 Volts 21.6 Volts 26.4 Volts 1.14 Volts 1.2 Volts 22 Nos 0.981818182 Volts 1.1 1.25 1 1 Ni-Cd 8 hrs MAIN HT PANEL
S.NO
DESCRIPTION
LOAD IN WATTS
Breakers Quantity 1 Relays O\C & E\F Relay Trip Circuit Supervision Relay Sensitive E\F Relay Master Tripping Relay 2 Indications Annunciator 9 window LED Indicating lamp(ON,OFF,TRIP,) Trip Circuit Healthy 3 Energising Coils VCB Tripping Coil VCB Closing Coil 3 5 5
0 3 5 5
5 5
5 5
LOAD NAME A1 A2 A3
TIME IN MIN
1 Period
2 Load in Amps
Section-1 1 Section-2 1 2 Section-3 1 2 3 Uncorrected cell size Corrected cell size Ah rating for the battery selected asper catolouge Charger rating 12.54166667 12.41666667 4.083333333 12.54166667 -0.125 -8.333333333 12.54166667 12.41666667 12.54166667 -0.125 12.54166667 12.54166667
AIN HT PANEL
EMERGENCY LOAD
0 0 0 0
0 18 30 30
0 21 35 35
27 3 3
3 3.5 3.5
0 0
30 30
180
Section-1 Sub total 1 119 120.00 119.00 2.8 2.8 Section-2 Sub Total 1 119 480 600.00 599.00 480.00 10.20 10.20 8.300 Section-3 Sub Total
9.907916667 35.11666667 -0.35 34.76666667 127.925 -1.275 -69.16666667 57.48333333 57.48333333 79.03958333 120 8.854166667
Battery Sizing Calculation As per IEEE Std 485-1997 Nominal Voltage Minimum Voltage Maximum Voltage End cell Voltage Voltage per cell No of Cells Minimum Cell Voltage Design Margin Aging factor Temprature correction factor Overload Factor Battery Type Back-Up time 24 Volts 21.6 Volts 26.4 Volts 1.14 Volts 1.2 Volts 22 Nos 0.981818182 Volts 1.1 1.25 1 1 Ni-Cd 8 hrs MAIN HT PANEL
S.NO
DESCRIPTION
LOAD IN WATTS
Breakers Quantity 1 Relays O\C & E\F Relay Trip Circuit Supervision Relay Sensitive E\F Relay Master Tripping Relay 2 Indications Annunciator 9 window LED Indicating lamp(ON,OFF,TRIP,) Trip Circuit Healthy 3 Energising Coils VCB Tripping Coil VCB Closing Coil
0 3 5 5
0 0 0 0
0 0 0
5 5
0 0
LOAD NAME A1 A2 A3
TIME IN MIN
1 Period
2 Load in Amps
Section-1 1 Section-2 1 2 Section-3 1 2 3 Uncorrected cell size Corrected cell size Ah rating for the battery selected asper catolouge Charger rating 9.625 9.5 1.166666667 9.625 -0.125 -8.333333333 9.625 9.5 9.625 -0.125 9.625 9.625
AIN HT PANEL
EMERGENCY LOAD
0 0 0 0
0 6 10 10
0 6 10 10
9 1 1
3 1 1
0 0
10 10
180
Section-1 Sub total 1 119 120.00 119.00 2.65 2.63 Section-2 Sub Total 1 119 480 600.00 599.00 480.00 10.20 10.20 8.300 Section-3 Sub Total
7.60375 25.50625 -0.32875 25.1775 98.175 -1.275 -69.16666667 27.73333333 27.73333333 38.13333333 120 4.458333333
CABLE USED 2Cx35SQMM COPPER XLPE ARMOURED POWER CABLE From To load current Distance(kM) Resistane/kM Drop %drop HT ROOM SDB-1 9.17 0.18 0.524 1.72983 7.20762 HT ROOM SDB-2 9.17 0.26 0.524 2.49864 0.104110067
2.5
Battery Sizing Calculation As per IEEE Std 485-1997 Nominal Voltage Minimum Voltage Maximum Voltage End cell Voltage Voltage per cell No of Cells Minimum Cell Voltage Design Margin Aging factor Temprature correction factor Overload Factor Battery Type Back-Up time 24 Volts 21.6 Volts 26.4 Volts 1.14 Volts 1.2 Volts 22 Nos 0.981818182 Volts 1.1 1.25 1 1 Ni-Cd 8 hrs MAIN HT PANEL
S.NO
DESCRIPTION
LOAD IN WATTS
Breakers Quantity 1 Relays O\C & E\F Relay Trip Circuit Supervision Relay Sensitive E\F Relay Master Tripping Relay 2 Indications Annunciator 9 window LED Indicating lamp(ON,OFF,TRIP,) Trip Circuit Healthy 3 Energising Coils VCB Tripping Coil VCB Closing Coil
0 3 5 9
0 0 0 0
0 0 0
5 5
0 0
LOAD NAME A1 A2 A3
TIME IN MIN
AIN HT PANEL
EMERGENCY LOAD
0 0 0 0
0 3 5 9
0 3 5 9
0 0
5 5