Qurayyah CCPP Project Fail Free Commissioning - Power Receiving


EPC) Commissioning Management Team

, , , , . This document is the informational asset of Doosan Heavy Industries & Construction. Thus, unauthorized access, revision, distribution and copying of this document are strictly prohibited.

Index

Power Receiving Concept Power Receiving for Block Power system Block MV SWBD Scheme & Power distribution Power Receiving for Common Power system Common MV SWBD Scheme Common MV SWBD Power distribution Components of each Electrical System
- Gas Insulated Switchgear - Unit Auxiliary Tr - Isolated Phase Busbar - Generator Step-up Tr - UPS & Battery - MV Switch Board - LV Switch Board

Power Receiving Concept


GRID Open Cycle Open Cycle

Block #1~5 (need each block individually)

Common

Power Receiving for Block Power system


GRID 380KV

GSU 380/18KV UAT 18/4.16KV

CB 4000A

CB 4000A (N.O)
MV SWBD 4.16KV

CB 1250A (N.O)

From Block Open Cycle 4.16KV 1250A (N.C)

LV SWBD 480V

From Common 4.16KV 4000A (N.C)

Block MV SWBD (4.16KV) Scheme & Power distribution

Normally UAT Incomer (4000A) & Bus section(4000A) CB will remain close to receive power at normal operation.
QOC Tie CB(1250A) and QCC Tie CB (4000A) will remain open for back-up stand-by. Once Block-1 power failure from grid, HSBT will close QCC Tie and open UAT incomer. Bus section CB will remain close. QOC Tie CB(1250A) will be an emergency backup from open cycle.

UAT Incomer

B/S

Power distribution

QCC Tie

QOC Tie

ST & HRSG CCWP CEP BFP CWP Air Compressor

ST generator power exports to GIS through GSU.

Power Receiving for Common Power System

From Open Cycle GT#12 18KV

ST#3 18/13.8KV CB 2500A

ST#4 18/13.8KV

From Open Cycle GT#15 18KV

MV SWBD 13.8KV

From Open Cycle 1600A SAT#5 13.8/4.16KV

From Open Cycle SAT #3&4 13.8/4.16KV CB 4000A MV SWBD 4.16KV 1600A SAT#6 13.8/4.16KV

CB 1250A

Tie CB 4000A To each Block 4.16KV SWBD

CB 1250A CB 1250A MV SWBD 4.16KV

Power Source
Back-Up Main Power Flow

Common MV SWBD Scheme


13.8KV SWBD
IC-A IC-B

Normally this SWBD Incomer CB(2500A) 1&2 receives

power from open cycle via ST 3&4.


When any incomer bus will fail, Bus section CB(2500A) will be closed and incomer 1 or 2 will be opened by HSBT. 4.16KV Station SWBD

B/S

13.8KV Station SWBD

IC-A IC-B

Normally this SWBD Incomer CB (4000A) 1&2 receives


power from 13.8KV SWBD via SAT 3&4.

4.16KV Station SWBD

When black out condition, this SWBD receives power from open cycle. (Two Tie CB 1600A)

Once each block power fail, this SWBD gives power to each block 4.16KV unit SWBD.

IC-A

IC-B

4.16KV CW Station SWBD


4.16KV CW Station SWBD

Normally this SWBD Incomer CB (1250A) 1&2 receives power from 13.8KV SWBD via SAT 5&6. When emergency condition, this SWBD receives power from 4.16KV Station SWBD.
6

Common MV SWBD Power Distribution


13.8KV Station SWBD Power Distribution Electrochlorination System Demin Transformer (for Demin Water system LV power)

4.16KV Station SWBD Power Distribution Brine Recirculation Pump

BOPT Transformer (for MSF system LV power)

4.16KV CW Station SWBD Power Distribution Sea Water supply Pump

Drum Screen Wash Water system


BOPT Transformer (for Trash Rake, Drum Screen, Chlorination system LV Power)

GIS (Gas Insulated Switchgear) Components

VOLTAGE TRANSFORMER

DISCONNECTOR

EARTHING SWITCH

CURRENT TRANSFORMER

CIRCUIT BREAKER

IPB (Insulation Phase Busbar) Components


Aluminum Conductor Conductor Enclosure

Conductor Angular Joint

Cast Resin Insulator

Disconnect & Ground Switch

Flexible Braids

(GSU) Generator Step-up Transformer Components

LV Side

Conservator Tank

Tap Changer

Cooler Bank with Cooling fans

Pressure Relief Device

HV Side

Temperature gauges

MS 3000

Control Cabinet

Buchholz Relay 10

UAT (Unit Aux Transformer) Components

LV Side

Conservator Tank

Tap Changer

Pressure Relief Device

HV Side

UAT Cooler Bank with Cooling fans Temperature gauges

Neutral Ground Resistor

Control Cabinet

Buchholz Relay

Gas & Moisture Monitor 11

MV SWBD Components

Vacuum Type Circuit Breaker

Bus & Cable Compartment

Instrument Compartment

PT Compartment

Current Transformer

Earthing Switch

Breaker Compartment

12

LV SWBD Components

Voltage Transformer

Bus bar

Instrument Compartment

Air Circuit Breaker

Current Transformer 13

UPS & Battery Charger Components

Battery Bank

Utility Power

Battery Monitoring & Battery Isolator

14